- 05000271/LER-1980-036-03, /03L-0:on 801017,standby Liquid Control Relief Valve Setpoints Found to Be Above Tech Spec 4.4.A Requirement of 1400 to 1490 Psig.Caused by Setpoint Drift. Relief Valves Adjusted,Bench Tested & Reinstalled + (ML19339C602)
- 05000267/LER-1980-063-03, /03L-0:on 801017,gas Waste Release Routed Through Unsampled Tank.Caused by Nonlicensed Operator Inadvertently Leaving Valve Open + (ML19339C603)
- 05000313/LER-1980-038, Forwards LER 80-038/03L-0 + (ML19339C604)
- ML19339C605 + (ML19339C605)
- 05000344/LER-1980-024, Forwards LER 80-024/03L-0 + (ML19339C606)
- 05000313/LER-1980-038-03, /03L-0:on 801013,during Monthly Surveillance Testing of Number One Diesel Generator,Voltage Regulator Failed to Respond to Higher or Lower Signal.Caused by Internal Mechanical Wear.Regulator Replaced + (ML19339C608)
- 05000344/LER-1980-024-03, /03L-0:on 801011,during Troubleshooting on Steam Generator Sample Valves,Blown Fuse Was Discovered in Automatic Start Circuit of diesel-driven Auxiliary Feedwater Pump.Caused by Ground in Unrelated But Connected Circuit + (ML19339C609)
- 05000306/LER-1980-032, Forwards LER 80-032/03L-0 + (ML19339C610)
- ML19339C611 + (ML19339C611)
- 05000327/LER-1980-167, Forwards LER 80-167/03L-0 + (ML19339C612)
- ML19339C613 + (ML19339C613)
- ML19339C614 + (ML19339C614)
- AECM-80-281, Second Interim Deficiency Rept Re Standby Diesel Generator Jacket Water Cooler Thermostatic Valve Fracture.Cause Not Stated.Magnetic Particle Exam Performed on Remaining Valve. Final Rept Will Be Submitted by 810205 + (ML19339C615)
- 05000339/LER-1980-073, Forwards LER 80-073/03L-0 + (ML19339C616)
- ML19339C617 + (ML19339C617)
- 05000306/LER-1980-032-03, /03L-0:on 801013,during Refueling,Circulating Water Intake Bay Was Drained.Caused by Inoperable Priming Exhauster & Cooling Water Pump 21.Piping Mods Are Being Considered to Allow Maint W/O Effecting Operation + (ML19339C618)
- 05000327/LER-1980-167-03, /03L-0:on 801013,auxiliary Bldg Vent Monitor O-RM-90-110 Declared Inoperable.Caused by Loss of Sampling Pump Due to Circuit Breaker Tripping During Momentary Overload.Circuit Breaker Reset & Monitor Returned to Svc + (ML19339C619)
- 05000325/LER-1980-084, Forwards LER 80-084/03L-0 + (ML19339C620)
- ML19339C621 + (ML19339C621)
- 05000339/LER-1980-073-03, /03L-0:on 801015,comparator Card in Channel II Low Pressure Reactor Trip Circuit Found Inoperative.Caused by Dirty Connector in Card.Card Replaced + (ML19339C622)
- 05000259/LER-1980-080, Forwards LER 80-080/03L-0 + (ML19339C623)
- ML19339C624 + (ML19339C624)
- ML19339C625 + (ML19339C625)
- 05000255/LER-1980-039-03, /03L-0:on 801023,during Review of Testing Requirements for CV-3027 & CV-3056 It Was Determined That Valves Must Be Stroked Quarterly.Caused by Testing Requirements Not Addresing Potential for Degraded Equipment + (ML19339C626)
- 05000366/LER-1980-142, Forwards LER 80-142/03L-0 + (ML19339C627)
- ML19339C628 + (ML19339C628)
- ML19339C629 + (ML19339C629)
- 05000339/LER-1980-081, Forwards LER 80-081/03L-0 + (ML19339C630)
