Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20065S859 + (ML20065S859)
- ML20065S861 + (ML20065S861)
- 05000265/LER-1982-017, Forwards LER 82-017/03L-0 + (ML20065S862)
- ML20065S864 + (ML20065S864)
- 05000318/LER-1981-021, Forwards LER 81-021/03L-0 + (ML20065S866)
- ML20065S869 + (ML20065S869)
- 05000265/LER-1982-017-03, /03L-0:on 821001,small Leak Discovered in HPCI Sys Supply Steam Line Break Flange.Caused by Failed Flange Gasket.Gasket Replaced like-for-like During & Prior to Outage.Leakage Stopped W/Flange Bolt Adjustments + (ML20065S875)
- ML20065S876 + (ML20065S876)
- ML20065S878 + (ML20065S878)
- ML20065S883 + (ML20065S883)
- 05000272/LER-1982-072, Forwards LER 82-072/03L-0.Detailed Event Analysis Encl + (ML20065S885)
- ML20065S888 + (ML20065S888)
- 05000318/LER-1981-021-03, /03L-0:on 810412,transient Occurred Causing Pressurizer Pressure to Drop Below 2225 Psig.Caused by Excessive Injection of Boric Acid by Operator to Level Power Increase.Personnel Counseled + (ML20065S892)
- 05000318/LER-1981-020, Forwards LER 81-020/03L-0 + (ML20065S895)
- ML20065S897 + (ML20065S897)
- 05000373/LER-1982-121, Forwards LER 82-121/01T-0 + (ML20065S898)
- 05000272/LER-1982-072-03, /03L-0:on 820925,exhaust Fan 11 Drive Belts in Fuel Handling Area Discovered Broken & Fan 12 Belts Loose & Operating at Less than Normal Speed.Caused by High Ambient Temp in Vicinity of Fans.Belts Replaced + (ML20065S902)
- ML20065S903 + (ML20065S903)
- 05000373/LER-1982-121-01, /01T-0:on 821012,found HVAC Duct Hangers S-2065 & S-2049 Not Installed Per Design Drawing.Caused by Inadvertent Substitution of Tube Steel.Design Drawing Will Be Revised + (ML20065S904)
- 05000272/LER-1982-075, Forwards LER 82-075/03L-0.Detailed Event Analysis Encl + (ML20065S908)
- ML20065S912 + (ML20065S912)
- 05000272/LER-1982-075-03, /03L-0:on 820927 Pressurizer Level Channel III Read High.Channel Bistable Placed in Tripped Condition Constituting Operation in Degraded Mode.Cause Under Investigation.Supplemental Rept Will Be Submitted + (ML20065S916)
- ML20065S917 + (ML20065S917)
- ML20065S924 + (ML20065S924)
- 05000352/LER-1990-026-01, :on 901118,full Reactor Scram Signal Generated on High Reactor Pressure Vessel Pressure of 1,033 Psig. Caused by Personnel Error.Operator Counseled & Event Will Be Included in Operator Training + (ML20065S926)
- 05000353/LER-1990-020-02, :on 901119,primary Containment post-LOCA Radiation Monitoring Sys Declared Inoperable Due to Deficient Circuit Board in Three of Four Channels.Caused by Inadequate Design Review.Replacement Installed + (ML20065S928)
- 05000318/LER-1981-020-03, /03L-0:on 810407,containment Atmosphere Particulate Radioactivity Detector Failed.Caused by Cable to Junction Box Connector Failure Due to Conductor Stress Formed During Repair Resulting in Split Connector Block + (ML20065S931)
- LIC-90-0982, Forwards Response to Generic Ltr 90-06, PORV & Block Valve Reliability;Addl Low Temp Overpressure Protection for Lwrs. Both PORV & Block Valves Tested in Inservice Test Program + (ML20065S933)
- ML20065S935 + (ML20065S935)
