MONTHYEARL-99-154, Monthly Operating Repts for Sept 199 for Bvps,Units 1 & 2. with1999-09-30030 September 1999 Monthly Operating Repts for Sept 199 for Bvps,Units 1 & 2. with L-99-140, Monthly Operating Repts for Aug 1999 for Bvps,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Bvps,Units 1 & 2. with L-99-126, Monthly Operating Repts for Jul 1999 for Beaver Valley Power Station,Units 1 & 2.With1999-07-31031 July 1999 Monthly Operating Repts for Jul 1999 for Beaver Valley Power Station,Units 1 & 2.With L-99-107, Monthly Operating Repts for June 1999 for Bvps,Units 1 & 2. with1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Bvps,Units 1 & 2. with L-99-096, Monthly Operating Repts for May 1999 for BVPS Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for BVPS Units 1 & 2. with L-99-079, Monthly Operating Repts for Apr 1999 for Beaver Valley Power Station,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Beaver Valley Power Station,Units 1 & 2.With L-99-058, Monthly Operating Repts for Mar 1999 for Bvps,Units 1 & 2. with1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Bvps,Units 1 & 2. with L-99-038, Monthly Operating Repts for Feb 1999 for Bvps,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Bvps,Units 1 & 2. with ML20203D4811999-01-31031 January 1999 Monthly Operating Repts for Jan 1999 for Bvps,Units 1 & 2, in Accordance with NRC GL 97-02.With ML20199C9971998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Bvps,Units 1 & 2. with L-98-229, Monthly Operating Repts for Nov 1998 for Bvps,Units 1 & 2. with1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Bvps,Units 1 & 2. with L-98-210, Monthly Operating Repts for Oct 1998 for Bvps,Units 1 & 2. with1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Bvps,Units 1 & 2. with L-98-197, Monthly Operating Repts for Sept 1998 for Beaver Valley Power Station,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Beaver Valley Power Station,Units 1 & 2.With L-98-178, Monthly Operating Repts for Aug 1998 for Bvps,Units 1 & 2. with1998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Bvps,Units 1 & 2. with L-98-168, Monthly Operating Repts for July 1998 for Bvps,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Bvps,Units 1 & 2 L-98-139, Monthly Operating Repts for June 1998 for Bvps,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Bvps,Units 1 & 2 L-98-119, Monthly Operating Repts for Bvps,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for Bvps,Units 1 & 2 L-98-096, Monthly Operating Repts for Apr 1998 for Bvps,Units 1 & 21998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Bvps,Units 1 & 2 L-98-068, Monthly Operating Repts for Mar 1998 for Bvps,Units 1 & 21998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Bvps,Units 1 & 2 L-98-036, Monthly Operating Repts for Feb 1998 for Beaver Valley Power Station1998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Beaver Valley Power Station ML20202F8191998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Beaver Valley Power Station,Units 1 & 2 ML20198L3981997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Beaver Valley Power Station,Units 1 & 2 L-97-072, Monthly Operating Repts for Nov 1997 for Bvps,Units 1 & 21997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Bvps,Units 1 & 2 L-97-057, Monthly Operating Repts for Oct 1997 for Beaver Valley Power Station,Units 1 & 21997-10-31031 October 1997 Monthly Operating Repts for Oct 1997 for Beaver Valley Power Station,Units 1 & 2 L-97-040, Monthly Operating Repts for Sept 1997 for Bvps,Units 1 & 21997-09-30030 September 1997 Monthly Operating Repts for Sept 1997 for Bvps,Units 1 & 2 ML20216H6031997-08-31031 August 1997 Monthly Operating Repts for Aug 1997 for Beaver Valley Power Station ML20210K5821997-07-31031 July 1997 Monthly Operating Repts for Jul 1997 for Bvps,Units 1 & 2 ML20140D7261997-05-31031 May 1997 Monthly Operating Repts for May 1997 for BVPS ML20141B3501997-04-30030 April 1997 Monthly Operating Repts for Apr 1997 for Beaver Valley