| issue date = 03/06/2018
| issue date = 03/06/2018
| title = Attachment - Vogtle Electric Generating Plant Unit 4 Amendment 111 (LAR-17-036)
| title = Attachment - Vogtle Electric Generating Plant Unit 4 Amendment 111 (LAR-17-036)
| author name = Patel C P
| author name = Patel C
| author affiliation = NRC/NRO/DNRL/LB4
| author affiliation = NRC/NRO/DNRL/LB4
| addressee name = Whitley B H
| addressee name = Whitley B
| addressee affiliation = Southern Nuclear Operating Co, Inc
| addressee affiliation = Southern Nuclear Operating Co, Inc
| docket = 05200025, 05200026
| docket = 05200025, 05200026
Line 15: Line 15:
| page count = 10
| page count = 10
| project = EPID:L-2017-LLA-0104
| project = EPID:L-2017-LLA-0104
| stage =  
| stage = Acceptance Review
}}
}}


=Text=
=Text=
{{#Wiki_filter:ATTACHMENT TO LICENSE AMENDMENT NO. 111 TO FACILITY COMBINED LICENSE NO. NPF-92 DOCKET NO. 52-026   Replace the following pages of the Facility Combined License No. NPF-92 with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change. Facility Combined License No. NPF-92 REMOVE INSERT 7 7   Appendix C to Facility Combined License No. NPF-92 REMOVE INSERT C-431a C-431a --- C-431b C-432 C-432 --- C-432a C-433 C-433 --- C-433a C-434 C-434 --- C-434a (7)       Reporting Requirements (a) Within 30 days of a change to the initial test program described in FSAR Section 14, Initial Test Program, made in accordance with     10 CFR 50.59 or in accordance with 10 CFR Part 52, Appendix D, Section VIII, for Changes and SNC shall report the change to the Director of NRO, or the designee, in accordance with 10 CFR 50.59(d). (b) SNC shall report any violation of a requirement in Section 2.D.(3), Section 2.D.(4), Section 2.D.(5), and Section 2.D.(6) of this license within 24 hours. Initial notification shall be made to the NRC Operations Center in accordance with 10 CFR 50.72, with written follow up in accordance with 10 CFR 50.73. (8)       Incorporation The Technical Specifications, Environmental Protection Plan, and ITAAC in Appendices A, B, and C, respectively of this license, as revised through Amendment No. 111, are hereby incorporated into this license. (9)       Technical Specifications The technical specifications in Appendix A to this license become effective upon a Commission finding that the acceptance criteria in this license (ITAAC) are met in accordance with 10 CFR 52.103(g). (10)   Operational Program Implementation SNC shall implement the programs or portions of programs identified below, on or before the date SNC achieves the following milestones: (a) Environmental Qualification Program implemented before initial fuel load; (b) Reactor Vessel Material Surveillance Program implemented before initial criticality; (c) Preservice Testing Program implemented before initial fuel load; (d) Containment Leakage Rate Testing Program implemented before initial fuel load; (e) Fire Protection Program 1. The fire protection measures in accordance with Regulatory Guide (RG) 1.189 for designated storage building areas (including adjacent fire areas that could affect the storage area) implemented before initial receipt 7 Amendment No. 111 C-431a Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 799 3.3.00.07d.i Inspections of the as-built raceways that route Class 1E cables will be performed to confirm that the separation between raceways that route Class 1E cables of different divisions, and between raceways that route Class 1E cables and raceways that route non-Class 1E cables is consistent with the following:    i)  Within the main control room and remote shutdown room (non-hazard areas), the minimum separation for low-voltage power cables and below is defined by one of the following: i) Within the main control room and remote shutdown room (non-hazard areas) the minimum separation for low-voltage power cables and below meets one of the following:   1) For configurations involving open configurations to enclosed configurations with low-voltage power cables, the minimum vertical separation is 3 inches and the minimum horizontal separation is 1 inch. 1For configurations involving open configurations to enclosed configurations with low-voltage power cables, the vertical separation is 3 inches or more and the horizontal separation is 1 inch or more. 2)  For configurations involving an enclosed raceway and an open raceway with low-voltage power cables, the minimum vertical separation is 1 inch if the enclosed raceway is below the open raceway. 2)  For configurations that involve an enclosed raceway and an open raceway with low-voltage power cables, the minimum vertical separation may be reduced to 1 inch if the enclosed raceway is below the open raceway. 3) For configurations that involve enclosed raceways, the minimum separation is 1 inch in both horizontal and vertical directions.
{{#Wiki_filter:ATTACHMENT TO LICENSE AMENDMENT NO. 111 TO FACILITY COMBINED LICENSE NO. NPF-92 DOCKET NO. 52-026 Replace the following pages of the Facility Combined License No. NPF-92 with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
C-431b Amendment No. 111 Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria   4) For configurations involving open configurations, and an enclosed raceway and an open raceway, with instrumentation and control cables, the minimum separation is 1 inch in both horizontal and vertical directions. 4)  For configurations that involve open configurations, and an enclosed raceway and an open raceway, with instrumentation and control cables, the minimum separation is 1 inch in both horizontal and vertical directions.
Facility Combined License No. NPF-92 REMOVE                               INSERT 7                                   7 Appendix C to Facility Combined License No. NPF-92 REMOVE                               INSERT C-431a                               C-431a
C-432 Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 800 3.3.00.07d.ii.a Inspections of the as-built raceways that route Class 1E cables will be performed to confirm that the separation between raceways that route Class 1E cables of different divisions, and between raceways that route Class 1E cables and raceways that route non-Class 1E cables is consistent with the following:
                          ---                               C-431b C-432                               C-432
C-432a Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria C-433 Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 801 3.3.00.07d.ii.b 7.d)  Physical separation is maintained between Class 1E divisions and between Class 1E divisions and non-Class 1E cables. Inspections of the as-built raceways that route Class 1E cables will be performed to confirm that the separation between raceways that route Class 1E cables of different divisions, and between raceways that route Class 1E cables and raceways that route non-Class 1E cables is consistent with the following:
                          ---                               C-432a C-433                               C-433
C-433a Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria C-434 Amendment No. 111  Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 802 3.3.00.07d.ii.c 7.d)  Physical separation is maintained between Class 1E divisions and between Class 1E divisions and non-Class 1E cables. Inspections of the as-built raceways that route Class 1E cables will be performed to confirm that the separation between raceways that route Class 1E cables of different divisions, and between raceways that route Class 1E cables and raceways that route non-Class 1E cables is consistent with the following:
                          ---                               C-433a C-434                               C-434
C-434a Amendment No. 111 Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria                                 
                          ---                               C-434a
}}
 
