{{#Wiki_filter:BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD | {{#Wiki_filter:BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD In the Matter of ) | ||
In the Matter of ) | |||
) Docket Nos. | ) Docket Nos. | ||
SOUTHERN CALIFORNIA EDISON COMPANY ) San Onofre 50-361 and 50-362-LA | SOUTHERN CALIFORNIA EDISON COMPANY ) San Onofre 50-361 and 50-362-LA | ||
Line 36: | Line 34: | ||
-------------------NOTE-------------------- | -------------------NOTE-------------------- | ||
Only required to be performed during RCS heatup and cooldown operations and RCS inservice leak and hydrostatic testing. | Only required to be performed during RCS heatup and cooldown operations and RCS inservice leak and hydrostatic testing. | ||
Verify RCS pressure, RCS temperature, and RCS heatup and cooldown rates within limits 51, 59, 72 3.4.3.1 specified in the PTLR. 30 minutes Removed requirement to check 3.4.3.2 irradiation specimen 88, 89, 95 3.4.4.1 Verify each RCS loop is in operation. 12 hours 108, 111, 121 3.4.5.1 Verify RCS loop is in operation. 12 hours Verify secondary side water level in each steam generator >= | Verify RCS pressure, RCS temperature, and RCS heatup and cooldown rates within limits 51, 59, 72 3.4.3.1 specified in the PTLR. 30 minutes Removed requirement to check 3.4.3.2 irradiation specimen 88, 89, 95 3.4.4.1 Verify each RCS loop is in operation. 12 hours 108, 111, 121 3.4.5.1 Verify RCS loop is in operation. 12 hours Verify secondary side water level in each steam generator >= | ||
108, 111, 121 3.4.5.2 50% 12 hours Verify correct breaker alignment and indicated power available to each required 108, 111, 121 3.4.5.3 pump (that is not in operation) 7 days 138, 143, 155 3.4.6.1 Verify required RCS loop or SDC train is in operation. 12 hours Verify secondary side water level in 138, 143, 155 3.4.6.2 required SG(s) is >= 50% 12 hours | 108, 111, 121 3.4.5.2 50% 12 hours Verify correct breaker alignment and indicated power available to each required 108, 111, 121 3.4.5.3 pump (that is not in operation) 7 days 138, 143, 155 3.4.6.1 Verify required RCS loop or SDC train is in operation. 12 hours Verify secondary side water level in 138, 143, 155 3.4.6.2 required SG(s) is >= 50% 12 hours | ||
-------------------------------NOTE------------------------------ | -------------------------------NOTE------------------------------ | ||
Not required to be performed until 24 hours after a required pump is not in operation. | Not required to be performed until 24 hours after a required pump is not in operation. | ||
Verify correct breaker alignment and indicated power 138, 143, 155 3.4.6.3 available to each required pump. 7 days 174, 179, 192 3.4.7.1 Verify required SDC train is in operation 12 hours | Verify correct breaker alignment and indicated power 138, 143, 155 3.4.6.3 available to each required pump. 7 days 174, 179, 192 3.4.7.1 Verify required SDC train is in operation 12 hours | ||
Line 47: | Line 43: | ||
-------------------------------NOTE------------------------------ | -------------------------------NOTE------------------------------ | ||
Not required to be performed until 24 hours after a required pump is not in operation. | Not required to be performed until 24 hours after a required pump is not in operation. | ||
Verify correct breaker alignment and indicated power 174, 179, 192 3.4.7.3 available to each required SDC pump. 7 days 208, 211, 221 3.4.8.1 Verify required SDC train is in operation 12 hours | Verify correct breaker alignment and indicated power 174, 179, 192 3.4.7.3 available to each required SDC pump. 7 days 208, 211, 221 3.4.8.1 Verify required SDC train is in operation 12 hours | ||
-------------------------------NOTE------------------------------ | -------------------------------NOTE------------------------------ |
Latest revision as of 09:54, 6 February 2020
ML12337A011 | |
Person / Time | |
---|---|
Site: | San Onofre |
Issue date: | 12/02/2012 |
From: | Lutz R Citizens Oversight Projects (COPS) |
To: | Atomic Safety and Licensing Board Panel |
SECY RAS | |
References | |
12-923-01-LA-BD01, RAS 23813, 50-361-LA, 50-362-LA | |
Download: ML12337A011 (8) | |
Text
BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD In the Matter of )
) Docket Nos.
SOUTHERN CALIFORNIA EDISON COMPANY ) San Onofre 50-361 and 50-362-LA
)
(San Onofre Nuclear Generating Station) ) December 2, 2012
_______________________________________________ )
ADDENDUM TO CITIZENS OVERSIGHT'S ANSWER TO SUBMISSIONS BY NRC STAFF AND SOUTHERN CALIFORNIA EDISON OPPOSING THE PETITION TO INTERVENE AND REQUEST FOR A HEARING BY CITIZENS OVERSIGHT.
The following table "EXHIBIT A" is an extraction from the proposed changes to the San Onofre License Technical Specifications regarding the Reactor Cooling System (RCS). This is a direct extraction from Attachment 1 Vol 7, Chapter 3.4 "Reactor Coolant System (RCS)" -
(ADAMS accession number ML11251A100). There are no arguments or statements by Citizens' Oversight in this addendum.