Power Station,Units 1 & 2 ML20137T1441997-03-31031 March 1997 Monthly Operating Repts for Mar 1997 for Beaver Valley Power Station Units 1 & 2 ML20136G4651997-02-28028 February 1997 Monthly Operating Repts for Feb 1997 for Beaver Valley Power Station,Unit 1 & 2 ML20134K1521997-01-31031 January 1997 Monthly Operating Repts for Jan 1997 for Beaver Valley Power Station,Units 1 & 2 ML20133F4831996-12-31031 December 1996 Monthly Operating Repts for Dec 1996 for Beaver Valley Power Station Unit 1 & 2 ML20132B1001996-11-30030 November 1996 Monthly Operating Repts for Nov 1996 for Beaver Valley Power Station Unit 1 & 2 ML20134H4921996-10-31031 October 1996 Monthly Operating Repts for Oct 1996 for Beaver Valley Power Station,Units 1 & 2 ML20128N1911996-09-30030 September 1996 Monthly Operating Repts for Sept 1996 for Beaver Valley Power Station Unit 1 & 2 ML20117M2091996-08-31031 August 1996 Monthly Operating Repts for Aug 1996 for Beaver Valley Power Station Units 1 & 2 ML20117B2481996-07-31031 July 1996 Monthly Operating Rept for July 1996 for Beaver Valley Power Station ML20115D4061996-06-30030 June 1996 Monthly Operating Repts for June 1996 for BVPS ML20117M1791996-05-31031 May 1996 Monthly Operating Repts for May 1996 for Beaver Valley Power Station,Units 1 & 2 ML20111B2441996-04-30030 April 1996 Monthly Operating Repts for Apr 1995 for Beaver Valley Power Station ML20101R0621996-03-31031 March 1996 Monthly Operating Repts for Mar 1996 for Beaver Valley Power Station ML20100R2841996-02-29029 February 1996 Monthly Operating Repts for Feb 1996 for Beaver Valley Power Station ML20097D4541996-01-31031 January 1996 Monthly Operating Repts for Jan 1996 for Beaver Valley Power Station ML20096B2531995-12-31031 December 1995 Monthly Operating Repts for Dec 1995 for Beaver Valley Power Station ML20095D8651995-11-30030 November 1995 Monthly Operating Repts for Nov 1995 for Beaver Valley Power Station ML20094H3631995-10-31031 October 1995 Monthly Operating Repts for Oct 1995 for Beaver Valley Power Station ML20092F4251995-08-31031 August 1995 Monthly Operating Repts for Aug 1995 for Beaver Valley Power Station ML20087F1331995-07-31031 July 1995 Monthly Operating Repts for Jul 1995 for Beaver Valley Power Station ML20086G1601995-06-30030 June 1995 Monthly Operating Repts for June 1995 for Beaver Valley Power Station Unit 1 & 2 1999-09-30
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARL-99-154, Monthly Operating Repts for Sept 199 for Bvps,Units 1 & 2. with1999-09-30030 September 1999 Monthly Operating Repts for Sept 199 for Bvps,Units 1 & 2. with L-99-139, LER 99-S01-00:on 990813,uncompensated Loss of Ability to Detect within Single Intrusion Security Detection Zone Occurred.Caused by Procedure non-compliance.Involved Personnel Received Counseling Re Event.With1999-09-0202 September 1999 LER 99-S01-00:on 990813,uncompensated Loss of Ability to Detect within Single Intrusion Security Detection Zone Occurred.Caused by Procedure non-compliance.Involved Personnel Received Counseling Re Event.With L-99-140, Monthly Operating Repts for Aug 1999 for Bvps,Units 1 & 2. with1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Bvps,Units 1 & 2. with L-99-126, Monthly Operating Repts for Jul 1999 for Beaver Valley Power Station,Units 1 & 2.With1999-07-31031 July 1999 Monthly Operating Repts for Jul 1999 for Beaver Valley Power Station,Units 1 & 2.With L-99-107, Monthly Operating Repts for June 1999 for Bvps,Units 1 & 2. with1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Bvps,Units 1 & 2. with ML20209D9531999-06-27027 June 1999 Inservice Insp Ninety-Day Rept Bvps,Unit 2 Outage 7,Year 1999 L-99-096, Monthly Operating Repts for May 1999 for BVPS Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for BVPS Units 1 & 2. with L-99-078, Special Rept:On 990326,seismic Monitoring Instruments Were Declared Inoperable.Caused by Resolution of Potential TS Compliance Issue & Work Scheduling Issue.Instrumentation Was Returned to Svc Following Calibr & Declared