ML24292A032
| ML24292A032 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde (NPF-074) |
| Issue date: | 10/17/2024 |
| From: | Dilorenzo M Arizona Public Service Co |
| To: | Office of Nuclear Reactor Regulation, Document Control Desk |
| References | |
| 102-08876-MDD/CJS | |
| Download: ML24292A032 (1) | |
Text
Technical Specification 5.6.8 A member of the STARS Alliance, LLC Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek Palo Verde Nuclear Generating Station 5871 S. Wintersburg Road Tonopah, AZ 85354 Mail Station 7636 Tel 623.393.5753 102-08876-MDD/CJS October 17, 2023 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Palo Verde Nuclear Generating Station Unit 3 Docket No. STN 50-530 Renewed Operating License No. NPF-74 24th Refueling Outage Steam Generator Tube Inspection Report Attached please find the Palo Verde Nuclear Generating Station (PVNGS) Unit 3 Steam Generator Tube Inspection Report prepared and submitted by Arizona Public Service Company pursuant to Technical Specification Reporting Requirement 5.6.8. This report describes steam generator tube inspection and plugging results from the Unit 3 twenty-fourth refueling outage that entered Mode 4 on May 8, 2024.
By copy of this letter, this submittal is being provided to the Nuclear Regulatory Commission (NRC) Region IV Administrator and the PVNGS Senior Resident Inspector.
No commitments are being made to the NRC by this letter.
Should you need further information regarding this submittal, please contact me at (623) 393-3495.
Sincerely, Michael D. DiLorenzo, Department Leader Nuclear Regulatory Affairs - Licensing MDD/CJS/cr
Enclosure:
Unit 3 - 24th Refueling Outage Steam Generator Tube Inspection Report cc:
J. D. Monninger NRC Region IV Regional Administrator W. T. Orders NRC NRR Project Manager for PVNGS L. N. Merker NRC Senior Resident Inspector for PVNGS Dilorenzo, Michael D(Z99838)
Digitally signed by Dilorenzo, Michael D(Z99838)
Date: 2024.10.17 22:38:33 -07'00'
Enclosure Unit 3 - 24th Refueling Outage Steam Generator Tube Inspection Report
UNIT 3 U3R24 ARIZONA PUBLIC SERVICE P. O. BOX 52034 PHOENIX, AZ 85072 Prepared by: Rachael Harley-Martin 9/18/24 Reviewed by:
Approved by:
Commercial Service Date: 1-8-88 Harley Martin, Rachael J(Z09624)
Digitally signed by Harley Martin, Rachael J(Z09624)
Date: 2024.10.03 08:31:57
-07'00' Toone, Spencer (Z07074)
Digitally signed by Toone, Spencer (Z07074)
Date: 2024.10.03 09:27:26 -07'00' Bolf, Boris B(Z99978)
Digitally signed by Bolf, Boris B(Z99978)
Date: 2024.10.03 15:46:31 -07'00'
Table of Contents 1.0
SUMMARY
2.0 SCOPE OF EXAMINATIONS PERFORMED 3.0 ACTIVE DEGRADATION MECHANISMS 4.0 NDE TECHNIQUES UTILIZED 5.0 INDICATION
SUMMARY
6.0 TUBES PLUGGED 7.0 PLUG HISTORY 8.0 CONDITION MONITORING APPENDIX A - TUBE SUPPORT DIAGRAM, LEGEND, and ANALYSIS CODES APPENDIX B - SG 31
SUMMARY
DATA SHEETS APPENDIX C - SG 32
SUMMARY
DATA SHEETS APPENDIX D - PLI and PLP DATA SHEETS APPENDIX E - PLUG MAPS APPENDIX F - FORM NIS - 1
UNIT 3 STEAM GENERATOR EDDY CURRENT U3R24 Refueling Outage 1.0 Summary This report is intended to satisfy the requirements of PVGS Technical Specifications 5.6.8 for the submittal of a Steam Generator Tube Inspection Report. The steam generator (SG) eddy current examination for the 24th refueling outage in Unit 3 (U3R24) was conducted during April 2024.
