Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000282/LER-1982-016, Forwards LER 82-016/03L-0 + (02:18:01, 17 December 2024)
- 05000280/LER-1982-091-03, /03L-0:on 820905,water & Sediment Found in Lube Oil of Charging Pump 1-CH-P-1A.Caused by Leak in One Tube of Lube Oil Cooler.Cooler Replaced,Oil Changed & Pump Returned to Svc + (02:18:03, 17 December 2024)
- 05000254/LER-1982-025, Forwards LER 82-025/03L-0 + (02:18:04, 17 December 2024)
- ML20063P526 + (02:18:04, 17 December 2024)
- 05000280/LER-1982-091, Forwards LER 82-091/03L-0 + (02:18:05, 17 December 2024)
- ML20063P521 + (02:18:05, 17 December 2024)
- 05000361/LER-1982-121-03, /03L-0:on 820920,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (02:18:07, 17 December 2024)
- ML20063P519 + (02:18:08, 17 December 2024)
- ML20063P518 + (02:18:08, 17 December 2024)
- ML20063P517 + (02:18:09, 17 December 2024)
- ML20063P516 + (02:18:09, 17 December 2024)
- 05000361/LER-1982-119-03, /03L-0:on 820919,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (02:18:11, 17 December 2024)
- ML20063P513 + (02:18:15, 17 December 2024)
- 05000361/LER-1982-107-03, /03L-0:on 820902,condensate Storage Tank T-120 Water Level Fell Below Tech Spec Limit While in Mode 2. Caused by Inadequate Makeup Water Control.Corrective Actions Include Better Planning & Timely Water Transfer + (02:18:19, 17 December 2024)
- 05000254/LER-1982-032-03, /03L-0:on 820905,HPCI Removed from Svc W/O Actuation of Electromatic Relief Valves.Caused by Need to Perform Scheduled Turbine Overspeed Surveillance Test.Hpci Sys Will Be Tested Operable Upon Return to Power + (02:18:21, 17 December 2024)
- ML20063P503 + (02:18:22, 17 December 2024)
- ML20063P501 + (02:18:23, 17 December 2024)
- ML20063P500 + (02:18:23, 17 December 2024)
- 05000254/LER-1982-032, Forwards LER 82-032/03L-0 + (02:18:24, 17 December 2024)
- 05000335/LER-1982-041-03, /03L-0:on 820907,at 99% Power,Reactor/Turbine Trip Occurred Resulting in Brief Loss of Vital Buses & Iodine Spike.Caused by Motor Auxiliary Contact Initiating False Loss of Load & Inhibit Signals + (02:18:28, 17 December 2024)
- 05000317/LER-1982-056, Forwards LER 82-056/03L-0 + (02:18:29, 17 December 2024)
- 05000335/LER-1982-041, Forwards LER 82-041/03L-0 + (02:18:30, 17 December 2024)
- 05000327/LER-1982-108-03, /03L-0:on 820907,during Mode 1,level Channel LT-63-50 on Refueling Water Storage Tank Declared Inoperable.Caused by Transmitter Out of Tolerance Due to Instrument Drift.Loop Recalibr + (02:18:32, 17 December 2024)
- ML20063P479 + (02:18:33, 17 December 2024)
- 05000327/LER-1982-108, Forwards LER 82-108/03L-0 + (02:18:34, 17 December 2024)
- 05000259/LER-1982-070-03, /03L-0:on 820908,while Calibr Reactor Protection Sys high-water Level Switches on Scram Discharge Tank,Level Switch LS-85-45E Operated at 27 Gallons,Contrary to Tech Specs.Caused by Calibr Drift on Level Switch SL-305-EI-X + (02:18:36, 17 December 2024)
- ML20063P469 + (02:18:38, 17 December 2024)
- ML20063P470 + (02:18:38, 17 December 2024)
- 05000373/LER-1982-100-03, /03L-0:on 820903,RCIC Equalizing Valves Failed to Close.Caused by Improperly Adjusted Spring Tension.Spring Tension Adjusted + (02:18:40, 17 December 2024)
- ML20063P465 + (02:18:41, 17 December 2024)
- ML20063P466 + (02:18:41, 17 December 2024)
- 05000259/LER-1982-070, Forwards LER 82-070/03L-0 + (02:18:42, 17 December 2024)
- 05000373/LER-1982-100, Forwards LER 82-100/03L-0 + (02:18:42, 17 December 2024)
- ML20063P459 + (02:18:43, 17 December 2024)
- 05000247/LER-1982-035-03, /03L-0:on 820829,nuclear Power Range Instrumentation Channel N41 Became Inoperative Due to Failure of Power Supply Unit.Cause of Unit Failure Not Stated.Defective High Voltage Power Supply Removed + (02:18:48, 17 December 2024)
- ML20063P452 + (02:18:49, 17 December 2024)
- 05000366/LER-1982-109-03, /03L-0:on 820908,performance of RCIC Preventative Maint Procedure Disclosed Inoperability of RCIC Trip & Throttle Valve & RCIC Sys.Caused by Closure of Turbine Trip & Throttle Valve.Trip & Throttle Valve Opened + (02:18:51, 17 December 2024)
- 05000247/LER-1982-035, Forwards LER 82-035/03L-0 + (02:18:52, 17 December 2024)
- 05000254/LER-1982-027, Forwards LER 82-027/03L-0 + (02:18:52, 17 December 2024)
- 05000346/LER-1982-043-03, /03L-0:on 820829,fire Door 428C to Electrical Isolation Room 429A Found Cracked Open.Caused by Component Failure.Latch Mechanism Repaired + (02:18:54, 17 December 2024)
- 2CAN108202, Responds to NRC Transmitting Amend 24 to License NPF-6 Re Seized Reactor Coolant Pump Shaft Event Reanalysis. Event Description & Results of Cycle 2 Seized Rotor Event Encl + (02:18:55, 17 December 2024)
- ML20063P440 + (02:18:55, 17 December 2024)
- 05000346/LER-1982-043, Forwards LER 82-043/03L-0 + (02:18:56, 17 December 2024)
- 05000366/LER-1982-109, Forwards LER 82-109/03L-0 + (02:18:56, 17 December 2024)
- 05000331/LER-1982-058-03, /03L-0:on 820910,river Water Supply Sys Traveling Screen 1F-36B Would Not Run in Auto or Continuous Mode. Caused by Low Discharge Pressure for Screen Wash Pump. Permissive Pressure Switch PS-2903 Recalibr + (02:18:58, 17 December 2024)
- 05000331/LER-1982-058, Forwards LER 82-058/03L-0 + (02:18:59, 17 December 2024)
- ML20063P420 + (02:18:59, 17 December 2024)
- 05000387/LER-1982-019-01, /01T-0:on 820920,during Power Ascension Testing, Turbine Bldg Vent Monitor Sys Became Inoperable.Caused by Failure to Remove Mechanical Vacuum Pump from Svc.Pump Stopped & Steam Jet Air Ejectors Placed in Svc + (02:19:04, 17 December 2024)
- 05000313/LER-1982-026-03, /03L-0:on 820901,installed Hose Reel (HR-49) Found Not Visually Inspected Per Tech Specs.Caused by Lack of Communication,Leading to Omission of HR-49 from Insp procedures.HR-49 Inspected & Procedure Revised + (02:19:06, 17 December 2024)
- ML20063P416 + (02:19:07, 17 December 2024)
- 05000313/LER-1982-026, Forwards LER 82-026/03L-0 + (02:19:08, 17 December 2024)