Semantic search
Jump to navigation
Jump to search
Issue date | Title | Topic | |
---|---|---|---|
ML20005D931 | 21 December 1989 | Special Rept:On 891122 & 1215,diesel Generator 0 Failed to Close,While Attempting to Parallel W/Offsite Power During Operability Surveillances.Caused by Defective Synchronizing Relay.Relay Replaced & Output Breaker Satisfactorily Tested | |
ML19327B762 | 2 November 1989 | Ro:On 890920 & 25 Detectors for Detection Zones 1-16 & 1-16P & Zones 1-17 & 1-17P,respectively,taken Out of Svc Due to Precaution to Prevent Spurious Zone Fire Alarms.Fire Watch Patrol Established During Time Detectors Inoperable | Fire Watch Hourly Fire Watch |
ML19325E522 | 27 October 1989 | Special Rept:On 891014,detection & Suppression Sys for Hot Lab Area Inoperable for Greater than 14-day Period Due to Local Detection Panel Not Resetting Properly.Root Cause Under Investigation & Expected for Completion by 891201 | Continuous fire watch |