- 05000369/LER-1981-006, Forwards LER 81-006/03L-0 + (ML20008E892)
- ML20008E893 + (ML20008E893)
- ML20008E895 + (ML20008E895)
- ML20008E898 + (ML20008E898)
- ML20008E900 + (ML20008E900)
- 05000369/LER-1981-006-03, /03L-0:on 810202,leaking Seal Discovered on RHR Pump.Caused by Improperly Loaded Spring Which Holds Seal Faces Together.Seal Replaced + (ML20008E901)
- 05000327/LER-1981-013, Forwards LER 81-013/03L-0 + (ML20008E904)
- ML20008E906 + (ML20008E906)
- 05000369/LER-1981-005-03, /03L-0:on 810202,power Supply to Both Excore Range Monitors Was Interrupted.Caused by Maint Personnel Cutting Off Power to Investigate Steam Generator Status Lights & lo-lo Level Alarms.Personnel Instructed + (ML20008E907)
- 05000409/LER-1981-003, Forwards LER 81-003/03L-0.Detailed Event Analysis Encl + (ML20008E908)
- 05000327/LER-1981-013-03, /03L-0:on 810203,liquid Radwaste Monitor, 0-RE-90-122,declared Inoperable.Caused by High Background Count Reading Due to Leak in Brooks Rotameter.Rotameter Seals Replaced,Sample Chamber Cleaned & Monitor Flushed Out + (ML20008E910)
- 05000254/LER-1981-005, Forwards LER 81-005/01T-0 + (ML20008E911)
- ML20008E912 + (ML20008E912)
- 05000327/LER-1981-016, Forwards LER 81-016/03L-0 + (ML20008E913)
- ML20008E914 + (ML20008E914)
- 05000409/LER-1981-003-03, /03L-0:on 810202,gross Alpha Activity of Primary Coolant Sample Exceeded Tech Spec.Caused by Degraded Fuel Cladding During Previous Fuel Cycles.Primary Purification Sys Operation Reduced Concentration to Allowable Level + (ML20008E915)
- 05000327/LER-1981-016-03, /03L-0:on 810206,diesel Generator 2B-B Breaker Tripped Twice While Attempting to Synchronize W/Tva Power Grid for Surveillance Test SI-7.Caused by Overcurrent During Paralleling Operation.Target Reset & Parallel Repeated + (ML20008E916)
- 05000336/LER-1981-008, Forwards LER 81-008/01T-0 + (ML20008E918)
- ML20008E919 + (ML20008E919)
- 05000254/LER-1981-005-01, /01T-0:on 810220,during Testing,Three of Four Condenser Low Vacuum Scram Switches Found Outside Setting Per Tech Spec 3.1-3.Caused by Instrument Setpoint Drift.All Switches Recalibr + (ML20008E920)
- 05000368/LER-1981-006, Forwards LER 81-006/03L-0 + (ML20008E921)
- ML20008E922 + (ML20008E922)
- 05000296/LER-1981-010, Forwards LER 81-010/03L-0 + (ML20008E923)
- ML20008E924 + (ML20008E924)
- 05000336/LER-1981-008-01, /01T-0:on 810213,determined Spring Can Type Hanger Installed Improperly,Resulting in Overstressed Socket Welded Joint.Caused by Incorrect Design.Hanger Removed & Pipe Isolated & Depressurized.Design to Be Corrected + (ML20008E925)
- 05000368/LER-1981-005, Forwards LER 81-005/03L-0 + (ML20008E926)
- ML20008E927 + (ML20008E927)
- 05000368/LER-1981-005-03, /03L-0:on 810204,core Operating Limit Supervisory Sys Rendered Inoperable.Caused by Computer Failure.Software Reloaded & Computer Restarted.Backup Computer Will Be Installed + (ML20008E928)
- 05000296/LER-1981-010-03, /03L-0:on 810213,drywell High Pressure Switch 3-PS-64-58C Found Above Tech Spec Limit.Caused by Setpoint Drift.Switch Recalibr & Will Be Replaced + (ML20008E929)
- 05000368/LER-1981-006-03, /03L-0:on 810204,containment Sump Level Indicator 2LI-5645-1 Was Declared Inoperable.Caused by Defective Converter.Converter Replaced + (ML20008E930)
- ML20008E931 + (ML20008E931)
- ML20008E934 + (ML20008E934)
- ML20008E936 + (ML20008E936)
- ML20008E937 + (ML20008E937)
- ML20008E938 + (ML20008E938)
- 05000267/LER-1981-016, Forwards LER 81-016/03L-0 + (ML20008E939)
- ML20008E940 + (ML20008E940)
- 05000334/LER-1981-015, Forwards LER 81-015/03L-0 + (ML20008E942)
- ML20008E943 + (ML20008E943)
- 05000334/LER-1981-015-03, /03L-0:on 810204,RCS Loop 1 Low Flow Annunciator Alarmed Intermittently.Flow Channel 414 Declared Inoperable & Bistable Tripped.Caused by Leaking Diaphragm.Diaphragm Replaced + (ML20008E944)
- 05000334/LER-1981-016, Forwards LER 81-016/03L-0 + (ML20008E945)
- ML20008E946 + (ML20008E946)
- 05000334/LER-1981-016-03, /03L-0:on 810207,packing Leak Found in Steam Trap Isolation Valve.Caused by Valve Stem Packing Failure.Packing Rings Added + (ML20008E947)
- 05000295/LER-1981-005, Forwards LER 81-005/03L-0 + (ML20008E948)
- 05000295/LER-1981-005-03, /03L-0:on 810204,shift Engineer Discovered That Two Hydrogen Recombiners Not Interchangeable as Implied in Fsar.Caused by 3-inch to 4-inch Reducer That Was Welded on Discharge Piping Making Recombiners Not Identical + (ML20008E950)
- ML20008E952 + (ML20008E952)
- 05000277/LER-1981-010, Forwards LER 81-010/03L-0 + (ML20008E954)
- ML20008E955 + (ML20008E955)
- 05000277/LER-1981-010-03, /03L-0:on 810127,drywell Radiation Monitor Found Out of Svc During Full Operation.Caused by No Sample Flow Through Sys Due to Manual Sample/Purge Valve Dislodged from Normal Sample Position.Valve Returned to Position + (ML20008E956)
- 05000339/LER-1981-017, Forwards LER 81-017/03L-0 + (ML20008E957)
- ML20008E958 + (ML20008E958)