(7)   Reporting Requirements (a)   Within 30 days of a change to the initial test program described in FSAR Section 14, Initial Test Program, made in accordance with 10 CFR 50.59 or in accordance with 10 CFR Part 52, Appendix D, Section VIII, Processes for Changes and Departures, SNC shall report the change to the Director of NRO, or the Directors designee, in accordance with 10 CFR 50.59(d).
(b)   SNC shall report any violation of a requirement in Section 2.D.(3),
Section 2.D.(4), Section 2.D.(5), and Section 2.D.(6) of this license within [[estimated NRC review hours::24 hours]]. Initial notification shall be made to the NRC Operations Center in accordance with 10 CFR 50.72, with written follow up in accordance with 10 CFR 50.73.
(8)   Incorporation The Technical Specifications, Environmental Protection Plan, and ITAAC in Appendices A, B, and C, respectively of this license, as revised through Amendment No. 111, are hereby incorporated into this license.
(9)   Technical Specifications The technical specifications in Appendix A to this license become effective upon a Commission finding that the acceptance criteria in this license (ITAAC) are met in accordance with 10 CFR 52.103(g).
(10) Operational Program Implementation SNC shall implement the programs or portions of programs identified below, on or before the date SNC achieves the following milestones:
(a)     Environmental Qualification Program implemented before initial fuel load; (b)     Reactor Vessel Material Surveillance Program implemented before initial criticality; (c)     Preservice Testing Program implemented before initial fuel load; (d)     Containment Leakage Rate Testing Program implemented before initial fuel load; (e)     Fire Protection Program
: 1.       The fire protection measures in accordance with Regulatory Guide (RG) 1.189 for designated storage building areas (including adjacent fire areas that could affect the storage area) implemented before initial receipt 7                               Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No.           Design Commitment                   Inspections, Tests, Analyses         Acceptance Criteria 799 3.3.00.07d.i 7.d) Physical separation is maintained  Inspections of the as-built       Results of the inspection will between Class 1E divisions and          raceways that route Class 1E       confirm that the separation between Class 1E divisions and non-      cables will be performed to        between raceways that route Class 1E cables.                        confirm that the separation        Class 1E cables of different between raceways that route       divisions, and between Class 1E cables of different      raceways that route Class 1E divisions, and between raceways    cables and raceways that route that route Class 1E cables and    non-Class 1E cables is raceways that route non-Class      consistent with the following:
1E cables is consistent with the following:
i) Within the main control        i) Within the main control room and remote shutdown          room and remote shutdown room (non-hazard areas), the       room (non-hazard areas) the minimum separation for            minimum separation for low-voltage power cables and      low-voltage power cables below is defined by one of the    and below meets one of the following:                         following:
: 1) For configurations              1) For configurations involving open configurations     involving open to enclosed configurations         configurations to enclosed with low-voltage power             configurations with low-cables, the minimum vertical       voltage power cables, the separation is 3 inches and the     vertical separation is minimum horizontal                 3 inches or more and the separation is 1 inch.             horizontal separation is 1 inch or more.
: 2) For configurations              2) For configurations that involving an enclosed raceway      involve an enclosed raceway and an open raceway with          and an open raceway with low-voltage power cables, the     low-voltage power cables, minimum vertical separation is     the minimum vertical 1 inch if the enclosed raceway     separation may be reduced is below the open raceway.         to 1 inch if the enclosed raceway is below the open raceway.
: 3) For configurations involving    3) For configurations that enclosed raceways, the             involve enclosed raceways, minimum separation is 1 inch in   the minimum separation is both horizontal and vertical      1 inch in both horizontal and directions.                        vertical directions.
C-431a                              Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment                 Inspections, Tests, Analyses       Acceptance Criteria
: 4) For configurations            4) For configurations that involving open configurations,    involve open configurations, and an enclosed raceway and      and an enclosed raceway an open raceway, with            and an open raceway, with instrumentation and control       instrumentation and control cables, the minimum              cables, the minimum separation is 1 inch in both     separation is 1 inch in both horizontal and vertical          horizontal and vertical directions.                       directions.
C-431b                              Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No.             Design Commitment                   Inspections, Tests, Analyses           Acceptance Criteria 800 3.3.00.07d.ii.a 7.d) Physical separation is maintained    Inspections of the as-built         Results of the inspection will between Class 1E divisions and            raceways that route Class 1E         confirm that the separation between Class 1E divisions and non-      cables will be performed to          between raceways that route Class 1E cables.                          confirm that the separation          Class 1E cables of different between raceways that route         divisions, and between Class 1E cables of different        raceways that route Class 1E divisions, and between raceways      cables and raceways that route that route Class 1E cables and      non-Class 1E cables is raceways that route non-Class        consistent with the following:
1E cables is consistent with the following:
ii.a) Within other plant areas      ii.a) Within other plant areas (hazard areas), the minimum          inside containment (hazard separation is defined by one of      areas), the separation meets the following:                      one of the following:
: 1) The minimum vertical              1) The vertical separation is separation is 5 feet and the        5 feet or more and the minimum horizontal separation        horizontal separation is 3 feet is 3 feet.                          or more.
: 2) The minimum vertical              2) The minimum vertical separation is 12 inches and the     separation is 12 inches and the minimum horizontal separation       minimum horizontal is 6 inches for raceways             separation is 6 inches for containing only instrumentation      raceways containing only and control and low-voltage          instrumentation and control power cables 2/0 AWG. This          and low-voltage power cables minimum vertical separation is       2/0 AWG. This minimum 3 inches for the configuration      vertical separation may be with a conduit above and            reduced to 3 inches for the crossing the open tray at an        configuration with a conduit angle equal to or greater than      above and crossing the open 45 degrees.                         tray at an angle equal to or greater than 45 degrees.
: 3) The minimum vertical              3) The minimum vertical separation is 12 inches and the      separation is 12 inches and the minimum horizontal separation        minimum horizontal is 6 inches between a conduit        separation is 6 inches between and an open configuration for        a conduit and an open low- voltage power cables           configuration for low- voltage greater than 2/0 AWG but not        power cables greater than greater than 750 kcmil. The          2/0 AWG but not greater than vertical separation is 3 inches if  750 kcmil. The vertical a conduit is above and crossing      separation may be reduced to an open tray at an angle equal to   3 inches if a conduit is above or greater than 45 degrees.          and crossing an open tray at an angle equal to or greater than 45 degrees.
C-432                                  Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment                  Inspections, Tests, Analyses          Acceptance Criteria
: 4) For configurations that          4) For configurations that involve exclusively limited        involve exclusively limited energy content cables              energy content cables (instrumentation and control),      (instrumentation and control),
