United Controls p !- International,Inc.
1554 Litton Drive Stone Mountain, GA 30083-1302 Phone: (770) 496-0884 FAX: (770) 496 7097 l
March 7,1997 Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555
Reference:
Docket No. 50-461,10CFR21 Final Report 21-97-004: Phoenix Power Systems Regulated Power Transformer Supplied and Qualified by United Controls International
Subject:
United Control Internationals reponse to the referenced filing
Dear Madam or Sir:
United Controls International (UCI) has carefully reviewed the referenced 10CFR, Part 21 filing, along with the applicable Illinois Power purchase order (PO552512) and associated specification. The following comments are offered in an effort to provide you with information which Illinois Power failed to report.
- 1. The referenced document states:"the purchase specification for the power transformer supplied requires voltage control from the no load condition to unit rating. Contrary to this requirement, IP has found that the transformer is not stable in the no load condition and trips when lightly loaded under various plant conditions."
A. This statement is partially true in that the specification (applicable excerpts included as Attachment I to this letter, along with the purchase order) states in division 3, section 301 that: "the transformer shall have a guaranteed output voltage of 117 volts
- 3% over an output power range of 0 to 15 KVA." The transformer provided is a Phoenix model P3C015C6/EAN which has operating specifications which require it to have a guaranteed output voltage of 117 volts
- 3% over an output power range of 0 to 15 KVA. The transformer is however reliable in the no load condition. In fact, this has been stated in a letter from Phoenix design engineer Todd Desiato (see Attachment 2 to this letter). In addition, enclosed is a copy of documented functional tests (Attachment 3), for each of the transformers supplied, which demonstrates that the transformer did perform reliably, within spec. requirements at no load.
9703120404 970307
[
/
PDR ADOCK 05000461 S
m as A..t z_a._
Page Two
- 2. The referenced document states:"lP has been advised by the manufacturer that the transformer units require a minimum load of 2 amps per phase to remain stable." This statement is misleading in that the transformer does skip from one tap to another, basically hunting for a load, when it is unloaded; however, the transformers input circuit breaker does not trip under these conditions. The transformer does perform reliably and provide the required output while under no load conditions as discussed in point 1, above. What is not mentioned by lilinois Power in the referenced Part 21 filing is that it was determined that the problem occuring, at Clinton Power Station, with these transformers was an EMI/RFI susceptability problem. When the manufacturer of the transformer (Phoenix Power Systems) was contacted, Illinois Power had provided them with a recorded output waveform that identified some type of spikes or noise occuring on the output of one phase of the transformer,just prior to the transfonriers input breaker tripping. Phoenix, upon review of this waveform, recommended to Illinois Power to apply a minimum load (approximately 5% of full load) in order to provide stable operation.
Phoenix made an assumption that the increased output current would decrease the affects of the apparent noise and therefore " stabilize" transformer operation. This approach did not reliably fix the problem; therefore, Illinois Power requested United Controls via Purchase Order PO704980 (Attachment 4) to perform EMI/RFI testing on the transformer in order to detennine problem frequencies and resolve the tripping problem.
- 3. The referenced document states on page 2 section vii that: "IP and representatives of United Controls are working on a network of filters / surge suppressors and minimum load resistors to eliminate the tripping problem." This is true; however, the effort has been temporarily halted by Illinois Power. Again the purpose of this " network"is to resolve the EMI/RFI susceptability problem with the transformers as stated in point 2, above. It should be noted that the original purchase order and specification to United Controls (see Attachment 1) did not request EMI/RFI testing to be performed.
United Controls International believes that the above comments as well as the attached documentation of the involved purchase order and specifications provides documented evidence that all transformers provided to Illinois Power meet the requirements of the applicable purchase order. Ifyou have any further questions in regard to this issue or need any additional information, please feel free to contact Mike LeBlanc, Director of Nuclear Engineering, Deborah Butler, QA Manager or me (Ben Camp).
i Sincerely; sh 0
Benfamp 7
President, United Controls International cc: Mike LeBlanc (UCI)
Deborah Butler (UCI)
--_u----
a4.m,,-
__mgg,a-g
__m-a,u_mausa
.44m.h.c spw-*..id..hRshW~Fa m-4mM.a*1-M-l--m'E-M.#p444WM-W h d A 4.aE. 4 R.,.Rs45,A h A
-A Ja6J e.W-A44--s8-4+ALd.A2 e
I N
4 4
s i
l 1
1 4
d I
i.
i h
n i,
3 1
4 1
4 i
1 t
h o
4 ATTACHMENT 1 i.
l 5
i l
l l
I a
l l
f I
l 1
3 i
f I
i 4
(
1 1
S i
4 4
i
r1AR-15-1996 13:02 NUCLEfR PURCHASING IP CPS mma i;LINCIS POWER PURCHASE ORDER O
Dars I
Munnes est,
asir Istress 6tLIvssy aATE 02/25/95 03/14/96i P0552512 000 005 /~
- iLL M T M B NO DISCOUNT-NET 30 DAYS
~
s liENTTMB COLLECT 3
.o.1 ms DESTINATION
- T0o 00X TAXABLE 6.25% SALES-USE TAX SUPPLIER NOT REGISTERED TO COLLECT TAX l
PAGE 1
mm HEMD OF CHANGE um l!araIwrMassaesLINE InuiiWCTIONS is UG74 02 I"s2*EE'a##'# e":.".".I,,
I UNITED CDNTROLS me emisms.iuseis sans vues
. es=.n 1 =
nail:aen=== smaamm=T me as== mas a v,
t-1554 LITTON DRIVE
[N jt STONE MOUNTAIN GA 50083 NUST MAIL INV01 lc
's = = - w - - '= r,:,r i -
paICE EMANTITY tsuT DEscaZPT1am
: T=====:===:=
t l
ATTENTION:
RGB HALE PRICE PER QUOTE ON OCTOBER 28, 1994.
I
.REFERENCE ATTACHMENT 1, PAGE 10A 0F 38.
4 1 EACH OF THE 10 EA OPTION B MODEL #P3C015C6-EAN l
TRANSFORMERS IS TO BE DROPPED SHIPPED FROM THE UPON MANUFACTURER To CLINTON POWER STATION.
RECEIPT THE TRANSFORMER IS TO BE HELD IN QC-HOLD FOR MEASUREMENTS BY AL HAUMANN.
UPON COMPLETION j
THIS TRANSFORMER IS TO BE SHIPPED ON TO UNITED CONTROLS FOR DEDICATION WITH THE REMAINING 9 i
TRANSFORMERS AT UNITED CONTROLS.
,d i
THIS MEMO OF CHANGE IS ISSUED To REVISE LINE ITEM 2
1 0F THIS ORDER.
3
[tEQUISITIONNUMBER:
6060S05P
,4 ALL OTHER TERMS AND CONDITIONS REMAIN THE SAME.
d
.mmmmmmmmmmmmmmmmmumemununummmmmmmmmmmmmmmmmu i
i fr.o,DescatrTIan ILLINDIS POWER COMPANY BUYGR/
ANALYST PHOIE IGNGER 1
AUTHOREZED BY 4
CG.S!Ti s 5 [*."(h~"'T.2::::Mit " " "ll"lll'.
l".f.'.'". :"U:"l':"' '" =
~
, "g:e,b"".".".=.'lll.':ll"."',:lll ",'.""' "m".8."'." "s "a'"ase"s.a"mm"'i w.s sv m w PLEASE ACKNONLEnet RECf!PT OF THIS ORDER n
gre
.m.m s..m.nse a.= m.sms a m
- v..setimme,
- o. maass e.er ses ON ATTACHED FOGM ADWISING WHEN YOU WILL SHIP s n
.. g ne g,as go.s_r.=
. : =.=lr., ::r==== ::,.n.===,- ' '= r.r:=..
ffi..gg.,'"":ii?
m.: e r=.=..
m-m-
-is
._.._-. _ _ _ _.. _ _ _.. _ _ _... _. ~.
._..___....._m
.. - =. -
W~AWAN 1 N kW M myy y 41f 700 4400 t t;;J
!
- LINOIS POWER PuncNASE oassa ftousasaesLIvtaYenTs
- naYa saaesa met nov 03/14/96 P0552512 000 005
- LLzsa Teens 428MF n ans
{ g 1rans l
i PAGE 2
isPutut nessAss Lins INSTRUCf!ONS
's UO74 02
" !2",'sE',, *;',llT'# /,$",.'.';,,
!E UNITED CONTROLS me apetsensta stLiems satas imms as a sesenate tres L
1554 LITTON DRIVE nail:sentmanasaseent me m - re, 4
E t
STONE MOUNTAIN GA 50085 MUST NAIL INVO j
- ,: m s ' F o w $ :: u > =
i P
D G M BK98.
A
.TI k TameTE A9E9E
^
ln"o N
Ea
.~. _.. _ _ _ -.-
- a T y - = L *.T C C " 5 ".
_mummmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmune l
i I
nummmmmmmmmmmmmmmmmmmmmmmmmmmanummmmmmmmmmmmmmmmmu mmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmunummmmmmmen l
nummmmmmmmmmmmuummmmmmmerummmmmmmmmuumummmmmmmmmme mVENDOR:
TO EXPEDITE INVOICE PROCESSING. PLEASE:
i
- 1. SHIP NO SUBSTITUTIONS WITHOUT PRIOR APPROVAL.
l SHIP NO MATERIAL OR EQUIPMENT CONTAINING 2.
l, ASSESTOS WITHOUT SPECIFIC PRIOR APPROVAL.
l
- 3. SEND ALL REQUIRED DOCUMENTATION WITH SHIPMENT.
- 4. MATERIALS / EQUIPMENT SHALL BE PACKAGED AND i
SHIPPhD USING GOOD COMMERCIAL PRACTICES.
IF i
GOVERNED BY ANSI STANDARDS, s/ ANSI M45.2.2.
'SPECIAL' LEVEL UR QUIREMENTS APPLY.
l REQUIREMENTS WILL BE 50 NOTED IN THE BODY OF i
THIS ORDER.
PART NUMBERS MUST BE CLEARLY IDENTIFIED FOR EACH ITEM AND SHOWN ON ALL j
SHIPPING PAPERS.
i IF SHELF LIFE APPLIES TO ANY ITEM DN THIS 5.
l ORDER, IT IS REQUIRED THAT A MINIMUM OF 80%
SHELF LIFE REMAINS ON THE ITEM AT TIME OF IF SHELF LIFE IS INDEFINITE, NOTIFY SHIPMENT.
THE BUYER PRIOR TO SHIPPING.
P.O.3fSCRZFT!!B0
-SHIP VIA ILLINDIS POWER COMPANY nuvent AMaLYST PM005 DENGfu Y
AUTHORIZED BY caselfiges estatut seAre Par ela
- em EIB Edtf amm sem emois as enmary masas n ein assert vus samaan a asummer to
.g assases ease an anname a m.ase ne suresammi er an parut u umom PLEASE ACK3EBest annF RECEIPT 01' THIS OEDSm as asus
, n mgeni ON ATTACH 2O FORN ADWISINS WHEN YOU WILL SMIP
- ' E E E Em"ma"" M "5' E" EEa"m*mm'es e " METE
- Ei5mTeEEe"ma'Nm"r EasEt"sess e esmer i
Y van as em vm es aset
& esertatt N EisEE8 an aset1IsasL
+
.18 e547 tute att spelleged 00m dB GEWriese
N 1 M 13:03 NJCLEFR PURCHHSINU JP LPb gly m ggg y, g LLINOIS POWER PURCNASE ORDER mate.
insess att new EOUIMD BELIVERY thATE 03/14/96 P0552512 000 003 ILLIIIB TERNB agreur Tasse
.oe sans PAGE 3
treINT IESSAAS LIld IId3788p i i - a, M i[EEmsamir.
ED NTROLS NAIL:wr=ma seasserr me au esanes== ar voi 1554 LITTON DRIVE nogy nagt gnygMM@l{
STONE NOUNTAIN SA 50083 e
= 1. %"P'Q =figa
=
d P_R.
SAN 9E91.
