Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20033D056 + (ML20033D056)
- ML20033D057 + (ML20033D057)
- ML20033D058 + (ML20033D058)
- 05000296/LER-1981-064, Forwards LER 81-064/03L-0 + (ML20033D059)
- 05000296/LER-1981-064-03, /03L-0:on 811028,A Deuterium Analyzer Was Removed from Svc.Caused by Broken Weld Joint on Gas Divider.Joint Welded + (ML20033D061)
- 05000259/LER-1981-065, Forwards LER 81-065/03L-0 + (ML20033D062)
- 05000259/LER-1981-065-03, /03L-0:on 811027,containment Atmosphere Dilution Tank a Indicated 3% Below Operable Level.Caused by Leaky Capacitor in Power Supply That Resulted in Output Voltage Drop.Power Supply Replaced & Loop Calibr Verified + (ML20033D064)
- 05000328/LER-1981-131, Forwards LER 81-131/03L-0 + (ML20033D065)
- ML20033D067 + (ML20033D067)
- 05000328/LER-1981-131-03, /03L-0:on 811027,centrifugal Charging Pumps 2A-A & 2B-B Taken Out of Svc.Caused by Need to Repair Leaking T58 Globe Valve Otherwise Inaccessible.Valve Locked Open & Identical Valve Installed Downstream + (ML20033D069)
- 05000327/LER-1981-129, Forwards LER 81-129/03L-0 + (ML20033D070)
- ML20033D072 + (ML20033D072)
- IR 05000348/1981022 + (ML20033D073)
- 05000327/LER-1981-129-03, /03L-0:on 811028,power Range Channel N-41 of Neutron Instrumentation Sys Declared Inoperable.Caused by Failure of Oscillator in High Voltage Power Supply to Start Following Channel Calibr.Fuses Pulled & Reinserted + (ML20033D074)
- 05000259/LER-1981-064, Forwards LER 81-064/03L-0 + (ML20033D075)
- ML20033D077 + (ML20033D077)
- 05000259/LER-1981-064-03, /03L-0:on 811027,switch 1 of Recirculation Discharge Valve Closure & Switch 2 of Cs/Rhr Valve Opening Permissive Were Outside Tech Spec Limits.Caused by Setpoint Drift.Switches Reset.Design Change Request Initiated + (ML20033D078)
- 05000366/LER-1981-107, Forwards LER 81-107/03L-0 + (ML20033D080)
- ML20033D082 + (ML20033D082)
- ML20033D083 + (ML20033D083)
- ML20033D085 + (ML20033D085)
- 05000366/LER-1981-107-03, /03L-0:on 811104,while Performing Control Board Walkdown,Torus to Reactor Bldg Vacuum Breaker 2T48-AOF-328A Found Inoperable.Cause Attributed to Component Failure. Investigation Revealed Defective Magnet.Magnet Replaced + (ML20033D087)
- ML20033D088 + (ML20033D088)
- ML20033D089 + (ML20033D089)
- 05000338/LER-1981-081, Forwards LER 81-081/03L-0 + (ML20033D090)
- ML20033D092 + (ML20033D092)
- ML20033D093 + (ML20033D093)
- ML20033D094 + (ML20033D094)
- ML20033D095 + (ML20033D095)
- ML20033D096 + (ML20033D096)
- ML20033D098 + (ML20033D098)
- ML20033D100 + (ML20033D100)
- ML20033D101 + (ML20033D101)
- ML20033D102 + (ML20033D102)
- 05000338/LER-1981-081-03, /03L-0:on 811103,during Mode 1 Operation,Boron Concentration in Safety Injection Accumulators Went Higher than Max Limit.Caused by Inleakage Into Makeup Supply Header from Spent Fuel Pit.Accumulator Drained + (ML20033D103)
- IR 05000395/1981029 + (ML20033D104)
- ML20033D105 + (ML20033D105)
- 05000339/LER-1981-080, Forwards LER 81-080/03L-0 + (ML20033D106)
- ML20033D108 + (ML20033D108)
- 05000366/LER-1981-109, Forwards LER 81-109/03L-0 + (ML20033D109)
- 05000339/LER-1981-080-03, /03L-0:on 811103,indication for Rod P-06 in Control Bank a Did Not Change When Bank Moved in 18 Steps. Caused by Bad Fuse Connection.Fuse Clip Replaced & Tightened & Surveillance Test Performed Satisfactorily + (ML20033D111)
- ML20033D112 + (ML20033D112)
- TXX-3443, Forwards Design Review of Radiation & Shielding for post-accident Operations + (ML20033D113)
- 05000339/LER-1981-082, Forwards Updated LER 81-082/03X-1 + (ML20033D114)
- ML20033D116 + (ML20033D116)
- 05000366/LER-1981-109-03, /03L-0:on 811107,while in Hot Standby,Reactor Bldg to Torus Vacuum Breaker Isolation Valve 2T48-F311 Opened on High Dp & Would Not Reset When Condition Cleared.Cause Attributed to Accumulation of Moisture in Sensing Lines + (ML20033D117)
- 05000339/LER-1981-082-03, Discovered That Periodic Test for Tech Spec Heat Tracing Circuits Not Performed within Required Surveillance Interval.Caused by Test Being Inadvertently Indicated as Completed + (ML20033D118)
- 05000366/LER-1981-105, Forwards LER 81-105/03L-0 + (ML20033D119)
- ML20033D121 + (ML20033D121)
- ML20033D122 + (ML20033D122)
- ML20033D123 + (ML20033D123)