the minimum vertical separation    the minimum vertical is 1 inch and the minimum          separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.
: 5) For configurations involving    5) For configurations that an enclosed raceway and an          involve an enclosed raceway open raceway with low-voltage      and an open raceway with power cables, the minimum          low-voltage power cables, the vertical separation is 1 inch if    minimum vertical separation the enclosed raceway is below      is 1 inch if the enclosed the open raceway.                  raceway is below the open raceway.
: 6) For configuration involving      6) For configurations that enclosed raceways, the              involve enclosed raceways, minimum separation is 1 inch in    the minimum vertical and both horizontal and vertical        horizontal separation is 1 inch.
directions.
: 7) The minimum vertical            7) The minimum vertical separation is 1 inch and the        separation is 1 inch and the minimum horizontal separation      minimum horizontal is 1 inch for configurations with  separation is 1 inch for a non-safety conduit and a free    configurations with a non-air safety cable with low-voltage  safety conduit and a free air power cables and below.            safety cable with low-voltage power cables and below.
C-432a                                Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No.              Design Commitment                  Inspections, Tests, Analyses          Acceptance Criteria 801 3.3.00.07d.ii.b 7.d) Physical separation is maintained  Inspections of the as-built        Results of the inspection will between Class 1E divisions and          raceways that route Class 1E        confirm that the separation between Class 1E divisions and non-      cables will be performed to        between raceways that route Class 1E cables.                        confirm that the separation        Class 1E cables of different between raceways that route        divisions, and between Class 1E cables of different        raceways that route Class 1E divisions, and between raceways    cables and raceways that route that route Class 1E cables and      non-Class 1E cables is raceways that route non-Class      consistent with the following:
1E cables is consistent with the following:
ii.b) Within other plant areas      ii.b) Within other plant areas (limited hazard areas), the        inside the non-radiologically minimum separation is defined      controlled area of the auxiliary by one of the following:            building (limited hazard areas), the separation meets one of the following:
: 1) The minimum vertical            1) The vertical separation is separation is 5 feet and the        5 feet or more and the minimum horizontal separation      horizontal separation is 3 feet is 3 feet.                          or more.
: 2) The minimum vertical            2) The minimum vertical separation is 12 inches and the    separation is 12 inches and the minimum horizontal separation      minimum horizontal is 6 inches for raceways            separation is 6 inches for containing only instrumentation    raceways containing only and control and low-voltage        instrumentation and control power cables  2/0 AWG. This        and low-voltage power cables minimum vertical separation is      2/0 AWG. This minimum 3 inches for the configuration      vertical separation may be with a conduit above and            reduced to 3 inches for the crossing the open tray at an        configuration with a conduit angle equal to or greater than 45  above and crossing the open degrees.                            tray at an angle equal to or greater than 45 degrees.
C-433                                Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment                  Inspections, Tests, Analyses            Acceptance Criteria
: 3) The minimum vertical              3) The minimum vertical separation is 12 inches and the      separation is 12 inches and the minimum horizontal separation        minimum horizontal is 6 inches between a conduit        separation is 6 inches between and an open configuration for        a conduit and an open low- voltage power cables            configuration for low- voltage greater than 2/0 AWG but not        power cables greater than greater than 750 kcmil. The          2/0 AWG but not greater than vertical separation is 3 inches if  750 kcmil. The vertical a conduit is above and crossing      separation may be reduced to an open tray at an angle equal to    3 inches if a conduit is above or greater than 45 degrees.          and crossing an open tray at an angle equal to or greater than 45 degrees.
: 4) For configurations that          4) For configurations that involve exclusively limited          involve exclusively limited energy content cables                energy content cables (instrumentation and control),      (instrumentation and control),
the minimum vertical separation      the minimum vertical is 1 inch and the minimum            separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.
: 5) For configurations involving      5) For configurations that an enclosed raceway and an          involve an enclosed raceway open raceway with low-voltage        and an open raceway with power cables, the minimum            low-voltage power cables, the vertical separation is 1 inch if    minimum vertical separation the enclosed raceway is below        is 1 inch if the enclosed the open raceway.                    raceway is below the open raceway.
: 6) For configuration involving      6) For configurations that enclosed raceways, the              involve enclosed raceways, minimum separation is 1 inch in      the minimum vertical and both horizontal and vertical        horizontal separation is 1 inch directions.
: 7) The minimum vertical              7) The minimum vertical separation is 1 inch and the        separation is 1 inch and the minimum horizontal separation        minimum horizontal is 1 inch for configurations with    separation is 1 inch for a non-safety conduit and a free      configurations with a non-air safety cable with low-voltage    safety conduit and a free air power cables and below.              safety cable with low-voltage power cables and below.
C-433a                                  Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No.              Design Commitment                  Inspections, Tests, Analyses          Acceptance Criteria 802 3.3.00.07d.ii.c 7.d) Physical separation is maintained  Inspections of the as-built        Results of the inspection will between Class 1E divisions and          raceways that route Class 1E        confirm that the separation between Class 1E divisions and non-      cables will be performed to        between raceways that route Class 1E cables.                        confirm that the separation        Class 1E cables of different between raceways that route        divisions, and between Class 1E cables of different        raceways that route Class 1E divisions, and between raceways    cables and raceways that route that route Class 1E cables and      non-Class 1E cables is raceways that route non-Class      consistent with the following:
1E cables is consistent with the following:
ii.c) Within other plant areas      ii.c) Within other plant areas (limited hazard areas), the        inside the radiologically minimum separation is defined      controlled area of the auxiliary by one of the following:            building (limited hazard areas), the separation meets one of the following:
: 1) The minimum vertical            1) The vertical separation is separation is 5 feet and the        5 feet or more and the minimum horizontal separation      horizontal separation is 3 feet is 3 feet.                          or more.
: 2) The minimum vertical            2) The minimum vertical separation is 12 inches and the    separation is 12 inches and the minimum horizontal separation      minimum horizontal is 6 inches for raceways            separation is 6 inches for containing only instrumentation    raceways containing only and control and low-voltage        instrumentation and control power cables 2/0 AWG. This        and low-voltage power cables minimum vertical separation is      2/0 AWG. This minimum 3 inches for the configuration      vertical separation may be with a conduit above and            reduced to 3 inches for the crossing the open tray at an        configuration with a conduit angle equal to or greater than 45  above and crossing the open degrees.                            tray at an angle equal to or greater than 45 degrees.
C-434                                Amendment No. 111
 
Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment                  Inspections, Tests, Analyses            Acceptance Criteria
: 3) The minimum vertical              3) The minimum vertical separation is 12 inches and the      separation is 12 inches and the minimum horizontal separation        minimum horizontal is 6 inches between a conduit        separation is 6 inches between and an open configuration for        a conduit and an open low- voltage power cables            configuration for low- voltage greater than 2/0 AWG but not        power cables greater than greater than 750 kcmil. The          2/0 AWG but not greater than vertical separation is 3 inches if  750 kcmil. The vertical a conduit is above and crossing      separation may be reduced to an open tray at an angle equal to    3 inches if a conduit is above or greater than 45 degrees.          and crossing an open tray at an angle equal to or greater than 45 degrees.
: 4) For configurations that          4) For configurations that involve exclusively limited          involve exclusively limited energy content cables                energy content cables (instrumentation and control),      (instrumentation and control),
the minimum vertical separation      the minimum vertical is 1 inch and the minimum            separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.
: 5) For configurations involving      5) For configurations that an enclosed raceway and an          involve an enclosed raceway open raceway with low-voltage        and an open raceway with power cables, the minimum            low-voltage power cables, the vertical separation is 1 inch if    minimum vertical separation the enclosed raceway is below        is 1 inch if the enclosed the open raceway.                    raceway is below the open raceway.
: 6) For configuration involving      6) For configurations that enclosed raceways, the              involve enclosed raceways, minimum separation is 1 inch in      the minimum vertical and both horizontal and vertical        horizontal separation is 1 inch.
directions.
: 7) The minimum vertical              7) The minimum vertical separation is 1 inch and the        separation is 1 inch and the minimum horizontal separation        minimum horizontal is 1 inch for configurations with    separation is 1 inch for a non-safety conduit and a free      configurations with a non-air safety cable with low-voltage    safety conduit and a free air power cables and below.              safety cable with low-voltage power cables and below.
C-434a                                  Amendment No. 111}}

