10 CFR 50, Appendix E

- Progress Energy Senal: RNP-RA/05-0110 NOV 1 I 2005 United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 DOCKET NO. 50-261/LICENSE NO. DPR-23 EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGES Ladies and Gentlemen:

In accordance with 10 CFR 50, Appendix E, Section VI, Carolina Power and Light Company, also known as Progress Energy Carolinas, Inc., is transmitting revisions to the H. B. Robinson Steam Electric Plant (HBRSEP), Unit No. 2, Emergency Response Data System (ERDS) Data Point Library.

The changes result from the replacement of the plant vent wide range airborne radioactivity monitoring system. The specific changes are:

  • Data point RMROOS1A (vent particulate) is deleted.
  • Data point RMROO5OA (vent iodine) is deleted.
  • Data point RMR0049A (vent noble gas lo), data point RMR0045A (vent noble gas midX and data point RMR0046A (vent noble gas hi) have been revised to increase the maximum range to 0. IE+08 cpm, and the Alarm/Trip Setpoints have been changed to reflect that the alarm setpoint is variable based on the latest calculation and monitor background.

The revised Data Point Reference File Sheets are attached.

If you have any questions concerning this matter, please contact me at (843) 857-1253.

Sincerely, C. T. Baucoi Supervisor - Licensing/Regulatory Programs Progress Energy Carolinas. Inc.

Robinson Nuclear Plant 3581 West Entrance Road Hartsville, SC 29550

United States Nuclear Regulatory Commission Serial: RNP-RA/05-0110 Page 2 of 2 RAC/rac Attachment C: Dr. William D. Travers, NRC, Region II NRC Resident Inspector, HBRSEP (w/o Attachment)

C. P. Patel, NRC, NRR (w/o Attachment)

United States Nuclear Regulatory Commission Attachment to Serial: RNP-RA/05-01 10 6 pages including cover page H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 REVISED DATA POINT REFERENCE F[LE SHEETS

DATA POINT REFERENCE FILE Data Point RMROO51A Deleted November 2005 (43)

DATA POINT REFERENCE FILE Data Point RMROO5OA Deleted November 2005 (44)

DATA POINT REFERENCE FILE Date: NOVEMBER 2005 Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: RMR0049A Plant Specific Point

Description:

R-14C PLT VENT EFL NOBLE GAS LO Generic/Condition

Description:

RADIOACTIVITY OF RELEASED GASES AnaloglDigital: A Engineering Units/Digital States: CPM Engineering Units Conversion: N/A Minimum Instrument Range: 0.100E+02 Maximum Instrument Range: 0.100E+08 I Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm/Trip Set Points: SEE UNIQUE SYSTEM DESCRIPTION NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System

Description:

ALARM SETPOINT IS VARIABLE BASED ON THE LATEST CALCULATION AND MONITOR BACKGROUND (45)

DATA POINT REFERENCE FILE Date: NOVEMBER 2005 Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: RMR0045A Plant Specific Point

Description:

R-14D PLT VENT EFL NOBLE GAS MID Generic/Condition

Description:

RADIOACTIVITY OF RELEASED GASES Analog/Digital: A Engineering Units/Digital States: CPM Engineering Units Conversion: N/A Minimum Instrument Range: 0. 100E+02 Maximum Instrument Range: 0. 100E+08 I

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm/Trip Set Points: SEE UNIQUE SYSTEM DESCRIPTION I

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System

Description:

ALARM SETPOINT IS VARIABLE BASED ON THE LATEST CALCULATION AND MONITOR BACKGROUND (46)

DATA POINT REFERENCE FILE Date: NOVEMBER 2005 Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: RMR0046A Plant Specific Point

Description:

R-14A PLT VENT EFL NOBLE GAS HI Generic/Condition

Description:

RADIOACTIVITY OF RELEASED GASES Analog/Digital: A Engineering Units/Digital States: CPM Engineering Units Conversion: N/A Minimum Instrument Range: 0.100E+02 Maximum Instrument Range: 0.100E+08 I Zero Point

Reference:

N/A Reference Point Notes: N/A PROC of SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm/Trip Set Points: SEE UNIQUE SYSTEM DESCRIPTION I NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System

Description:

ALARM SETPOINT IS VARIABLE BASED ON THE LATEST CALCULATION AND MONITOR BACKGROUND (47)