99i Tadnare 19E9C pages neursteigen gunmTITY UNIT THIS PURCHASE ORDER IS FOR GOODS AND/OR SERVICES TO BE USED AT THE CLINTON POWER STATION, WHICH IS JOINTLY OWNED BY ILLIN0IS POWER COMPANY AND SOYLAND POWER COOPERATIVE, INC., AND TITLE TO SUCH GOODS AND/OR SERVICES SHALL PASS TO THEN IN f
PROPORTION TO THEIR RESPECTIVE OWNERSHIP SHARES.
ALL MATERIAL OR EQUIPMENT SUPPLIED UNDER OUR PURCHASE ORDERS SHALL DE FURNISHED IN A NEW UNUSED USED REBUILT OR REFURBISHED ITEMS ARE CONDITION, UNACCEPTABLE UNLESS SPECIFICALLY NOTED IN WRITING ON OUR PURCHASE DOCUMENT.
SELLER AGREES THAT THE MERCHANDISE AND/OR SERVICES COVERED BY THIS CONTRACT SHALL BE OR HAVE BEEN MANUFACTURED OR PERFORNED, PRICED AND SOLD IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL LAWS, INCLUDING WITHOUT LIMITATION, THE FAIR LABOR STANDARDS ACT, THE EQUAL OPPORTUNITY CLAUSE SET FORTH IN 41 C.F.R.
SECTION 60-1.4CA), AND THE AFFIRMATIVE ACTIDH CLAUSES SET FORTH IN 41 C.F.R.
SECTIONS60-250.4,-741.4.
P.O.h5 W 78 TION ILLINDIS POWER CONPANY auvsnt amatyst ruena Nuessa Y
aurnanzzes av ommtfins "Im'
= =M II. E E"".' " i"E'iE"." " "."E's"I ILLINOIS POWER COMPANY M M E M 95 W84f7 6 11 SEA EsEH DE
- SE M #
MN
. vgwg y manam,me e amame as sans na arouneme w me estan se assammua ON ATTACHED FOAM ADWISZIIB WHEN V8u WILL SetIP
- E E E E,EsemasEs"s. E E"""!.t"ll'"'".'l" 7 "J'"' '".ll
- '"r,:."l".l".GTr. 7,3ti""Er." E4.:'. :"
- $h"""'h""[" "d""E':".,:'J: 'A'..
ix s 19 W NEW && 888kamd m am unattug
.~-
em-4:>-ino ia.m m.cm rum.rmuu ir v,
<. 4,
m-c. w.,
LLINOIS POWliR puRcNASE ORDER anTa paneet est new sautane entzweay eaTg 03/14/96 P0552512 000 003 ILLum Tsans REIGHT TEAfe
.oe ' tass PAGE 5
EGPRIlff 1.semans LIBE Iia.i a iiGNS
" O E '* W I -'
E ED CONTROLS a.9.p LIs LE ILL8 es 3.Lg5 1. m.4 A Mr.naTE I'T F a
1554 LITToN DRIVE naxt:========r
.a emanner ess voi (N
I STONE MOUNTAIN GA 30083 MUST MAIL INVS
- n : w r - - =
= r,: - ' -
Y VENDOR DOCUMENTATION REQUIRED: CB,DS,EI,FT,MI,SE,*
- 1) CERTIFICATE OF CONFORMANCE (CE) PER ATTACHED.
- 2) DRAWING SUBMITTAL REQUIRED CDS)
- 3) ENVIRONMENTAL REPORT TO IEEE 323-1974 CEI)
FUNCTION TEST REPORTS (FT) 4)
MAINTENANCE / INSTRUCTION MANUAL SUBMITTAL REQUIR ED (MI).
5)
DOCUMENTATION CODE 'MI' SHALL ALSD INCLUDE REQUEST ED IN
{
DESCRIPTIVE PHOTOGRAPHS AND BULLETINS AS SPECIFIED o
ATTACHMENT 1, PAGE 10 PARAGRAPH 16.1.
- 6) SEISMIC REPORT TO IEEE 344-1975 m, VENDOR SHALL SUBMIT GENERATED HEAT (BTU /HR)
.DADING 7)
DOCUMENTATION SPECIFIED IN ATTACHMENT 1, REv. 2, PAGE 6, PARA. 306.
THE SELLER QUALITY ASSURANCE PROGRAM REQUIREMENTS PER ATTACHED, SHALL APPLY TO THIS ORDER.: A,I,J,K m
TECHNICAL REQUIREMENTS: *, DESIGN, MANUFACTURE, AN 3 TESTING 3N 2, REQUIREMENTS SHALL CONFORM TO THE FURNISHED DIVISI DIVISION 3, & STANDARD SPECIFICATIONS FOR DRY TYPE REGULATING TRANSFORMERS (ATTACHMENT 1, REV. 2, ALL INCLUSIVE).
P.o.asere,rtres SHIP VIA ILLINDIS POWER COMPANY awsme aftaLYST risessE paNGER y
l aunientzsa av I
i
- 3 " ".l"l'#. M "."2 "." "."'L" "lET.""3 EJ:".12l'.lll"2. m IIIINOIS POWER COREPANY
'"." "T.2 e..
u.
u
.-n =
. 5%" "3 "# " '"u"." ". 2.""'m'"
" ' ' ' ' ^ ~ " " " " ' ' ' " " ' ' " ' ' ' ' ' "
i
.. ".M, 'l:'l"."a'.l..
'" ^"^"*' '" "**2"' ""'" '** 'erLL seize i
. T."
."'!h f". :' '.'"lll=f.". :'.:l'r:13.
man nm rreseer aas e
7=
ne n:: "X "" " l':"i.'*.*.' t.'ll"'E' "." :.ll' llll' a.
u
. T.*.ll"." :'?" "lll2
MAR-15-1996 13:05 NJCLEAR PURCHASING IP CPS 217 935 4258 P.08 P
fg(,g $ op b ]
i i
DRY _ TYPE REGULATED _ POWER TRANSFORMERS i
-s
~
~...
DIVISION 3 - Technical Requirements I
e
-m J
a 301 Each transformer shall be a self contained, dry type i
1 regulating transformer, three phase, 60 Hertz 15 KVA with an input voltage of 480 volts 15%, and a guaranteed ouput voltage of 117 volts 3% over an output power range of 0 to 8g 15 KVA.
The regulating transformers shall be qualified 1E i
i 3
per IEEE 323 and Clinton Form 1999-D.
The Vendor must 1 h) f supply supporting documentation and test results prior to shipment.
x 202 h e environmental and radiation qualification conditions are specified as follows:
1 NORMAL ABNORMAL LOCA j
- a. Temperature:
50-90'F 104*F 104*F
- b. Pressures Atmosphere 10.5 in W.G.
10.5 in W.G.
- c. Relative 30-90%
5-90%
5-90%
Humidity:
- d. Radiation Intega!ated radiation exposure for Gamma and 4 Rads lx104 Rads i
Beta 1x104 Rads lx10 Neutron sogligible Negligible Negligible i [ 4V h l Transformer conduit entrance shall be furnished to al 303 back and top entry for incoming 3/C - #19/22 1KV Cable and j
outgoing 3/C - #2 1KV' Cable.
The mavieum conduit size to be used is 3 in.
304 Transformers shall be designed for floor mounting.
The floor demensions shall be 21" x 19" d and must not be h
altered without approval of the purchaser. -The transformers must be. seismically qualified so the Purchaser can choose to mount the transformer to the floor using bolting or welded connection.
The Contractor must supply the purchaser with the mounting detail used to qualify the transformers.
305 The transformer shall include an over voltage protection device which will trip the transformer if the output exceeds a preset valve.
The trip device must be settable between j
120 and 125 volts.
ph The Vendor must aussly aneuracy data so the Purchaser can 7J perform a set point' calculation per Instrument society of gf America Standard S67.04-88 " Set Points for Nuclear Safety P'
Related Instrumentation."
?
~
haumann/183/llr
p - -,,.;;;;, 3,,7 -
u ; ;;7 m z;3; ; ; 3 3 -
{
/
,yg. tootro.sost' -
n ** T unmovvi
,v" 5 } ** "*
O "b i
The revisions to section 301 and 305 of the specification for DRY TYPE REGULATING TRANSFORMERS that is part ofIllinois Power Co s purchase order PO552512 with United Controls International are beiry made so United Controls can dehver a product that will meet IP's needs. These cunges are at the request of United Controls i
. and are, therefore, not in addition to the originalIP order. There will be no additional charge associated with these changes. The revised SectionsR(and 305 are to read as follows-jllu
- s-s-w 4
DRY TYPE REGULATED POWER TRANSFORMERS DIVISION 3 - Technical Raquirernents 301 Each h. f css shall be a selfcontained, dry type regulating transformer, three phase, nominal 480V delta 202/117V wye, 60 Hertz,15 KVA. The transformer shall be capable of operating with an input voltage between 530.4 and 414 volts, while m-a kke a guaranteed output voltage between 113.5 and 121 volts over an output power range The regulating transformers shall be qualified IE per IEEE 323 and Clinton Form 1999-D. De Vendor must supply supporting documentation and test results prior to ah'==aa' 305 The transformer shall include an over voltage protection device that will protect the 120 volt level equipment from extended periods of over voltage. The over-voltage protective device must trip (shut down) the transfomier if the output exceeds a pre-set value. De Transformer over voltage trip must be manually reset. The protective device must trip prior to the output exceeding 124.5 volts, but not less than 121. It shall have a time delay of sumcient duration to allow the ram'h'ar to ride through both supply voltap transients and low side step load changes. He transient is expected to last o.t.u.10 and 60 cycles. Therefore, i
the over voltage trip device sull have a delay of about I second.
The transformer may have an undervoltage trip (due to low input voltage) provided the trip autornatically resets prior to the input voltage reaching 408 volts,
l 3-1
I
(
l 4
i 1,
,I
?
s 5
i 1
i 1
ii k
i 4
i ATTACHMENT 2 1
4 d.
J 4
l 1
l j
l d
\\
t l
1 4
s i
l 4
i i
J I
l l
1 l
i 1
l
)
I 1
1
M2v-07-97 01:23P P.01 f
- Y PHOENIX POWER SYSTEMS innovation a'nd Excellence in Power Protection 10547 Viper,Way, San Diego, Califomia 92121 1
619/ 450-9620 Fax 619/ 450-9662 Web Page: http- /www.phoenixpower.com 1
1 FACSIMILE COVER SHEET i
To: Mike Lal3tanc From: Todd Desiato e
h i
i Fax: 770-496-7097 No. Pages: 1 i
Date: 03/07/971:05 PM CC: Al Bagherian 1
j No: 15kVA Regulating Transformer i
i
Dear Mr. La5!!anc,
This is a suinrtary of our conversation of 3n/97. The 15kVA Regulating Transformers provid! I by Phoenix Povw will operate within the specified 117 Vac +/- 3% for an output load of zero to ilWA.
Having no kmd applied will not cause the circuit breaker to trip. Our investigation has shown that the circuit breaker trips due to EMI being fed back from the load, and a filter applied to the output r f the transformer will solve the problem. When we were informed that Illinois Power was having a problem with the circot breaker tripping, it was suggested that a minimum resistive load be applied to d lermine if the poor qual.ty output load waveform that we were shown was the cause of the problem. The result was that the minimum load helped delay the tripping but the unit still tripped. I hope this clarifies your situation. Please call me if you need further assistance.
I Sincerely, odd Desiah Chief Engindar 4
i r
i 1
2
1 5
4 1
1 1
J I
l.
4 1
1 1
i ATTACHMENT 3 I
1 1
a I
(
I t
1 i
I
(
l
?
1 l
i i
d I
e i
I 4
)
4 I
't.
h 4
i
,i i
s n
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER of 2 b-$ Page 1 02 Test Procedure No. NOTP-836.1.1 UCI S/N Description Phoenix Power Transformer Part No.:
P3C015C6/EAN Functional Type be C
Test Date b ' O D Test N r
i 24 4C.
MFR S/N D D5 ~I A Ambient Temperature INSTRifMENT AND EOIITPMENT LTAT ITEM SERTAL NO-RANGE CALTBRATION DATE FLwke 6c6c A 47M ib2 6-2W 2-26 %
(dE D)
FLM So$tA
%4OAo c.366st/
u-Io - Tr
( de h)
Ak HY ftT ll24-M ioco V 2 % (dwe ' 47)
FluhG Eol* A
'( O B W 90 0 - 40 A A
% - 4 94 (d% ' en)
TEST PROCEDtJRE TEST DATA TFST REOUIREMENTS Insulation Resistance:
5dAA )
a co M,5L-10 Megohm or Primary to Secondary Primary to Ground (la_D A I I to 7 H JL.