Mode 4 entry was on May 8, 2024. The initial examination plan for both steam generators is listed in Table 1. This table summarizes the examinations performed for each of the various categories, examination types, extents, and the number of tubes or tube locations completed. This examination was a 100% full length tubing inspection.
The examinations resulted in a total of 5 tubes being plugged in SG 31, and 8 tubes being plugged in SG 32. A description of the previous plugging history for these replacement steam generators is contained in Appendix E.
2.0 Scope of Examinations Performed The original examination plan was developed based on the Palo Verde Generating Station U3R24 Steam Generator Inspection Degradation Assessment (Intertek document number AIM 240211390-2Q-1, Revision 1 dated April 11, 2024). This document was developed per PVGS Procedure 81DP-9RC01 as required by NEI 97-06. In addition, possible damage mechanisms were reviewed along with the specific requirements set forth in Procedure 73TI-9RC01 and the PVGS Technical Specifications.
This original plan, along with the examinations performed as a result of bobbin indications noted, is summarized in Table 1 of this report.
3.0 Active Degradation Mechanisms The only degradation noted during the examinations was determined to be wear. Section 8.0 contains further discussions relating to this mechanism. Table 2 summarizes the results into categories and Appendix B and C itemizes all indications reported.
4.0 NDE Techniques Utilized The following table documents the site validated and qualified techniques utilized during this outage:
BOBBIN Examinations Damage Mechanism Location ETSS NO QUAL STATUS Extended Applicability BC DET BC SIZE TECH Comment Wear BWs, VSs, ECs (not dented) 96004.1 R14 SITE VALIDATED Tube Proximity Y
Y Volt DIFF Note Wear Loose Part 27091.2 R2 QUALIFIED Tubesheet Transition Y
N Volt DIFF Note ARRAY Examinations Damage Mechanism Location ETSS NO QUAL STATUS Extended Applicability DET SIZE TECH Comment Wear BWs, ECs, VSs 11956.3 R2 11956.4 R2 QUALIFIED Wear at Dented Supports Y
Y X-Probe Note The U3R24 Degradation Assessment and associated site validation provides details for the qualification and use of the above techniques The eddy current examinations were performed by Westinghouse Electric Company using the Core Star OMNI 200 eddy current instrument. Westinghouse Anser software was utilized to acquire the data along with the Pegasys robotic manipulator. This robot was configured with a dual guide tube in each of the hot and cold legs.
The tubing was examined with Core Star manufactured bobbin coil probes and Zetec array style probes. The probe diameter utilized for all bobbin examinations was 0.610. Array probes were used for the characterization of non-quantifiable or distorted bobbin indications as well as to provide length measurements for wear.
Fiber optic cable was used from containment to the data acquisition room located at the PVGS North Annex. Primary and Secondary analysis, the Primary and Secondary Resolution Analysts, Independent Review Analysts, and Data Management were located at the Westinghouse Waltz Mill facility in Pennsylvania. Westinghouse provided the data acquisition and primary data analysis.
Anatec provided the secondary data analysis and the independent quality data analysis.
Each individual from Westinghouse and Anatec who performed data analysis was required to complete and pass a PVGS site specific Eddy Current Data Analysis Course as well as an associated performance and written examination. All individuals performing data analysis were also required
to have Qualified Data Analyst (QDA) certification. Per 73TI-9RC01, all certification records are maintained in the Nuclear Information Records Management System.
5.0 Indication Summary A detailed listing of the location and measured sizes of all service induced indications recorded is included in Appendix B and C. A summary of these indication results is located in Table 2. In addition, Appendix A contains a reference drawing of steam generator support locations and report legend.
Appendix D contains a listing of the possible loose part (PLP) indications that were confirmed with an array examination. Note Section 8.0 for further discussion on the PLPs.
