Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000368/LER-1982-027-03, /03L-0:on 820811,while at 82% Full Power,Position Indication for Control Element Assembly 67 Calculator Malfunctioned.Caused by Spikes at Random Intervals in Incoming Rspt Voltage + (ML20063N394)
- ML20063N395 + (ML20063N395)
- ML20063N425 + (ML20063N425)
- ML20063N426 + (ML20063N426)
- ML20063N428 + (ML20063N428)
- ML20063N430 + (ML20063N430)
- ML20063N431 + (ML20063N431)
- ML20063N435 + (ML20063N435)
- ML20063N444 + (ML20063N444)
- ML20063N450 + (ML20063N450)
- ML20063N465 + (ML20063N465)
- ML20063N468 + (ML20063N468)
- ML20063N470 + (ML20063N470)
- 05000321/LER-1982-081, Forwards LER 82-081/03L-0 + (ML20063N472)
- 05000321/LER-1982-081-03, /03L-0:on 820821,while Operating at Steady State, Fission Product Low Flow Alarm Sounded in Control Room. Sample Pump Discovered Off.Caused by Component Failure of Particulate Vacuum Pump Carbon Vanes.Pump Repaired + (ML20063N474)
- 05000325/LER-1982-099, Forwards LER 82-099/03L-0 + (ML20063N475)
- 05000325/LER-1982-099-03, /03L-0:on 820820,review of Fire Protection Sys Annunciator Procedures Revealed That 241 of 300 safety-related Procedures Did Not Exist or Were Not Adequate + (ML20063N477)
- 05000272/LER-1982-062, Forwards LER 82-062/03L-0.Detailed Event Analysis Encl + (ML20063N480)
- 05000272/LER-1982-062-03, /03L-0:on 820813,RCS Chemistry Surveillance Not Completed on Schedule.Caused by Oversight of Chemistry Analyst.Surveillance Completed & Analyst Cautioned + (ML20063N483)
- 05000296/LER-1982-035, Forwards LER 82-035/03L-0 + (ML20063N490)
- 05000387/LER-1982-013, Forwards LER 82-013/03L-0 + (ML20063N492)
- 05000331/LER-1982-054, Forwards LER 82-054/03L-0 + (ML20063N493)
- 05000296/LER-1982-035-03, /03L-0:on 820821,valve FCV-77-2B Failed to Close When HS-77-2B Placed in Closed Position.Sump Sampling Sys Rendered Inoperable.Caused by Stuck Piston in Versa Solenoid Valve.Solenoid Cleaned & Returned to Svc + (ML20063N495)
- 05000331/LER-1982-054-03, /03L-0:on 820816,RHR Svc Water Pump 1P22A Failed to Develop Required Discharge Pressure at Rated Flow.Caused by Normal Pump Wear Causing Excessive Clearances to Develop Between Pump Impeller & Casing Wear Rings.Impeller Adju + (ML20063N496)
- ML20063N501 + (ML20063N501)
- 05000324/LER-1982-096, Forwards LER 82-096/03L-0 + (ML20063N502)
- 05000311/LER-1982-081, Forwards LER 82-081/03L-0.Detailed Event Analysis Encl + (ML20063N505)
- ML20063N507 + (ML20063N507)
- 05000324/LER-1982-096-03, /03L-0:on 820814,review of Primary Containment Isolation Logic Revealed Failure to Meet Requirement to Have Low Condenser Vacuum Switches B21-PS-N056 (A-D) in Svc When Vessel Pressure Was Greater than or Equal to 500 Psig + (ML20063N508)
- 05000311/LER-1982-081-03, /03L-0:on 820813,RCS Chemistry Surveillance,Due 820813,had Not Been Completed Until 820814.Caused by Oversight by Chemistry Analyst.Chemistry Analyst Counseled + (ML20063N509)
- 05000366/LER-1982-094, Forwards LER 82-094/03L-0 + (ML20063N510)
- 05000366/LER-1982-094-03, /03L-0:on 820817,volumetric Weighted Average Drywell Air Temp Exceeded 135 F Tech Spec Limit.Caused by Procedural Deficiency.Primary Containment Chilled Water Sys Procedure Will Be Revised + (ML20063N513)
- 05000339/LER-1982-052, Forwards LER 82-052/03L-0 + (ML20063N516)
- 05000339/LER-1982-052-03, /03L-0:on 820822,one RCS Subcooling Margin Monitor Failed.Caused by Internal Circuit Locking Processor in Alarm Mode.Alarm Reset + (ML20063N520)
- 05000339/LER-1982-050, Forwards LER 82-050/03L-0 + (ML20063N521)
- 05000339/LER-1982-050-03, /03L-0:on 820816,RHR Pump 1A Removed from Svc Leaving One Loop for Decay Heat Removal Operable.Caused by Need to Replace Mechanical Seal Due to Primary O Ring Overheating + (ML20063N524)
- PLA-1238, Responds to NRC Re Violations Noted in IE Emergency Preparedness Appraisal Rept 50-387/82-12. Corrective Actions:Procedure Will Be Revised to Reflect Lead Shift Technical Advisor Responsibilities + (ML20063N525)
- 05000311/LER-1982-091, Forwards LER 82-091/01T-0.Detailed Event Analysis Encl + (ML20063N536)
- 05000311/LER-1982-091-01, /01T-0:on 820906,containment Fan Coil Unit 23 Found Leaking Svc Water.Caused by Erosion of Copper Nickel Cooling Coils by Silt Laden Svc Water.Leaking Coil Blanked Off.Coils Will Be Replaced W/Erosion Resistant Matl + (ML20063N545)
- 05000321/LER-1982-079, Forwards LER 82-079/03L-0 + (ML20063N560)
- 05000346/LER-1982-037, Forwards LER 82-037/03L-0 + (ML20063N562)
- ML20063N564 + (ML20063N564)
- 05000321/LER-1982-079-03, /03L-0:on 820819,reactor Water Cleanup Sys Differential Flow Instrument F.T. & C. Test Not Completed as Required by Tech Specs.Caused by Personnel Error.Person Responsible Reprimanded & Counseled + (ML20063N566)
- 05000346/LER-1982-037-03, /03L-0:on 820816,door 306 Failed to Close Properly,Due to Bent Bottom Seal Plate.Cause Unknown.Seal Plate Replaced to Allow Proper Door Operation + (ML20063N567)
- ML20063N568 + (ML20063N568)
- 05000311/LER-1982-072-03, /03L-0:on 820820,reactor Trip Breaker B Would Not Trip as Required During Surveillance Testing.Caused by Failure of Undervoltage Coil.Reactor Trip Breaker Replaced W/Train Bypass Breaker a + (ML20063N571)
- ML20063N573 + (ML20063N573)
- ML20063N576 + (ML20063N576)
- AECM-82-389, Discusses Independent Design Review Per License Condition 2.C(43).Design Verification Program to Provide Addl Assurance That Design & Const Activities Meet 10CFR50,App B Requirements Will Be Performed by Cygna Energy Svcs + (ML20063N581)
- ML20063N584 + (ML20063N584)
- ML20063N585 + (ML20063N585)