ML20237H37514 August 1987NPDES Noncompliance Notification:Between 870726-0803 Temp Noncompliances Occurred in Plant Discharge Canal. Noncompliances Resulted from Unusually High River Temps & Continued Hot Weather Conditions
ML20205R77727 March 1987NPDES Noncompliance Notification:On 870319,water Above Daily Max Biological Oxygen Demand Limitations at 005 Discharge. Sys Stabilized by Pumping Cells Out & Increasing Wasting Activities
ML20207M9876 January 1987NPDES Noncompliance Notification:During 861216-870104. Difficulty Experienced W/Maintaining 004 Discharge in Compliance w/7.0 Ph Value.Caused by Increased Vol of Water Discharged to Settling Pond.Water Vol Restricted
ML20205H7924 August 1986NPDES Noncompliance Notification:On 860721,discharge of Ph at Discharge 004 Rated Above Daily Concentration Limits. Caused by Lack of Proper Surveillance to Splitter Box Ph by Station Personnel.Personnel Increased Surveillance
ML20212F3181 August 1986Updated NPDES Noncompliance Notification:On 860723,discharge of Ph Above Daily Concentration Limits Occurred.Results of Flow & Ph Sampling Listed
ML20212B37629 July 1986NPDES Noncompliance Notification:On 860602,while Draining Water Treatment Sludge Pond,Discharge Limitation Exceeded. Pond Drained & Cleaned & Temporary Diversion of Clearwell Overflow to 002 Discharge Discontinued
ML20207K86325 July 1986NPDES Noncompliance Notification:On 860723,discharge of Ph Above Daily Concentration Limitations Occurred.Caused by Inability of Acid Pumps to Control Ph of Water When Lime Feed Sys Malfunctioned.Lime Sys Repair Parts on Order
ML20137P96027 January 1986NPDES Noncompliance Notification:On 860116,biochemical Oxygen Demand Exceeded Limit.Caused by Lack of Proper Attention by Operators & Dumping of Floor Wax Matl Into Wastewater Treatment Sys.Surveillance of Sys Increased
ML20137B0936 January 1986NPDES Noncompliance Notification:On 851231,total Suspended Solids from Discharge Point 005 Analyzed at 1.85 Kg/Day & 98mg/l,exceeding Permit Levels.Caused by Variable Flows to Treatment Plant & Operator Errors
ML20137Z1752 December 1985NPDES Noncompliance Notification:On 851121,biochemical Oxygen Demand & Total Suspended Solid Noncompliances Occurred.Caused by Variable Flows to Treatment Plant & Operator Inattentiveness
ML20138J53418 October 1985NPDES Noncompliance Notification:On 851014,increased Flows & Flow Surges to Treatment Plant Occurred.Cause Not Stated
ML20133H98731 July 1985NPDES Noncompliance Notification:Test Results from 850716 Effluent Sample Indicated Limits Exceeded Per NPDES Discharge Permit.Cause & Corrective Actions Not Specified
ML20129H99428 May 1985NPDES Noncompliance Notification:On 850415,biochemical Oxygen Demand Exceeded Max 1.71 Kg/Day Limit.Caused by Addl People on Site as Result of Repiping & Refueling Outage & Flow Surges to Treatment Plant
ML20127M70110 May 1985NPDES Noncompliance Rept:During Apr,Water Samples for Fecal Coliform Counts Not Collected at 005 Discharge
ML20108C8441 March 1985NPDES Noncompliance Notification:Biochemical Oxygen Demand & Total Suspended Solid Noncompliance Occurred.Caused by Increased Flow to Treatment Plant & Inflated Calculated Discharge Due to Line Break in Potable Water Sys
ML20105B78225 January 1985NPDES Noncompliance Notification:On 850116,biochemical Oxygen Demand Exceeded Permit Limit.Caused by Flow Surges & Increased Flow Due to Addl Workers During Refueling
ML20104B68322 January 1985NPDES Noncompliance Notification:On 841219,total Daily Suspended Solids Found Above Limit.Caused by Problems W/Sewage Treatment Tanks & Increased Sewage Load.Load Limiting Effort UnderwayGrab sample