Greater Secondary to Ground
( C A)
Sb M.2 Electrical Output Check (ifnit Unloaded)
Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC I AO 3 2 113 - 121 VAC
'l C 6
3 113 - 121 VAC
\\6' -9 at 414 VAC 1 113 - 121 VAC
!! A. b 2 113 - 121 VAC (18.O 3 113 - 121 VAC ll7,a at 530 VAC 1 113 - 121 VAC l 'A C 1 2 113 - 121 VAC I AO-B 3 113 - 121 VAC 110,5 Dropout Voltace Prgagy Secgary low end 312-360VAC 1
Alarm no 2
4V5 9 4 't Alarm no 3
3M
'l19 Alarm no Unit picks up at Pr(gary SecoAdary 360-408VAC 1
WO 10/
Alarm Clears Yno i
2 47 4 I c'7 Alarm Clears no 3
1 6 4-IC b Alarm Clears no 5$
1 b
\\
2 944 1A3 4 3
<46 113 4 Dropout Time Delay bO Ncket
=1 second no Unit does not return yes no until input breaker reset Page 12
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED Test Procedure No. E P-836.1.1 UCI S/N bhI R
Eo os7 A Electrical Output check. Unit Loaded Load Condition output Stable yes o
at 480VAC input at 480 VAC 1 113 - 121 VAC Ill
- l 2 113 - 121 VAC til 0 3 113 - 121 VAC til. a at 414 VAC 1 113 - 121 VAC tl 4 S 2 113 - 121 VAC tt 4. 5 3 113 - 121 VAC 11L 5 at 530 VAC 1 113 - 121 VAC 10-7 2 113 - 121 VAC tt7 7 3 113 - 121 VAC t il 4 Dropout Voltage Primary SecpDdary low end 312-360VAC 1 5%
't A M-Alarm no 2
3 3 to
%,B Alarm no 3
A35 9a. 6 Alarm no Unit picks up at Pripyt Segqndary 360-408VAC 1
7o MA Alarm Clears no 2
344 IuA Alarm Clears no 3
b 84-I a Alarm Clears no Dropout Voltage Prir ry SecondaY
>530VAC 1
5 4-lA3 2
K5b IM 6 3
557 1 A 5.7 Unit does not return yes o
until input breaker reset Temperature Rise Check or = 90*above ambient NN at O eratinb emperature T
f 11 loa Ambient Temperature < or - 40' C Ambient Temperature Simulated SCR Short Test VAC Power Module 1
Shut Down at short 2
3 GKI-VAC 3
} F3 4-VAC Circuit Breaker Trip no r
e-4 Ah SC Tested by:
Reviewed by:
u Page 13
DATA SHEET FOR FUNCTIONAL TESTING OF. POWER TRANSFORMER Page 1 of 2 Test Procedure No. NOTP-836.1.1 UCI S/N b3b-I -03 Description Phoenix Power Tran<;former Part No.:
P3C015C6/EAN bC C*
Test Date 8"23'3b Functional Type o
Test Number I
Ambient Temperature Mb MFR S/N EDoSBA IMSTRUMrNT mfd EOUTPMENT LTST ITEM SERIAL. NO.
RANGE CALTBRATION DATE FLuM BOCA
- 4. l 25KA 6 - 2. e v 2.te- % (Lc' on) r u e BogeA
% 4.512c o 'Inv N lido-f5 Oc' %)
4 H'ifuT
~7Ia 4 5g touc 2,-r? - % ( du ' TI)
TFET PROCEDURE TEST DATA TFST REOUIREMENTS Insulation' Resistance $
MM E NE 10 Megohm or Primary to Secondary Primary to Ground l tr MAL
% M J.
Greater Secondary to Ground
((M hA1 46 149 Electrical Outout Check (Unit Unloaded)
Three Phase 480 Applied LED's Illuminated No.
Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC LI 0 0 2 113 - 121 VAC lG.0 3 113 - 121 VAC tl % 4-at 414 VAC 1 113 - 121 VAC ll 8. Q 2 113 - 121 VAC i l 6L o 3 113 - 121 VAC
_ t i n, I at 530 VAC 1 113 - 121 VAC (20. Q 2 113 - 121 VAC i AO. O 3 113 - 121 VAC 12 0. b Dropout Voltage Primary Secondary low end 312-360VAC 1
170 CL3 Alarm no 2
'43d.
C 4. 6 Alarm no 3
MR 1AO Alarm no j
Unit picks up at Primary Secondary l
360-408VAC 1
3M 10 4 Alarm Clears no 2
3 B2 10 h Alarm Clears no 3
9GK in 9 Alarm Clears no DrobVACout Voltage Pr y
Second y
>53 1
l'A 4.
I 2
C 4.4.
\\ 13, <.6 3
C45 174_7 Dropout Time Delay NNC C al second no Unit does not return yes no until input breaker reset Page 12
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED 83L-l'Page 2 of 2 D3 Test Procedure No. NOTP 836.1.1 UCI S/N C.D DC 6 A ElectrtOcl Output Check. Unit Loaded Load Condition Output Stable yee no at 480VAC input at 480 VAC 1 113 - 121 VAC 11 Q. 0 2 113 - 121 VAC 11 7 4-3 113 - 121 VAC 1 ' 1, W at 414 VAC 1 113 - 121 VAC t15.3 2 113 - 121 VAC ll A 4 3 113 - 121 VAC 1ti 6 at 530 VAC 1 113 - 121 VAC
~lfMlb 2 113 - 121 VAC 11 M. rA 3 113 - 121 VAC
\\1M.3 Dropout Voltage PrtrA U Secondary low end 312-360VAC 1 T4M 4a 3 Alarm no 2
h %'
41.1 Alarm no 3
% % 4-49,5 Alarm no
-4 AC 1
2 Alarm Clears no 2
362 IOR Alarm Clears no 3
3662 lo'A ~
Alarm Clears no si8?n "
"'WY S*MtT, 1
2 5A9 l'AM, R 3
KMn L 'WA, b Unit does not return yes no until input breaker reset l
Temperature Rise Check Operating Temperature
< or = 90'above ambient NIk at full load Ambient Temperature < or - 40* C Ambient Temperature u/A Simulated SCR Short Test 3b VAC Power Module 1
Shut Down at short 2
%Oa VAC 3
TM VAC Circuit Breaker Trip no Tested by:
kG" MM t
Reviewed by:
[
[
G t
Page 13
4 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER Test Procedure No. NOTP-836.1.1 UCI S/N d -l-Description Phoeniv Power Transformer Part No.:
P3C015C6/EAN Functional Type b ic Test Date 5-l~i' %
o Test Number I
Ambient Temperature 24 C MFR S/N Enoc 9A INSTRtIMENT AND EOffTPMENT LTMT ITEM SERIAL NO.
RANGE CALTBRATTON DATE Rv.hs BoGoA 4.1'A5 lu o-4e v 2 1e -$.
(d4e ' 97 )
RuceoDA
'W&Sne o-2%ou iM o-E (d*'ad A% M 'I foT
'lu4'3 A 10A6\\/
A ll- % (ds '9l)
FLuhe 6clu Ao6 4 1o o - Ao.uA
'A -2 0 % (de'97)
. TFST PROCEDtJRE TEST DATA TEST RFOtJIREMENTS Insulation Resistance:
Primary to Secondary HM) 9l O 10 Megohm or Primary to Ground n nA) n MA Greater Secondary to Ground j Q h A) M H A-Electrical Outout Check (tini t IJnloaded)
Three Phase 480 Applied LED's Illuminated o
Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC l A07 2 113 - 121 VAC tio.T 3 113 - 121 VAC n 2 4. c at 414 VAC 1 113 - 121 VAC 617. 1 2 113 - 121 VAC tit 4 3 113 - 121 VAC li 8. 6 at 530 VAC 1 113 - 121 VAC 420.3 2 113 - 121 VAC I A 0. E 3 113 - 121 VAC IAo K Dropout Voltage Pripary Secondary low end 312-360VAC 1
T92 MS l Alarm no 2
131 4+ 4 Alarm no 3
135 9EC Alarm no ry Secqndpry Unit icks up at Pr 360-4 8VAC 1
i 3 0 'f Alarm Clears no 2
3 63 10 9 Alarm Clears no 3
- 1. E I I6H Alarm Clears no Dropout Voltage Pri
- y Secondary
>530VAC 1
'1 1115 l
2 G 4. 3
\\ 11 b 3
4 430 i 14-3 l
Dropout Time Delay O Or((r 3 al second
/no Unit does not return yes no until input breaker reset Page 12
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED
$%-\\ Page 2 of 2 04 Test Procedure No. NOTP-836.1.1 UCI S/N EO oS9A Electrien1 Outout check Unit Loaded Load Condition Output Stable yes/ o at 480VAC input at 480 VAC 1 113 - 121 VAC i17 0 2 113 - 121 VAC i17 3 3 113 - 121 VAC i i ~1. B i
at 414 VAC 1 113 - 121 VAC ist e 2 113 - 121 VAC 115 t 3
3 113 - 121 VAC it%.o at 530 VAC 1 113 - 121 VAC ii e. 4 2 113 - 121 VAC 18 s 2 3 113 - 121 VAC it 6 5 l
Primgry Secgngary Dropout Voltage 3-9 -
Alarm no l
low end 312-360VAC 1 2
YLA 9a.
Alarm
/no 3
3M 93 0 Alarm no r ' e r, y Secon.dary Unit picks up at o
360-408VAC 1
80 (C 6 Alarm Clears no 2
.b 6 2 I C 'A Alarm Clears.
no 3
356 161 Alarm Clears :q no Dropout Voltage Pripary Secondary
>530VAC 1
SSR i'11.4 2
c,G R IM.E 3
EG 3 IM 9 Unit does not return yes no j
until input breaker reset i
Temperature Rise Check
< or = 90*above ambient nib at 0beratinbTemperature f li loa Ambient Temperature < or - 40' C Ambient Temperature WA Simulated SCR Short Test Power Module 1
3bN VAC Shut Down at short 2
383 VAC 3
7 t3 A VAC Circuit Breaker Trip o
y Tested by:
94 4A Reviewed by:'I
/
Page 13
4 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER 1 of 2 M -lPage Test Procedure No. NOTP-836.1.1 UCI S/N Description Phoenix Power Transformer Part No.:
P3C015C6/EAN Functional Type i(.a b%
Test Date
$~D~ %
0.
Test Number l
Ambient Temperature 14 C-MFR S/N 6 D ObO A INSTRUMENT AND EOUTPMENT LTAT ITEM SERTAL NO.
RANGE CALTERATTON DATE
{LukG 805hA 4M E lbQ aosu O2R. 94 (tL/q-))
Fe M to5cA
% 4-513 o
'Acss v i t-(0- 4G (Le%)
M, M6'T
-i t a 4-M iousi 2-D -(N S c % )
E'uhG eo(6A
% o (3 M%
aoM A 26-94 (dd W TEST PROCEDURE TEST DATA EST REOUTREMENTS Insulation Resistance:
(lluA)
% M A.
10 sepeam or Primary to Secondary Primary to Ground f u. u A 1 71 M1 Greater Secondary to Ground (1A n A1 So M -Q.
Electrical Outout Check (Unit Unloaded)
Three Phase 480 Applied LED's Illuminated o
Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC ll 4 1 2 113 - 121 VAC ti q c 3 113 - 121 VAC 110.I at 414 VAC 1 113 - 121 VAC i14.0 2 113 - 121 VAC i t 7. E 1
3 113 - 121 VAC ti A 6 at 530 VAC 1 113 - 121 VAC 110.9 2 113 - 121 VAC i 2 0. ';
3 113 - 121 VAC tio.7 Dropout Voltage Primary Cecondary low end 312-360VAC 1
330 45 0 Alarm no 2
336 Cis co Alarm no 3
111 9La Alarm no j
Unit picks up at Primary Secondary 360-408VAC 1
462 IC S Alarm Clears no 2
161 i
O Alarm Clears no 3
LP 10Q Alarm Clears no 08E V lt*9*
"'Dy Segdgry 1
2 550 i A4.,3 3
E 44
- 13.4 (co rMt.