- ML19339C631 + (ML19339C631)
- 05000259/LER-1980-080-03, /03L-0:on 801015,valve O-FCV 39-11 on Fire Protection Sys Had Actuating Piston Seal Leak.Caused by Piston Cup Wearing Out W/Natural Aging.Part Replaced + (ML19339C632)
- 05000325/LER-1980-084-03, /03L-0:on 801016,during Normal Surveillance, Containment Atmospheric Monitor Oxygen Analyzer 1-CAC-AT- 1259-2 Was Indicating Upscale.Caused by Instrument Drift. Monitor Was Recalibr & Will Be Replaced During Outage + (ML19339C633)
- 05000270/LER-1980-020, Forwards LER 80-020/03L-0 + (ML19339C634)
- 05000366/LER-1980-142-03, /03L-0:on 801014,while Operating at Steady State 2,138 Mwt Power Level,Break in 3-h Fire Rated Wall Identified.Caused by Personnel Oversight in Followup of Sealing New Penetrations.Fire Watch Posted + (ML19339C635)
- 05000339/LER-1980-081-03, /03L-0:on 801021,deviation of Greater than 12 Steps Observed Between Indication for Control Bank B Rod D10 & Shutdown Bank a Rod J03 & Respective Group Demand Position.Caused by Instrument Drift.Channels Recalibr + (ML19339C636)
- 05000324/LER-1980-078, Forwards LER 80-078/03L-0 + (ML19339C637)
- ML19339C638 + (ML19339C638)
- ML19339C639 + (ML19339C639)
- 05000295/LER-1980-046, Forwards LER 80-046/03L-0 + (ML19339C640)
- ML19339C642 + (ML19339C642)
- 05000324/LER-1980-077, Forwards LER 80-077/03L-0 + (ML19339C643)
- ML19339C644 + (ML19339C644)
- 05000324/LER-1980-078-03, /03L-0:on 801014,during Normal Operation W/Power at 50%,primary Containment Oxygen Concentration Exceeded Tech Specs.Caused by Operator Removal of Clearance from CAC Sys W/O Allowing Time for Primary Containment Inerting + (ML19339C645)
- 05000295/LER-1980-046-03, /03L-0:on 801009,during Normal Operation,Passive Failure Gas Monitor 1RT-PR15 Repeatedly Tripped Off.Caused by Burned Limit Switch Due to Loose Contacts.Valve Actuator Replaced.Monitor Returned to Svc + (ML19339C646)
- 05000255/LER-1980-041-01, /01T-0:on 801030,during Routine Surveillance Testing of Diesel Generator 1-2,emergency Diesel Generator Charging Was Inoperable for Tests While Pump P-55C Was Inoperable for Repairs.Caused by Deficient Test Procedure + (ML19339C648)
- 05000324/LER-1980-077-03, /03L-0:on 801017,during Normal Surveillance, Containment Atmospheric Monitor Oxygen Analyzer 2-CAC-AT- 1259-2 Was Indicating Downscale.Caused by Instrument Drift. Analyzer & Transmitter Were Recalibr + (ML19339C649)
- 05000255/LER-1980-042-01, /01T-0:on 801031,during Plant Cooldown,Steam Generator Dp Exceeded 1,380 Psid Limit for Approx 85 Minutes.Caused by Operator Misplotting of Power Conversion Sys Vs Pressure.Operator Counseled + (ML19339C650)
- 05000255/LER-1980-040-01, /01T-0:on 801023,while Sluicing Resins from T-50 to T-69,waste Gas Monitor RIA-1113 Alarmed,Indicating Airborne Release.Caused by Leakage in T-50 Air Supply. Waste Gas Surge Tank Was Pumped Down + (ML19339C651)
- ML19339C652 + (ML19339C652)
- ML19339C654 + (ML19339C654)
- ML19339C656 + (ML19339C656)
- ML19339C657 + (ML19339C657)