Operable1999-05-0303 May 1999 Special Rept:On 990326,seismic Monitoring Instruments Were Declared Inoperable.Caused by Resolution of Potential TS Compliance Issue & Work Scheduling Issue.Instrumentation Was Returned to Svc Following Calibr & Declared Operable L-99-079, Monthly Operating Repts for Apr 1999 for Beaver Valley Power Station,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Beaver Valley Power Station,Units 1 & 2.With ML20205L0401999-04-0909 April 1999 SER Accepting Util Relief Requests for Inservice Insp Second 10-year Interval for Beaver Valley Power Station, Unit 2 L-99-054, Special Rept:On 990320,meteorological Tower Wind Speed Sensors Were Declared Inoperable.Caused by Calibration Completed by Vendor Did Not Adequately Cover Full Operating Range of Sensors.Removed Sensors & Sent Offsite1999-04-0505 April 1999 Special Rept:On 990320,meteorological Tower Wind Speed Sensors Were Declared Inoperable.Caused by Calibration Completed by Vendor Did Not Adequately Cover Full Operating Range of Sensors.Removed Sensors & Sent Offsite L-99-058, Monthly Operating Repts for Mar 1999 for Bvps,Units 1 & 2. with1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Bvps,Units 1 & 2. with ML20196K7981999-03-25025 March 1999 Rev 4 to COLR, for Cycle 8 L-99-038, Monthly Operating Repts for Feb 1999 for Bvps,Units 1 & 2. with1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Bvps,Units 1 & 2. with ML20203E1181999-02-10010 February 1999 SER Accepting Proposed Revs to Plant,Units 1 & 2 Quality Assurance Program Description L-99-019, Special Rept:On 990120,meteorological Tower Wind Speed Sensors Declared Inoperable.Caused by Processor Card for Sensor Locked Up & Needed to Be Reset.Heater That Fit Around Shaft of Sensor Replaced1999-02-0505 February 1999 Special Rept:On 990120,meteorological Tower Wind Speed Sensors Declared Inoperable.Caused by Processor Card for Sensor Locked Up & Needed to Be Reset.Heater That Fit Around Shaft of Sensor Replaced ML20196F7011999-01-31031 January 1999 BVPS Unit 2 Heatup & Cooldown Limit Curves During Normal Operation at 15 EFPY Using Code Case N-626 ML20203D4811999-01-31031 January 1999 Monthly Operating Repts for Jan 1999 for Bvps,Units 1 & 2, in Accordance with NRC GL 97-02.With ML20207E6631999-01-28028 January 1999 Rev 0 to EMECH-0713-1, Operational Assessment of SG Tubing at Beaver Valley Unit 1,Cycle 13 ML20210G7041999-01-22022 January 1999 BVPS Unit 1 Facility Changes,Tests & Experiments for 980123-990122 ML20207E5861998-12-31031 December 1998 Annual Rept 1998 for Toledo Edison ML20207E5601998-12-31031 December 1998 Annual Rept 1998 for Pennpower ML20198B9021998-12-31031 December 1998 BVPS Unit 1 Simulator Four Yr Certification Rept for 1995-1998 ML20207E5901998-12-31031 December 1998 Dqe 1998 Annual Rept to Shareholders ML20199C9971998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Bvps,Units 1 & 2. with ML20207E5521998-12-31031 December 1998 Annual Rept 1998 for Ohio Edison ML20207E5761998-12-31031 December 1998 Annual Rept 1998 for Illuminating Co ML20204J6751998-12-31031 December 1998 1998 Annual Rept for Dbnps,Unit 1,PNPP,Unit 1 & BVPS Units 1 & 2 ML20199F5341998-12-29029 December 1998 Safety Evaluation Granting Relief Requests 1-TYP-3-B3.140-1, 1-TYP-3-B5.70-1,1-TYP-3-RH-E-1-1,1-TYP-3-B-G-1, 1-TYP-3-APP-I-1,1-TYP-3-UT-1,1-TYP-3-N-509,1-TYP-3-N-521, 1-TYP-3-N-524,1-TYP-3-B3.120-1 & 1-TYP-3-C6.10-1 ML20198K8551998-12-21021 December 1998 SER Granting Relief Request PRR-5 for Third 10-year Inservice Testing for Beaver Valley Power Station,Unit 1 ML20198A1631998-12-0909 December 1998 SER Approving Implementation Program to Resolve USI A-46 at Facility That Has Adequately Addressed Purpose of 10CFR50.54(f) Request L-98-229, Monthly Operating Repts for Nov 1998 for Bvps,Units 1 & 2. with1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Bvps,Units 1 & 2. with ML20195J3131998-11-12012 November 1998 Safety Evaluation Granting First & Second 10-yr Interval Inservice Insp Request for Relief