05000461/FIN-2007003-01: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
Line 15: Line 15:
| CCA = N/A for ROP
| CCA = N/A for ROP
| INPO aspect =  
| INPO aspect =  
| description =  Section F of Clinton Power Stations operating license NPF-62, states that the licensee shall implement and maintain in effect all provisions of the approved fire protection program as described in the USAR. The USAR required that the fire protection program follow the requirements of Branch Technical Position APCSB 9.5-1, Appendix A, Plants Under Construction and Operating Plants. Branch Technical Position APCSB 9.5-1, Appendix A, requires that floors, walls and ceilings enclosing separate fire areas be sealed or closed to provide a fire resistance rating at least equal to the fire barrier itself. On November 2, 2006, the licensee identified two open, unsealed, 12" x 12" penetrations in the floor of the Division 3 switchgear room. The penetrations were under the main feed and reserve feed breakers to the 4kV switchgear for Division 3 . The inspectors determined that the failure to seal two penetrations between separate fire zones was a performance deficiency warranting a significance determination. The inspectors performed a Phase 2 evaluation using IMC 0609, Appendix F, Fire Protection Significance Determination Process. The inspectors determined that a credible fire scenario existed in that an energetic fault in the 4 kV Division 3 switchgear located directly above the open penetrations could ignite a non-safety related cable tray located directly below the open penetrations. A fire could then propagate horizontally along the non-safety related cable tray and then involve a Division 1 cable tray. The inspectors conservatively assumed that only Division 2 equipment would be available in such a scenario. Based on four vertical cabinet sections as being potential ignition sources, a 30 minute fire propagation time to reach the Division 1 cable tray, and remaining mitigating Division 2 equipment available, the inspectors determined that the issue was of very low safety significance.
| description =  Section F of Clinton Power Stations operating license NPF-62, states that the licensee shall implement and maintain in effect all provisions of the approved fire protection program as described in the USAR. The USAR required that the fire protection program follow the requirements of Branch Technical Position APCSB 9.5-1, Appendix A, Plants Under Construction and Operating Plants. Branch Technical Position APCSB 9.5-1, Appendix A, requires that floors, walls and ceilings enclosing separate fire areas be sealed or closed to provide a fire resistance rating at least equal to the fire barrier itself. On November 2, 2006, the licensee identified two open, unsealed, 12\" x 12\" penetrations in the floor of the Division 3 switchgear room. The penetrations were under the main feed and reserve feed breakers to the 4kV switchgear for Division 3 . The inspectors determined that the failure to seal two penetrations between separate fire zones was a performance deficiency warranting a significance determination. The inspectors performed a Phase 2 evaluation using IMC 0609, Appendix F, Fire Protection Significance Determination Process. The inspectors determined that a credible fire scenario existed in that an energetic fault in the 4 kV Division 3 switchgear located directly above the open penetrations could ignite a non-safety related cable tray located directly below the open penetrations. A fire could then propagate horizontally along the non-safety related cable tray and then involve a Division 1 cable tray. The inspectors conservatively assumed that only Division 2 equipment would be available in such a scenario. Based on four vertical cabinet sections as being potential ignition sources, a 30 minute fire propagation time to reach the Division 1 cable tray, and remaining mitigating Division 2 equipment available, the inspectors determined that the issue was of very low safety significance.
}}
}}

Revision as of 20:32, 20 February 2018

01
Site: Clinton Constellation icon.png
Report IR 05000461/2007003 Section 4OA7
Date counted Jun 30, 2007 (2007Q2)
Type: NCV:
cornerstone Pr Safety
Identified by: Licensee-identified
Inspection Procedure:
Inspectors (proximate) D Tharp
M Mitchell
S Mischke
J Mcgee
INPO aspect
'