- ML20210V087 (← links)
- 05000366/LER-1989-005-03, :on 890903,feedwater Sys Master Controller Placed in Automatic Following Change from Single Element to Three Element Control,Controller Output Signal Suddenly Went to Zero.Caused by Component Failure (← links)
- 05000259/LER-1987-015-01, :on 870709,reactor Protection Sys (RPS) Circuit Protector Tripped de-energizing RPS Bus a Causing RPS Half Scram.Caused by Mods Craftsmen Working Near Circuit Jarring Panel.Craftsmen Counseled (← links)
- 05000277/LER-1987-020-01, :on 870904,HPCI Sys Determined Inoperable Due to Opening of Resistor in Voltage Dropping Assembly.Exact Cause for Opening of Resistor Unknown.Resistor Replaced on 870914 (← links)
- 05000318/LER-1986-005, :on 860725,RCS Leakage Determined to Be Greater than 1 Gallon Per Min.Caused by Separated Compression Fitting from Flexible Metal Hose Installed on Reactor Coolant Pump Tubing.Hose Repaired (← links)
- 05000461/LER-1997-029, :on 971113,failure to Follow Plant Procedure When Erecting Scaffold Resulted in SR Area Cooler Becoming Inoperable Due to Seismic Qualification Concerns.Caused by Failure to Follow Plant Procedure.Modified Scaffold (← links)
- 05000370/LER-1997-001-06, :on 970527,DG Load Sequencer 2B Inadvertent Esfa Occurred.Caused by Inadequate Development & Review of Change Made to Sequencer Timer Calibr Procedure.Review of Similar Procedures Being Conducted (← links)
- 05000289/LER-1997-001-01, :on 970117,potential Overpressurization of Piping Between Closed Reactor Building Isolation Valves Occurred Due to Inadequate Design Code Guidance.Results of This Review Will Be Documented (← links)
- 05000325/LER-1992-021, :on 920920,south CS Room Fire Protection Sprinkler Sys Placed Under Clearance W/O Required Fire Watch.Event Reviewed W/Operations Personnel Emphasizing Need for Precise Communications Between Groups (← links)
- 05000373/LER-1996-001-06, :on 960213,missed TS Required Fire Protection Valve Position Verification Occurred.Caused by Human Performance.Operating Dept Senior Mgt Reinforced Expectations W/Sros & Shift Supervisors (← links)
- 05000336/LER-1995-039, :on 951010,SW Pump Performance SR Less Stringent than TS Due to Personnel Error.Performed Review Which Confirmed That Most Recent SW Test Results Met TS Requirements (← links)
- IR 05000309/1982004 (← links)
- 05000483/LER-1990-004, :on 900330,licensed Util Personnel Discovered Standing Oil on Generator.Oil Had Splashed Through Ventilation Screens Into Generator.Cause Unknown.Collector Rings & Stator Windings Cleaned (← links)
- 05000368/LER-1980-075-03, /03L-0:on 801007,A Safety Injection Tank Pressure Found to Be Less than 600 Psia Per Tech Spec 3.5.1.d.Caused by Vol Loss Due to Sampling W/O Capability of Remote Repressurization Due to Inoperable Control Valve (← links)