=1 second yes no Dropout Time Delay Unit does not return yes no until input breaker reset Page 12
I t-DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED b h -lPage 2 of 2 l
-OG Test Procedure No. NOTP-836 1.1 UCI S/N co-che A Electrical Outout Check. Urii t Loaded Load Condition Output Stable yes o
at 480VAC input IN*O at 480 VAC 1 113 - 121 VAC 2 113 - 121 VAC LI 5 l 3 113 - 121 VAC 117, 7 at 414 VAC 1 113 - 121 VAC o 5. ~3 2 113 - 121 VAC 615. E 3 113 - 121 VAC 114. 6 at 530 VAC 1 113 - 121 VAC It B B 2 113 - 121 VAC ti W 5 3 113 - 121 VAC 115 4 Dropout Voltage Prfmary Secondary low end 312-360VAC 1
)M
'l 2. D Alarm no 2
334 MLt Alarm no 3
SS2 42.1 Alarm no Unit picks up at Pr;'macy Segoqdary 360-408vAC 1
36A to+
Alarm Clears no 2
%eA 10 3 Alarm Clears no 3
377 to'2 Alarm Clears no DrobVACout Voltage Prim,ary Secondary
>53 1
S51 l'A1. B 123. b 2
S5a i A3 - 5 3
5 4. Fb L13 6 Unit does not return yes o
until input breaker reset i
Temperature Rise Check T
< or = 90*above ambient M
at O eratinb emperature f 11 loa M
Ambient Temperature < or = 40' C Ambient Temperature Simulated SCR Short Test Power Module 1
N VAC Shut Down at short 2
5 tB A VAC 3
3Oi VAC Circuit Breaker Trip no Tested by:
A Nhh Reviewed by:
MU Page 13
a 4
DATA SHEET FOR FUNCTIONAL TEST).NG OF POWER TRANSFORMER Page 1 of 2 Test Procedure No. NOTP-836.1.1 UCI S/N 83b ' l " O b Description Phoenix Power Transformer Part No.:
P3C015C6/EAN Functional Type Dedtc Test Date
$~O'N c
Test Number i
Ambient Temperature 7-4 C MFR S/N ED Obt R INSTRUMrNT AND FOUTPMENT LTST ITEM SERIAL NO.
RANGE CALTERATION DATE 3
R u he Go5cA dJ72 GIGA 0-%V A %
Uc' 77 )
rtuke ec5cA
%4Sla o o-2 teo V ll-(0 CiG (b ' %)
A% hY?or 7iR4m 16e v 2 % Qd 47)
F PR C D JRE T DATA
~
TFST reb R ENT Insulation Resistance:
Primary to Secondary (DOA)
I% HE 10 Megehm or Primary to Ground it, uA )
nNE Greater Secondary to Ground WmA1 4 b N ll Electrical Outnut Check (Unit Unloaded) j Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC it 9.0 2 113 - 121 VAC t AO. 3 3 113 - 121 VAC 110 0 at 414 VAC 1 113 - 121 VAC t l 6. o 2 113 - 121 VAC
. li G s 3 113 - 121 VAC 11') -5 at 530 VAC 1 113 - 121 VAC 414 4 2 113 - 121 VAC (Ao %
3 113 - 121 VAC I AQ. R Dropout Voltage Ptirary Secpdary low end 312-360VAC 1
3 T b-92 6 Alarm no 2
Mlb Ci35 Alarm no 3
ble 44 9 Alarm no Unit picks up at Primary Secqndary 360-408VAC 1
LGO 10 %
Alarm Clears no 2
379 (O b Alarm Clears no 3
3et i 6 '5 Alarm clears no Dropout Voltage Primary Seco d ry A
>530VAC 1
448 1
2 (46 I A 3 'I 3
c44 iM 7 Dropout Time Delay NM cI -
al second no Unit does not return yes no until input breaker reset Page 12
s i
DATA SHEET FOR FUNCTIONAL TESTING l
OF POWER TRANSFORMER CONTINUED-bbl Pabe 2 of 2 l
O Test Procedure No; NOTP-836.1 1 UCI S/N i
EO O(ol A Electrical Outout Check. Un i t-Loaded 1
Load Condition Output Stable no at 480VAC input at 480 VAC 1 113 - 121 VAC IIS'I 2 113 - 121 VAC l il '7 i
3 113 - 121 VAC tlBt l
at 414 VAC 1 113 - 121 VAC i1%.3 i
2 113 - 121 VAC a l TT C l
3 113 - 121 VAC nt< O at 530 VAC 1 113 - 121 VAC li d 4 2 113 - 121 VAC 116 9 3 113 - 121 VAC 11 M. a Dropout Voltage Primgry Secoqdary low end 312-360VAC 1 334-43I Alarm no 2
AA9 4l-5 Alarm no 3
13T 46 1 Alarm no Unit picks up at Pripary Secondary
)
360-408VAC 1
3UO 10%
Alarm Clears no 2
466 to A Alarm Clears no 3
TMl to a Alarm Clears
/no Seco ay Voltage Prigr 2
55A 1%J.4 3
M ts l'Ad f Unit does not return yes/ o until input breaker reset i
Temperature Rise Check
< or = 90*above ambient M
at 0eratinbTemperature f 11 loa blb Ambient Temperature < or - 40' C Ambient Temperature Simulated SCR Short Test Power Module 1
N9 VAC Shut Down at short 2
W7 O VAC 3
3e1 VAC Circuit Breaker Trip o
S Tested by: - A Reviewed by: __
/
Page 13
1 t
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER of 2
% -l Page 1 07 Test Procedure No. NOTP-836.1.1 UCI S/N Description Phoenix power Transformar Part No.:
P3C015C6/EAN Functional Type
't to W Test Date b - I'?" %
Test Number i
A4OC MFR S/N E O ob F1 A Ambient Temperature INSTRUMENT AND EOffTPMENT LTRT J
ITEM SERIAL NO.
RANGE CALTERATTON DATE FL4h6 80500 61 'A G l(o 2 MOV
'A -2 6 Cl b be '9-d ThhG8s2A
%+5 i h Aons/
11-6 9 5 Q w ' % )
c As.u m t 7 i 24u iew v 2 n-% (L'qd
[N PR D
T DATA TEST R di i
Insulation Resistance:
Primary to Secondary J.iA) lii M JL 10 Megohm or Primary to Ground A1 t ou h 3 Greater Secondary to Ground thA 1 a.% M 1.
Electrica] Output check flinit Unloaded)
Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC tt R. 5 2 113 - 121 VAC t i e. 5 3 113 - 121 VAC 11 @. 4 at 414 VAC 1 113 - 121 VAC ttG.n 2 113 - 121 VAC ta T. B 3 113 - 121 VAC i n A. o at 530 VAC 1 113 - 121 VAC t i 4. R 2 113 - 121 VAC i1B 4 3 113 - 121 VAC it 4 7 Dropout Volta e Prgry Segngary low end 312-3 OVAC 1
~
Alarm no 2
333 94 t Alarm no 3
'4 A 5 ct %. o Alarm no Unit picks up at Prlmary Secondary 360-408VAC 1
h ? ~?
W 4-Alarm Clears no 2
V) '1 10 ~7 Alarm Clears no 3
1, O D I O ~7 Alarm Clears no
?ti8 e v t^9*
"'kW S* &T"Y i
i 2
C16 iAA 9 3
s45 12 4. R d
=1 second
/no l
Dropout Time Delay L C Cy e'
Unit does not return yesjno until input breaker reset I
Page 12 l
l
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMFR CONTINUED Test Procedure No. NOTP-836.1.1 UCI S/N bbl
- EO %M Electrical Outout check. Unit Loaded Load Condition Output Stable yes o
at 480VAC input at 480 VAC 1 113 - 121 VAC til 3 2 113 - 121 VAC t i7.1 3 113 - 121 VAC u 7. I at 414 VAC 1 113 - 121 VAC i t a. 7 2 113 - 121 VAC t i d.. I 3 113 - 121 VAC 146 6 at 530 VAC 1 113 - 121 VAC tt%o 2 113 - 121 VAC t t 8. o 3 113 - 121 VAC i t A. O Dropout Voltage Pr W ry Secondary low end 312-360VAC 1 D3 TO. 9 Alarm no 2
334 92 5 Alarm no 3
'L 2 b
'4o 5 Alarm no Pr%79imary Secondary
' Unit picks up at IDI Alarm Clears no 360-408VAC 1
2 1&R iO2 Alarm Clears no 3
't A e t02
. Alarm Clears no Dropout Voltage Primary Secondary
>530VAC 1
G42 l AO l 2
' R 44-t Al 0 3
%52 t%2.1 Unit does not return yes no until input breaker reset Temperature Rise Check Operating Temperature
< or = 90*above ambient _ Nt A at full load Ambient Temperature < or - 40' C Ambient Temperature N
Simulated SCR Short Test Power Module 1
3@D VAC Shut Down at short 2
%7 M VAC 3
%7 Es VAC Circuit Breaker Trip
/no L
Tested by:
tW 8DSDM Reviewed by:
~
9 Page 13
- DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER 1 of 2 83(.- l Page 00 Test Procedure No. NOTP-836.1.1 UCI S/N Description Phoenix Power Tranciformer Part No.:
P3C015C6/EAN
$" O-N e
't C IW Test Date Functional Type o
Test Number I
Ambient Temperature A4 b MFR S/N E D Olo3 A IMSTRifMENT AND eof f T PMENT LTST ITEM SERIAL NO.
RANGE CALTRRATTON DATE P Luk C 8bSeA.
- 4. % S l(o 2 O-26U LIS- % ( dw ' 47)
Flukc Go5o A
-4b4E\\2 o 0- %&c\\/
\\I-(0- is Q* ' t(,)
At HY 9t> r
~7124'n 1%sV 2-D - % ( M ' co )
TkSbRO TEST R b R
EN E IIRE DATA 1
Insulation Resistance:
Primary to Secondary (loajd im RA 10 Megohm or Primary to Ground it't m AL WL H L Greater Secondary to Ground f 18 2i A I
% H.51_
Electrical Outout check (Unit Unicaded)
Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC h9M 2 113 - 121 VAC n t>
T 3 113 - 121 VAC i t 9. a at 414 VAC 1 113 - 121 VAC i n. 4 '
2 113 - 121 VAC it O A 3 113 - 121 VAC tt B.'A at 530 VAC 1 113 - 121 VAC
_l 'A O 4 2 113 - 121 VAC i16 E 3 113 - 121 VAC 12 o. b Dropout Voltage Primary Secondary low end 312-360VAC 1
331 941 Alarm no 2
3M 9 E. b Alarm no 3
317 9k1 Alarm ye no Unit picks up at Pr$ary SecoMary 360-408VAC 1
36T 16 0 Alarm Clears no 2
3Go 10 to Alarm Clears no 3
% 9I IOb Alarm Clears no hh N
f 1
2 C 4-4 i A t. O 3
c 40 i r2. 6 Dropout Time Delay b0 Whed
=)
second no Unit does not return yes o until input breaker reset Page 12
k 6
4 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMFA CONTINUED 4
%-lPagg 2 of 2
-Bu Test Procedure No. NOTP-836.1.1 UCI S/N.
E0043 A Electrical Output check. Unit Loaded Load Condition Output stable yes no at 480VAC input Il b' k at 480 VAC 1 113 - 121 VAC 2 113 - 121 VAC 117.7 3 113 - 121 VAC 147-9 at 414 VAC 1 113 - 121 VAC 115 3 2 113 121 VAC 11 5'. o 3 113 - 121 VAC 115 2 i
at 530 VAC 1 113 - 121 VAC lt M*7 l
2 113 - 121 VAC 1 1 B. 4-3 113 - 121 VAC lid 4_
Dropout Voltage Pri ry Secordary low end 312-360VAC 1 A
94 9 Alarm no 2
T3E 43 4___
Alarm no 3
337 44G Alarm no Unitb8VACicks up at Priark Secondary 360-4 1
6 104 D Alarm Clears no
~
1 2
574 102.t Alarm Clears no 3
5R6 I O 'A A Alarm Clears no g Voltage Prirrg Seeggy 2
AKI 113.5
-6a 4, 111.0 3
Unit does not return no until input breaker reset f'
Temperature Rise Check or = 90*above ambient at OeratinbTemperature f 11 loa Ambient Temperature < or - 40* C Ambient Temperature Nb Simulated SCR Short Test 3
VAC Power Module 1
Shut Down at short 2
'5 6R VAC 3
3HX VAC Circuit Breaker Trip o
Tested by:
1.@
M5h Reviewed by:
l 6
Page 13
1 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER Page 1 of 2 Test Procedure No. NOTP-836.1.1 UCI S/N %%-l-OCl Description Phoenix Power Transformer.