Latest revision as of 20:25, 7 March 2020

Attachment - Vogtle Electric Generating Plant Unit 4 Amendment 111 (LAR-17-036)
ML18040B084
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 03/06/2018
From: Chandu Patel
NRC/NRO/DNRL/LB4
To: Whitley B
Southern Nuclear Operating Co
patel c/415-3025
Shared Package
ML18040B074 List:
References
EPID L-2017-LLA-0104, LAR 17-036
Download: ML18040B084 (10)


Text

ATTACHMENT TO LICENSE AMENDMENT NO. 111 TO FACILITY COMBINED LICENSE NO. NPF-92 DOCKET NO.52-026 Replace the following pages of the Facility Combined License No. NPF-92 with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

Facility Combined License No. NPF-92 REMOVE INSERT 7 7 Appendix C to Facility Combined License No. NPF-92 REMOVE INSERT C-431a C-431a

--- C-431b C-432 C-432

--- C-432a C-433 C-433

--- C-433a C-434 C-434

--- C-434a

(7) Reporting Requirements (a) Within 30 days of a change to the initial test program described in FSAR Section 14, Initial Test Program, made in accordance with 10 CFR 50.59 or in accordance with 10 CFR Part 52, Appendix D, Section VIII, Processes for Changes and Departures, SNC shall report the change to the Director of NRO, or the Directors designee, in accordance with 10 CFR 50.59(d).