There were no indications that were identified as linear during this outage.
6.0 Tubes Plugged A summary of the tubes plugged is located in Table 2. Appendix E contains a map that details the plugged tube location along with the previously plugged tubes.
7.0 Plug History A summary of the number and percentage of tubes plugged is also located in Table 2.
8.0 Condition Monitoring Tube Inspection Summary Per the Steam Generator Program, as defined in PVGS Procedure 81DP-9RC01, a condition monitoring evaluation was conducted by PVGS Engineering. The results of the eddy current examinations are provided in Section 5.0. An engineering evaluation of the as-found condition of inservice tubes did not reveal any degradation exceeding the threshold values for structural and leakage integrity. As such, all steam generator performance criteria were satisfied for Unit 3 Cycles 23 and 24. No tube pulls or in-situ pressure testing were required based on the results of the examinations.
Chemical Cleaning and Sludge Lancing A chemical cleaning was performed in both SGs during U3R24. The Framatome DMT process was utilized. A total of 7056 lbs. of material (predominantly iron with a small amount of copper) was removed from both SGs combined. This amount does not include the sludge removed from sludge lancing. Sludge Lancing was performed in 3R24 in SG 31 and SG 32. A total of 387 lbs. of sludge was removed from SG 31 and a total of 556 lbs. of sludge was removed from SG 32. These amounts were as expected compared to the previous campaigns in Unit 1 (2022) and Unit 2 (2023).
The sludge lancing system grit screen was inspected post sludge lancing in both steam generators. The captured screen debris was primarily composed of small, broken, and tumbled fragments of sludge rocks, non-metallic gaskets, and scale. Only two instances of metal objects were noted. The items were of insignificant size as they are too small to become caught against a tube and wear due to flow-induced fretting; thus, they do not pose a threat to steam generator tube
integrity. These two rounded metallic items observed were likely fine weld spatter that were carried downstream from feedwater system repairs.
Foreign Object Search and Retrieval (FOSAR)
FOSAR was performed at the tubesheet elevation in the annulus region and the blowdown lane. The applicable requirements of Revision 5 of the EPRI Steam Generator Integrity Assessment Guidelines Section 10.3, Foreign Object Search and Retrieval, were applied for the FOSAR inspections.
PVGS uses any combination of the following 2 methods to inspect the Flow Distribution Plate (FDP) area:
- 1. Use ECT to detect the presence of foreign objects or foreign object wear (virtual method)
- 2. Perform a physical FOSAR, utilizing either the FDP robot or guide tubes with video probes.
Due to the uncertainties introduced by the settling of chemical cleaning deposits on the FDP, both the ECT (virtual) and physical FOSAR methods were planned in the FDP area for 3R24. Visual FOSAR was attempted using guide tubes and video probes, but with limited success. The amount of deposits that had settled on the FDP post chemical cleaning had precluded the performance of an adequate visual inspection. A previous evaluation had been prepared to evaluate the impact of not performing the visual FDP FOSAR, but rely solely on eddy current results, and assess how it would impact the Steam Generator Tube Integrity. As part of the evaluation, a Data Union Study was prepared by Westinghouse. The study validated that the bobbin probe is capable of detecting a potential loose part in the FDP sludge pile region. Eddy current monitoring of the FDP area in SG31 and SG32 during U3R24 identified one instance of a foreign object with foreign object wear in SG32, so further investigation of the area was performed. The results are discussed in section SG32 - Foreign Object Summary.
The only existing degradation method noted during the 3R24 refueling outage was wear. Following is a summary of the metallic foreign objects that were identified in each SG. Sludge rocks and graphite are not discussed, since they are not considered as a threat to tube integrity.
SG31 -Foreign Object Summary One piece of wire-like material was retrieved from the cold leg (CL) tubesheet by tube R151C55.
