- RBG-41486, Discusses LAR 94-04,extending Action Times of Leakage Control Sys + (ML20083R845)
- 05000237/LER-1976-073-03, /03L-0:on 761117 During Start Up Operations, Nitrogen Storage Tank Level Dropped Below Tech Spec Limit. Addl Nitrogen Delivered to Restore Storage Tank Level + (ML20083R847)
- ML20083R860 + (ML20083R860)
- 05000237/LER-1976-039-03, /03L-0:on 760531,LPCI & Core Spray Monthly Operability Checks Not Performed as Required by Tech Specs. Caused by Personnel Error.Lpci Subsys Operated on Several Occasion + (ML20083R863)
- 05000244/LER-1976-011-01, /01T:on 760308,during Flow Test of Control Room Ventilation Sys,Zero Flow Indicated for Cleanup Path Designed for 25% Total Sys Flow.Caused by Drive Piston Being Improperly Mounted During const.W/7760319 Ltr + (ML20083R872)
- ML20083R873 + (ML20083R873)
- ML20083R879 + (ML20083R879)
- B11099, Forwards Revised Summary of NRC 840214 Meeting W/Util & S&W Re Status & Proposed Resolution of Draft SER Open Items on Geotechnical Issues,Per NRC Request for Addl Info.W/Seven Oversize Figures.Aperture Cards in PDR + (ML20083R882)
- ML20083R888 + (ML20083R888)
- SNRC-1024, Submits Results of Actions Taken to Comply W/Requirements of IE Bulletin 83-08 Re Electrical Circuit Breakers W/Undervoltage Trip Feature in Use in safety-related Applications Other than Reactor Trip Sys + (ML20083R891)
- 2CAN948404, Forwards Comprehensive Rept & Schedules for Proposed Instrument Upgrades,Per Suppl 1 to NUREG-0737 & Reg Guide 1.97.Progress of Implementation & Upgrades Will Be Reported Biannually + (ML20083R892)
- ML20083R896 + (ML20083R896)
- 05000237/LER-1976-038-01, /01T-0:on 760526,sample Valve Reopened Per Procedure When Valve Discovered Closed for 40-h Period During Routine Counting of Chimney Sample Cartridges.Caused by Personnel Error + (ML20083R906)
- ML20083R910 + (ML20083R910)
- ML20083R915 + (ML20083R915)
- 05000244/LER-1976-008-01, /01T:on 760227,during Planned Current Insp of Steam Generator tubes,39 Tubes in Steam Generator Inlet a & 2 Tubes in Steam Generator Inlet B Showed Defects Above Wastage Limit.Caused by Corrosion + (ML20083R916)
- 05000387/LER-1984-020, :on 840321,shutdown Cooling Suction Inboard & Outboard Isolation Valves Closed Due to Spurious Actuation of RHR Sys Differential Pressure Switches.Cause Not Stated. Shutdown Cooling Operation Will Be Observed + (ML20083R917)
- 05000237/LER-1976-072-03, /03L-0:on 761228,during Start Up Operations,Crd J-11 Found to Uncouple & Overtravel When Withdrawn to Position H8.Caused by Loosened Inner Filter.Crd J-11 to Be Disassembled & Inspected + (ML20084A010)
- ML20084A012 + (ML20084A012)
- ML20084A013 + (ML20084A013)
- ML20084A014 + (ML20084A014)
- ML20084A018 + (ML20084A018)
- 05000237/LER-1976-037-03, Reactor Protection Sys Bypass Pressure Switch Ps 2-263-51A Found to Actuate Above Tech Spec Limit.Caused by Instrument Setpoint Drift.Switch Adjusted.Monthly Insp Will Be Conducted + (ML20084A024)
- ML20084A026 + (ML20084A026)
- ML20084A027 + (ML20084A027)
- ML20084A028 + (ML20084A028)
- ML20084A034 + (ML20084A034)
- 05000244/LER-1976-007, Revised LER 76-07/30:on 760207,relays for Train a Containment Isolation & Ventilation Isolation Failed to Latch.Caused by MG-6 Relays Having Improper Latch Screw Factory Adjustment + (ML20084A035)
