- ML18089A227 +
- ML14332A074 +
- ML040970490 +
- ML030560491 +
- ML20070H602 +
- ML20081C292 +
- ML20135G133 +
- ML20140H044 +
- ML20135A983 +
- 05000000/LER-1986-013, Partially Deleted LER 86-013-00:on 860414,vital Area Door W/O Alarm Capability Discovered.Caused by Personnel Error. Personnel Removed from Shift & Vital Area Checked for Unauthorized Personnel W/None Being Found +
- 05000336/LER-1986-022-01, :on 861223,reactor Tripped Due to Low Water Level in Steam Generator 1.Caused by Improperly Installed Bus Voltage Potential Transformer Drawer.Drawer & Cover Realigned & Reinstalled Squarely W/Bolts +
- 05000336/LER-1986-020-01, :on 861129 & 1223,sensed Undervoltage Condition Caused Loss of 4,160-volt Power to Vital Bus 24C.Caused by Improperly Installed Bus Voltage Potential Sensing Drawer. Drawer & Cover Realigned +
- 05000454/LER-1999-003-02, :on 990513,automatic Reactor Occurred Due to Human Error During Surveillance Procedure.Appropriate Mgt Action Taken with Instrument Maint Involved & Sp Bsir 3.1.6-200 Revised.With +
- 05000412/LER-1988-007, :on 880404,reactor Coolant Pump Tripped Initiating Reactor Trip.Caused by Blocking Relay Malfunction That Resulted in Undervoltage Relay Actuation & Loss of 4 Kv Bus 2A Motor Loads.Relay Adjusted & Calibr +
- 05000331/LER-1986-004, :on 860212,RWCU Sys Isolated Due to High Differential Temp Indication.Caused by Minor Degradation of Manual Valves on Vent & Drain Lines of Regenerative HX A. Valves Tightened +
- 05000341/LER-1985-010, :on 850427,reactor Protection Sys Tripped. Caused by APRM E Upscale Trip Due to Recorder Door Malfunction.Lprm Cables & Connectors Repaired & Chart Recorder Door Modified +
- 05000374/LER-1985-014-04, :on 850409,spurious Div I RHR Shutdown Cooling Isolation Occurred.Caused by Momentary Power Loss to Relay 2B21H-K74 During Installation of Environ Qualification Mod M-1-2-84-117.Work Completed 850414 +
- 05000412/LER-1990-025, :on 901201,intake Structure Instrument Air Compressor Failed to Automatically Start on Low Air Pressure During Power Operation.Caused by Failed Pressure Switch.New Pressure Switch Calibr & Installed +
- IR 05000324/1981031 +
- NUREG-0227, Partial Draft of Nuclear Power Plant Operating Experience - 1978, Section 3.0, Plant Outages. Portions of NUREG-0483, NUREG-0366 & NUREG-0227 (Plant Operating Experience for 1977,1976 & 1974-75,respectively) Encl +
- 05000397/LER-1995-001, :on 950113,failed to Satisfy Single Failure Criteria for Containment Isolation Function Due to Electrical Separation Plate in Control Panel Missing. Replaced Missing Barrier +
- ML20062G638 +
- PLA-7928, Annual Radiological Environmental Operating Report +
- 05000374/LER-1992-006-03, :on 920420,high Differential Flow Alarm Signal Received from Sys Instrumentation While RWCU Sys Being Shut Down.Caused by RWCU Valve Closing Prior to Shutdown. Stroke Testing Completed for Isolation Valves +