Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML18085B081 + (ML18085B081)
- ML18085B086 + (ML18085B086)
- IR 05000272/1980033 + (ML18085B088)
- ML18085B090 + (ML18085B090)
- ML18085B093 + (ML18085B093)
- 05000272/LER-1981-007, Forwards LER 81-007/01X-1.Detailed Event Analysis Encl + (ML18085B094)
- ML18085B095 + (ML18085B095)
- 05000272/LER-1981-007-01, /01X-1:on 810119,throttling Valves 14SJ16,11SJ138, 12SJ138 & 13SJ138 Found Out of Position.Caused by Procedure Inadequacy & Personnel Error.Valves Moved to Correct Positions & Procedures Changed + (ML18085B096)
- ML18085B098 + (ML18085B098)
- 05000272/LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl + (ML18085B100)
- ML18085B101 + (ML18085B101)
- 05000272/LER-1981-021-03, /03L-0:on 810227,boric Acid Tanks 11 & 12 Declared Inoperable.Caused by Loss of Level Indication for Both Tanks Due to Sensing Lines Plugged W/Boric Acid. Transmitter Sensing Lines Cleaned + (ML18085B102)
- ML18085B108 + (ML18085B108)
- ML18085B109 + (ML18085B109)
- ML18085B110 + (ML18085B110)
- 05000272/LER-1978-073, Forwards LER 78-073/01X-1.Detailed Event Analysis Encl + (ML18085B116)
- ML18085B117 + (ML18085B117)
- 05000272/LER-1978-073-01, /01X-1:on 781127,loss of Vital Instrument Bus 1B de-energized RCP Breaker Open Relay in Solid State Protection Sys,Initiating Reactor Trip.Caused by Failure of Output Transformer in Supply Inverter + (ML18085B118)
- 05000272/LER-1980-063, Forwards LER 80-063/01X-1.Detailed Event Analysis Encl + (ML18085B119)
- ML18085B120 + (ML18085B120)
- 05000272/LER-1980-063-01, /01X-1:on 801208,found That Auxiliary Feedwater Pumps 11 & 12 Could Be Stopped from Control Console If Steam Generator Low Low Level Is Received During Safeguards Equipment Control Sys Operation.Caused by Design Error + (ML18085B121)
- 05000272/LER-1981-023, Forwards LER 81-023/03L-0.Detailed Event Analysis Encl + (ML18085B122)
- ML18085B123 + (ML18085B123)
- 05000272/LER-1981-023-03, /03L-0:on 810305,containment Air Lock Leak Rate Exceeded Tech Spec Limit During Surveillance Procedure at Elevation 100 Feet.Caused by Inner Door Seal Not Holding Pressure.Seals Repaired.Engineering Evaluation Request Encl + (ML18085B125)
- 05000272/LER-1980-056, Forwards LER 80-056/01X-2,replacing Previously Sent LER 80-56/01X-2.Detailed Event Analysis Encl + (ML18085B126)
- ML18085B127 + (ML18085B127)
- 05000272/LER-1980-056-01, /01X-2:on 801107,discovered That Discrepancy Exists Between Const Specs & Design Drawings for Masonry Block Wall in Auxiliary Bldg Elevation 122 Feet.Caused by Conflict Between Specs & Drawings for Walls + (ML18085B128)
- 05000272/LER-1981-017, Forwards LER 81-017/03L-0.Detailed Event Analysis Encl + (ML18085B129)
- ML18085B130 + (ML18085B130)
- 05000272/LER-1978-072, Forwards LER 78-072/01X-1.Detailed Event Analysis Encl + (ML18085B131)
- ML18085B132 + (ML18085B132)
- 05000272/LER-1981-017-03, /03L-0:on 810223,RHR Pump 12 Declared Inoperable to Perform Test Per IE Bulletin 81-01.Caused by Defective Snubber Due to Intermittent Seizing of Balls in Race from Internal Corrosion.Snubber Replaced + (ML18085B133)
- ML18085B135 + (ML18085B135)
- 05000272/LER-1978-072-01, /01X-1:on 781107,svc Water Isolation Valves to All Five Containment Fan Coil Units Found Tripped Closed.Caused by Design Deficiency in Installation of RMS Detectors for Containment Fan Coil Unit Svc Water.Detectors Shielded + (ML18085B136)
- ML18085B137 + (ML18085B137)
- ML18085B138 + (ML18085B138)
- ML18085B139 + (ML18085B139)
- 05000272/LER-1981-022, Forwards LER 81-022/03L-0.Detailed Event Analysis Encl + (ML18085B140)
- ML18085B141 + (ML18085B141)
- 05000272/LER-1981-022-03, /03L-0:on 810301,boric Acid Storage Sys Vol Fell Below Tech Spec Level.Caused by Rapidly Borated RCS Due to Failure to Two Control Rod Position Indicators,Following Reactor Trip.Batching Commenced & Vol Raised + (ML18085B143)
- ML18085B144 + (ML18085B144)
- ML18085B145 + (ML18085B145)
- ML18085B146 + (ML18085B146)
- IR 05000311/1981002 + (ML18085B148)
- PNO-I-81-039, on 810328,vibration of Low Pressure Turbine 13 Required Load Reduction & Subsequent Orderly Reactor Shutdown.Cause of Turbine Vibration Is Under Investigation + (ML18085B149)
- ML18085B150 + (ML18085B150)
- ML18085B153 + (ML18085B153)
- ML18085B154 + (ML18085B154)
- ML18085B155 + (ML18085B155)
- ML18085B157 + (ML18085B157)
- ML18085B167 + (ML18085B167)