In this table, the licensee proposes that the Surveillance Frequency specification is to be replaced with the phrase "According to the Surveillance Frequency Control Program." There are approximately 53 instances of specifications being relocated in this single attachment of the Technical Specifications, and there are a total of 15 such attachments.
Citizens' Oversight will refer to this table in the scheduled Oral Arguments proceeding of December 5, 2012.
This concludes the introductory remarks about this addendum.
Page 1
EXHIBIT A - TABLE OF CHANGES TO THE RCS TECHNICAL SPECIFICATIONS Surveillance Page Desig Desc Frequency Comment Verify pressurizer pressure is within the limits specified in the 6, 9 3.4.1.1 COLR. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Verify RCS cold leg temperature is within the limits specified in 6, 9 3.4.1.2 the COLR. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Verify RCS total flow rate is greater than or equal to the limits also deletes phrase stating 7, 10 3.4.1.3 specified in the COLR. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> check performed in Mode 1.
31, 32 3.4.2.1 Verify RCS Tc in each loop >= 522 degrees F. 30 minutes 39 3.4.2.1 Verify RCS Tc in each loop >= 522 degrees F. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
NOTE--------------------
Only required to be performed during RCS heatup and cooldown operations and RCS inservice leak and hydrostatic testing.
Verify RCS pressure, RCS temperature, and RCS heatup and cooldown rates within limits 51, 59, 72 3.4.3.1 specified in the PTLR. 30 minutes Removed requirement to check 3.4.3.2 irradiation specimen 88, 89, 95 3.4.4.1 Verify each RCS loop is in operation. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 108, 111, 121 3.4.5.1 Verify RCS loop is in operation. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Verify secondary side water level in each steam generator >=
108, 111, 121 3.4.5.2 50% 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Verify correct breaker alignment and indicated power available to each required 108, 111, 121 3.4.5.3 pump (that is not in operation) 7 days 138, 143, 155 3.4.6.1 Verify required RCS loop or SDC train is in operation. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Verify secondary side water level in 138, 143, 155 3.4.6.2 required SG(s) is >= 50% 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
NOTE------------------------------
Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.
Verify correct breaker alignment and indicated power 138, 143, 155 3.4.6.3 available to each required pump. 7 days 174, 179, 192 3.4.7.1 Verify required SDC train is in operation 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
174, 179, 192 3.4.7.2 Verify required SG secondary side water level is > 50% 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
NOTE------------------------------
Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.
Verify correct breaker alignment and indicated power 174, 179, 192 3.4.7.3 available to each required SDC pump. 7 days 208, 211, 221 3.4.8.1 Verify required SDC train is in operation 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
NOTE------------------------------
Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.
Verify correct breaker alignment and indicated power available to 208, 211, 221 3.4.8.2 required SDC pump (that is not in operation) 7 days 234, 236, 244 3.4.9.1 Verify pressurizer water level <= 57%. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 234, 236 3.4.9.2 Verify capacity of each group of pressurizer heaters >= 150 kW 92 days 244 3.4.9.2 Verify capacity of each group of pressurizer heaters >= 150 kW 18 months differs from other sections Verify that the SDCS Relief Valve isolation valves 2HV9337, 2HV9339, 262, 266 3.4.12.2.1 2HV9377, and 2HV9378 are open. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> In accordance with the Inservice Testing Program (no 262, 266 3.4.12.2.2 Verify relief valve setpoint constraints )
Verify each pressurizer safety valve is OPERABLE in accordance with inservice testing program. Following testing, asfound lift settings shall be within +3% or 3.4.10.1 -2%. However, pressurizer safety valves In accordance with the or shall be set to within +/-1% of the specified Inservice Testing Program (no 262, 266 3.4.10.3 setpoint. constraints )
3..4.12.1. Verify a maximum of two HPSI pumps are 297, 302, 318 1 capable of injecting into the RCS. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 3..4.12.1.
297, 302, 318 2 Verify each SIT is isolated 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for unlocked open vent valve(s)
AND 31 days for locked, sealed, or otherwise secured open vent valve(s),
or open flanged 3..4.12.1. Verify RCS vent >= 5.6 square inches is RCS 297, 302, 318 3 open penetrations Verify the OPERABLE SDCS Relief Valve isolation valve pair (valve pair 2HV9337 and 2HV9339, or valve pair 2HV9377 and 2HV9378) is in the power-lock open 297, 302, 318 3.4.12.1.4 condition. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Not proposed moved to SFCP Verify that SDCS Relief Valve isolation valves 2HV9337, 2HV9339, 2HV9377, and 297, 302, 318 3.4.12.1.5 2HV9378 are open 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Verify required SDCS System relief valve Setpoint is within In accordance with the 297, 302, 318 3.4.12.1.6 limits. Inservice Testing Program To minimize the potential for a low temperature overpressure event by limiting the mass input capability, not more than two HPSI pumps are verified OPERABLE with the other pump locked out with power removed and the SIT discharge incapable of injecting into the RCS. The HPSI pump is rendered incapable of injecting into the RCS through removing the power from the pump by racking the breakers out under administrative control. An alternate method of LTOP control may be employed using at least two independent means to prevent a pump start such that a single failure or single action will not result in an injection into the RCS. This may be accomplished through the pump control 3.4.12.1 & switch being placed in pull to lock and at least one valve in the 336-340 3.4.2 discharge flow path being closed 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
requires verifying that the required RCS vent is open
[1.3] square inches is proven OPERABLE by verifying its open condition or the valve is locked closed and power is removed. Additionally, the SIT discharge isolation valves are 336-340 3.4.12.3 verified closed and deactivated See below
- a. Once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for a valve that is unlocked open (valves that are sealed or secured in the open position are considered "locked" in this context) or
- b. Once every 31 days for other vent path(s) (e.g., a vent valve that is locked, sealed, or secured in position, a removed pressurizer safety valve, or open manway).
