Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19338G140 + (ML19338G140)
- 05000293/LER-1980-070-01, /01T-0:on 801010,480 Volt Breaker 52-204 Tripped Twice within 10 Minutes de-energizing 480 Volt Bus B14, Disabling Loop a of Rbccw.Cause Unknown.Breaker Closed,Bus Returned to Svc & Loop a Returned to Normal + (ML19338G141)
- ML19338G142 + (ML19338G142)
- 05000293/LER-1980-073, Forwards LER 80-073/03L-0 + (ML19338G143)
- ML19338G144 + (ML19338G144)
- ML19338G145 + (ML19338G145)
- ML19338G146 + (ML19338G146)
- 05000348/LER-1980-057-03, /03L-0:on 800922,during Startup,Rhr Sys Was Removed from Svc & Isolated from RCS at 250 F.Caused by Operator Error.Tech Specs Changed to Clarify Svc Procedure + (ML19338G147)
- 05000293/LER-1980-073-03, /03L-0:on 800917,mgt Review of Records Revealed That Monthly Surveillance Test SP74-41,visual Insp of Energy Piping Outside Containment,Was Not Performed within Required Interval.Caused by Scheduling Error + (ML19338G148)
- ML19338G149 + (ML19338G149)
- 05000259/LER-1980-074-03, /03L-0:on 800924,during Normal Operation,Seismic Monitor SMA2 Found Inoperable.Caused by Failed Printed Wiring Board 100935.Assembly Repaired,Tested & Returned to Svc.Failure Considered Random.No Further Action Planned + (ML19338G151)
- 05000267/LER-1980-054, Forwards LER 80-054/03L-0 + (ML19338G152)
- ML19338G153 + (ML19338G153)
- ML19338G155 + (ML19338G155)
- 05000334/LER-1980-075-01, /01T-0:on 801008,determined That Overstress Condition Exists on Reactor Coolant Fill Header from High Head Charging Pumps.Cause Unknown.Necessary Mods Made Prior to Start Up + (ML19338G156)
- 05000313/LER-1980-037, Forwards LER 80-037/03L-0 + (ML19338G157)
- ML19338G158 + (ML19338G158)
- 05000213/LER-1980-014-03, /03L-0:on 800926,during Surveillance Testing of Diesel Fire Pump,Pump Discharge Pressure at 2500 RPM Found Below Tech Spec Limit.Caused by Low Operating RPM of Diesel Motor.Adjustments Made to Increase Motor RPM + (ML19338G159)
- 05000267/LER-1980-053, Forwards LER 80-053/03L-0 + (ML19338G160)
- ML19338G161 + (ML19338G161)
- 05000213/LER-1980-015-03, /03L-0:on 801020,while Boiling Down Aerated Drains Tank Waste Evaporator in Preparation for Drumming,Level Indication Was Lost.Caused by Failed Gasket on Discharge Piping of Reboiler Pump.Gasket Replaced + (ML19338G162)
- ML19338G163 + (ML19338G163)
- 05000302/LER-1980-040, Forwards LER 80-040/04L-1 + (ML19338G164)
- ML19338G165 + (ML19338G165)
- 05000313/LER-1980-035-99, /99X-0:on 800916,during Investigation of Svc Water Condition,Flow Check & Cooling Coil Indicated Southwest Side of Coolers VCC2C & D Were Partially Restricted.Caused by Buildup of Asian Clams.Engineering Evaluation Is Contin + (ML19338G166)
- ML19338G168 + (ML19338G168)
- 05000325/LER-1980-080, Forwards LER 80-080/03L-0 + (ML19338G169)
- ML19338G170 + (ML19338G170)
- 05000325/LER-1980-080-03, /03L-0:on 800923,low Level Switch 1-B21-LIS-N031A-2 Failed to Actuate.Caused by Sticking Switch Actuator.Switch Actuator Was Cleaned + (ML19338G172)
- ML19338G173 + (ML19338G173)
- 05000313/LER-1980-027, Forwards Updated LER 80-027/03X-1 + (ML19338G174)
- ML19338G175 + (ML19338G175)
- 05000339/LER-1980-064, Forwards LER 80-064/03L-0 + (ML19338G176)
- ML19338G177 + (ML19338G177)
- 05000267/LER-1980-054-03, /03L-0:on 800926,during Maint Shutdown Period, Scheduled Surveillance Showed Eight Hydraulic Snubbers to Be Inoperable.Caused by One Empty Reservoir,Two Interference Problems & Five Snubbers W/Improper Stroke + (ML19338G178)
- 05000313/LER-1980-027-03, Average Gross Gas Release Rate for 3rd Quarter Was Exceeded.Caused by Presence of 0.19% Failed Fuel & Two Shutdowns.Attempts Will Be Made to Repair or Replace Failed Fuel + (ML19338G179)
- ML19338G180 + (ML19338G180)
- 05000339/LER-1980-064-03, /03L-0:on 800924,indicated Axial Flux Difference Exceeded 5% Target Band.Caused by High Bearing Temp Tripping Condensate Pump.Boron Added to RCS & Control Rods Withdrawn Until Axial Flux Difference Was Back Inside Target Ban + (ML19338G181)
- ML19338G182 + (ML19338G182)
- ML19338G183 + (ML19338G183)
- 05000259/LER-1980-077, Forwards LER 80-077/01T-0 + (ML19338G185)
- ML19338G186 + (ML19338G186)
- 05000259/LER-1980-077-01, /01T-0:on 801010,anchor Bolts Associated W/ Seismic Restraints on RHRSW Piping Had Been Degraded by Earth Settling in RHRSW Tunnels.Caused by Design Error. Pipe Restraints Modified + (ML19338G187)
- 05000324/LER-1980-067, Forwards LER 80-067/03L-0 + (ML19338G188)
- ML19338G189 + (ML19338G189)
- 05000313/LER-1980-037-03, /03L-0:on 800929,during Monthly Surveillance of Lead Hydrogen Purge Sys,Supply Fan VSF-30A Flow Slowly Degraded & Exhaust Fan VEF-37A Tripped.Caused by Sticking Check Valves & Restricted Filters.Valves Cleaned + (ML19338G190)
- ML19338G191 + (ML19338G191)
- 05000293/LER-1980-076, Forwards LER 80-076/03L-0 + (ML19338G192)
- ML19338G193 + (ML19338G193)
- 05000324/LER-1980-067-03, /03L-0:on 800923,following Reactor Scram,Reactor Core Isolation Cooling Injection Valve 2E51-F013 Would Not Fully Open.Caused by Missing Electrical Jumper.Jumper Installed + (ML19338G194)
- 05000293/LER-1980-076-03, /03L-0:on 800923,flow Integrator Fq 7032 for Drywell Floor Sump Pump Was Not Operating.Cause Undetermined + (ML19338G195)