Part No.:
P1C015C6/EAN Functional Type e
'l c bh Test Date 5 ' l'I" %
Ambient Temperature 14 *C Test Number 1
i MFR S/N Ego 64. A INSTRIIMENT AN'D EOffTPMENT LTST ITEM SERTAL NO.
RANGE CALTRRATION DATE MhC 8068A d.7 A $ I @
O-20bo\\/
A 'L O- % h b hG hoscA
%%i 2o o-ace V 11- ( %
9 5 idd %)
AV, mfPoT 7124n towv 2-r1 -% %'m)
ThMT D)
ROCEDI E TE DATA TEST REOJk S
Insulation Resistance:
Primary to Secondary (leuAl im H S 10 Megehm or Primary to Ground (t b u A) 77 H &
Greater Secondary to Ground 7 St2A)
% M.q_
Electrical Outout Check (tIni t 17nicadedi Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC
\\l94-2 113 - 121 VAC 119 5 3 113 - 121 VAC L 19 7 at 414 VAC 1 113 - 121 VAC 11 1.5 2 113 - 121 VAC 1 l '7. B 3 113 - 121 VAC 117,7 at 530 VAC 1 113 - 121 VAC
- 19. l 2 113 - 121 VAC
'W-3 3 113 - 121 VAC 1AO,3 Dropout Voltage Primary Secondary low end 312-360VAC 1
331 41.R Alarm no 2
333 44.O Alarm no 3
AM 44.1 Alarm s no Unit picks up at Primary Secondary 360-408VAC 1
1 Cs 4-Ib7 Alarm clears no 2
%6C 10 6 Alarm Clears es/no 3
'l es T to N Alarm clears no Dropout Voltage Primary Sec@dary
>530VAC 1
G44 I AL b 2
T 47 1A3 3 3
s&
I A1 I Dropout Time Delay MN def
=1 second hno Unit does not return no until input breaker reset Page 12
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED Page 2 of 2 Test Procedure No. NOTP 836.1.1 UCI S/N 6%-l-09 EOC44 A Electrical Outnut Check. Unit Loaded Load Condition Output Stable yes no at 480VAC input IO*i at 480 VAC 1 113 - 121 VAC 2 113 - 121 VAC i ll O 3 113 - 121 VAC 1 r1 I at 414 VAC 1 113 - 121 VAC i n d., 9 2 113 - 121 VAC 1 l(L 'A 3 113 - 121 VAC itL 4 at 530 VAC 1 113 - 121 VAC
'M 7, Cl 2 113 - 121 VAC 11 1.'7 3 113 - 121 VAC i t'L $
Pri Sec y
DropoutVoltake low end 312-3 OVAC 1 Alarm no
)
2 33 4' M a.2 Alarm no 3
'4 M
_ Qa A Alarm no icks up at Pri Secondary Unit 360-4b8vAC 1
IOb Alarm Clears no 2
3 65 10 3 Alarm Clears no 3
'3 E A loa Alarm Clears no Voltage Prirgr Secg 2
K5o I A 3,7 3
KC2 IAR,6 Unit does not return y'no until input breaker reset Temperature Rise Check or = 90*above ambient N/A at Oberatinb emperature T
f il loa Ambient Temperature < or - 40* C Ambient Temperature N/A Simulated SCR Short Test
. b b 4-Power Module 1
VAC Shut Down at short 2
AF5 VAC 3
bB$
VAC Circuit Breaker Trip do t
Tested by:
A NW Reviewed by:
b M
d Page 13
4 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER 1 of 2
- b -kPage Test Procedure No._NOTP-8I6.1.1 UCI S/N 10 Description Phoenix Power Transformer Part No.:
P3C015C6/EAN Functional Type e 't r^
Test Date 5-b N O
Test Number i
Ambient Temperature MC MFR S/N IF 0045 A INSTRUMENT AND EOffTPMENT LTRT ITEM SERIAL NO.
RANGE CALTGRATION DA'"'E FLakG BO M 47Mia o-m u 2-16. % (c6'9)
FluhG Ec5u
'% 45 ni o o 'A%W cauA IHo-TS(du'%)
M, a s r am mv 2 - v -,<. c M v )
\\
TEST PROCEDURE TEST DATA TEST REOUTREMENTS i
Insulation Resistance:
bhd ll M S-10 Megohm or Primary to Secondary
@f(t B SO S G H R-Greater Primary to Ground
'A u A )
4.5 M JL, Secondary to Ground Electrical Output Check (Unit Unloaded)
Three Phase 480 Applied LED's Illuminated Yes No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC I i 9. O 2 113 - 121 VAC l i b. 4 3 113 - 121 VAC t t 9. 6 at 414 VAC 1 113 - 121 VAC t t 8. 4 2 113 - 121 VAC 11 R C 3 113 - 121 VAC ti4 b at 530 VAC 1 113 - 121 VAC L ACL'7 2 113 - 121 VAC t h. 4.
3 113 - 121 VAC I Ac.2 Dropout Voltage Primar_y Se dary low end 312-3e0VAC 1
%AM D
Alarm no i
2 1, 'r7 c19,9 Alarm no 3
31 6 43.I Alarm no Unit picks up at Primag Secon@ry 360-408VAC 1
38A 10 b Alarm Clears no 2
3 6'A IO2 Alarm Clears no 3
%&A In 9 Alarm Clears no j
hN h[
1 g
2 C; 4 A l 'A 3. 4 3
g pC
~ t 'A 2 R Dropout Time Delay N SA.ke' E
=1 second
/no Unit does not return yes no until input breaker reset Page 12
1 DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED l
Test Procedure No. NOTP-836.1.1 UCI S/t bbI EO %EA i
Electrical Output Check. Unit Loaded Load Condition Output Stable yes/ o j
at 480VAC input at 480 VAC 1 113 - 121 VAC II7.7 2 113 - 121 VAC ll~i. 6 3 113 - 121 VAC i t7, b at 414 VAC 1 113 - 121 VAC t 14. E 2 113 - 121 VAC t ii. M l
3 113 - 121 VAC fld. 7 i
at 530 VAC 1 113 - 121 VAC 11 M."A 2 113 - 121 VAC 11 B. I 3 113 - 121 VAC
\\1A_b Dropout Voltage PrJggry Secon@ry low end 312-360VAC 1
'5 S 1 41 I Alarm no 2
3 30
- 41. 7 Alarm no 3
'524 40 1 Alarm no f
Unitb8vACicks up at Pr' b Secob ary Alarm Clears no 360-4 1
l 2
A W4 lO A Alarm Clears no 3
3 FI i 10 l Alarm Clears s o Voltage Prgmgy Secgdr 2
556 i A5.5 3
__ 5 4-h n'A2.2 Unit does not return ye. no until input breaker reset Temperature Rise Check Nlb at T
< or = 90*above ambient Oberatinb emperature i
f il loa Nb Ambient Temperature 4 or - 40' C Ambient Temperature Simulated SCR Short Test Power Module 1
361 VAC Shut Down at short 2
%R&
VAC 3
- t. A b, VAC Circuit Breaker Trip yes no I
T
(
~
Tested by:
ib OD Reviewed by:
/
l i
Page 13
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER 1 of 2 b h"I Page Il Test Procedure No. NOTP-836.1.1 UCI S/N Description Phoeniy Power Tranc:former Part No.:
P3C01SC6/EAN Functional Type di 6%
Test Date S-lb' 9 b Test Number i
MoC MFR S/N EOMA Ambient Temperature IMSTRUMENT AND eof fTPMr'NT LTST ITEM SERIAL NO.
RANGE CALTERATION DATE So bh pluhC _
Ac %4 90 Acco\\14 %g 2 -1@, % ( dq, '
b % A FLuhG 3 (o45 llo acbV ll-Ib - 95 ( de ' Td AA per fwT 7tA432 mv 2-n-w ( dm%)
TEST PROCEDURE TEST DATA TWRT REOUTREMENTS Insulation Resistance:
L(b tAA) b3 h il 10 Mecohm or Primary to Secondary gt. LAI fn 1 M L.
Greater Primary to Ground Secondary to Ground gn A )
A t 4 JL, Electrien1 Output Check (tinit Unicaded)
Three Phase 480 Applied LED's Illuminated No Output Voltage Actual Input Voltage Required at 480 VAC 1 113 - 121 VAC l19 D 2 113 - 121 VAC ti 4. 4 3 113 - 121 VAC t l 4. A at 414 VAC 1 113 - 121 VAC it7 2 2 113 - 121 VAC in.S 3 113 - 121 VAC lt7 7 at 530 VAC 1 113 - 121 VAC I AO S 2 113 - 121 VAC 111 0 3 113 - 121 VAC i 10. O Dropout Voltage Primary Secondary low end 312-360VAC 1
'5 2 5 90.0 Alarm no 2
FK 90 0 Alarm no 3
A2'?
9 A C>
Alarm no Unit picks up at Primary Secondary 360-408VAC 1
WL IO9 Alarm Clears no 2
363 IG6 Alarm Clears no 3
1 W1 16 6 Alarm Clears no Dropout Voltage Primary Secondar,y
>530VAC 1
iA4>A iAT.5 2
44 2' i235 3
G.i Dropout Time Delay (rOgsjer
=1 second no Unit does not return yes no until input breaker reset Page 12
DATA SHEET FOR FUNCTIONAL TESTING OF POWER TRANSFORMER CONTINUED Test Procedure No. NOTP-836.1.1 UCI S/N bb - I ccbwA Electrical Output Check. Ifnit Loaded Load Condition Output Stable ye no at 480VAC input at 480 VAC 1 113 - 121 VAC h73 2 113 - 121 VAC 117. 9 3 113 - 121 VAC in 4 i
at 414 VAC 1 113 - 121 VAC lio 4 1
2 113 - 121 VAC ii M.o j
3 113 - 121 VAC tie.3 at 530 VAC 1 113 - 121 VAC it7.7 2 113 - 121 VAC f 18 4 3 113 - 121 VAC iib 4 Dropout Voltage PrJ.inary Secondary
)
low end 312-360VAC 1 5%
91 0 Alarm no
)
2 33'i 9 L.t Alarm no 3
%Ab C10. o Alarm no Unit icks up at Pricutry Secondary 360-4 BVAC 1
'i B 3 i%
Alarm Clears no 2
383 f02 Alarm Clears no 3
3 CC4 iO a Alarm Clears no Dropout Voltage Primary Seqqndary
>530VAC 1
RGT l'A 1. 0 2
c42 111.o 3
F45 t 16. 7 U'
not return yes/no um Jt breaker reset Temperature Rise Check Operating Temperature
< or = 90*above ambient Nik at full load Ambient Temperature < or = 40' C Ambient Temperature illb Simulated SCR Short Test NA Power Module 1
VAC Shut Down at short 2
th VAC 3
% Cs N VAC Circuit Breaker Trip no 1
.----l Tested by:
LG^
MMbL Reviewed by:
t/
Page 13
l 1
1 4
i 4
i 4
I i
i i
i t
l i
i i
\\
J N
1 1
i i
ATTACHMENT 4 i
4 s
I l
1 1
{
I 4
i 1i a
1 i
4i
(
l 1
a 1
}
l I
Fax Cover Sheet l
TILINOIS POWER COMPANY CLWTON PDWIR STATION l
POST OFFICE BOX 678
{
CLINTON, ILLINOIS 61727 i
DATE: 2-6'f 7 TIME:
ATTENTION: b,
S/ww
>W COMPANY /
hhlh
]
TELECOPY:
776 - V9/e - 709 7 FROM:
UNDA DEGROFFT PHONE: 217-9354881, EXT 3839 4
FAX:
217 435-4258 f
G NUMBER OF PAGES
+ COVER, SHEET 4
i l
e m
}
~ - - ---- --
. LINCI3, poler puncNAsa Ca5ER naft uunnan att aav lassessesLrvanemais 01/24/97
! M us Tunne NO DISCOUNT-NET 30 DAYS 02/06/97 P0704970 0o0 005 j usur muss PREPAY AND SILL i 3/ D ORIGIN l}
.00X TAXABLE 6.25% SALES-USE TAX SERVICE BLANKET i
um NEMO 0F CHANGE un PAGE 1
l Patur nuasaan a INsTRUCTIous i
i U074 02 UNITED CONTROLS me misessa aunees amas imme a..m.E.a*e'sRe
=
vu are 1554 LITTON DRIVE nazkraar=========r au STONE NOUNTAIN GA 30083 MuBT NAIL Inve M E 4
r,:-
w e m & ".r =Y t'..