(b) SNC shall report any violation of a requirement in Section 2.D.(3),

Section 2.D.(4), Section 2.D.(5), and Section 2.D.(6) of this license within 24 hours1 days <br />0.143 weeks <br />0.0329 months <br />. Initial notification shall be made to the NRC Operations Center in accordance with 10 CFR 50.72, with written follow up in accordance with 10 CFR 50.73.

(8) Incorporation The Technical Specifications, Environmental Protection Plan, and ITAAC in Appendices A, B, and C, respectively of this license, as revised through Amendment No. 111, are hereby incorporated into this license.

(9) Technical Specifications The technical specifications in Appendix A to this license become effective upon a Commission finding that the acceptance criteria in this license (ITAAC) are met in accordance with 10 CFR 52.103(g).

(10) Operational Program Implementation SNC shall implement the programs or portions of programs identified below, on or before the date SNC achieves the following milestones:

(a) Environmental Qualification Program implemented before initial fuel load; (b) Reactor Vessel Material Surveillance Program implemented before initial criticality; (c) Preservice Testing Program implemented before initial fuel load; (d) Containment Leakage Rate Testing Program implemented before initial fuel load; (e) Fire Protection Program

1. The fire protection measures in accordance with Regulatory Guide (RG) 1.189 for designated storage building areas (including adjacent fire areas that could affect the storage area) implemented before initial receipt 7 Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 799 3.3.00.07d.i 7.d) Physical separation is maintained Inspections of the as-built Results of the inspection will between Class 1E divisions and raceways that route Class 1E confirm that the separation between Class 1E divisions and non- cables will be performed to between raceways that route Class 1E cables. confirm that the separation Class 1E cables of different between raceways that route divisions, and between Class 1E cables of different raceways that route Class 1E divisions, and between raceways cables and raceways that route that route Class 1E cables and non-Class 1E cables is raceways that route non-Class consistent with the following:

1E cables is consistent with the following:

i) Within the main control i) Within the main control room and remote shutdown room and remote shutdown room (non-hazard areas), the room (non-hazard areas) the minimum separation for minimum separation for low-voltage power cables and low-voltage power cables below is defined by one of the and below meets one of the following: following:

1) For configurations 1) For configurations involving open configurations involving open to enclosed configurations configurations to enclosed with low-voltage power configurations with low-cables, the minimum vertical voltage power cables, the separation is 3 inches and the vertical separation is minimum horizontal 3 inches or more and the separation is 1 inch. horizontal separation is 1 inch or more.
2) For configurations 2) For configurations that involving an enclosed raceway involve an enclosed raceway and an open raceway with and an open raceway with low-voltage power cables, the low-voltage power cables, minimum vertical separation is the minimum vertical 1 inch if the enclosed raceway separation may be reduced is below the open raceway. to 1 inch if the enclosed raceway is below the open raceway.
3) For configurations involving 3) For configurations that enclosed raceways, the involve enclosed raceways, minimum separation is 1 inch in the minimum separation is both horizontal and vertical 1 inch in both horizontal and directions. vertical directions.

C-431a Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria

4) For configurations 4) For configurations that involving open configurations, involve open configurations, and an enclosed raceway and and an enclosed raceway an open raceway, with and an open raceway, with instrumentation and control instrumentation and control cables, the minimum cables, the minimum separation is 1 inch in both separation is 1 inch in both horizontal and vertical horizontal and vertical directions. directions.

