 Issue dateTitleTopic
ML20005D93121 December 1989Special Rept:On 891122 & 1215,diesel Generator 0 Failed to Close,While Attempting to Parallel W/Offsite Power During Operability Surveillances.Caused by Defective Synchronizing Relay.Relay Replaced & Output Breaker Satisfactorily Tested
ML19327B7622 November 1989Ro:On 890920 & 25 Detectors for Detection Zones 1-16 & 1-16P & Zones 1-17 & 1-17P,respectively,taken Out of Svc Due to Precaution to Prevent Spurious Zone Fire Alarms.Fire Watch Patrol Established During Time Detectors InoperableFire Watch
Hourly Fire Watch
ML19325E52227 October 1989Special Rept:On 891014,detection & Suppression Sys for Hot Lab Area Inoperable for Greater than 14-day Period Due to Local Detection Panel Not Resetting Properly.Root Cause Under Investigation & Expected for Completion by 891201Continuous fire watch
ML20023D0301 July 1982Ro:Fire Dampers Supplied by American Warming & Ventilation, Inc Declared Inoperative.Caused by Discrepancy in Fuse Link Assembly Size.Fuse Assemblies Will Be Replaced.Jv Winkle Ltr Re News Telecast & J Dierbeck Note Encl