- LIC-90-0983, Responds to NRC Re Violations Noted in Insp Rept 50-285/90-38.Corrective Actions:Hydrostatic Pressure Test Will Be Performed on Applicable Sections of Piping During 1991 Refueling Outage to Establish Pressure of 395 Psig + (ML20065S937)
- 05000440/LER-1990-034, :on 901125,discovered That Reactor Pressure Vessel Water Level Instrumentation Equalizing Valve Mispositioned.Caused by Personnel Error.Equalizing Valve Closed & Walkdown Performed + (ML20065S939)
- 05000311/LER-1982-116, Forwards LER 82-116/03L-0.Detailed Event Analysis Encl + (ML20065S946)
- RBG-13-164, Responds to NRC Re Violations Noted in IE Insp Rept 50-458/82-03.Corrective Actions:Review of All Warehouse Records Performed to Determine If Other Equipment Requiring Maint Had Gone Undetected + (ML20065S959)
- 05000311/LER-1982-116-03, /03L-0:on 820927 & 28,RCS Subcooling Margin Monitor Failed.Caused by Malfunction of Computer Logic Board in Process Computer & Previous Repair of Computer, Respectively.Logic Board Replaced & Point Reset + (ML20065S963)
- 0CAN098202, Summarizes 820908 Telcon Re IE Bulletin 82-01,Revision 1, Suppl 1.Bulletin Requires Radiograph Sets of Welds Associated W/Pipe Walls Less than 1/2 Inch & Applies Only to Unit 2 + (ML20065S970)
- ML20065S971 + (ML20065S971)
- ML20065S973 + (ML20065S973)
- ML20065S974 + (ML20065S974)
- ML20065S977 + (ML20065S977)
- 05000416/LER-1990-025, :on 901122,actuation of Reactor Protection Sys Occurred During Surveillance of Reactor Mode Switch.Caused by Diminishing Power Supply of Test Equipment.Evaluation Will Be Conducted + (ML20065S980)
- 05000311/LER-1982-107, Forwards LER 82-107/03L-0.Detailed Event Analysis Encl + (ML20065S981)
- 05000311/LER-1982-110, Forwards LER 82-110/03L-0.Detailed Event Analysis Encl + (ML20065S985)
- 05000311/LER-1982-107-03, /03L-0:on 820923,axial Flux Distribution Went Out of Target Band Due to Turbine Load Reduction When Turbine Generator Stator Water Temp Increased.Temp Increase Caused by Clogged Ports on Valve Positioner 2ST1 + (ML20065S987)
- 05000318/LER-1981-017, Forwards LER 81-017/03L-0 + (ML20065S990)
- 05000282/LER-1990-017-01, :on 901121,discovered That Bus Duct Cooling Fan 11 Not Running & Supply Breaker Tripped,Resulting in Main Generator,Turbine & Reactor Trip.Caused by Inadequate Design.Supply Breaker Replaced + (ML20065S992)
- 0CAN038201, Forwards Decription of Design Changes Which Required Safety Evaluation & Were Completed in 1981 + (ML20065S996)
- 05000318/LER-1981-017-03, /03L-0:on 810414,drain Line Accidentally Broken from Emergency Discharge of ECCS Pump Room Cooler 22.Caused by Dropped Tool Breaking Plastic Nipple.Scaffolding Checked to Ensure Required Toe Boards + (ML20065T001)
- 2CAN098207, Provides Summary Evaluation of Design & Performance of Core During Cycle 3 Operation at 100% Rated Core Power. No Unreviewed Safety Questions Exist + (ML20065T004)
- ML20065T008 + (ML20065T008)
- ML20065T009 + (ML20065T009)
- 05000311/LER-1982-110-03, /03L-0:on 820926,no Indication of Seal Interspace Air Pressure Found on Containment Air Lock.Air Lock Also Failed Seal Leakage Test.Caused by Loose Pivot on Air Interlock Linkage.Leakage Caused by Failure of Seal Joint + (ML20065T011)