Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000346/LER-1980-064, Forwards LER 80-064/03L-0 + (ML19338D702)
- ML19338D703 + (ML19338D703)
- 05000296/LER-1980-032, Forwards LER 80-032/03L-0 + (ML19338D704)
- ML19338D705 + (ML19338D705)
- 05000296/LER-1980-034-03, /03L-0:on 800829,during Normal Operation, Investigation of Overload for RHR Area Cooler Fans Revealed Overload for RHR Pump Area Cooler Fan 3A Was Set Too High. Cause Unstated.Relay Replaced + (ML19338D706)
- ML19338D707 + (ML19338D707)
- 05000346/LER-1980-064-03, /03L-0:on 800822,station Experienced Loss of Essential Instrument Ac Panel Y2.Caused by Failure of YV-2 Inverter Output Fuse.No Cause Determined for Fuse Failure. Failed Fuse Replaced + (ML19338D709)
- 05000346/LER-1980-062, Forwards LER 80-062/03L-0 + (ML19338D712)
- ML19338D713 + (ML19338D713)
- ML19338D715 + (ML19338D715)
- 05000346/LER-1980-062-03, /03L-0:on 800903,while Performing Walkdown Per IE Bulletin 80-11,discovered That Protective Curbs Had Not Been Provided Around One of Pipe Chases in Mechanical Room 3 & 4.Caused by Ae Error.Curbs Will Be Added + (ML19338D716)
- 05000317/LER-1980-045, Forwards LER 80-045/03L-0 + (ML19338D717)
- ML19338D718 + (ML19338D718)
- ML19338D719 + (ML19338D719)
- ML19338D721 + (ML19338D721)
- ML19338D722 + (ML19338D722)
- 05000317/LER-1980-045-03, /03L-0:on 800820,computer Indication Failed Except for Control Element Assembly Position Indication.Caused by Loose Wire Connectors at Several Edge Connector Pins for Analog Bus Segmentation Cards.Connectors Soldered in Plac + (ML19338D724)
- ML19338D725 + (ML19338D725)
- ML19338D726 + (ML19338D726)
- ML19338D727 + (ML19338D727)
- ML19338D728 + (ML19338D728)
- 05000304/LER-1980-003-03, /03L-0:on 800816,MSIV Low Pressure Annunciator Alarmed & Oil Pump Would Not Run.Caused by Failed Control Power Transformer.Transformer Replaced + (ML19338D729)
- 05000368/LER-1980-068, Forwards LER 80-068/03L-0 + (ML19338D730)
- ML19338D731 + (ML19338D731)
- 05000259/LER-1980-063, Forwards LER 80-063/03L-0 + (ML19338D732)
- ML19338D733 + (ML19338D733)
- ML19338D735 + (ML19338D735)
- 05000325/LER-1980-067, Forwards LER 80-067/03L-0 + (ML19338D736)
- ML19338D737 + (ML19338D737)
- 05000348/LER-1980-049, Forwards LER 80-049/03L-0 + (ML19338D738)
- ML19338D739 + (ML19338D739)
- ML19338D740 + (ML19338D740)
- 05000368/LER-1980-068-03, /03L-0:on 800823,during Mode 1,leak Was Discovered on B Charging pump,2P36B,discharge Header at Discharge Relief Valve Pipe.Apparent Cause Is Vibration Induced from Positive Displacement Pumps.Mods Made to All Three Pumps + (ML19338D741)
- 05000259/LER-1980-063-03, /03L-0:on 800820,during Normal operation,CAM-1-RH- 90-251 for Turbine Bldg Roof Vent Removed from Svc for Period Exceeding 1-h Due to Failure of Schwitzer Series 325 Model 145473 Vacuum Pump.Pump Replaced + (ML19338D742)
- 05000259/LER-1980-064, Forwards LER 80-064/03L-0 + (ML19338D744)
- ML19338D745 + (ML19338D745)
- 05000325/LER-1980-067-03, /03L-0:on 800822,while Withdrawing Control Rods During Startup,Erroneous Rod Blocks Were Received from Rod Worth Minimizer.Also,Plant Process Computer Printed Notch Errors While None Existed.Cause Not Determined + (ML19338D746)
- 05000325/LER-1980-063, Forwards LER 80-063/03L-0 + (ML19338D747)
- ML19338D749 + (ML19338D749)
- 05000324/LER-1980-050, Forwards LER 80-050/03L-0 + (ML19338D750)
- ML19338D751 + (ML19338D751)
- ML19338D752 + (ML19338D752)
- 05000348/LER-1980-048, Forwards LER 80-048/03L-0 + (ML19338D753)
- ML19338D754 + (ML19338D754)
- ML19338D755 + (ML19338D755)
- ML19338D757 + (ML19338D757)
- 05000324/LER-1980-050-03, /03L-0:on 800821,switch 2 of 2-B21-PIS-N021B, Barton Model 288 Found Out of Calibr.Probably Caused by Accidental Bumping by Personnel During Refueling Outage. Switch & Instrument Recalibr & Returned to Svc + (ML19338D758)
- 05000259/LER-1980-064-03, /03L-0:on 800820,during Normal operation,CAM-1- RM-90-249 for Turbine Bldg Roof Vents Removed from Svc for Period Exceeding 1-h.Caused by Personnel Error.Personnel Cautioned to Observe Time Limit + (ML19338D759)
- 05000348/LER-1980-048-03, /03L-0:on 800817,containment Atmosphere Gaseous & Particulate Radioactivity Monitoring Sys Were Declared Inoperable Due to Pump Failure & Pump Trip on Low Flow. Caused by Pump Burnout & Sys Flow Maladjustment + (ML19338D760)
- ML19338D762 + (ML19338D762)
- 05000293/LER-1980-057, Forwards LER 80-057/03L-0 + (ML19338D764)