L-98-210, Monthly Operating Repts for Oct 1998 for Bvps,Units 1 & 2. with1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Bvps,Units 1 & 2. with ML20206G0291998-10-31031 October 1998 BVPS Unit 2 Facility Changes,Tests & Experiments for Period 971101-981031 ML20154R9121998-10-20020 October 1998 Safety Evaluation Accepting Proposed Changes to QA Program Description in Chapter 17.2 of BVPS-2 Ufsar.Proposed Changes Would Modify QA Organization to Allow Warehouse QC Inspectors to Report to Manager of Nuclear Procurement Dept ML20154P7491998-10-19019 October 1998 SE Accepting Second ten-year Interval Inservice Insp Request for Relief RR-1-TYP-2-B5.40-1,Rev 0,for Plant, Unit 1 ML20198F7611998-10-0606 October 1998 Duquesne Light Co,Beaver Valley Power Station 1998 Emergency Preparedness Ingestion Zone Exercise, Conducted on 981006 ML20154C6711998-10-0101 October 1998 Safety Evaluation Concluding That Revised Model Identified in Dl Submittal Was Appropriate for Analysis of Installed Conduit Ampacity Limits.Determined That There Are No Outstanding Safety Concerns with Respect to Ampacity ML20154D5001998-09-30030 September 1998 Special Rept on Overview of BVPS-1 & BVPS-2 TS Compliance Issues & Corrective Action Taken L-98-197, Monthly Operating Repts for Sept 1998 for Beaver Valley Power Station,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Beaver Valley Power Station,Units 1 & 2.With ML20154E2171998-09-28028 September 1998 Follow-up Part 21 Rept Re Defect with 1200AC & 1200BC Recorders Built Under Westronics 10CFR50 App B Program. Westronics Has Notified Bvps,Ano & RBS & Is Currently Making Arrangements to Implement Design Mods L-98-188, Special Rept:During 1998,Unit 2 SG Eddy Current exam,26 Tubes Were Improperly Encoded in SG 2RCS-SG21C During Previous Outage.Use of Independent Databases to Track New Indications Being Implemented as Preventive Measure1998-09-21021 September 1998 Special Rept:During 1998,Unit 2 SG Eddy Current exam,26 Tubes Were Improperly Encoded in SG 2RCS-SG21C During Previous Outage.Use of Independent Databases to Track New Indications Being Implemented as Preventive Measure L-98-178, Monthly Operating Repts for Aug 1998 for Bvps,Units 1 & 2. with1998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Bvps,Units 1 & 2. with ML20155B5871998-08-28028 August 1998 Non-proprietary Rev 1 to 51-5001925-01, Risk Assessment for Installation of Electrosleeves at BVPS & Callaway Plant ML20236X2351998-08-0505 August 1998 Part 21 Rept Re Defect Associated W/Westronics 1200AC & 1200BC Recorders Built Under Westronics 10CFR50,App B Program.Beaver Valley,Arkansas Nuclear One & River Bend Station Notified.Design Mod Is Being Developed L-98-168, Monthly Operating Repts for July 1998 for Bvps,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Bvps,Units 1 & 2 L-98-157, Special Rept:On 980423,inoperability of Seismic Monitoring Instrument Noted.Caused by Obsolescence of Instrument & Inability to Obtain Necessary Spare Parts.Design Change Is Being Pursued to Obtain Replacement Product1998-07-29029 July 1998 Special Rept:On 980423,inoperability of Seismic Monitoring Instrument Noted.Caused by Obsolescence of Instrument & Inability to Obtain Necessary Spare Parts.Design Change Is Being Pursued to Obtain Replacement Product L-98-139, Monthly Operating Repts for June 1998 for Bvps,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Bvps,Units 1 & 2 L-98-119, Monthly Operating Repts for Bvps,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for Bvps,Units 1 & 2 1999-09-30
[Table view] |
Text
R
. . , .,=, -l l
"%s M teennone sm 393 5000
=~
snimnowi PA tson om March 8, 1991 Beaver Valley _ Power Station Unit 1 - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthlv Operatina Report U. S. Nuclear Regulatory Commission Document Control Desk Washirgton, D.C. 20555 Gentlemen:
In accordance with Appendix A, Technical Specifications, the Monthly Operatirs Report is submitted for Unit 1- and Unit _2 _for_- the month'of February, 1991.
