Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19345A914 + (ML19345A914)
- 05000296/LER-1980-043, Forwards LER 80-043/03L-0 + (ML19345A916)
- ML19345A917 + (ML19345A917)
- ML19345A918 + (ML19345A918)
- ML19345A919 + (ML19345A919)
- 05000324/LER-1980-088, Forwards LER 80-088/03L-0 + (ML19345A921)
- ML19345A922 + (ML19345A922)
- ML19345A923 + (ML19345A923)
- 05000324/LER-1980-088-03, /03L-0:on 801028,during Checks on Reactor Low Water Level Numbers 2 & 3,found Low Level Switch 2-B21-LIS-N031D-3 Actuated at 118 Inches of Water.Caused by Instrument Drift.Switch Recalibr + (ML19345A924)
- 05000296/LER-1980-043-03, /03L-0:on 801019,flow Bias Circuitry of Average Power Range Monitor High Flux Drifted High & Declared Inoperative.Caused by Water from Removal of RHR Heat Exchanger Head Draining on Panel 25-7,shorting Out Leads + (ML19345A925)
- 05000324/LER-1980-087, Forwards LER 80-087/03L-0 + (ML19345A926)
- ML19345A927 + (ML19345A927)
- ML19345A930 + (ML19345A930)
- 05000324/LER-1980-087-03, /03L-0:on 801025,w/diesel Generator 2 Out of Svc for Maint,Generator 3 Failed to Start within Required 10-s. Caused by Defective Check Valve in Diesel 3 Fuel Oil Supply Line.Check Valve Replaced + (ML19345A931)
- ML19345A933 + (ML19345A933)
- ML19345A937 + (ML19345A937)
- 05000327/LER-1980-173, Forwards LER 80-173/01T-0 + (ML19345A938)
- ML19345A939 + (ML19345A939)
- ML19345A942 + (ML19345A942)
- 05000327/LER-1980-173-01, /01T-0:on 801105,potential Discovered for Line Failure During Seismic Event Due to Missing Hangers on Component Cooling Water Supply Piping to Centrifugal Charging Pump Mechanical Seals.Caused by Drawing Omission + (ML19345A943)
- ML19345A944 + (ML19345A944)
- 05000334/LER-1980-078, Forwards LER 80-078/01T-0 + (ML19345A945)
- ML19345A946 + (ML19345A946)
- 05000344/LER-1980-021-03, During Temporary Plant Test,C Main Steam Isolation Valve Did Not Fully Close. Caused by Component Failure.Test Completed Successfully & Valve Closed + (ML19345A947)
- 05000285/LER-1980-027, Forwards LER 80-027/03L-0 + (ML19345A948)
- ML19345A949 + (ML19345A949)
- AECM-80-286, Second Interim Deficiency Rept Re Procedural Violation in Cutting Rebar,Initially Reported on 800602.Constructor Issued Stop Work Order.Method to Evaluate Unlogged Cut Rebar Is Being Developed.Final Rept Will Be Provided by 810801 + (ML19345A950)
- ML19345A952 + (ML19345A952)
- 05000334/LER-1980-078-01, /01T-0:on 801114,determined That,If Safety or Relief Valves Challenged W/Water Loop Seals on Inlet, Downstream Piping Could Be Overstressed.Caused by Inadequate Design.Loop Seal Drains Installed + (ML19345A953)
- 05000285/LER-1980-027-03, /03L-0:on 801027,during Monthly Ac Sequencer Timer Test,Timer FW-6 on Sequencer S1-2 Failed to Time Out within Prescribed Limit.Caused by Sticky Operating Mechanism.Timer Replaced W/Spare + (ML19345A954)
- 05000325/LER-1980-076, Forwards LER 80-076/03L-0 + (ML19345A956)
- ML19345A957 + (ML19345A957)
- 05000325/LER-1980-076-03, /03L-0:on 801022,primary Containment Oxygen Analyzer 1-CAT-AT-1259-2 Observed Indicating Upscale.Caused by Failed Magnetic Analyzer Sample Cell.Magnetic Unit Replaced & Analyzer Returned to Satisfactory Operation + (ML19345A958)
- 05000324/LER-1980-085, Forwards LER 80-085/03L-0 + (ML19345A959)
- ML19345A960 + (ML19345A960)
- 05000324/LER-1980-084, Forwards LER 80-084/03L-0 + (ML19345A961)
- ML19345A962 + (ML19345A962)
- 05000324/LER-1980-085-03, /03L-0:on 801024,containment Atmosphere Dilution Sys Valves 2-CAD-V55 & 56 Would Not Fully Open.Caused by Deformed Stem Seals in Each Valve Operator.New Stem Seals Installed + (ML19345A963)
- 05000267/LER-1980-067, Forwards LER 80-067/01T-0 + (ML19345A964)
- ML19345A965 + (ML19345A965)
- 05000324/LER-1980-084-03, /03L-0:on 801024,containment Atmosphere Dilution Tank Flow Control Valves 2-CAC-FCV-2717 & 2720 Would Not Operate.Caused by Accumulation of Water in Electropneumatic Converter of Valve 2720.Water Removed + (ML19345A966)
- 05000219/LER-1980-048, Forwards LER 80-048/03L-0 + (ML19345A967)
- ML19345A968 + (ML19345A968)
- 05000267/LER-1980-067-01, /01T-0:on 801107,tritium Concentration Exceeded Limit Specified in LC04.8.24.8.2(a).Caused by Inadequate Deviation 80-445 to Surveillance Procedure SR 5.8.2bc-M. Procedure & Design Changes Under Investigation + (ML19345A969)
- ML19345A970 + (ML19345A970)
- ML19345A972 + (ML19345A972)
- 05000219/LER-1980-048-03, /03L-0:on 801029,during Functional Testing,Snubber 23-7 Failed to Lock Up in Tension Direction.Cause Unknown. Snubber Replaced + (ML19345A973)
- ML19345A974 + (ML19345A974)
- 05000334/LER-1980-077, Forwards LER 80-077/01T-0 + (ML19345A975)
- ML19345A976 + (ML19345A976)
- 05000334/LER-1980-077-01, /01T-0:on 801114,overstress Condition Determined to Exist on Main Steam Line Branch Line Support.Caused by Thermal Movement of Main Steam Line Affecting Branch Line Support.Pipe Support Rod Completed + (ML19345A977)