Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19332A602 + (08:19:12, 31 December 2024)
- 05000334/LER-1980-064-03, /03L-0:on 800825,chemist Failed to Analyze Reactor Coolant for Chloride & Fluoride & Did Not Analyze Until 800827.Caused by Personnel Error.Chemists Were Reinstructed in Sampling Requirements + (08:19:13, 31 December 2024)
- 05000334/LER-1980-064, Forwards LER 80-064/03L-0 + (08:19:15, 31 December 2024)
- 05000327/LER-1980-152-03, /03L-0:on 800812,diesel Generator Battery IB-B Cells 49-51 Were Found in Discharged Condition.Caused by Inadequate Procedure.Procedure Has Been Changed & Personnel Reinstructed + (08:19:17, 31 December 2024)
- 05000327/LER-1980-152, Forwards LER 80-152/03L-0 + (08:19:19, 31 December 2024)
- ML19332A594 + (08:19:20, 31 December 2024)
- ML19332A593 + (08:19:20, 31 December 2024)
- 05000334/LER-1980-059-01, /01T-0:on 800823,during Diesel Restart on Low Pressure Following Shutdown from Surveillance Run,Starter Motor Burned Up.Caused by Open Field Winding.Starter Was Replaced + (08:19:22, 31 December 2024)
- ML19332A590 + (08:19:23, 31 December 2024)
- ML19332A591 + (08:19:23, 31 December 2024)
- ML19332A589 + (08:19:24, 31 December 2024)
- 05000334/LER-1980-059, Forwards LER 80-059/01T-0 + (08:19:25, 31 December 2024)
- ML19332A586 + (08:19:28, 31 December 2024)
- ML19332A585 + (08:19:29, 31 December 2024)
- ML19332A584 + (08:19:30, 31 December 2024)
- ML19332A583 + (08:19:31, 31 December 2024)
- ML19332A582 + (08:19:32, 31 December 2024)
- ML19332A580 + (08:19:32, 31 December 2024)
- 05000295/LER-1980-007-01, /01T-0:on 800815,during Normal Operation While Mods Were Performed on post-LOCA Hydrogen Recombiner Piping, Hydrogen Purge Fan IRV020 Was Made Inoperable.Caused by Failure of Const Dept to Notify Operating Dept of Mod + (08:19:34, 31 December 2024)
- 05000327/LER-1980-146-03, /03L-0:on 800617,following post-maint Testing of Safety Injection Pump 1B-B,one Step of Venting Instructions Not Signed.Caused by Lack of Immediate Followup Action to Determine Cause Before Entering Mode 3 + (08:19:36, 31 December 2024)
- ML19332A576 + (08:19:37, 31 December 2024)
- 05000327/LER-1980-146, Forwards LER 80-146/03L-0 + (08:19:42, 31 December 2024)
- ML19332A573 + (08:19:43, 31 December 2024)
- ML19332A572 + (08:19:44, 31 December 2024)
- ML19332A571 + (08:19:44, 31 December 2024)
- 05000327/LER-1980-155-03, /03L-0:on 800813,w/unit in Mode 3,remote Shutdown Monitoring Channel L-68-312c Was Found Inoperable.Caused by Flaw in Plant Operating Procedures & Unsealed Transmitter Leg.Transmitter Leg Was Drained + (08:19:46, 31 December 2024)
- 05000334/LER-1980-008-01, /01T-1:on 800225,during in-plant Insp,Potential Overstress Condition of Cable Spreading Room Floor Indicated Due to Postulated Seismic Loading.Caused by Utilizing Underside of Floor to Higher Degree than Original Design + (08:19:47, 31 December 2024)
- 05000327/LER-1980-155, Forwards LER 80-155/03L-0 + (08:19:52, 31 December 2024)
- 05000334/LER-1980-008, Forwards LER 80-008/01T-1 + (08:19:54, 31 December 2024)
- ML19332A562 + (08:19:56, 31 December 2024)
- ML19332A561 + (08:19:57, 31 December 2024)
- 05000327/LER-1980-151-03, /03L-0:on 800811,turbine Driven Auxiliary Feedwater Pump Failed to Start After Loss of Both Main Feedwater Pumps.Caused by Torque Switch Failure,Causing Valve FCV-1-51 Motor Operator to Short + (08:20:00, 31 December 2024)
- ML19332A558 + (08:20:01, 31 December 2024)
- ML19332A557 + (08:20:02, 31 December 2024)
- ML19332A556 + (08:20:03, 31 December 2024)
- 05000327/LER-1980-151, Forwards LER 80-151/03L-0 + (08:20:06, 31 December 2024)
- ML19332A550 + (08:20:07, 31 December 2024)
- AECM-80-213, Second Interim Deficiency Rept Re Defective Leak Detection Equipment Used to Qualify Farr Co NPP-2 Carbon Filters for Use in Control Room Standby Air Units.Filters Have Been Returned to Vendor.Final Rept Will Be Submitted by 801125 + (08:20:08, 31 December 2024)
- ML19332A547 + (08:20:10, 31 December 2024)
- ML19332A546 + (08:20:11, 31 December 2024)
- 05000327/LER-1980-145-03, /03L-0:on 800807,in Mode 2 Operation,Cell 51 in Diesel Generator Battery 1B-B Shorted & Failed,W/Three Addl Cells Already Strapped Out.Cause Not Stated.Diesel Generator Cells Restored W/Cells from Diesel Generator 2B-B + (08:20:13, 31 December 2024)
- 05000327/LER-1980-145, Forwards LER 80-145/03L-0 + (08:20:14, 31 December 2024)
- ML19332A542 + (08:20:15, 31 December 2024)
- ML19332A541 + (08:20:16, 31 December 2024)
- ML19332A533 + (08:20:17, 31 December 2024)
- ML19332A532 + (08:20:18, 31 December 2024)
- ML19332A530 + (08:20:20, 31 December 2024)
- ML19332A526 + (08:20:21, 31 December 2024)
- ML19332A522 + (08:20:22, 31 December 2024)
- 05000327/LER-1980-147-03, /03L-0:on 800807,during Support & Hanger Insp,Addl Hanger Not Required by Design Analysis Was Found Installed on Containment Spray Piping.Hanger Was Temporary & Inadvertently Left in Place.Hanger Was Removed + (08:20:23, 31 December 2024)
- 05000327/LER-1980-147, Forwards LER 80-147/03L-0 + (08:20:25, 31 December 2024)