ML18023B246: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
(2 intermediate revisions by the same user not shown) | |||
Line 2: | Line 2: | ||
| number = ML18023B246 | | number = ML18023B246 | ||
| issue date = 10/05/2017 | | issue date = 10/05/2017 | ||
| title = | | title = Updated Final Safety Analysis Report (Ufsar), Amendment 27, 11.6 Table - Condenser Circulating Water | ||
| author name = | | author name = | ||
| author affiliation = Tennessee Valley Authority | | author affiliation = Tennessee Valley Authority | ||
Line 16: | Line 16: | ||
=Text= | =Text= | ||
{{#Wiki_filter:BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions) | {{#Wiki_filter:BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions) | ||
Cooling Tower No. 1 2 3 4 5 6 7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5}} |
Latest revision as of 03:19, 22 October 2019
Text
BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions)
Cooling Tower No. 1 2 3 4 5 6 7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5