- ML19208D495 + (04:18:16, 5 January 2025)
- 05000324/LER-1979-078-03, /03L-0:on 790831,while Removing Rwcv,Suction Inboard Value F001 Failed in mid-position.Caused by Torque Limit Switch Opening & Causing Motor to Stop.Valve Tested & Problem Did Not Recur.No Further Action Necessary + (04:18:18, 5 January 2025)
- ML19208D492 + (04:18:18, 5 January 2025)
- ML19208D491 + (04:18:19, 5 January 2025)
- 05000324/LER-1979-078, Forwards LER 79-078/03L-0 + (04:18:21, 5 January 2025)
- 05000298/LER-1979-023-03, /03L-0:on 790809,Barton Model 288 Differential Pressure Indicating Switch MS-DPIS-119B Was Found in Excess of Tech Specs Table 3.2.A.Caused by Faulty Switch. Microswitch Assembly Was Replaced + (04:18:25, 5 January 2025)
- ML19208D487 + (04:18:26, 5 January 2025)
- 05000324/LER-1979-080-03, /03L-0:on 790830,primary Containment Ambient Temp Exceeded Tech Spec Limits,Causing Small Steam Leak.Caused by Leakage & Steam Cut of King Pin Cover on Feedwater Check Valve B21-F010B.Leak Repaired & Leakage Decreased + (04:18:28, 5 January 2025)
- 05000324/LER-1979-080, Forwards LER 79-080/03L-0 + (04:18:35, 5 January 2025)
- 05000313/LER-1979-016-03, /03L-0:on 790827,diesel Generator 2 Tripped on Low Oil Pressure,Rendering Generator Inoperable.Caused by Leak Allowing Water to Enter Oil Sys,Causing High Crankcase Pressure.Oil Cooler Replaced + (04:18:37, 5 January 2025)
- ML19208D478 + (04:18:39, 5 January 2025)
- 05000298/LER-1979-023, Forwards LER 79-023/03L-0 + (04:18:40, 5 January 2025)
- 05000333/LER-1979-052-04, /04L-0:on 790830,computer Calculations for Condenser Inlet Water & Plant Cooling Water Discharge Temp Differential Temp Were Found Out of Calibr.Cause Not Stated. Instruments Recalibr within Tech Specs Limits + (04:18:42, 5 January 2025)
- ML19208D474 + (04:18:43, 5 January 2025)
- 05000313/LER-1979-015-99, /99X-0:on 790817,as Result of Analysis of Seismic Category I Pipe supports,37 Restraints Were Identified to Have Safety Factor of Less than Two.Supports Modified + (04:18:45, 5 January 2025)
- ML19208D471 + (04:18:46, 5 January 2025)
- 05000333/LER-1979-052, Forwards LER 79-052/04L-0 + (04:18:47, 5 January 2025)
- ML19208D468 + (04:18:49, 5 January 2025)
- ML19208D466 + (04:18:49, 5 January 2025)
- 05000368/LER-1979-077-03, /03L-0:on 790826,safety Injection Tank 2T2D Level Could Not Be Maintained Above 80.1% Due to Makeup Valve 2CV-5064 Failing to Open on Command.Caused by Improper Spring Tension on Valve Operator Gate.Tension Adjusted + (04:18:51, 5 January 2025)
- 05000298/LER-1979-020-03, /03L-0:on 790809,while Performing Surveillance Procedure on Relief Valve Bellows Monitoring Sys,Pressure Switch MS-PS-71G Failed to Actuate.Caused by Improper Assembly.Switch Was Replaced + (04:18:52, 5 January 2025)
- ML19208D462 + (04:18:54, 5 January 2025)
- 05000368/LER-1979-076-03, /03L-0:on 790821,control Room Emergency Air Conditioning Unit 2VE1B Failed to Start.Caused by Crankcase Oil Leak.Leak Repaired,Oil & Freon Added + (04:18:55, 5 January 2025)