- ML20084A041 + (ML20084A041)
- 05000237/LER-1976-071-03, /03L-0:on 761223,audit Revealed Some Surveillance Intervals Inadvertently Exceeded During 6-month Period Following Tech Spec Rev.Computer Reprogrammed to Schedule Surveillances on Weekly Basis + (ML20084A045)
- ML20084A048 + (ML20084A048)
- ML20084A057 + (ML20084A057)
- 05000237/LER-1976-035-03, /03L-0:on 760527,during Drywell Inerting,Nitrogen Storage Tank Level Dropped to 54 Inches & Remained Below 60 Inches for 2 H.Caused by Unanticipated Delay in Delivery of Nitrogen.Level Promptly Restored + (ML20084A060)
- ML20084A061 + (ML20084A061)
- ML20084A065 + (ML20084A065)
- 05000364/LER-1984-004-01, :on 840327,reactor Tripped from 100% Power Due to Power Range Neutron High Flux Negative Rate.Caused by Control Rods Dropping Into Core Due to Voltage Surge Caused by Severe Lightning.Power Supplies Reset + (ML20084A066)
- 05000373/LER-1984-019, :on 840320,while Investigating Differential Flow Indication Problem,Incorrect Calibr Data Used to Calibr Reactor Water Cleanup Sys Inlet Flow Transmitter.Caused by Conflicting Instrument Data Sheets + (ML20084A067)
- ML20084A068 + (ML20084A068)
- 05000237/LER-1976-070-03, /03L-0:on 761218,diesel Generator Failed to Carry Required Load Following Monthly Surveillance.Caused by Water in Diesel Fuel Supply.Fuel Oil Day Tank Drained & Lines & Piping Flushed + (ML20084A073)
- 0CAN948401, Informs of Effects of Util General Ofc Work Disruption Due to 840408 Electrical fire.NUREG-0737,Suppl 1 Unit 2 Safety Parameter Display Sys Safety Analysis & NUREG-0737,Suppl 1 Update Will Be Delayed Due to Word Processor Breakdown + (ML20084A074)
- 2CAN948403, Forwards Results of Fuel Insps at End of Third Cycle.Rept Completes FSAR Commitment for Fuel Insp Submittals + (ML20084A077)
- PLA-2033, Interim Deficiency Rept Re Clamps on Control Rod Drive Insert/Withdraw Lines Not Providing Axial Restraint. Initially Reported on 831209.Design Mod to Pedestal Support Initiated.Also Reportable Per Part 21 + (ML20084A079)
- RBG-17-615, Forwards State of La Re Historical & Archaeological Investigation of Ruins of Nineteenth Century Sugar Mill in West Feliciana Parish,La,Per Request. Property Ineligible for Inclusion in Natl Register + (ML20084A086)
- 05000237/LER-1976-034-01, /01T-0:on 760525,during Automatic Blowdown Surveillance Testing,Relief Valve 203-3A Remained Open. Caused by Excessive Leakage in Pilot Stage of Valve.Valve Pilot & Secondary Stages Replaced + (ML20084A087)
- ML20084A090 + (ML20084A090)
- ML20084A093 + (ML20084A093)
- 3F0484-15, Forwards Annual Financial Repts 1983 for Florida Power Corp & Participants,Excluding Cities of Kissimmee & Tallahassee. Comprehensive Financial Statements & Auditors Rept Also Encl + (ML20084A094)
- ML20084A097 + (ML20084A097)
- ML20084A099 + (ML20084A099)
- 05000237/LER-1976-069-01, /01T-0:on 761214,notification Received from GE That MAPLHGR Limits No Longer Considered Sufficiently Conservative.Caused by Adminstrative Error.Tech Spec Rev Request Initiated + (ML20084A104)
- 05000244/LER-1976-007-03, /03L:on 760227,sump a Discharge AOV Not Closed. Caused by Westinghouse Type MG-6 Relays Having Improper Latch Screw Factory Adjustment.Relays Replaced + (ML20084A105)