The object was approximately 1.25 long and 1/16 diameter. There was no wear identified by bobbin testing attributed to this object. Additionally, the item held no signs of recent wear and no signs of recently broken pieces that might remain within the SG.
A stiff wire bristle was retrieved from the cold leg tubesheet by tube R171C87. The wire was approximately 1.875 long and 1/32 diameter. There was no wear identified by bobbin testing attributed to this object. Additionally, the item held no signs of recent wear and no signs of recently broken pieces that might remain within the SG.
SG32 -Foreign Object Summary FOSAR activities did not identify any foreign objects at the top of tubesheet in SG32.
There was one foreign object identified by eddy current in SG 32 just above the flow distribution plate. The object was called as a Potential Loose Part with Indication, or PLI at cold leg location R160C89. The PLI call was new and had not existed at this location previously. Historically, the loose part had been contacting this tube in both 3R20 and 3R22 inspections. Wear noted during the 3R24 inspection at location R160C89 did not exist during the previous 3R22 inspection. The adjacent tubes R158C89, R157C90, and R159C90 also had PLP calls, though no wear existed at these locations. This item was not able to be retrieved, so it was decided to conservatively plug all adjacent tubes that were in contact with the object, even though only one tube had experienced
wear. All four of the plugged tubes were stabilized to preclude any future undetected through-tube wear that could impact surrounding tubes.
Potential Loose Parts (PLP) Summary With the exception of the item discussed in the paragraph above (SG32 - Foreign Object Summary), all other PLP signals detected by eddy current were resolved by FOSAR and historical reviews.
Blowdown Patch Plate Weld Inspection Summary Also included in the scope of the FOSAR effort was an inspection of the blowdown patch plate welds in SG31 and SG32. These same welds in the Unit 2 replacement steam generators were originally found to be cracked during 2R15 secondary inspections. Subsequently, inspection activities monitor these same cracked weld conditions in all 3 units during each secondary inspections to confirm that the weld material in the vicinity of the cracked weld on all 4 patch plates (2 per SG) is intact, and a loose parts concern is not being created. A previous evaluation concluded that, with the presence of the cracked welds, the patch plates in the Unit 3 SGs will continue to perform their design function and that the probability of loose parts being formed is remote. Thus, there is a very low risk that the cracked welds will affect the structural or leakage integrity of tubes in these steam generators.
Upper Internals Inspection No Upper Internals Inspections were performed in 3R24. The next scheduled inspections will occur in 3R26 (Spring of 2026). It should be noted that a camera was inserted into the central cavity region above the stay cylinder in 3R24 to visually assess general conditions. This visual inspection was performed after chemical cleaning. No anomalies were noted as a result of this general visual inspection.
Plug Inspections Summary The EPRI PWR Steam Generator Examination Guidelines require that a visual inspection of the previously installed steam generator plugs be performed to assess plug integrity. Additionally, the Examination Guidelines require a verification of the location and presence of existing in-service plugs. The conduct of the plug location and integrity verification was performed in 3R24 per the applicable procedure. A review of the inspection results indicated that all plugs were accounted for, and no evidence of potential plug leakage was identified.
Channel Head Inspection Summary A channel head inspection was also performed in response to Westinghouse Engineering Nuclear Safety Advisory Letter (NSAL) 12-1, dated January 5, 2012. The inspection identified no degradation. In addition, a general visual examination was performed of the primary side tube-to-tubesheet welds looking for evidence of crackingDVUHTXLUHGSHU/LFHQVH5HQHZDO&RPPLWPHQW
. All examination results were satisfactory with no anomalies detected.