- ML19208D460 + (04:18:56, 5 January 2025)
- 05000298/LER-1979-020, Forwards LER 79-020/03L-0 + (04:18:58, 5 January 2025)
- ML19208D456 + (04:18:59, 5 January 2025)
- ML19208D454 + (04:19:01, 5 January 2025)
- ML19208D452 + (04:19:04, 5 January 2025)
- ML19208D450 + (04:19:05, 5 January 2025)
- 05000321/LER-1979-072-03, /03L-0:on 790827,plant Svc Water Supply Isolation Valves for Standby Gas Treatment Charcoal Filter Fire Protection Deluge Valves Were in Closed Position.Caused by Low Svc Water Pressure and Very Sensitive Deluge Valves + (04:19:06, 5 January 2025)
- ML19208D448 + (04:19:07, 5 January 2025)
- 05000321/LER-1979-072, Forwards LER 79-072/03L-0 + (04:19:08, 5 January 2025)
- ML19208D445 + (04:19:10, 5 January 2025)
- ML19208D443 + (04:19:11, 5 January 2025)
- ML19208D444 + (04:19:11, 5 January 2025)
- 05000298/LER-1979-022-03, /03L-0:on 790812,water from Carbon Absorber Housing of Standby Gas Treatment Sys a Sprayed Carbon Absorber Trays,Rendering Trays Inoperable.Caused by Inadequate Seating Area Between Valve Clapper & Latch + (04:19:13, 5 January 2025)
- 05000298/LER-1979-022, Forwards LER 79-022/03L-0 + (04:19:15, 5 January 2025)
- 05000324/LER-1979-079-03, /03L-0:on 790831,operator Noticed Drywell Oxygen/Hydrogen Monitor Had Low Flow Condition & Indicated Abnormally.Caused by Frozen Air Dryer.Dryer de-energized & Allowed to Thaw.Dryer Inspected W/No Problem + (04:19:17, 5 January 2025)
- 05000220/LER-1979-079, Forwards LER 79-079/03L-0 + (04:19:19, 5 January 2025)
- ML19208D435 + (04:19:20, 5 January 2025)
- 05000366/LER-1979-103-03, /03L-0:on 790907,drywell Average Air Temp Rose to 145.8 F While Maint Personnel Were Adjusting Flow to Lower Drywell Temp.Temp Increase Caused by Suspected Steam Leak. Flow Increased to Reduce Drywell Average Temp + (04:19:21, 5 January 2025)
- 05000366/LER-1979-103, Forwards LER 79-103/03L-0 + (04:19:23, 5 January 2025)
- 05000366/LER-1979-096-03, /03L-0:on 790912,HPCI Flow Control Loop Inoperative.Caused by Bad Ramp Generator in Turbine Control Loop.Generator Replaced & Loop Functionally Tested to Ensure Operability + (04:19:25, 5 January 2025)
- 05000366/LER-1979-096, Forwards LER 79-096/03L-0 + (04:19:27, 5 January 2025)
- ML19208D427 + (04:19:28, 5 January 2025)
- ML19208D425 + (04:19:33, 5 January 2025)
- 05000298/LER-1979-021-03, /03L-0:on 790811,carbon Absorber in Standby Gas Treatment Sys B Was Wetted W/Water When Control Room Received Actuation Alarm for Deluge Sys.Caused by Improper Installation of Baseplate of Fire Detection Unit + (04:19:35, 5 January 2025)
- 05000333/LER-1979-053-03, /03L-0:on 790901,floor Sleeve 1FC023R18 Was Intentionally Opened.Caused by Need to Pull New Cable as Part of Plant Mod.Fire Watch Stationed & Maintained Until Floor Sleeve Was Resealed + (04:19:37, 5 January 2025)
- ML19208D419 + (04:19:38, 5 January 2025)
- 05000333/LER-1979-053, Forwards LER 79-053/03L-0 + (04:19:39, 5 January 2025)
- ML19208D415 + (04:19:40, 5 January 2025)