Very truly yours,
. D.--Sieber ice President Nuclear Group MAW /Img Enclosures cc: NRC Regional Office King of Prussia, PA i
9103140259 910228 PDR R ADOCK 05000334 f Ih\
PDR
f
, NARRATIVE SLM%RY OF KND{LY OPEATING EXPERIENCE j UNI'I I FEBRUARY 1991 February 1 The unit remained shutdown to repair the main turbine's D.C.
Bearing Oil Pump. At 2009 hours0.0233 days <br />0.558 hours <br />0.00332 weeks <br />7.644245e-4 months <br /> the unit was synchronized and the unit's output was escalated to a ncaninal value of 100%.
February 2 The unit operated at a ncaninal value of 100% output.
Fabruary 3 At 0150 hours0.00174 days <br />0.0417 hours <br />2.480159e-4 weeks <br />5.7075e-5 months <br /> the unit's output was reduced-to approximately 80% to load follow. At 0847 hours0.0098 days <br />0.235 hours <br />0.0014 weeks <br />3.222835e-4 months <br /> the unit's output was escalated to 100%. At 2315 hours0.0268 days <br />0.643 hours <br />0.00383 weeks <br />8.808575e-4 months <br /> the Unit's output was reduced to 80% to load follow.
FeW' 4 At 0500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> the unit's output was escalated to 100%.
February 5 The unit operated at a ncxninal value of 100% output.
through February 28
- i AVmAGE IRILY LNIT METR LEVEL Docket 14o. 50-334 Unit BVPS LMit 1 Date March 7. 1991 Capleted by M. A. Wirner Telephone (1121393-7621 P.Dtml FEBRUARY 1991 IAY AVERAGE !*ILY TWIR ILVfL DAY AVmAGE (WILY K MER LEVIL
(!He-Net) (!We-Het) 4 1 _ _ _ _
0 17 821 2 690 18 ,,,- 813 _
l 3 775 19 808 -
-i 4 771 20 81" 5 825 21 f21 6 __- 821 22 r14 .,
7 813 23 814 8 817 24 821-( 9 821 2,r , 813 ,
i 10 825 26 817 11 817 27 817 ,_,_
12 821 28 813 13 813 ,
14 817 15 023
-16 810 __,
INS'IRUCI' IONS -
On this format, list the average daily unit power level-in IWe-Net for each day in the reporting month, cmpute to the nearest whole megawatt.:
l u
, . '1
Unti SmuTDoves AmD PovER REDUCTIONS Docket he. 50-334 -
Unit mere RVPS Unit #1 Date perch T. 1991 Completed 3y R.A. Winner REPORT N0sTE FE9#UARY 199* Telephone (6123 393-7621 Methed of ticeauce Cause & Cone t ive Duration Shutting Ew nt System Component Action to Co.
Date Typel (Nours) Reason 2 Dawn Reactor 3 Report 8 Code 4 Code 5 Prevent Recurrence 910201 20.1 A 4 m/A NA PUMPXE Unit remained shutdou* to repair 3 F main Turbine's 9. 5. Lube ett Pump.
4 '910203 S 0 N 5 m/m ZZ ZZZZZZ Out pt:t reduced free 100% to 801 to toed foltou.
T 910203 5 0 5 m/A ZZ ZZZZZZ output reduced from 1001 to 801
- 5 N to lead foltou.
t 1
2 3 4 7 .
'F-Forced Reason: .
Method: Enhibit G-instructions for S-Scheduled. A-Equipment Felture (Exptein) 1-menuel Preparatier of Date Entry Sheets 8-Meintenance or' Test 2-Manost Scree for Licensee Event Report (LER) File C-Refueling .
3-Automatic seres (suREG0161).
