ML19338G158

From kanterella
Jump to navigation Jump to search
Forwards LER 80-037/03L-0
Date released: 12/18/2019 Download: ML19338G158


LER 80-037/03L-0:on 800929,during Monthly Surveillance of Lead Hydrogen Purge Sys,Supply Fan VSF-30A Flow Slowly Degraded & Exhaust Fan VEF-37A Tripped.Caused by Sticking Check Valves & Restricted Filters.Valves Cleaned
ML19338G190
Person / Time
Site: Arkansas Nuclear 
Issue date: 10/23/1980
From: Bramlett L
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19338G190 (2)
Forwards LER 80-037/03L-0
ML19338G157
Person / Time
Site: Arkansas Nuclear 
Issue date: 10/23/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: SEYRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19338G157 (1)