Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000316/LER-1978-037-01, /01T-1:on 780615,both Diesel Generators Placed in Condition Where Neither Engine Capable of Automatic Start. Operator Closed & Tagged Out Starting Air Pilot Valves on Wrong Diesel Generator.Operator Reprimanded + (18:25:57, 25 May 2025)
- ML20128C299 + (18:26:15, 25 May 2025)
- TAC:M84072 + (18:27:21, 25 May 2025)
- IR 05000324/1992032 + (18:28:03, 25 May 2025)
- IR 05000446/1992201 + (18:28:13, 25 May 2025)
- IR 05000298/1992201 + (18:29:02, 25 May 2025)
- IR 05000255/1992023 + (18:29:59, 25 May 2025)
- ML20128B645 + (18:30:24, 25 May 2025)
- ML20128B602 + (18:30:37, 25 May 2025)
- ML20128B480 + (18:31:39, 25 May 2025)
- IR 05000498/1992017 + (18:31:50, 25 May 2025)
- TXX-9304, Forwards Rev 10 to Technical Requirements Manual + (18:32:00, 25 May 2025)
- ML20128B359 + (18:32:14, 25 May 2025)
- IR 05000282/1992029 + (18:40:52, 25 May 2025)
- 05000528/LER-1985-035, :on 850525 & 0604,pump Performance Test Results Not Reviewed within 96 H as Required by ASME Boiler & Pressure Vessel Code,Section Xi.Caused by Procedural Errors in Test Data Routing.Routing Methods Revised + (18:41:50, 25 May 2025)
- 05000327/LER-1981-053-03, /03L-1:on 810503,liquid Radwaste Effluent Monitor O-RM-90-122 Failed to Source Check.Caused by High Background Accumulation in Sample Chamber Due to Failure to Change Out Chamber.Chamber Coated W/Epoxy Paint + (18:41:54, 25 May 2025)
- ML20128A725 + (18:42:10, 25 May 2025)
- IR 05000348/1992035 + (18:42:12, 25 May 2025)
- 05000282/LER-1985-005, :on 850123,one Containment Isolation Check Valve Exhibited Leakage in Excess of Tech Spec Limits During Local Leakage Rate Testing at Refueling.No Cause Determined. Valve Replaced + (18:42:42, 25 May 2025)
- IR 05000327/1992036 + (18:44:39, 25 May 2025)
- IR 05000282/1992025 + (18:45:13, 25 May 2025)
- IR 05000369/1993001 + (18:45:24, 25 May 2025)
- TAC:M83330 + (18:45:45, 25 May 2025)
- IR 05000369/1992028 + (18:48:05, 25 May 2025)
- IR 05000213/1992022 + (18:49:17, 25 May 2025)
- NUREG-1358, Forwards NRC Info Notice 92-076, Issuance of Suppl 1 to NUREG-1358, Lessions Learned from Special Insp Program for EOPs (Conducted Oct 1988-Sept 1991). W/O Encl + (18:49:34, 25 May 2025)
- NUREG-0902, Forwards Listed Reg Guides & NUREGs in Response to Interest Expressed at Blue Ribbon Commission on Siting 921116 Meeting.W/O Encls + (18:49:37, 25 May 2025)
- TAC:M55120 + (18:50:09, 25 May 2025)
- NUREG-0408, Discusses Review of Generic Mark I Containment Short Term Program Conducted by Owners Group.Info Avaiable in NUREG-0408 + (18:51:44, 25 May 2025)
- IR 05000320/2004020 + (18:53:19, 25 May 2025)
- 05000255/LER-1985-005, :on 850414,during Power Reduction for Turbine Control Problems,Safeguards Bus 1C Failed to Transfer.Cause Unknown.Investigation Continuing.Proper Hand Switch Operation Will Be Discussed W/Operators + (18:53:38, 25 May 2025)
- ML20127N896 + (18:53:49, 25 May 2025)
- ML20127N652 + (18:55:12, 25 May 2025)
- IR 05000277/1992032 + (18:55:12, 25 May 2025)
- TAC:M81880 + (18:56:18, 25 May 2025)
- IR 05000323/2005006 + (18:57:56, 25 May 2025)
- 05000336/LER-1992-015, :on 920821,determined That SPEC 200 Cabinets May Not Be Qualified as Result of Missing Bumpers.Caused by Lack of Adequate Vendor Instruction to Install Seismic Bumpers.Equipment Insp & Bumpers Installed + (18:59:24, 25 May 2025)
- IR 05000440/1992024 + (19:00:16, 25 May 2025)
- IR 05000255/1992028 + (19:00:22, 25 May 2025)
- 05000301/LER-1992-006-01, :on 921020,inadvertent ESF Actuation Occurred as Result of as-built Wire Tracing & Disconnected Output from 2B04 Lockout Relay.Cabling Reconnected on 921020 + (19:01:17, 25 May 2025)
- ML20127M368 + (19:02:34, 25 May 2025)
- 05000293/LER-1992-013, :on 921024,automatic Actuation of Main Steam Sys/Group 1 Portion of Primary Containment Isolation Control Sys Occurred Due to False High Rv Water Level Signal. Possible Internal Leakage Paths Addressed + (19:02:56, 25 May 2025)
- ML20127M192 + (19:03:30, 25 May 2025)
- IR 05000335/1985010 + (19:05:17, 25 May 2025)
- IR 05000326/2004025 + (19:05:29, 25 May 2025)
- IR 05000277/1992082 + (19:06:36, 25 May 2025)
- ML20127L561 + (19:08:20, 25 May 2025)
- ML20127L527 + (19:08:33, 25 May 2025)
- 05000440/LER-1992-020, :on 921023,inadequate Reset of Containment Air Lock Door Discovered Resulting in TS Violations.Caused by Drawing Discrepancy.Piping Sys Diagram Being Revised to Properly Identify Pressure Switches + (19:08:37, 25 May 2025)
- 05000443/LER-1992-013, :on 920827,determined That Six Plant Doors Did Not Have Tornado Design to Withstand Differential Pressure, Per Updated Fsar.Caused by Failure to Include Doors in United Engineers & Constructors Spec.Updated FSAR Revised + (19:08:54, 25 May 2025)
- 05000263/LER-1992-012, :on 920824,six RHR Svc Water Valves,Two ESW Valves & Two EDG Emergency Svc Water Valves,Noted During NRC Insp,Not Included in ASME Section XI Program.Caused by Code Misinterpretation.All Components Will Be Tested + (19:09:24, 25 May 2025)