B-Regulatory Restriction 4-Cont *d. free Prewfous Month E-Operator Training & License Exam 5-Reduction 5 F-Administrattwe 9-Other Exhibit 3-Seme source.
s-operationet Error (Emptain)
N-Other (Emplain).-
}
l i
OPERATING DATA REPORT DOCKET NO. 50-334 REPORT DATE: 03/07/91 COMPLETED BY: M.A.WINGER TELEPHONE: (412) 393 7621 OPERATING STAIMS
- 1. UNIT NAME: BEAVER VALLEY POWER STATION, UNIT 1 Notes
- 2. REPORTINC PERIOD: FEBRUARY 1991
- 3. LICENSED THEP. MAL POWER (MWt): 2652
- 4. NAMEPLATE RATING (Cross MWe): 923
- 5. DESIGN ELECTRICAL RATING (Net MWe): 835
- 6. MAX DEPENDABLE CAPACITY (Gross MWe): 860 g
- 7. MAX. DEPENDABLE CAPACITY (Not MWe): 81n B. IP CHANCES OCCUR IN CAPACITY RATINGS SINCE LAST REPORT, GIVE REASONS:
w
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (Net MWe): None i 10. REASONS FOR RESTRICTIONS, IF ANY: _ _ _ N/A THIS MONTH YEAR TO DATE CUMULATIVE
- 11. HOURS IN REPORTING PERIOD: 672.0 1416.0 130008.0
- 12. NO. OF HRS. REACTOR WAS CRITICAL: 672.0 1075.5 81369.9
- 13. REACTOR RESERVE SHUTDOWN HOURS: 0.0 0.0 4462.8
- 14. HOURS GENERATOR WAS ON LINE: 651.9 1041.8 79586.8
- 15. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
- 16. GROSS THERMAL ENERGY GEN. (MWH): 1698024.0 2660994.0 188949441.5
- 17. GROSS ELECT. ENERGY GEN. (MWH): 553420.0 861390.0 60694119.0
- 18. NET ELECTRICAL ENERGY GEN. (MWH): 524150.0 813910.0 56678110.0
- 19. UNIT SERVICE FACTOR: (PERCENT) 97.0 73.6 63.4
- 20. UNIT AVAILABILITY FACTOR:(PERCENT) 97.0 73 6 63.4
- 21. UNIT CAPACITY FACTOR (MDC): PCT 96.3 71.0 56,'i
- 22. UNIT CAPACITY FACTOR (DER): PCT 93,4 68.8 55.0
- 23. UNIT FORCED OUTAGE RATE: ' PERCENT) 3,0 26.4 16.5
- 24. SHUTDOWNS SCHEDULED CVER NEXT SIX MONTHS (TYPE,DATE AND DURATION OF EACH):
THE UNIT IS SCHEDULED TO SHUTDOWN F0]LIllE UNIT' S 8TH REFUELING OMI6GE ON APRIL 12.1991. THE UNIT IS SCHEDULED TO BE SHUTDOWN FOR 10 WEEKS.
- 25. IF SHUT DOVN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED INITIAL CRITICALITY N/A N/A INITIAL ELECTRICITY N/A N/A COMMERCIAL OPERATION N/A N/A l
!#RPATIVE SLIMJtY OT lotfIHLY OPIRi&I!)3 D3'IRIDJCE UGT II ITERUARY 1991 ,
I rebruary 1 The Unit operated at a rmtnni value of 100% eutput.
