- ML20082M869 + (09:24:20, 26 May 2025)
- 05000362/LER-1983-099-03, /03L-0:on 831031,during Reactor Trip from Mode 1, Auxiliary Feedwater Pump 3P-140 Failed to Start.Cause Under Investigation.Pump Manually Reset & Started + (09:24:21, 26 May 2025)
- ML20082M860 + (09:24:23, 26 May 2025)
- ML20082M854 + (09:24:25, 26 May 2025)
- TAC:53345 + (09:24:26, 26 May 2025)
- 05000361/LER-1983-138-03, /03L-0:on 831021,containment Isolation Valve 2HV7258 Failed to Close During Waste Gas Quarterly Valve Test.Caused by Loose Connection on Terminal Block in Closing Circuit.Connection Tightened + (09:24:33, 26 May 2025)
- 05000361/LER-1983-127-03, /03L-0:on 831020,28 fire-rated Assemblies in Various Zones Inoperable.Caused by Design or Const Errors. Compensatory Measures in Place Until Rated Assemblies Repaired + (09:24:42, 26 May 2025)
- ML20082M732 + (09:24:44, 26 May 2025)
- ML20082M731 + (09:24:45, 26 May 2025)
- 05000368/LER-1983-047-03, /03L-0:on 831023,channel Functional Test of Source Range Neutron Flux Monitors Not Performed within Required Surveillance Requirements.Procedure Changed + (09:24:46, 26 May 2025)
- ML20082M724 + (09:24:48, 26 May 2025)
- 05000353/LER-1995-006, :on 950322,inadvertent Division 2 Loss of Coolant Accident Signal Occurred Due to Screws on Signal Common Bus Loose.Suspect Trip Unit for Card File E21A-Z4B Replaced + (09:24:49, 26 May 2025)
- 05000362/LER-1983-096-03, /03L-0:on 831022,auxiliary Feedwater Pumps 3P-140 & 3P-504 Rendered Inoperable to Allow Repairs on Emergency Feedwater Actuation Sys 1 Circuitry.Caused by Failed solid-state Relay.Relay Replaced + (09:24:51, 26 May 2025)
- ML20082M691 + (09:24:57, 26 May 2025)
- ML20082M686 + (09:25:00, 26 May 2025)
- 05000374/LER-1995-006-02, :on 950302,primary Containment Maximum Allowable Leakage Exceeded Due to LLRT Failure.Generated Action Requests to Repair 2RE024 & 2RE025 + (09:25:04, 26 May 2025)
- 05000265/LER-1983-022-01, /01T-0:on 831115,during Routine Insp,Msiv Room Interlock Doors Found Defeated,While MSIV Room Part of Secondary Containment,Resulting in Degradation of Secondary Containment Integrity + (09:25:05, 26 May 2025)
- 05000457/LER-1995-002, :on 950215,containment H Monitor Train Was Inoperable Due to Procedural Deficiency & Personnel Error. Revised ILRT Procedure & Site Procedure on Conduct of Station Personnel,Counseling & Training + (09:25:08, 26 May 2025)
- 05000361/LER-1983-126-03, /03L-0:on 831018,review of Nuclear Instrumentation Sys Safety Channel Drawer Records Indicated Surveillance for Channels A,B & D Not Completed within Required Interval. Caused by Personnel Error + (09:25:10, 26 May 2025)
- ML20082M635 + (09:25:17, 26 May 2025)
- ML20082M587 + (09:25:24, 26 May 2025)
- ML20082M571 + (09:25:32, 26 May 2025)
- ML20082M556 + (09:25:34, 26 May 2025)
- ML20082M512 + (09:25:44, 26 May 2025)
- 05000317/LER-1991-005-01, :on 910730,determined That Circuitry for Smoke Detectors in Purge Air Supply Room Not Tested Every 6 Months.Caused by Personnel Error & Inadequate Technical Review.Detectors Tested & Procedure Corrected + (09:25:46, 26 May 2025)
- ML20082M487 + (09:25:50, 26 May 2025)