C-431b Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 800 3.3.00.07d.ii.a 7.d) Physical separation is maintained Inspections of the as-built Results of the inspection will between Class 1E divisions and raceways that route Class 1E confirm that the separation between Class 1E divisions and non- cables will be performed to between raceways that route Class 1E cables. confirm that the separation Class 1E cables of different between raceways that route divisions, and between Class 1E cables of different raceways that route Class 1E divisions, and between raceways cables and raceways that route that route Class 1E cables and non-Class 1E cables is raceways that route non-Class consistent with the following:

1E cables is consistent with the following:

ii.a) Within other plant areas ii.a) Within other plant areas (hazard areas), the minimum inside containment (hazard separation is defined by one of areas), the separation meets the following: one of the following:

1) The minimum vertical 1) The vertical separation is separation is 5 feet and the 5 feet or more and the minimum horizontal separation horizontal separation is 3 feet is 3 feet. or more.
2) The minimum vertical 2) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches for raceways separation is 6 inches for containing only instrumentation raceways containing only and control and low-voltage instrumentation and control power cables 2/0 AWG. This and low-voltage power cables minimum vertical separation is 2/0 AWG. This minimum 3 inches for the configuration vertical separation may be with a conduit above and reduced to 3 inches for the crossing the open tray at an configuration with a conduit angle equal to or greater than above and crossing the open 45 degrees. tray at an angle equal to or greater than 45 degrees.
3) The minimum vertical 3) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches between a conduit separation is 6 inches between and an open configuration for a conduit and an open low- voltage power cables configuration for low- voltage greater than 2/0 AWG but not power cables greater than greater than 750 kcmil. The 2/0 AWG but not greater than vertical separation is 3 inches if 750 kcmil. The vertical a conduit is above and crossing separation may be reduced to an open tray at an angle equal to 3 inches if a conduit is above or greater than 45 degrees. and crossing an open tray at an angle equal to or greater than 45 degrees.

C-432 Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria

4) For configurations that 4) For configurations that involve exclusively limited involve exclusively limited energy content cables energy content cables (instrumentation and control), (instrumentation and control),

the minimum vertical separation the minimum vertical is 1 inch and the minimum separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.

5) For configurations involving 5) For configurations that an enclosed raceway and an involve an enclosed raceway open raceway with low-voltage and an open raceway with power cables, the minimum low-voltage power cables, the vertical separation is 1 inch if minimum vertical separation the enclosed raceway is below is 1 inch if the enclosed the open raceway. raceway is below the open raceway.
6) For configuration involving 6) For configurations that enclosed raceways, the involve enclosed raceways, minimum separation is 1 inch in the minimum vertical and both horizontal and vertical horizontal separation is 1 inch.

directions.

7) The minimum vertical 7) The minimum vertical separation is 1 inch and the separation is 1 inch and the minimum horizontal separation minimum horizontal is 1 inch for configurations with separation is 1 inch for a non-safety conduit and a free configurations with a non-air safety cable with low-voltage safety conduit and a free air power cables and below. safety cable with low-voltage power cables and below.

C-432a Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 801 3.3.00.07d.ii.b 7.d) Physical separation is maintained Inspections of the as-built Results of the inspection will between Class 1E divisions and raceways that route Class 1E confirm that the separation between Class 1E divisions and non- cables will be performed to between raceways that route Class 1E cables. confirm that the separation Class 1E cables of different between raceways that route divisions, and between Class 1E cables of different raceways that route Class 1E divisions, and between raceways cables and raceways that route that route Class 1E cables and non-Class 1E cables is raceways that route non-Class consistent with the following:

1E cables is consistent with the following:

ii.b) Within other plant areas ii.b) Within other plant areas (limited hazard areas), the inside the non-radiologically minimum separation is defined controlled area of the auxiliary by one of the following: building (limited hazard areas), the separation meets one of the following:

1) The minimum vertical 1) The vertical separation is separation is 5 feet and the 5 feet or more and the minimum horizontal separation horizontal separation is 3 feet is 3 feet. or more.
2) The minimum vertical 2) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches for raceways separation is 6 inches for containing only instrumentation raceways containing only and control and low-voltage instrumentation and control power cables 2/0 AWG. This and low-voltage power cables minimum vertical separation is 2/0 AWG. This minimum 3 inches for the configuration vertical separation may be with a conduit above and reduced to 3 inches for the crossing the open tray at an configuration with a conduit angle equal to or greater than 45 above and crossing the open degrees. tray at an angle equal to or greater than 45 degrees.

C-433 Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria

3) The minimum vertical 3) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches between a conduit separation is 6 inches between and an open configuration for a conduit and an open low- voltage power cables configuration for low- voltage greater than 2/0 AWG but not power cables greater than greater than 750 kcmil. The 2/0 AWG but not greater than vertical separation is 3 inches if 750 kcmil. The vertical a conduit is above and crossing separation may be reduced to an open tray at an angle equal to 3 inches if a conduit is above or greater than 45 degrees. and crossing an open tray at an angle equal to or greater than 45 degrees.
4) For configurations that 4) For configurations that involve exclusively limited involve exclusively limited energy content cables energy content cables (instrumentation and control), (instrumentation and control),

the minimum vertical separation the minimum vertical is 1 inch and the minimum separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.