threnxjh February 28 ,
1 i
l
OPERATING DATA REPORT DOCKET NO.. 50 412 REPORT DATE: 03/07/91 COMPLETED BY: M.A.WINGER TELEPHONE: (412) 393 7621 OPERATING STATUS
- 1. UNIT NAME: BEAVER VALLEY POW *R STATION, UNIT 2 Notes
- 2. REPORTING PERIOD: FEBRUAhY +i91
- 3. LICENSED THERMAL POWER (MWt): 2652
- 4. NAMEPLATE RATING (Crost MWe): 923
- 5. DESIGN ELECTRICAL RATING (Net MWe): 836
- 6. MAX DEPENDABLE CAPACITY (Cross MWe): 870
- 7. MAX. DEPENDABLE CAPACITY ' Net MWe): 820
- 8. IF CHANCES OCCUR IN CAPACITY RATINGS SINCE IAST REPORT, CIVE REASONS:
- 9. POWER LEVEL TO VHICH RESTRICTED, IF ANY (het MWe): None
- 10. REASONS FOR RESTRICTIONS, IF ANY: ,
N/A THIS MONTH Yi.AR TO DATE CUMUIATIVE
- 11. HOURS IN REPORTING PERIOD: 672.0 1416.0 28791.0
- 12. No OF HRS. REACTOR WAS CRITICAL: 672.0 1416.0 23763.3
- 13. REACTOR RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0 :
- 14. HOURS CENER/iTOR WAS ON LINE: 672.0 1416.0 23577.8
- 15. UNIT RESERVL 3HUTDOWN HOURS: 0.0 0.0 0.0
- 16. CROSS THERMAL ENERGY GEN. (MVH): 1772383.0 3738488.0 56866104.4
- 17. GROSS ELECT. ENERGY GEN. (MVH): 573700.0 1209000.0 182458u0.0
- 18. NET ELECTRICAL ENERCY GEN. (MWH): 544633.0 1148384.0 17191708.0
- 19. UNIT SERVICE FACTOR: (PERCENT) 100.0 100.0 81.9
- 20. UNIT AVAILABILITY FACTOR:(PERCENT) 100.0 100.0 81.9
- 21. UNIT CAPACITY FACTOR (MDC): PCT 98.8 98.9 71.8
- 22. UNIT CAPACITY FACTOR (DER): PCT 96.9 97.0 71.4
- 23. UNIT FORCED OUTAGE RATE: (PERCENT) 0.0 0.0 4.9
- 24. SHUTDOWNS SCHEDULED OVER NEXT SIX MONTHS (TYPE,DATE, AND DURATION OF EACH):
- 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE 00 STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED INITIAL CRITICALITY __ N/A N/A INITIAL ELECTRICITY N/A N/A COMMERCIAL OPERATION N/A N/A l
l l
l 1
-_ _._ __ _ _ - . . . . . __-. .. . _ . _ _ ,_ _ . . . _ < _ _ . ...___m
_ _ _.m.. _ . . . . - .
4 l i
- 1 UNIT SMUYDOWNS AND POWER REDUCTIces Docket me. 50-412 Unit Name SWP5 Unit #2 i Date March T. 1991
- I Completed By M.A. Winger f REPORT MouTM FEsaumat 1991 Telephone .(412) 393-7621 .
- i
- h. Method of Licensee Cause & Corrective [
Duration Shutting Event System Component Action to f
.co. Date- Typet (nours) Reeson2 Down acactor3 seport # code' code 5 Prevent accurrence 1
l Cone f I !
f 5
4 ,
i t i~ [
t' 4 I
+
3 l
4 i
i r
I 4
. i 1 2 3 4 ?
F-Forced Reesoe: Method: Exhibit G-instructions for !
S-Scheduled A-Equipment Failure (Emplain) 1-menvat ' Preparation of Bate Entry Sheets 'i S-Meintenance or Test 2-menvat scree- for Licensee Event Report (LER) File' i
!' C-Refueling 0-megulatory' Restriction
_3-Automatic scram 4-Cont'd. from Previous Month (uueEG0161). [
t E-Operator Training & License Ex==
5-Redvetion 5 i
_ 'F-Administrative.: 9-Other Exhibit 1-Same Source. l
! G-operational Error (Emptain) [
N-Other (Emplain) {
i i
i ,
3
}
4 1 2
t i ~ - -
I
._.__ ~ , _ .. _ _ . _ _ . _ ._ _ . _ _ .. . .,..
e i
AVERAGE CAILY TWIT POWFR LEVEL l
l 1
DrAet No. 50-412 1 Unit BVPS Unit 2 .
j Date j$ar d 7. 1991 l j Ccmpleted W M. A. Winaer ,
! Telephone (412) 393-7621 1
1 '
!Dml FI21RUARY_199.1 ;
DAY AVERAGE DAILY POWER LEVEL DAY. AVERAGE DAILY POWER LEVEL
(!We-Net) (l@e-Net) 1 807 , , , , 17 811 i 2 807 18 811 i :
i
< 3 811 19 807 1
4 811 20 811 t
5 811 21 811 l 6 811' 22 807 ,
7 815 23 811 !
t, 1 8 811 24 802 '
9 815 25 811 ,
10 815 26 811 11 811 27 811 I
12 811 28 807 ?
i 13- 807 1 14 811 ,
i 15 815 t 16 815 INSIRUCTICNS l t On this format, list the average daily unit power level in PWe-Net for each day :
in the reporting month. - Ctmpute to the nearest whole megawatt. -;
i i
l l