Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000272/LER-1981-078-01, /01T-0:on 810903,during Surveillance Test,Svc Water Discovered Leaking from Top Secondary Coil 11 on Containment Fan Coil Unit.Caused by Failure of Secondary Coil.Coil Repaired & Returned to Svc + (ML20010G869)
- ML20010G871 + (ML20010G871)
- 05000272/LER-1981-076-01, /01T-0:on 810902,NRC Notified of Svc Water Leaking from Secondary Coil on Containment Fan Coil Unit (Cfcu) 14, Per IE Bulletin 80-24.CFCU Removed from Svc & Declared Inoperable.Caused by Secondary Coil Failure + (ML20010G873)
- ML20010G874 + (ML20010G874)
- IR 05000317/1981013 + (ML20010G875)
- AECM-81-282, Final Deficiency Rept Re GH-Bettis Spring Return Actuators, Initially Reported on 801222.Spring Guide Sleeve Shifting Internally Could Prevent Movement of Actuator.Caused by Design Deficiency.Actuators Repaired & Redesigned + (ML20010G877)
- ML20010G878 + (ML20010G878)
- ML20010G879 + (ML20010G879)
- ML20010G880 + (ML20010G880)
- ML20010G881 + (ML20010G881)
- 05000369/LER-1981-136, Forwards LER 81-136/01T-0.Detailed Event Analysis Encl + (ML20010G882)
- ML20010G883 + (ML20010G883)
- ML20010G884 + (ML20010G884)
- ML20010G885 + (ML20010G885)
- 05000311/LER-1981-085, Forwards LER 81-085/01T-0.Detailed Event Analysis Encl + (ML20010G887)
- ML20010G888 + (ML20010G888)
- 05000369/LER-1981-136-01, /01T-0:on 810825,during Test of Turbine Driven Auxiliary Feedwater Pump,Suction Piping Was Overpressurized When Pump Tripped.Caused by Lack of Protection for Auxiliary Feedwater Pump Suction Piping.Damaged Instruments Checke + (ML20010G889)
- 05000280/LER-1981-041-03, /03L-0:on 810820,PT-27D Revealed That Amp Readings for Heat Tracing Panel 9 Circuit 7A Were Below Acceptance Criteria.Caused by Inadvertent Cutting of Heat Tracing Tape During Cleanup Operations on Boric Acid Flat + (ML20010G890)
- ML20010G891 + (ML20010G891)
- ML20010G893 + (ML20010G893)
- ML20010G895 + (ML20010G895)
- ML20010G897 + (ML20010G897)
- 05000280/LER-1981-039-03, /03L-0:on 810815,accumulator a Level Dropped Due to Inadvertent Opening of Drain Valve HCV-1852A Instead of Fill Isolation Valve HCV-1851A.Caused by Operator Error. Operator Reinstructed in Proper Procedures + (ML20010G898)
- ML20010G899 + (ML20010G899)
- ML20010G901 + (ML20010G901)
- 05000321/LER-1981-088, Forwards LER 81-088/03L-0 + (ML20010G902)
- ML20010G903 + (ML20010G903)
- ML20010G904 + (ML20010G904)
- ML20010G905 + (ML20010G905)
- 05000311/LER-1981-085-01, /01T-0:on 810901,redundant Power Cable,Conduit 2BDD-B(5inch) Discovered Not to Have Fire Wrap Protection. Caused by Personnel Inadvertent Oversight.Complete Review of Design Change Conducted + (ML20010G907)
- IR 05000289/1981009 + (ML20010G908)
- ML20010G910 + (ML20010G910)
- 05000321/LER-1981-088-03, /03L-0:on 810811 & 18,oil Leaks Discovered on HPCI Oil Sys.Caused by Ruptured Diaphragm on Diaphragm Control Valve.Diaphragm Replaced + (ML20010G912)
- ML20010G913 + (ML20010G913)
- ML20010G914 + (ML20010G914)
- IR 05000271/1981008 + (ML20010G916)
- ML20010G923 + (ML20010G923)
- IR 05000382/1981019 + (ML20010G924)
- ML20010G925 + (ML20010G925)
- AECM-81-338, Final Deficiency Rept Re Defective Terminations in Ite/Brown Boveri Electric Breakers & Switchgears,Initially Reported on 800703.Insp Also Covered Breakers Identified in IE Info Notice 81-06 + (ML20010G926)
- ML20010G929 + (ML20010G929)
- 05000369/LER-1981-140, Forwards LER 81-140/03L-0.Detailed Event Analysis Encl + (ML20010G930)
- ML20010G931 + (ML20010G931)
- 05000369/LER-1981-140-03, /03L-0:on 810814,channel 3 of Pressurizer Water Level Instrumentation Discovered to Have Failed.Caused by Improperly Seated Tubing Ferrule in High Pressure Ref Leg Side of Level Detector Sensing Line.Line Repaired + (ML20010G937)
- 05000259/LER-1981-046, Forwards LER 81-046/03L-0 + (ML20010G938)
- ML20010G939 + (ML20010G939)
- 05000259/LER-1981-046-03, /03L-0:on 810816,CAM 1-RM-90-250 Declared Inoperable for 12.5-h.Caused by Pump Failure & Unavailability of Spare.Schwitzer Model 325 Vacuum Pump Replaced + (ML20010G942)
- 0CAN088105, Forwards Proprietary Version of Slide Presentation Re Facility Security Sys Made During 810623 Nrc/Util Meeting Concerning IE Insp Repts 50-313/81-09 & 50-368/81-08. Slide Presentation Withheld (Ref 10CFR2.790) + (ML20010G943)
- PNO-I-81-104, on 810916,found Two Reactor Core Isolation Cooling Steam Isolation Valves Remained Open W/O Sufficient Assurance Valves Would Have Closed for on Isolation Signals.Caused by de-energized Faulted Bus Section + (ML20010G944)
- ML20010G945 + (ML20010G945)
- ML20010G949 + (ML20010G949)