5) For configurations involving 5) For configurations that an enclosed raceway and an involve an enclosed raceway open raceway with low-voltage and an open raceway with power cables, the minimum low-voltage power cables, the vertical separation is 1 inch if minimum vertical separation the enclosed raceway is below is 1 inch if the enclosed the open raceway. raceway is below the open raceway.
6) For configuration involving 6) For configurations that enclosed raceways, the involve enclosed raceways, minimum separation is 1 inch in the minimum vertical and both horizontal and vertical horizontal separation is 1 inch directions.
7) The minimum vertical 7) The minimum vertical separation is 1 inch and the separation is 1 inch and the minimum horizontal separation minimum horizontal is 1 inch for configurations with separation is 1 inch for a non-safety conduit and a free configurations with a non-air safety cable with low-voltage safety conduit and a free air power cables and below. safety cable with low-voltage power cables and below.

C-433a Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria 802 3.3.00.07d.ii.c 7.d) Physical separation is maintained Inspections of the as-built Results of the inspection will between Class 1E divisions and raceways that route Class 1E confirm that the separation between Class 1E divisions and non- cables will be performed to between raceways that route Class 1E cables. confirm that the separation Class 1E cables of different between raceways that route divisions, and between Class 1E cables of different raceways that route Class 1E divisions, and between raceways cables and raceways that route that route Class 1E cables and non-Class 1E cables is raceways that route non-Class consistent with the following:

1E cables is consistent with the following:

ii.c) Within other plant areas ii.c) Within other plant areas (limited hazard areas), the inside the radiologically minimum separation is defined controlled area of the auxiliary by one of the following: building (limited hazard areas), the separation meets one of the following:

1) The minimum vertical 1) The vertical separation is separation is 5 feet and the 5 feet or more and the minimum horizontal separation horizontal separation is 3 feet is 3 feet. or more.
2) The minimum vertical 2) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches for raceways separation is 6 inches for containing only instrumentation raceways containing only and control and low-voltage instrumentation and control power cables 2/0 AWG. This and low-voltage power cables minimum vertical separation is 2/0 AWG. This minimum 3 inches for the configuration vertical separation may be with a conduit above and reduced to 3 inches for the crossing the open tray at an configuration with a conduit angle equal to or greater than 45 above and crossing the open degrees. tray at an angle equal to or greater than 45 degrees.

C-434 Amendment No. 111

Table 3.3-6 Inspections, Tests, Analyses, and Acceptance Criteria No. ITAAC No. Design Commitment Inspections, Tests, Analyses Acceptance Criteria

3) The minimum vertical 3) The minimum vertical separation is 12 inches and the separation is 12 inches and the minimum horizontal separation minimum horizontal is 6 inches between a conduit separation is 6 inches between and an open configuration for a conduit and an open low- voltage power cables configuration for low- voltage greater than 2/0 AWG but not power cables greater than greater than 750 kcmil. The 2/0 AWG but not greater than vertical separation is 3 inches if 750 kcmil. The vertical a conduit is above and crossing separation may be reduced to an open tray at an angle equal to 3 inches if a conduit is above or greater than 45 degrees. and crossing an open tray at an angle equal to or greater than 45 degrees.
4) For configurations that 4) For configurations that involve exclusively limited involve exclusively limited energy content cables energy content cables (instrumentation and control), (instrumentation and control),

the minimum vertical separation the minimum vertical is 1 inch and the minimum separation is 1 inch and the horizontal separation is 1 inch. minimum horizontal separation is 1 inch.

5) For configurations involving 5) For configurations that an enclosed raceway and an involve an enclosed raceway open raceway with low-voltage and an open raceway with power cables, the minimum low-voltage power cables, the vertical separation is 1 inch if minimum vertical separation the enclosed raceway is below is 1 inch if the enclosed the open raceway. raceway is below the open raceway.
6) For configuration involving 6) For configurations that enclosed raceways, the involve enclosed raceways, minimum separation is 1 inch in the minimum vertical and both horizontal and vertical horizontal separation is 1 inch.

directions.

7) The minimum vertical 7) The minimum vertical separation is 1 inch and the separation is 1 inch and the minimum horizontal separation minimum horizontal is 1 inch for configurations with separation is 1 inch for a non-safety conduit and a free configurations with a non-air safety cable with low-voltage safety conduit and a free air power cables and below. safety cable with low-voltage power cables and below.

C-434a Amendment No. 111