- - =
M Pm E
f cs l
N
_._.._-._---**~""--a m_.
..o f
mummmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmumm l
THIS IS A MUCLEAR SAFETY RELATED ORDER unne mema l
nummmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmman i
ATTENTION: SEN CAMP m SOURCE SURVEILLANCE REQUIRED THIS MENO OF CHANGE IS TO REVISE THE BREAKER i
l AND SHUNT PART NUMBERS AS FOLLOWS:
ITEN 91 l
UNITED CONTROLS TO PROVIDE 10 EA. BREAKER P/N MG24545 AND 10 EA. SHUNT TRIP P/N MG26973 CPH0ENIX P/M 182-0052) WITH ANY MOUNTING l
HARDWARE REQUIRED FOR INSTALLATION TO J
REPLACE THE EXISTING BREAKERS IN THE PHOENIX POWit j
SYSTEM TRANSFORMER ORIGINALLY PROVIDED UNDER i
THE INTENT OF THE NEW BREAKER IS To l
P0552512.
MAINTAIN THE EXISTING SHUNT TRIP FUNCTION CFOR i
OVER VOLTAGE, OVER TEMPERATURE AND SCR SHORT) BUT NOVE THE INSTANTANEDUS TRIP FEATURE WELL ABOVE ThE j
REGULATING TRANSFORNER AVAILABLE SHORT CIRCUIT 4
CURRENT.
THE NEW BREAKER MUST MEET THE SAME
~
J.asacarrTrou ILLINDIS POWER COMPANY i
SINER/
ANALYST PMWIs 8ESGGa TO AlmIORIZs3 SY cmestase masa tar ath e
, =.,, =, = = = = = ' - = = = = ' = = = = = = " " "
nsasa a-saan nicarrr or Turs oness
=as,=, : :===="===EsEsm*"n' Em*mesE E"""'
- """'"ED #
aus aTTAcusa 70eN ASWISIMB mMEll TOW WILL SMEP E E E Ee"n. "u p
' " "sm"s"e "umu"s" E'='$ YsmMaE E,m."rE'E'a"ss "ea'm ess y mesasi s
'h" ["2" 3."". :".l". ".E"'a. --. -..-
m, e.
m
m_.._.__..__..
m..
j VEMUUMA b u f" ?
{.INOIS,PO1ER puncunst oRasa
{ name snorvusv nata are ses.se est nev
- . Des Tsals 02/06/97 P0704970 000 003 i taur vunns
.r-sus 1,-
t PAGE 2
i eenrr MasamE LDIE i
IlesTRUCTIONS NITED C NTROLS
,m,..
.I. O. in, E,
=
1554 LITTON DRIVE naxt - am a. a e.sans se.s =
STONE MOUNTAIN GA 50083 MusT NAIL INVO2 I
'22 a "iTIEL" 2;,'"'*.a',1*=
...M -
4 pezcg lf waassrzTv sam 7 nascas,Tuus i
2 1
l kCCOUNTINGDATATOBESHOWNONALLINVOICES:
4 TAS.E #1 9300-28651-350 j
THE PURCHASE ORDER ACKNOWLEDGEMENT SHALL BE i
RETURNED TO THE SUPPLIER RELATIONSHIP TEAM LEADER WITHIN 14 DAYS AFTER RECEIPT OF PURCHASE ORDER.
i COMPENSATION SHALL BE AS FOLLOWS NOT.TO EXCEED $10,000.00 WITHOUT PRIOR
}!
APPROVAL.
10 BREAKER P/M M-24545 3 8415.00 EACH 10 EACH SHUNT TRIP P/N MG-26973 3 6165.00 EACH 1 EACH SEISMIC QUALIFICATION AND REPORT a 84,000.00/ LOT T
VENDOR DOCUMENTATION: CE,DS.EI.FT,MI,SEu, we, e j
APPLY TO THIS PURCHASE ORDER.
CCB) CERTIFICATE OF CONFORMANCE, PER ATTACHED me.m=.s t, vu..
ILLINDIS POWER COMPANY
)
imu ANhLYST 70 44m,08 2EB SY c stsee E, 'F.E.@=,._..,=_N=='=: ~ ~== ~ ~
1ttryoI,,owna coy,,yy
..2,,.,.__._,,.
=,= 2
. m c s, v., mt
===== :.
- .:.=.=.: :-
'= =.-. =..._.,
- .=.
er..= :::.n = w=..
g5,p _... _3E= =.::.=.-, __..
7
' LIN515 POWER PURomsE oRasR aaTE massa REL Rev j asam RELtwEev earg_
02/06/97 P0704970 000 003 i.L2ms Teus
- IIsur Tuus
', i.r - ass i
PAGE 3
iPRIMFMES$eggLINE INSTRUCTIONS UO74 02
".l2*o'"n; Jag',l",'g,',=",,,
i UNITED CONTROLS
"" "a E "am'u N '," M ". " * ** * " '"",..
l 1554 LITTON DRIVE',
n STONE NOUNTAIN
.GA 30083 MUSTNAILINVOIb M
wr.=r.::.vi-s:,:--
l
, R.E.P. ' '
W m
d i
rasca f
em urxTV uurf assattrTzan
'"0!
""""'"O "5"""T T" :::: !2! 1;7; l
(FT) FUNTIONAL TEST REPORT j
NAINTENANCE/ INSTRUCTION NANUAL SUSNITTAL CNI)
CSEM) SEISMIC REPORT TO IEEE 344-1975 m THE CERTIFICATION SHALL ALSO STATE TWE BREAKER MEETS THE REQUIREMENTS OF IEEE 323-1974, IEEE i
344-1975 AND IEEE 627-1980, SLISHIC RESPONSE SPECTRA CALC. No. EMD-02*464 R/0 SHEETS 1-4 AND CLINTON FORM 1999-D SUPPLEMENTAL SPECIFICATION FOR ENVIRONMENTAL QUALIFICATION (mm) UNITIED CONTROL TO SUPPLY A TIME CURRENT CURVE FOR THE BREAKERS SUPPLIED.
(4) UNITED CONTROLS TO PROVIDE THE FOLLOWING DESIGN INFORMATION ON THE TRANSFORMERS SUPPLIED UNDER P0552512
- 1) PROVIDE TRANSFORMER IMPEDANCE EXPRESSED AS "PER UNIT
- OR PERCENT. 2) PROVIDE "X"
TO "R" RATIO IN "PER UNIT" OR PERCENT. 3)
PROVDIE THE LOCKTIGHT TYPE COMPOUNT (IE UNITIED CONTROLS PART NO. AND MSDS) USED ON THE MOUNTING HARDWARE AND THE BREAKER TERMINATION.
SELLER QUALITY ASSURANCE PROGRAM REQUIREMENTS PER THE ATTACHED, SHALL APPLY TO THIS ORDER: A,I,J,K,L
.nsscarrrten ILLINOIS POWER COMPANY suveer ANALYST Ptges Insett T
aufgenavrsn my
...s..u."'*'"**
- '""L'/." "". "l':".*" llll'l" ll111:":"m." ":"lT. lll' ": 74l".T.l"!
ILIJNOIS POWER COMPANY 4
T I4"lT.S
, i...
s.-
. n.=
$ = Y Em Ess" "ns"."as T..".""u"a7aas's s. eru. san a.r some.
mas.
s sEs.sS m. s.es ne s us s.m. son".
summer e.ns. sus.: e as som O E. y".O"I'5.Es u.m.
ne in.se.amm.s.
fr
". ". ". " = ". "
sum : e.
au.
u.s a a s a r.s a.usen y,g
- "l:' ": 2.:. ':nl ",.=.'"."::: " :.:'."'.=.. -,.
1".'".""" ="J n
N-es -Am imms
- runu,noaiu 4e vs a, u,3 wa y,,,
venuuws t.ury
~ ~ ~ " - " ~ "
.INOIS POWER PURCHASE ORDER natt asssa est new JISES OR2vtav nats 2 TWB 02/06/97 P0704970 000 005 tour Tams
./ Nsus PAGE 4
amT nessama L!ss INSTRUCTIONS UO74 02 UNITED CONTROLS
.m u -
..E""a"d U = %=
1554 LITTON DRIVE nast
.u -
n.
STONE MOUNTAIN GA 30085 NUST MAIL INWOI
..,y m N M...
GMAIITITY WET DESCRIPT10sl pmICE TEC:"':01'. : 1""L :5 0 ':: 0 """C::105 000".
3 m = TEST PLAN AND FINAL QUALIFICATION REPORT SHALL BE APPROVED BY IPC PRIO2 TO SHIPMENT.
kLL QTHER TERMS AND CONDITIONS REMAIN THE SAME.
mummmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmumann monumannummuunummmmmmmm mmmm mmmmmmmmmmmmmmmm mmmmmme a FOLLOWING ENCLOSED INFORMATION FOR IP USE ONLY w REQUISITION NUMBER: 7027551P REQUISITION ORIGINATOR: J. BLOUNT FOR A. HAUMAN SUPPLIER RELATIONSHIP TEAM LEADER: LINDA DEGROFFT, X-3859 MWR NUMBER: D75398 NSED REVIEW NUMBER: 89350, REY. 03 J. I K. 50,21,S L.
I M.
B
- 0. N P. N R. ID.DA.D0 S.
Y m RISK HOLD PENDING APPROVAL OF ECN TO ALLOW THE NEW BREAKERS. ECN TO BE ISSUED BY AL HAUMAN.
assCarnrom ILLINDIS POWER COMPANY emnu ANALYST "o**
runs semen um.=nen av aus a n
.m m
- """.ll'. l".2lll" "E l"". ".".' 5 "..".' " ""u""."."*: '" ".". lllll" ""..
ILLINOIS POWER COMPANY 3"L".1 J..T 3lll.'s.".*." "*" llll"l'm"
'"^*' ^ ~"" " "'882" "'
rs ossea 3":ll"ll'l.". -.
5" E ". J "" '.".s"'""
5 E.s. E..u as m. s eu. w.ma u
mu an m. = n e..n -r. r m.s.ma gg
.em
'=='3
- llt.'lmi r.
'lll'a".2. 'JR'.n. -..
?f."l".,.dll:'t
7 c-.--..~..
VENDORS CDPY
- LINCIS PotSR i
PutcuAss DRsER lweaseasLzwasyaatti nais masse att nev l.L2mm1saus J'/06 / 9 7 P0704970 000 005
- !!aur Tsans
'! 3 -
- sens 1-i a
PAGE 5
! rezar unasana Lams INSTRucTIOma UNITED DNTROLS
,ui u
.. Y, ",N=, U,=E' i,
1554 LITTON DRIVE maII.:ar= = samman.r
.u v..
l STONE NOUNTAIN GA 50083 Nusf MAIL I N
aw sesent M, g. n to.
g j
l7 queurtTV issT anacarrTzou enzca i
r rrr:::::::::::::::::::::::::::::::::::::::::::::
i ammmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmm ITEN 82 ATTENTION: NIKE LABLANC/ BEN CAMP p
SOURCE INSPECTION / SURVEILLANCE IS REQUIRED ON THIS ORDER REFER TO ATTACHED.
I j
THIS REVISION IS TO ADD ITEM 92 (REF. QUOTE OF 1
2/6/97) AS FOLLOWS 4
l UCI TO PEFORN ENI/RFI TESTING OF THE 15 KVA PHOENIX POWER GUARDIAN TRANSFORNER SUPPLIED TO l!
IPC UNDER IPC P0552512 AND RETAINED BY UCI.