TABLE 1 EXAMINATION
SUMMARY
SCOPE DESCRIPTION SG 31 SG 32 Exam Description Extents Scope Scope FULL LENGTH BOBBIN TEC-TEH 12442 12440 HOT LEG ARRAY VARIOUS 238 156 COLD LEG ARRAY VARIOUS 156 173 U-BEND
+Point 7H-3.0 - VS3+3.00 0
1 COLD LEG
+Point FDP-3.00 - FDP+3.00 0
6 Notes:
ARRAY probe technology utilized the X-Probe'
TABLE 2 INDICATION
SUMMARY
DAMAGE MECHANISM STEAM GENERATOR 31 STEAM GENERATOR 32 Tubes Indications BW VS EC Tubes Indications BW VS EC WEAR 1% - 19%
20% - 29%
30% - 39%
> 40%
PLUGGED 1368 109 10 0
(4) 1569 116 10 0
517 44 2
0 784 68 8
0 268 4
0 0
1512 91 3
0 (4) 1720 94 3
0 421 31 0
0 1008 51 3
0 291 12 0
0 Possible Loose Parts (Array Probe)
PLI & SVI W/PLP HISTORICAL PLP NEW PLP PLUGGED 0
6 4
(0) 1 1
3 (4)
PREVENTATIVE (1)
(0)
PLUGGED (5)
(8)
TOTAL PLUGGED /
( 143 / 1.14 % )
( 148 / 1.18% )
NOTES:
- 1. Numbers in (X) are tubes numbers plugged in each category
- 2. The Tubes column above represents Bobbin Coil results for the number of tubes; using the largest wear indication
- 3. The Indications column above represents Bobbin Coil results for the number of wear indications LEGEND:
BW - batwing VS - vertical strap EC - eggcrate
APPENDIX A TUBE SUPPORT DIAGRAM, LEGEND, and ANALYSIS CODES
PVGS Steam Generator REPLACEMENTS VS1 VS3 VS4 VS2 VS5 07H 06H 05H 04H 03H 02H 01H Inlet Outlet 09C 07C 06C 05C 04C 03C 02C FDP 20 36.33 36.33 36.34 35.95 35.95 35.95 16.5 24 28.125 32.25 26 Typical Spacing Center of 08H to 08C Row 1 - 17.415 Row 2 - 19.736 Row 3 - 22.056 Row 4 - 24.377 Row 5 - 26.698 Row 6 - 29.019 28.125 01C 08H 08C 35.95 36.75 09H 36.75 10C 36.75 11C BW2 BW1 11H 10H 25 + 0.25 clad
LEGEND ROW:
Indicates the row number of a given tube.
COL:
Indicates the column number of a given tube.
VOLTS:
Indicates the peak-to-peak voltage of a given indication response.
DEG:
The measured phase angle of a given indication response.
IND:
Indicates the analysis code or PCT for percent PER or PCT:
The percent through the tube wall of a given indication CRLEN:
Indicates the flaw length, used to identify the length of a wear indication CHN:
Indicates the channel used to make the call LOCN:
Gives indication location at INCH1 to INCH2 relative to known landmarks such as supports, vertical straps, and batwings. Typical location codes are as follows:
- 1 Vertical Strap................................VS1
- 1 Batwing.........................................BW1
- 1 Support Plate in Hot Leg...............01H
- 7 Support Plate in Cold Leg.............07C Top Tube Sheet Cold Leg..................TSC Tube End Hot Leg..............................TEH Tube End Cold Leg............................TEC BEGT and ENDT:
Indicates the beginning and of the test; together they document the examination extent PDIA:
Documents the probe diameter PTYPE:
Documents the probe type CAL:
Indicates calibration number L:
Indicates the leg the examination was conducted from IDX:
This comment field is utilized to document comments UTIL1 & 2: Utility columns to support administrative notes
Analysis CODES:
Absolute Drift.................................................................... ADI Bulge.................................................................................. BLG Dented Buff Mark.............................................................. DBM Deposit............................................................................... DEP Dent.................................................................................... DNT Data Quality Acceptance.................................................... DQA Distorted Support Signal With Indication.......................... DSI Distorted Top of Tubesheet With Indication...................... DTI Geometric Indication.......................................................... GEO ID Chatter........................................................................... IDC Indication Not Found......................................................... INF Indication Not Reportable.................................................. INR Large Noise Indication.LNI Multiple Axial Indication................................................... MAI Manufacturer Burnishing Mark.......................................... MBM Mixed Mode Indication...................................................... MMI Multiple Circumferential Indication................................... MCI Multiple Volumetric Indication.......................................... MVI No Detectable Defect......................................................... NDD No Discontinuity Found..................................................... NDF Non-Quantifiable Indication.............................................. NQI No Tube Sheet Expansion.................................................. NTE Obstructed.......................................................................... OBS Over Expanded................................................................... OXP Previous Array Call.PAC Previous Bobbin Call......................................................... PBC Percent.PCT Possible Deposit................................................................. PDP Positive Identification........................................................ PID Positive Identification Verified.......................................... PIV Possible Loose Part with Indication................................... PLI Possible Loose Part............................................................ PLP Previous RC Call................................................................ PRC Proximity.....PRX Possible Support Anomaly................................................. PSA Possible Support Indication................................................ PSI Permeability Variation Noise............................................. PVN Retest Bad Data.................................................................. RBD Retest Identification Check................................................ RIC Retest with Magnetic Bias RC Probe................................. RMB Single Axial Indication...................................................... SAI Single Circumferential Indication...................................... SCI Single Volumetric Indication............................................. SVI Senior (Lead) Analysis Review.......................................... SR Sludge................................................................................ SLG To Be Plugged.................................................................... TBP Volumetric Indication........................................................ VOL Wear.WAR
