Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000369/LER-1982-045-03, /03L-0:on 820527,HEPA & Carbon Adsorber Filters Periodic Test Revealed That Carbon Adsorber Filters on Auxiliary Bldg Ventilation Sys Failed to Pass Freon Penetration Test.Caused by Carbon Settlement +
- 05000315/LER-1982-045-03, /03L-0:on 820528,security Officer Discovered Low Pressure Carbon Dioxide Sys for Auxiliary Cable Vault Isolated W/O Personnel on Duty.Caused by Personnel Error. Need for Full Compliance W/Fire Protection Emphasized +
- 05000338/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000311/LER-1982-045, Forwards LER 82-045/03L-0.Detailed Event Analysis Encl +
- 05000325/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000324/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000366/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000302/LER-1982-045, Informs That Special Rept Supposedly Encl in 821001 Submitted LER 82-045 Determined to Be More Useful as Basis of Tech Spec Change Request to Be Submitted at Later Date +
- 05000335/LER-1982-045, Forwards LER 82-045/43X-0 +
- 05000317/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000416/LER-1982-045, Forwards LER 82-045/01T-0 +
- 05000361/LER-1982-045, Forwards LER 82-045/03L-0.Detailed Event Analysis Submitted +
- 05000331/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000321/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000339/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000259/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000368/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000395/LER-1982-045, Forwards LER 82-045/03L-0.Detailed Event Analysis Encl +
- 05000327/LER-1983-045, Forwards LER 83-045/03L-0 +
- 05000237/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000334/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000219/LER-1982-045, Forwards LER 82-045/03L-0.Detailed Event Analysis Encl +
- 05000293/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000333/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000318/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000302/LER-1983-045, Rev 1 to LER 83-045/03X-1:on 831016,1104 & 08,175-ft Wind Speed Instrumentation & on 831028 & 1102,33-ft Wind Direction Instrumentation Discovered Inoperable.Caused by Severe Weather Damage & Component Failure +
- 05000325/LER-1983-045, Updated LER 83-045/03L-2:on 830919 & 24,inboard PCIV Steam Supply Valve ES1-F007 to RCIC Sys Would Not Completely Reopen.Caused by Loose Limitorque Motor Operator Spring Pack +
- 05000255/LER-1982-045, Forwards LER 82-045/01T-0 +
- 05000324/LER-1983-045, Forwards LER 83-045/03L-0 +
- 05000387/LER-1983-045, Forwards LER 83-045/03L-0 +
- 05000267/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000416/LER-1983-045, Forwards LER 83-045/99X-0 +
- 05000423/LER-1996-045, Forwards LER 96-045-00,documenting Condition That Was Determined at Millstone Unit 3 on 961107.LER Submitted Pursuant to 10CFR 50.73(a)(2)(ii).Commitments Encl +
- 05000293/LER-1978-045, Forwards LER 78-045/03L-0 +
- 05000366/LER-1978-045, Forwards LER 78-045/03L-0 +
- 05000247/LER-1982-045, Corrected LER 82-045/01T-0:on 821108,insp Revealed That Upper End Plug from Fuel Rod within Assembly Separated from Fuel Tube.Cause Not Stated.Assembly Replaced +
- 05000272/LER-1982-045, Forwards Corrected LER 82-045/04L-0.Detailed Event Analysis Encl +
- 05000000/LER-1986-045, Forwards LER 86-045-00 Re Physical Security Event.Rept Withheld (Ref 10CFR73.21) +
- 05000410/LER-1987-045, Corrected LER 87-045-00:on 870729,two Separate ESF Actuations Occurred.Caused by Lack of Administrative Controls & Personnel Error.Surveillance Procedures Revised to Prohibit Concurrent Performance +
- 05000362/LER-1984-045, Forwards LER 84-045-00 for 1984 & 85 Occurrences Re Dose Equivalent Iodine Concentrations That Exceeded TS Limits,But Were Not Reported as Required by TS in Effect at That Time. Healt Nor Safety of Plant Personnel or Public Was +
- 05000312/LER-1980-045, Forwards LER 80-045/01T-0 +
- 05000373/LER-1982-045, Forwards LER 82-045/03L-0 +
- 05000315/LER-1976-045, Forwards Updated LER 76-045/03X-1 & LER 82-036/03L-0 +
- 05000352/LER-1989-045, :on 890716,radiation Monitor Indication Drifted Above Isolation Setpoint of 1.35 Mr/H Causing ESF Actuation. Caused by Equipment Failure.Radiation Monitor Declared Inoperable & Isolation Reset +
- 05000461/LER-1987-045, :on 870729,automatic Actuation of Main Control Room Ventilation Sys Into High Radiation Mode Occurred. Caused by Detector Circuit Card Failure.Circuit Board Replaced & Monitor Declared Operable +
- 05000423/LER-1987-045, :on 871121,emergency Diesel Generator Fuel Oil Analysis for Kinematic Viscosity Before Addition to Storage Tanks Missed.Caused by Incorrect Acceptance Criteria Comparison Between Two Forms.Forms Updated +
- 05000312/LER-1987-045, :on 871105,surveillance Procedure for Weekly Battery Testing Not Performed by Tech Spec Required Date. Caused by Personnel Error.Manual Tracking Schedule for Surveillance Procedures Instituted +
- 05000327/LER-1987-045, :on 871009,discovered That Potential Failure of non-class 1E Speed Switches Could Render Safety Grade ERCW Inoperable.Caused by Inadequate Design Control Process in Place at Time ERCW Traveling Screens Upgraded +
- 05000424/LER-1987-045, :on 870702,centrifugal Charging Pumps Removed from Svc.Caused by Personnel Error.Personnel Responsible for Writing,Reviewing & Approving Clearance Associated W/Closure of Incorrect Valves Counseled +
- 05000482/LER-1987-045, :on 871002,determined That on Four Occasions Between 861118 & 1207,ASME Boiler & Pressure Vessel Code Piping Not Properly Pressure Tested Following Repair.Caused by Inadequate Procedure.Procedures Revised +