BASED 1
ON TESTING UCI TO SELECT OR DESIGN A FILTER TO l
FILTER DUT ALL FREQUENCIES WHICH COULD HAVE AN j
ADVERSE AFFECT ON THE TRANSFORNER. TRANSFORMER TO BE TESTED PER UCI QUOTATION DATED 2/6/97 SPECIFIC RESISTIVE CBASE) LOAD TO BE SPECIFIED BY IPC LATER.
ALL TESTING SHALL BE PERFORNED IN ACCORDANCE WITH EPRI TR-102323 R/1.
TEST SHALL INCLUDE CE 101, CE 102, RE 101, RE 102. CS 01, CS 02, lEC 801-4, IEC 801-5, AND RS 103.
UCI TO SUPPLY IPC WITH 10 CLASS 1E QUALIFIED FILTERS.
..DESCRZrTzan ixr vsa ILLINDIS POWER COMPANY awsa/
Amu.vsr sans piens,asmaa to a m oazzan av E.881I 2.,, =,.,.,.,.. =
ILLINOIS POWER COMPANY m,,, _
sill". ink ~:.. :g;.,,q;;-- _-,,-,--',,..
- m-a.
- m1u..m2, i.,=.,,.
=r.r: r :-===..=..=:=.=,.... _.
.n
- " "" ~ "" "*"""'"""'
VENDORS CDPY
- ).LDiOIS. POWER, MNtCHASE ORDER
] eusse astzveer am natu names asL nev
- Lunevaum 02/06/97 P0704970 000 005
! stant run s l 3 ' ' YBER l
m maam L2m PAGE 6
In ineviinus i -
U074 02 l!
UNITED CONTROLS
" E m E =YIE'E.~aa"=='t.
1554 LITTON DRIVE munans asumeis ansa vues as a saneam num nazti -=====r an =6.---
v..
STONE MOUNTAIN GA 30083 NUST NAIL INVO N
=v.a ~~ ~=:,r~w~
re j
p a_
.itaru.ve Asame O!
i THE PURCHASE ORDER ACKNOWLEDGEMENT SHALL BE i
RETURNED TO THE SUPPLIER RELATIONSHIP TEAM LEADER q
WITHIN 14 DAYS AFTER RECEIPT OF PURCHASE ORDER.
i j
ACCOUNTING DATA TO BE SHOWN ON ALL INVOICES:
ITEM 42 950s 28631 350 l
COMPENSATION SHALL BE AS FOLLOWS:
PREPARATION OF TEST PROCEDURE / PERFORM EMI/RFI TESTING = 459,850.
}
FILTER DESIGN SELECTION AND ASSEMBLY = $12,500.
j SEISMIC QUALIFICATION OF FILTER = 43,500.
l ASSEMBLY AND DEDICATION OF (10) i FILTERS = $17,560.
j CERTIFICATION AND DOCUMENTATION = $5,000.
t EXPEDITING TO MEET 5 WEEK SCHEDULE = $8,000.
VENDOR DOCUMENTATION: CB, DS, NI, M APPLIES TO i
THIS PURCHASE ORDER.
(DS) DRAWING SUBMITTAL REQUIRED l
(CB) CERTIFICATE OF CONFORMANCE (PER ATTANCED) THE i
CERTIFCATION SHALL ALSO STATE THE FILTERS 4
- sascarnram i:pvu ILLIN05S POWER CONPANY wesa/
AleALyst isse 3
PMmE 9853ER 4
4 h
AUTWOAIZES SY
. =,, _ " =, _ =
~
ILLINOIS POWER COMPANY 3.,g p
,t,A., -.
,,,,,vurs seesa amena.me.. ses - m e a w i jg g g = ma,.,g,g,.,g my 086 ATTAC358 FOAM ASWESIIS INEN y0W ttILL SHIP s."aE.u.
.w een
. an. air.s m s y;+ 1_3id $_.= =.r.
,. _. _ y _ _
- - ~ ~ ' ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ '
2
- * * * * * * * * * " ~ ~ * * * * * * * * * "
MO.IS POWER VENDORS COPY s
PuncNAss 0asan i meses emIvaev natt Daft sesses est.
asv
' E2ue fEMS 02/06/97 P0704970 000 003 i IIENT TEES l a.a,7855 l
! wear nessaar La$
PAGE 7
UO74 02 r
wiicus I
UNITED CONTROLS o
su mi. m.
. *.E."E.' E E **
r
=
i 1554 LITTON DRIVE nastaie==== =9==r an esamu.mene ni j,
STONE MOUNTAIN GA 50083 MUST MAIL INVO N
i er. --
- u-N"--
I
_. M.... _..
!7 WmMTTTY uutt assearrrten
- pass, j
7::T :n: - :":: nreT: 0.-
i 1974 AND 627-1980.
NOTE: THE SEISMIC SPECTRA PREVIOUSLY SUPPLIED WITH P0552512 l
CMI) MAINTENANCE INSTRUCTION MANUAL SUENITTAL i
REQUIRED.
MAINTENANCE INSTRUCTION TO INCLUDE ANY PREVENTIVE MAINTEANCE REQUIREMENT, I.E.
REPLACE FILTER EVERY FIVE YEARS.
j Cu)
UNITED CONTROLS, INC. TO PROVDIE IPC WITH i
FINAL EMI/RFI TEST RESULTS AND SEISMIC i
QUALIFICATION REPORT.
UCI TO FAX TEST l
RESULTS TO IPC PURCHASING DEPARTMENT ATTNs l
LINDA DEGROFFT; FAX e 217-935-4258.
ALL i
DOCUMENTATION SHALL BE SUBMITTED TO IPC l
PURCHASING DEPARTMENT; ATTH: LINDA DEGROFFT.
SELLER QUALITY ASSURANCE PROGRAM REQUIREMENTS PER l
THE ATTACHED, SHALL APPLY TO THIS ORDER: A.I J,K,L TECHNICAL: m APPLIES TO THIS PURCHASE ORDER.
l m = UNITED CONTROLS, INC. SHALL PROVIDE IPC THE TEST PLAN / SEISMIC PLAN FOR APPROVAL PRIOR
.TO ANY TESTING.
SUBMIT TEST PLAN (FAXED)
TO ILLINDIS POWER COMPANY 217-935-4258, ATTN LINDA DEGROFFT.
IPC SHALL PROVIDE iasscarerram ar vza ILLINDIS POWER COMPANY SINEE/
- wrr amuY8T ji ria.s uween l
t l
Aurneezzas av i.:.r. s ="""'"..-,,. _
i, !" " F.E'E*' ** """" """ " "="="" ".' "=""s"=
="="=". ' "==" ""="=' "
ILLINOIS POWER COMPANY u
=
g
=g g ===,=,,= g gi g = -
==
y,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
! $ "m"e E "e"s "eeEmEs*E E.EsE E""""' *""""' " " "'" " " '"
on ATTAcut0 FOMI ASWISIMO WIEEm YOU WILL SM!r l.".m"esEmmaas M as M EiEu"rE""Ese" *NE IenNeEseyson=
g gh",,7",":d5'R".". " "..lll"' *..
E g....
e r.sa aa a ma e
- s *e
, w m i - <w. i =
.s
<.4 a --~
i.w
- MOIS N VENDORS COPY PunenAsa cassa i :mgage esLxvumv nave n4TE senses set agy
} n2ms ruuss 02/06/97 P0704970 000 003 lE2anttemps 3 a - Tanns t
j lIremrNEstantLIng PAGE 8
ti i--W1-
};
UO74 02 i
UNITED CONTROLS
.,.u im.==,=.
.m* E n'= E.E. %=
t 1554 LITTON DRIVE nazLi u==na me=====r m
i STONE MOUNTAIN GA 30083 MUsf MAIL INve
=~ w ~'y p.rx:a ~
.. - m,.
1 J{7 suasertTY usT assCSIPT!m pagte l
TEST DATA.
TECNNICAL CONTACT AT IPC IS AL HAUMAN 217-935-8541. X-4074.
I kLLOTHERTERMSANDCONDITIONSREMAINTHESAME.
sammmmmmmmmmmmmmmmmmmmmmmmmmmmmmmusammmmmmmmmmmmme a FOLLOWING ENCLOSED INFORMATION FOR IP USE ONLY a REQUISITION NUMBER: 7035S$1P REQUISITION ORIGINATOR: JERRY BLOUNT j
SUPPLIER RELATIONSHIP l
TEAM LEADER:
LINDA DEGROFFT j
MWR NUMBERr AP031 MSED REVIEW NUMBER: 89422 REV. 0 l
J.
I K. 50,21.S L. V M.
5 O. N P. N R.
ID,DA,DO S.
\\
T. RK = RISK HOLD PENDING ECN TO AUTHORIZE THE i
FILTER PER AP028.
I nummmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmuummmma 1
1 g
naammmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmmme monummmmmmmmmmmmmmmemoramanummmmmmmmmmmmmmmmmmmmen ma m mm m m m m m mm mm m mmm m m m u u mu n u m mmmm m mmm mmm a nu ma mmmun e M
7 VIA ILLINOIS POWER COMPANY amens mentysT MIP a
russa saansa AUTN00!2IB SV
)
as er oss sese, ma,e amami 1 NEs Ese"a"m"".* ""ase's."s="=E."'EE'eE" "m"sYE,e m
?,
3""'.:"
m== -
n.=
=
ILLINOIS POWER COMPANY
$"d %"'="="=*a=7 ="='"E*a= ====== = = a*' " ""
etusa =.=.===== nacazer or Turs onesa I
12 "' = ". "," : ". t "" l:RE ". ""*' *"'"" " "" '""" " " '"
on arnemas rann aavaszus men you mIu. sure
'emie aEsse v. A ~w msuELE EEme"r !'eEE'"asse".[.'E EsYse !"mes w.uwt I
I.N. EY.dI.'.5'.'::::".E.ll'.:'"#.. s..
s.meea4eegs m essempts ass.Instaus
. -. A ~W T T ~ ~
WLW7W~ ~ ~ ~ ~
r-ca v.m asst wo
- ~ ~ " " ~ " " " " " " "
VENDORS COPY
.LDICIS PO1GR puRcNAsE oRosR amass astrvaar ears nars sessen est aav m Tess 02/06/97 P0704970 000 003 user Time v man PAGE 9
reser mannaes Las U074 02 UNITED CONTROLS v".l="*e'"sr '."E'# ~a"m.'r.
.19 AP8 LIE.EE SLLI.GES SeL88 TAM AS A MTE 1735 1554 LITTON DRIVE nan:armaninsaammer
.t,,,,,,,,,,,,,,
STONE MOUNTAIN GA 50083 MusT MAIL Inve M a
..,L.
.,.a
... N..
.v..
i f
3MaNTITY Last nascatPTime rests e::xce.
- ::r::::: :n :: : c ::::::ee.. ten::;
- 1. SHIP NO SUBSTITUTIONS WITHOUT PRIOR APPROVAL.
- 2. SHIP NO MATERIAL OR EQUIPMENT CONTAINING ASSESTOS WITHOUT SPECIFIC PRIOR APPROVAL.
- 3. SEND ALL REQUIRED DOCUMENTATION WITH SHIPMENT.
- 4. MATERIALS /EDUIPMENT SHALL BE PACKAGED AND SHIPPED USING GOOD COMMERCIAL P,RACTICES.
IF GOVERNED BY ANSI STANDARDS, 7 ANSI N45.2.2, LEVEL & REQUIREMENTS APPLY.
'SPECIAL' REQUIREMENTS WILL BE SO NOTED IN THE BODY OF THIS ORDER.
PART NUMBERS MUST BE CLEARLY IDENTIFIED FOR EACH ITEM AND SHOWN ON ALL SHIPPING PAPERS.
5.
IF SHELF LIFE APPLIES TO ANY ITEM ON THIS ORDER, IT IS REQUIRED THAT A MINIMUM OF 80%
l SHELF LIFE REMAINS ON THE ITEM AT TIME OF l
SHIPMENT.
IF SHELF LIFE IS INDEFINITE, NOTIFY THE BUYER PRIOR TO SHIPPING.
l THIS PURCHASE ORDER IS FOR G30DS ANd/OR SERVICES l
TO BE USED AT THE CLINTON POWER STATION. WHICH IS JOINTLY OWNED BY ILLINDIS POWER COMPANY AND SOYLAND POWER COOPERATIVE, INC.. AND TITLE TO SUCH GOODS AND/OR SERVICES SHALL PASS TO THEM IN i asscazrrzan lPWIA ILLINCIS POWER COMPANY avvise ltIP Puma manen i
i A4minE! ZED BY
!.,,..u.'""'""