APPENDIX B STEAM GENERATOR 31
SUMMARY
DATA SHEETS
U3R24 PVGS SG31 All Data Page 1 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 23 2
3.01 179 DNT P1 08C 1.38 TEH TEC 0.61 CBAY2 34 C
165 31 23 2
NDF P14 08C 1.35 VS3 TEC 0.61 NYAX2 266 C
56 31 23 2
NDF 94 08C 4
VS3 TEC 0.61 NYAX2 266 C
56 31 23 2
NDF 91 08C 8.01 VS3 TEC 0.61 NYAX2 266 C
56 31 23 2
NDF 91 08C 8.68 VS3 TEC 0.61 NYAX2 266 C
56 31 23 2
NDF 30 07C 18.73 VS3 TEC 0.61 NYAX2 266 C
56 31 32 3
3.1 178 DNT P1 VS3 0.03 TEH TEC 0.61 CBAY2 34 C
158 31 32 3
NDF P27 VS3 0.03 VS3 TEH 0.61 NYAX2 67 H
40 31 36 3
3.66 178 DNT P1 VS3
-0.16 TEH TEC 0.61 CBAY2 34 C
160 31 36 3
NDF P28 VS3
-0.16 VS3 TEH 0.61 NYAX2 67 H
39 31 54 11 0.36 60 PCT 13 P2 09H 0.8 TEH TEC 0.61 CBAY2 26 C
180 31 51 12 0.3 98 PCT 11 P2 09H 0.79 TEH TEC 0.61 CBAY2 34 C
19 31 19 14 0.35 74 PCT 11 P2 VS3
-0.12 TEH TEC 0.61 CBAY2 4
C 33 31 63 14 4.06 178 DNT P1 08H 7.77 TEH TEC 0.61 CBAY2 26 C
151 31 58 15 0.42 29 PCT 11 P2 09H 0.82 TEH TEC 0.61 CBAY2 4
C 68 31 51 16 0.4 100 PCT 12 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 28 C
159 31 83 16 0.52 87 PCT 15 P2 VS4 0.83 TEH TEC 0.61 CBAY2 28 C
143 31 83 16 0.34 64 PCT 11 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 28 C
143 31 76 17 0.34 117 PCT 11 P2 VS2 0.59 TEH TEC 0.61 CBAY2 36 C
40 31 55 18 0.25 143 PCT 10 P2 BW1
-1.61 TEH TEC 0.61 CBAY2 26 C
128 31 75 18 0.5 92 PCT 16 P2 VS2
-0.69 TEH TEC 0.61 CBAY2 26 C
138 31 81 18 0.22 120 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 55 H
10 31 80 19 0.53 115 PCT 19 P2 VS2 0.78 TEC TEH 0.61 CBAY2 55 H
11 31 90 19 0.46 123 PCT 17 P2 VS4
-0.7 TEC TEH 0.61 CBAY2 55 H
15 31 85 20 0.27 91 PCT 12 P2 VS4 0.82 TEC TEH 0.61 CBAY2 55 H
21 31 99 20 0.21 99 PCT 10 P2 BW1 1.02 TEC TEH 0.61 CBAY2 55 H
178 31 96 21 0.23 131 PCT 11 P2 VS2
-0.88 TEC TEH 0.61 CBAY2 55 H
28 31 75 22 0.31 123 PCT 12 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 26 C
67 31 83 22 0.34 130 PCT 13 P2 VS4
-0.61 TEH TEC 0.61 CBAY2 64 C
167 31 87 22 0.28 125 PCT 11 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 64 C
169 31 89 22 0.31 138 PCT 12 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 64 C
170 31 101 22 0.18 161 PCT 7
P2 VS2
-0.75 TEC TEH 0.61 CBAY2 53 H
153 31 92 23 0.24 130 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 64 C
161 31 98 23 0.23 124 PCT 11 P2 VS2 0.72 TEC TEH 0.61 CBAY2 55 H
177 31 71 24 0.31 121 PCT 10 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 28 C
63 31 79 24 0.36 115 PCT 12 P2 VS2 0.76 TEH TEC 0.61 CBAY2 28 C
70 31 79 24 0.35 88 PCT 11 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 28 C
70 31 85 24 0.43 97 PCT 13 P2 VS2
-0.67 TEH TEC 0.61 CBAY2 66 C
189 31 87 24 0.65 126 PCT 19 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 68 C
50 31 87 24 137.9 6
OXP 2
TEH 21.16 TEH TEC 0.61 CBAY2 68 C
