U-601078, Advises That Part 21 Defect 21-87-03 Re Damaged High Pressure Core Spray Diesel Generator Exciter Leads Will Be Replaced During Dec 1987 Instead of During Fall Maint Outage Due to Schedule Constraints

From kanterella
Jump to navigation Jump to search
Advises That Part 21 Defect 21-87-03 Re Damaged High Pressure Core Spray Diesel Generator Exciter Leads Will Be Replaced During Dec 1987 Instead of During Fall Maint Outage Due to Schedule Constraints
ML20236K642
Person / Time
Site: Clinton Constellation icon.png
Issue date: 11/03/1987
From: Hall D
ILLINOIS POWER CO.
To: Davis A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-PT21-87, REF-PT21-87-198-000 21-87-03, 21-87-3, PT21-87-198, PT21-87-198-000, U-601078, NUDOCS 8711090294
Download: ML20236K642 (1)


Text

.1 0d' U-601078.

L16-87 (11 -03 ) -L 1A.120

/LLINDIS POWER 00MPANY

, CLINTON POWER $tATION, P.O. BOX C78. CLINTON, ILbN IS 61727 f

November 3,.1987_

~

Docket No. 50-461 1

Mr. A. B. Davis. .J Regional Administrator j i.egion III U.S. Nuclear Regulatory Commission l 799 Roosevelt Road '!

' Glen Ellyn, Illinois. 60137

Subject:

10CFR21 Defect 21-87-03: -]

HPCS (Division III) DIESEL GENERATOR EXCITER LEADS' 1

.j

Dear Mr. Davis:

Illinois Power Company. reported'a 10CFR21 defect j concerning damaged High Pressure Core Spray (Division'III). 1 Diesel Generator Exciter LeadsLby. Illinois Power. Company-Letter U-601030 dated 9/8/87. The letter indicates that-l the exciter leads'will be replaced-during the Fall i l Maintenance Outage planned for October-1987. Due to. i schedule constraints,- the exciter leads' will not Int replaced during the Fall Maintenance-Outage. .The .

replacement has been rescheduled and will occur;during the-j month of December 1987. Nuclear Station' Engineering' l Department has evaluated the? temporary repair on the l exciter leads that was completed on August.13, 1987, under l

Temporary Modification 87-130 and has' determined that the.

temporary repair is adequate for continued ~ operation 1of the diesel generator until the exciter leads are replaced i during the month of December 1987.

Sincerely yours, l

.. . Hall-Vice President a

l RSF/krm L cc: USNRC Resident Office; V-690 Director'of Inspection-and Enforcement;(3 copies)"

INPO Records Center i Illinois Department of Nuclear' Safety i Energy Systems Division f

8711090294 871103 '