- ".'"'.
- lll."":'"" '"" l':llll "."'J."."'." "L'" ".='E :'J" T,., m 1:""'.E
.. w.am n ma ILLINOIS PO1ER COMPANY
- w S."'.'" "."""" T lE'J'
===.
^8^""""""""*82""**'""
- ."l"l"": ~.
'E.E'a"."E.E." s E 5s"E'E'E.Es am.
s er.esu se m.u
.e n y as.-t uim :a mas.a.ms a. ei.e
! ='.""E "J.".e."Wlll "l:'"".""".'l.:'Jl"'=..
! Y.2 :'"Jlll'lF
.----...,,u IINQ17. POWER VENDORS COPY j
om em.
esv j - --y,,,,
02/06/97 P0704970 000 003 i ). Arame l
femt REBame LZam PAGE 10 e
2 _.-- s zoNs U
TED ONTROLg W. %.
1554 LITTON DRIVE mmar-ma=====v=r me au amm mmes =,
l STONE NOUNTAIN GA 30083 gygg gagg 3 6 g i
' "a*s*.E '**' *M"?ns%'*****
s
....N
.. _. =
!I
-o..
"3
......--.--. -- --..-~.... -.
j ALL NATERIAL OR EQUIPNENT SUPPLIED UNDER QUR i
PURCHASE ORDERS SHALL BE FURNISHED IN A NEW UNUSED l
CONDITION.
USED REBUILT OR REFURBISHED ITEMS ARE UNACCEPTABLE UNLESS SPECIFICALLY NOTED IN WRITING I
ON OUR PURCHASE DOCUNENT.
SELLER AGREES THAT THE NERCHANDISE AND/OR i
SERVICES COVERED BY THIS CONTRACT SHALL BE OR HAVE BEEN NANUFACTURED OR PERFORNED, PRICED l
AND SOLD IN ACCORDANCE WITH ALL FEDERAL, STATE, l
AND LOCAL LAWS, INCLUDING WITHOUT LINITATION, THE FAIR LABOR STANDARDS ACT, THE EQUAL OPPORTUNITY CLAUSE SET FORTH IN 41 C.F.R.
SECTION 60-1.4CA), AND THE AFFIRNATIVE ACTION CLAUSES SET FORTH IN 41 C.F.R.
4 i
SECTIONS60-250.4,-741.4.
i QAP-407.02F02, REV. 2 (2 PAGES), IS INCLUDED i
NEREWITH AND IS AN INTEGRAL PART OF THIS PURCHASE l
ORDER.
I i
4 lasscazerson BREAKERS END OF ORDER / SIGNATURE PAGE p vga AIR EXPRESS ILLINDIS POWER COMPANY CLINTDM POWER STATION IP800 2
2 RR 3, P.O.
BOX 678 (RT. 54 E.)
an s.vsr L. D. D E G R D F F T CLI"sTON IL 61727 Paus sammen C217) 935-8881 a
STORES SUPERVISOR 217-935-8881
[
aurwoezzas av
.=
eem m
.e s.
m mesa, suma.uma e au
'l
'E'E'.2-m.
,.==mm m.m-.m
.a-ILI.INOIS POWER COMPANY
].,.." %"' """ T "."E
sa m=. === =====
ptage
.,n m.m,r w Tsus osesa g ",,, M ",*,",,",,",g " "E'7'"'""""*"""'*"#"'"
ON ATTACMB FOAM ASWISIME IAW8 YOU NILL 38GP m' ".m". "m u m as N 's,e M S Em "e."sma"a.'s"am"Ess".*a# E *ess an,
e.us y am.s.
g.E-@~d
=.. _=.=:r.=..
, _ _ - -. _ _ - ~.. _ _. _ _ _ _ _ _ _. _... _ _ _ _ _ _ _ _ _. _ _ _. _. _. _, _ _ _ _, _ _, _
r w.~..,...,
. ~.......
),e maasta or..-....... cone en l
===:r=== or om c -
(035tMur nuisans 1MR2 D0 NOR 5353 ars unemommer - assarrzan) 1 i
l War ansk heat et w=1 3st of antautal, og item deLLeeses, the aggpume shall j
i suavide a easttelsettes that the them eendesas ' e aLL af the maquisemente of the t
j ausuhase ceder See, that iems. Ther eastitimatism shmLL Edam *3*y the part i
ammmer(s), semist ammher(s),1st ammber(s), ses. (seen used), se =m11 as the N e
'W"*'*8==*i - endas,.and standands, to endsen that item consens. m date, title, ont adgaa*=== et the
- r--- =ts e eme ada v=4h1= individual la the suppLimir's
. -==-r en.he -..
e daa====*{s) ehell madnemans ttie IP Perchase Geder Neuber -(and item mesher, if roamized, to assess : - - - " < *y), or other **====M. e d=== < et wa =. m, l
{
2he vender shall oestify that ths !past, belag supplied aests the requinuments for Eess, fit,
- ===*ia=.==a== del-and. -way psommes ida=*Lff ad by 'the Tender's draniag/part amhoss oyersified on this pumahama cedes.
I l
l l
i i
1 l
1 o
9 3
l i
i l
l, l
9 1
4 t
l l
l
(
4 i
s j
1 k
4 en I
i
]y a
i s
cco,o us,
-~
.. ~...
Lasten%g
- f
.,.. e PRSass March 18, 1996 cansa.a. spa l
c-w-
reau ur,.eas 1
l
~.
l 4,
TD All Vendors and M14-3
?
i i
The massage at the w a=4== of this ordar contains some j
very 44 information, desir-d to help you process our requirements.
i i
1 i
Items tuo (2) through four (4) are self9===tm and generally do w pose a problem with fim==,caders.
1
'Item cos(1) and its intent is the purpose of this notica-
= ship no. substitutions without prior approval" is the
=, = m--.1-you need to understand.
2 If what you intend to ship to us is not an EIM5' METE to i
l the descrird
'and the part smsbar.in the Dutchase order DQ EXE l
parn.TE Plasse call the Bayer shoun on.tha. last pass.of'%s Cedar f
f immediately and e4*y him/her, of the discrepancy.
You will receive furt.har instrumdans'at that ~'4*.
WIzz FaK EEEEMEDEB, ZF WERE TOtt SED DeRE,302 NETS SER MegagyEur er iEE cEngs., seIEEEE or TOUR. 2E. veICE WIIss[SE .-
i m.
l We don't want that and neither do you.
j Thank M for your cooperation.
1
- Regards, l
?
l i
3
- Rualear Purobassagr Team 1
i I
i i
}
4
]
e i
]
w -,v,.u,rua j
Revisicn y
.s j.
REXERIMONNUMBER P. O. NUhDIER i
i Check bemoswhinkapply:
~
i j
M Samme ImammedentSurvedlaman Natifismana
'Os suppliar shan psevids assess to the Supplids plant fiuGisies and monsds pesemining as this punknas essersur she
- = pans 5 ympes af pheming and podaming somme inspanion/suv insam ass sies. m weddes days advemme madne est the anyer noid poins win bo nneed.
& supplist shaR esmanet Ibs asyWs demismased suyassesseive prise to seembing 's hold point and the di 3'Pl er wiR ant pened pas that point unit inspannen has base ambildad er waned by em Emper.
nesonowinghold aismapptr.
P m b, A i (1 s.0 %
D \\bluit b n > uf,,
. A Le si un e.a 06
%u t
i s
s Consasc h> c %
Phone: G17) 935-4881.Est. _ </odb V
/ 0' I
I M 1005 Surveillance loos serveinsam appians to this ader, the Suppliar shan provida access as iba pleut imGidas and rommak postaming a this seder at any tias work is perforused soganEass of es ties of day or day of the wesir. Weak shaR mot psmemed wi6ces the passess of the serveiBaat, aussyt as assued to by the serveinaar. IFisnobeandded weekmg days priorto abssamt ofweek.
Comeost:
Phams: G17) 9354881. Est.
l lu wcmiirunnan Annmval sappiisa pedmasing wesk at cimaan Power Smden who inssed b use abair seu prosadans shnu seimmit the pennedsmus to Ibn desigssend aquusmensve listed belour for sevesw and appuoset.
Commse Phame: Q17) 9354881.Est.
I iu
> calibrinan sappiins who popos e as their own Mg and tas equpeset at C11mson Power Sudan shall have cabbsensa esm5eans tassabis to tbs NasionalIammas of 3 aminsds and Tashmology (N.LS.T)
I inshuding vandsadas that abs==ai&=a= pievided is valid. If abe equipsames is of sedi a sanan that it l
commes be teamed to N.LS.T., the basis for calibension abnB be provkind.
1 con===
Pham: a17) ns488,nat.
1 l
J Page 2 of 2 i
o TOTAL P.15 i
8 QUALI1T ASSURANCE PROGRAM REQUZIEMIrfs gap q.y,o %.
,s RaviDion y i
PURCHASE ORDEE l
A. The sder shnu psevids shs issa or servios bF.DEutTED j
la sondens wisk the geger's 10CFR50, Appedia B Quakey Ammunes Progsam i
swismed and appseved ny 3. osigns a G. This psumammet simu be in acaudamm she appassed QumWy Aammunes ymsma wie de Agumment for Equipummt and j{
Savists dansd' 11/19/35 g,s shaR bs ambmiend as W for apparval.
j Qashey Ammmmen psogang g Wadagboam Eleussic Caspammien ad shd be imumposted la ab 46sr pammment BBasis Power campsey, no.inen.6, i
desumanas as asquised by seGar's appasved h almE be supplied in ansesdenes wkh l
QuaileyAssumn.spoem
.de Wushaghomas Qummy Ammmmes Psossam -
as M in WCAF 8370, WCAF 9245 or
'6 O B. The sauer shnu psovide de hasa or arvicew'*-
- w sh n Asus de in anonnianos widt the sauer's Quahry Ammmme ymsnm avisand and approved ] H. 3 F
by IP. Chamse a de appsved Quey 9 utility shnu punis tha ha m or Amammes Pmgram shd be abaised 2 IP mems la usoniamse with the muity's 1
for apparvaL quailey A=--=
= pagna Appendix B Quality Am
=p-=== shnu be '
ja sw.,
7""""" d="uma as aquimd by sens appamd 4,misey am se I.
n is
- i.,is a hj : a is. - f a
Pmgma.
Tids 10 of she Cods of Fedmal Ragnimiens, 1
Pas 21. If aminemos in evehanha pomadal deviadoes under 10CPR21 is segebed.
i C. Tha seller shd provida absimmior answa is asandsam widt de sene. Asus
"""T=-i-she be addened not seeins m Qantity Asemamm Psegna ad Menger W Unusing & Safay IHimais appambas Asus Cadames,i.-i m.,de P'"*r C'"rmy. Should sdar anim any Quaiity Asumanos onessels of 10CFR50, 4 to de NRC uisde to desones
""""4 by tocFR21. whidt me==Imand so l
A,ps.dia n.
o ssa u e de app
,,.d i"m' *' '"'i ""m'd by 'his 7ma==mmt Qasey Ammmen passa den be W comuses assismaism shau be
==h=in=d so W ihr enview.
nudeso: Idemager of Yla===iar & safsey,
' PeuerCompany.
O D. Ds sauerabaupsowedsthelaumaerservens In aamudsmas widt dem Esiler's AsME NCA-J.
IRheis Feuer Campey gP) maanes dooo qu.sey Am ma ya,s i.mt amniske orm.ms, seris,.mi.rm sieby i
appumus Asua em4 e or its demisesad pm me,e, s du Asshmiedenwhkdmidies,ing-assauls and pisms Ansignies of bodi ths sauer ad dews h and appuns.
- 1) nled pasty inspemos mot sequisud; and
- 2) ASME Code sammgang mot aquised.
Appsevel by W is sequised for an % w n.m a.
C E.
Gement BIsserts Chunggy wlE mimpip Is* er supair". -
Thess W noman admaland en W shat be b=h. dad k wi& unir Qadey Amusum= Pressna m O"I
" punknas aunt to P.
idennSad la NEDO 11209 04A. Qanges to the -;j Quality A====== Program shsH be submined to 2 forappsoval.
L OtherW AttachedPaes2.
l Page 1 of 2
- --