- 05000275/LER-1981-003-03, Liquid Radwaste Effluent Line Radiation Monitor RM-18 Found Inoperable.Caused by Separated Ctr Wire in Coax Connector Cable at Junction Between Connector Pin & Wire.Design Revised + (09:25:54, 26 May 2025)
- ML20082M437 + (09:25:59, 26 May 2025)
- ML20082M417 + (09:26:01, 26 May 2025)
- GO2-83-106, Final Deficiency Rept,Condition 286 Re Linear Indication on Containment Weld Pads.Initially Reported on 831014.Potential for Beam Seat Separation Under Worst Case Loads Nonexistent. Item Not Reportable Per 10CFR50.55(e) + (09:26:03, 26 May 2025)
- GO2-83-109, Final Deficiency Rept,Condition 274 Re Excessive Gapping Between Pipe Support baseplates.Fifty-nine of 2,299 Baseplates Require Rework to Correct Deficient Baseplate Gap + (09:26:30, 26 May 2025)
- ML20082L884 + (09:26:58, 26 May 2025)
- 05000333/LER-1995-001, :on 950106,test Results for Five of Six Valves Exceeded 1% Tolerance Allowed by TS for Valve Actuation. Caused by Initial Lift Setpoint Drift Set High for All Pilot Mechanisms.Replaced SRV Pilot Assemblies + (09:27:07, 26 May 2025)
- ML20082L356 + (09:27:51, 26 May 2025)
- 05000311/LER-1982-017, Supplemental LER 82-017/03X-1:on 820228,svc Water Flow Indicated Zero Upon Starting Containment Fan Coil Unit 22 (Cfcu).On 820301,svc Water Flow to Cfcu 23 Less than Required 2,500 Gpm.Caused by Stuck Valve + (09:28:09, 26 May 2025)
- ML20082L197 + (09:28:13, 26 May 2025)
- 05000272/LER-1982-024, Svc Water Flow to Containment Fan Coil Unit 12 Discovered Less Required than 700 Gpm.Caused by Closed Flow Control Valve 125w223.Valve opened.W/831117 + (09:28:32, 26 May 2025)
- 05000311/LER-1982-001, Supplemental LER 82-001/03X-1:on 820110,steam Generator 24 Pressure Channel 4 Failed High.Caused by Ventilation Damper Stuck Open,Freezing Pressure Sensing Line.Damper Freed, Exercised & Closed + (09:29:01, 26 May 2025)
- 05000293/LER-1993-003, :on 930301,found Settings of RWCU High Switches Out of Tolerance During Surveillance.Caused Setpoint Drift. Re-calbr DPIS-1243 & DPIS-1244 in Accordance W/Procedure 8.M2-12.1 W/Satisfactory Results 930301 + (09:29:40, 26 May 2025)
- 05000254/LER-1983-024-03, While Performing QOS-1600-1,Div 1 Position Indication Lights for Vacuum Breaker 1-601-33F Indicated Valve Not Closed.Caused by Binding in Switch Due to Corrosion + (09:30:33, 26 May 2025)
- ML20082J662 + (09:30:39, 26 May 2025)
- ML20082J656 + (09:30:42, 26 May 2025)
- 05000293/LER-1991-005, :on 910325,loss of AC Power to B Train of Safety Sys Occurred.Caused by Failure of Automatic Voltage Regulator.Calibr Frequency to Be Established & Calibr Procedures to Be Developed + (09:33:38, 26 May 2025)
- ML20082H148 + (09:33:52, 26 May 2025)
- ML20082H143 + (09:33:55, 26 May 2025)
- ML20082H132 + (09:33:57, 26 May 2025)
- ML20082G996 + (09:34:12, 26 May 2025)
- TAC:M88316 + (09:34:31, 26 May 2025)
- SNRC-1782, Provides Clarification of 910115 Request for Limited Scope Exemption from Seismic Qualification Requirements of Criterion 2,App A,10CFR50 Re Facility 125 Volt Dc Batteries + (09:34:37, 26 May 2025)
- 05000482/LER-1995-001, :on 950308,reactor Tripped Resulting in Loss of Two CW Sys Pumps,Condenser Vacuum & Two Rcps.Caused by Failure of RT Manual Actuation Switch Contacts to Maintain Continuity.Surveillance Procedures Revised + (09:36:17, 26 May 2025)