- 05000219/LER-1979-040, Forwards LER 79-040/03L-0 + (ML19260B144)
- ML19260B145 + (ML19260B145)
- ML19260B146 + (ML19260B146)
- ML19260B147 + (ML19260B147)
- ML19260B148 + (ML19260B148)
- ML19260B149 + (ML19260B149)
- 05000219/LER-1979-040-03, /03L-0:on 791102,NRC Audit Noted Standby Gas Treatment Sys Charcoal Filters Not Tested Per Tech Spec. Caused by Not Including Methyl Iodide Removal Efficiency Test on Master Test Schedule & in-plant Procedure + (ML19260B150)
- ML19260B152 + (ML19260B152)
- ML19260B153 + (ML19260B153)
- ML19260B155 + (ML19260B155)
- 05000219/LER-1979-037, Forwards LER 79-037/03L-0 + (ML19260B156)
- ML19260B157 + (ML19260B157)
- ML19260B158 + (ML19260B158)
- 05000219/LER-1979-037-03, /03L-0:on 791103,during Monthly Surveillance Test, Core Spray Booster Pump NZ03B Failed to Start.Pump Breaker Control Power Fuse Checked.Caused by Loose Fuse.Fuse Clip Tightness Checked & Fuse Replaced + (ML19260B159)
- ML19260B160 + (ML19260B160)
- 05000245/LER-1979-032, Forwards LER 79-032/03L-0 + (ML19260B161)
- 05000245/LER-1979-032-03, /03L-0:on 791106,during Routine Monthly Surveillance on Reactor Protection Sys Drywell Pressure Switches,Discovered Ps 2206-1621B & Ps 2206-1621C Tripped at Values Outside Tech Specs.Caused by Setpoint Drift + (ML19260B164)
- 05000277/LER-1979-047-03, /03L-0:on 791029,valves SV2671A & SV2671B Failed to Close During Surveillance Testing of Dioxide Analyzer Primary Containment Valves.Caused by Piston Binding in Valve Body.Valve Internals Rebuilt + (ML19260B165)
- 05000219/LER-1979-039, Forwards LER 79-039/03L-0 + (ML19260B166)
- ML19260B167 + (ML19260B167)
- ML19260B168 + (ML19260B168)
- ML19260B169 + (ML19260B169)
- 05000219/LER-1979-038, Forwards LER 79-038/03L-0 + (ML19260B170)
- ML19260B171 + (ML19260B171)
- ML19260B172 + (ML19260B172)
- ML19260B173 + (ML19260B173)
- 05000219/LER-1979-039-03, /03L-0:on 791105,while Performing Average Power Range Monitor Surveillance Test & calibr,100% Flow Rod Block Setpoint on Channel 1 Found to Be 107% of Rated Neutron Flux.Caused by Instrument Drift.Channel 1 Readjusted + (ML19260B174)
- 05000219/LER-1979-038-03, /03L-0:on 791105,diesel Generator 1 Failed to Start During Diesel Generator 20% Plus Load Test.Caused by Component Failure.Breaker Position Switch Readjusted + (ML19260B175)
- ML19260B176 + (ML19260B176)
- ML19260B177 + (ML19260B177)
- ML19260B178 + (ML19260B178)
- ML19260B179 + (ML19260B179)
- 05000336/LER-1979-034, Forwards LER 79-034/03L-0 + (ML19260B180)
- ML19260B181 + (ML19260B181)
- ML19260B182 + (ML19260B182)
- 05000336/LER-1979-036-03, /03L-0:on 791101,during Cold Shutdown,Containment Personnel Air Lock Inner & Outer Doors Opened at Same Time for 30-s.Caused by Bent Operating Shaft.Shaft Straigtened & Lock Operable + (ML19260B183)
- 05000338/LER-1979-152-01, /01T-0:on 791116,nonconservatism Found in Error Analysis of Nuclear Instrumentation Reactor Rate Trip Circuit.Caused by Improper Treatment of Factors Affecting Accuracy of Reactor Protection Rate Trip Circuitry + (ML19260B184)
- ML19260B185 + (ML19260B185)
- 05000338/LER-1979-153-01, /01T-0:on 791116,nonconservatism Found in Method Used to Generate Power Distributions & Rod Worths for Dropped Rod Events.Caused by Improper Analysis of Reactivity Distributions & Rod Worths + (ML19260B186)
- 05000293/LER-1979-042, Forwards LER 79-042/03L-0 + (ML19260B187)
- ML19260B188 + (ML19260B188)
- ML19260B191 + (ML19260B191)
- 05000293/LER-1979-042-03, /03L-0:on 791101,oxygen Analyzer Valves A0-5065- 10,12,15,16,17,23 & 26 Did Not Meet Primary Containment Isolation Timing Requirements.Caused by Faulty Position Indication Lights on A0-5045-12 & 15 + (ML19260B192)
- ML19260B193 + (ML19260B193)
- ML19260B195 + (ML19260B195)
- IR 05000546/1979007 + (ML19260B196)
- ML19260B198 + (ML19260B198)
- 05000285/LER-1979-021, Forwards LER 79-021/21L-0 + (ML19260B201)
- ML19260B202 + (ML19260B202)
- 05000338/LER-1979-145, Forwards LER 79-145/03L-0 + (ML19260B203)
- ML19260B204 + (ML19260B204)