05000311/LER-1982-091, Forwards LER 82-091/01T-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 82-091/01T-0.Detailed Event Analysis Encl
ML20063N536
Person / Time
Site: Salem PSEG icon.png
Issue date: 09/08/1982
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20063N537 List:
References
NUDOCS 8209220170
Download: ML20063N536 (4)


LER-1982-091, Forwards LER 82-091/01T-0.Detailed Event Analysis Encl
Event date:
Report date:
3111982091R00 - NRC Website

text

0 PSEG Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station September 8, 1982 Mr.

R.

C.

Haynes Regional Administrator USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Haynes:

LICENSE NO. DP R-7 5 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 82-091/0lT Pursuant to the requirements of Salem Generating Station Unit No.

2, Technical Specifications, Section 6.9.1.8.c, we are submitting Licensee Event Report for Reportable Occurrence 82-091/0lT.

This report is required within fourteen (14) days of the occurrence.

Sincerely yours, Sb, ?h$'*"

/

H.

J.

Midura General Manager -

Salem Operations RH:ks Cf CC:

Distribution 8209220170 G20908 PDR ADOCK 05000311 S

PDR The Energy People p0

& J 1 :-),

i1 P '

s

Report Number:

82-091/0lT Report Date:

09-08-82 Occurrence Date:

09-06-82 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Containment Service Water Leak - No. 23 Containment Fan Coil Unit.

This report was initiated by Incident Report 82-252.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 64% - Unit Load 650 MWe.

DESCRIPTION OF OCCURRENCE:

At 1420 hours0.0164 days <br />0.394 hours <br />0.00235 weeks <br />5.4031e-4 months <br />, September 6, 1982, while performing a containment surveillance, an operator discovered a small service water leak of approximately 0.25 GPM on No. 23 Containment Fan Coil Unit (CFCU).

No. 23 CFCU was declared inoperable and the leak was isolated.

Prompt notification was made to the NRC by telephone at 1425 hours0.0165 days <br />0.396 hours <br />0.00236 weeks <br />5.422125e-4 months <br />, in accordance with NRC IE Bulletin 80-24, with written confirmation transmitted on September 6, 1982.

Limiting Condition for Operation Action Statement 3.6.2.3a was already in force as of 2218 hours0.0257 days <br />0.616 hours <br />0.00367 weeks <br />8.43949e-4 months <br />, September 4, 1982, because No. 25 CFCU was inoperable.

Because both CFCU's are in the same group, Action Statement 3.6.2.3a still applied, and no new action statement was entered.

Both containment spray systems were operable throughout the occurrence.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Investigation of the problem revealed that the leakage was due to erosion of the cooling coils.

The coils are fabricated of copper nickel alloy, which is susceptible to erosion by silt laden service water.

Similar failures of other CFCU's have been noted, with most leaks occurring at bends where erosion is more significant.

ANALYSIS OF OCCURRENCE:

Primary containment is a design feature which ensures that the release of radioactive materials in the event of accident con-ditions will be restricted such that site boundary radiation doses will be within the limits of 10CFR100.

i LER 82-091/0lT -e>

ANALYSIS OF OCCURRENCE:NRC IE Bulletin 80-24 requires that any service water leak inside the containment be considered as a degradation of the containment boundary.

If containment pressure increased to the design pressure of 47 psig during an accident, there is a possibility of the re-lease of radioactivity through the service water discharge.

The occurrence, therefore, constituted an abnormal degradation of the primary containment and is reportable in accordance with Technical Specification 6.9.1.8.c.

The CFCU's operate in conjunction with the containment spray systems to remove heat and radioactive contamination from the containment atmosphere in the event of a design basis accident.

Operability of either all fan coil groups or of both containment spray systems is necessary to ensure offsite radiation dose is maintained within the limits of 10CFR100.

Action Statement 3.6.2.3a requires:

With one group of CFCU's inoperable and both contain-ment spray systems operable, restore the inoperable group of cooling fans to operable status within 7 days, or be in at least hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Because the leakage was immediately isolated, containment integrity was maintained.

Containment cooling capability was provided by the containment spray systems.

The occurrence, therefore, involved'no risk to the health or safety of the public.

Due to the loss of redundancy in design and engineered safety features, the event constituted operation in a degraded mode permitted by the limiting conditions for operation.

CORRECTIVE ACTION

As noted, the leakage was immediately isolated and prompt notifi-cation of the NRC was performed in accordance with Technical Specification 6.9.1.8.

The leaking coil was blanked off, and No. 23 CFCU was satisfactorily tested.

Because No. 25 CFCU was still inoperable, Limiting Condition for Operation Action State-ment 3.6.2.3a was not terminated.

Design Change Request 2EC-0505 has been issued to replace the CFCU cooling coils with coils manufactured of AL-6X steel, *or improved erocion and corrosion resistance in the service water environment.

This change is scheduled for implementation during the next refueling outage.

A commitment to submit a Supplemental Report upon completion was made in LER 82-070/0lT.

LER 82-091/OlT.g FAILURE' DATA:

A number of containment service water leaks due to similar failures of CFCU cooling coils have occurred'since January 1,~1982.

Westinghouse Electric Corporation Containment Fan Coil Unit U-Tube Cooling Coil.

Prepared By R.

Heller

/

e#

Gen 6ral Manager -

Salem Operations SORC Meeting No.

82-82