336-340 3.4.12.4 This SR verifies the valves are open to confirm the flow paths. see above The SDC System relief valve setpoint is verified periodically to 336-340 3.4.12.5 be within limits 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> page 360 has a description of leakage, page 443 says this Not required to be performed in MODE 3 or 4 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> of SR is performed at increased steady state operation. Not applicable to primary to secondary frequency of 24 and 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
LEAKAGE. Verify RCS operational LEAKAGE is within limits by There is no note about move to 347, 349, 357 3.4.13.1 performance of RCS. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> SFCP.
NOTE--------------------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishment of steady state operation.
Verify primary to secondary LEAKAGE is 347, 349, 357 3.4.13.2 < 150 gallons per day through any one SG. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />
In accordance with the Inservice Testing Program or 24 months AND Prior to entering MODE 2
NOTES------------------- whenever the
- 1. Not required to be performed in unit has been MODES 3 and 4. in MODE 5 for
- 2. Not required to be performed on the 7 days or more, RCS PIVs located in the SDC flow path if leakage when in the shutdown cooling mode of testing has not operation. been performed
- 3. RCS PIVs actuated during the in the previous performance of this Surveillance are 9 months not required to be tested more than AND Within 48 once if a repetitive testing loop hours cannot be avoided. following valve
actuation due Verify leakage from each RCS PIV specified to automatic or in Table 3.4.14-1 is equivalent to manual action
- 0.5 gpm per nominal inch of valve size up or flow through to a maximum of 5 gpm at an RCS pressure the valve for 377, 385, 399 3.4.14.1 $ 2215 psia and # 2255 psia. valves Verify SDC System interlock function prevents the valves from being opened with a simulated or actual 377, 385, 399 3.4.14.2 RCS pressure signal 380 psia 18 months 407 3.4.14.1 [PIV Valve] 9 to 18 months 409 3.4.14.2 [SDC Interlocks] 18 months Perform CHANNEL CHECK of the required containment atmosphere gaseous 420, 425, 437 3.4.15.1 radioactivity monitor. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Perform CHANNEL CHECK of the required containment atmosphere particulate 420, 425, 437 3.4.15.2 radioactivity monitor. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Perform CHANNEL FUNCTIONAL TEST of the required containment atmosphere gaseous 420, 425, 437 3.4.15.3 radioactivity monitor. 92 days
Perform CHANNEL FUNCTIONAL TEST of the required containment atmosphere particulate 420, 425, 437 3.4.15.4 radioactivity monitor. 92 days Perform CHANNEL CALIBRATION of the required 420, 425, 437 3.4.15.5 containment sump monitor. 24 months Perform CHANNEL CALIBRATION of the required containment atmosphere gaseous 420, 425, 437 3.4.15.6 radioactivity monitor. 24 months Perform CHANNEL CALIBRATION of the required containment atmosphere particulate 420, 425, 437 3.4.15.7 radioactivity monitor. 24 months Verify reactor coolant DOSE EQUIVALENT XE-133 458, 463, 476 3.4.16.1 specific activity <= 500 mCi/gm. 7 days Verify reactor coolant DOSE EQUIVALENT I-131 specific activity 458, 463, 476 3.4.16.2 # 1.0 Ci/gm. 14 days (+ text)
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of )
)
SOUTHERN CALIFORNIA EDISON, CO. )
)
(San Onofre Nuclear Generating Station - ) Docket Nos. 50-361-LA and 50-362-LA Units 2 and 3) )
CERTIFICATE OF SERVICE I hereby certify that copies of the foregoing document "ADDENDUM TO CITIZENS OVERSIGHT'S ANSWER TO SUBMISSIONS BY NRC STAFF AND SOUTHERN CALIFORNIA EDISON OPPOSING THE PETITION TO INTERVENE AND REQUEST FOR A HEARING BY CITIZENS OVERSIGHT" have been served upon the parties by the Electronic Information Exchange.
Respectfully submitted,
/s/ Raymond Lutz Raymond Lutz Citizens Oversight Projects (COPS) 771 Jamacha Road Suite 148 El Cajon, CA, 92020 Tel: (619) 447-3246 Email: raylutz@citizensoversight.org Date: December 2, 2012