50 31 87 24 NDF P16 TEH 21.16 01H TEH 0.61 NYAX2 67 H
35 31 89 24 2.54 106 WAR 29 0.37 P20 VS2
-0.97 VS3 TEH 0.61 NYAX2 67 H
32 31 89 24 1.11 101 PCT 25 P2 VS2
-1.1 TEH TEC 0.61 CBAY2 66 C
191
U3R24 PVGS SG31 All Data Page 2 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 93 24 0.3 64 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 66 C
193 31 95 24 0.37 132 PCT 11 P2 10H 0.7 TEH TEC 0.61 CBAY2 66 C
194 31 95 24 0.3 52 PCT 10 P2 VS3
-0.82 TEH TEC 0.61 CBAY2 66 C
194 31 97 24 0.35 88 PCT 14 P2 VS3
-1.05 TEC TEH 0.61 CBAY2 55 H
169 31 97 24 0.21 123 PCT 10 P2 BW1 0.1 TEC TEH 0.61 CBAY2 55 H
169 31 97 24 0.21 135 PCT 10 P2 VS2 0.72 TEC TEH 0.61 CBAY2 55 H
169 31 99 24 0.44 102 PCT 17 P2 BW2 0.83 TEC TEH 0.61 CBAY2 55 H
170 31 99 24 0.21 95 PCT 10 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 55 H
170 31 101 24 0.32 114 PCT 13 P2 BW1 0.99 TEC TEH 0.61 CBAY2 55 H
171 31 101 24 0.27 127 PCT 12 P2 BW2 0.92 TEC TEH 0.61 CBAY2 55 H
171 31 101 24 0.37 153 PCT 10 P2 10H 0.68 TEC TEH 0.61 CBAY2 55 H
171 31 101 24 0.22 105 PCT 10 P2 VS2 0.79 TEC TEH 0.61 CBAY2 55 H
171 31 101 24 0.21 101 PCT 10 P2 VS3
-0.99 TEC TEH 0.61 CBAY2 55 H
171 31 107 24 0.34 99 PCT 14 P2 BW1 1
TEC TEH 0.61 CBAY2 55 H
174 31 109 24 1.72 75 PCT 32 P2 VS3
-1.07 TEC TEH 0.61 CBAY2 53 H
157 31 109 24 2.2 78 WAR 27 0.2 P21 VS3
-0.98 VS3 TEH 0.61 NYAX2 67 H
31 31 109 24 PID P2 VS3
-1.07 TEH TEC 0.61 CBAY2 68 C
49 31 90 25 0.42 120 PCT 13 P2 10C
-1.25 TEH TEC 0.61 CBAY2 66 C
184 31 94 25 0.33 116 PCT 10 P2 VS2 0.61 TEH TEC 0.61 CBAY2 66 C
182 31 77 26 0.3 76 PCT 12 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 22 C
109 31 81 26 0.36 110 PCT 13 P2 VS4
-0.7 TEH TEC 0.61 CBAY2 64 C
149 31 89 26 NDF 74 09C 34.89 VS3 TEC 0.61 NYAX2 266 C
52 31 111 26 0.78 164 PCT 11 P2 10H 0.56 TEC TEH 0.61 CBAY2 53 H
139 31 113 26 0.46 77 PCT 14 P2 VS3 0.85 TEC TEH 0.61 CBAY2 53 H
147 31 82 27 2.21 116 WAR 27 0.38 P12 VS2 0.72 VS3 TEH 0.61 NYAX2 67 H
37 31 82 27 0.8 105 PCT 22 P2 VS2 0.72 TEH TEC 0.61 CBAY2 22 C
49 31 98 27 0.4 148 PCT 10 P2 10H 0.7 TEC TEH 0.61 CBAY2 55 H
168 31 102 27 1.84 135 PLP 8
TSC 14.15 TEC TEH 0.61 CBAY2 53 H
133 31 102 27 17.22 109 PLP 44 TSC 14.49 01C TEC 0.61 NYAX2 266 C
33 31 35 28 0.29 127 PCT 10 P2 BW1 0.94 TEH TEC 0.61 CBAY2 24 C
92 31 79 28 0.27 95 PCT 10 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 24 C
114 31 85 28 0.71 89 PCT 18 P2 VS3 0.72 TEH TEC 0.61 CBAY2 66 C
170 31 89 28 0.47 63 PCT 14 P2 VS4 0.88 TEH TEC 0.61 CBAY2 66 C
172 31 99 28 0.34 79 PCT 11 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 66 C
177 31 99 28 0.31 37 PCT 10 P2 BW1 0.89 TEH TEC 0.61 CBAY2 66 C
177 31 99 28 3.74 93 PLP 164 TSC 13.46 01C TEC 0.61 NYAX2 266 C
45 31 101 28 1.27 70 PLP 7
TSC 14.05 TEH TEC 0.61 CBAY2 66 C
178 31 101 28 9.36 105 PLP 160 TSC 14.05 01C TEC 0.61 NYAX2 266 C
39 31 103 28 0.41 56 PCT 12 P2 BW1 0.92 TEH TEC 0.61 CBAY2 66 C
179 31 103 28 12.1 111 PLP 164 FDP
-0.64 01C TEC 0.61 NYAX2 266 C
34 31 46 29 0.34 107 PCT 11 P2 BW1 0.9 TEH TEC 0.61 CBAY2 24 C
62 31 110 29 2.37 111 WAR 28 0.37 P23 VS4
-0.78 VS3 TEC 0.61 NYAX2 266 C
21 31 110 29 0.82 112 PCT 24 P2 VS4
-0.75 TEC TEH 0.61 CBAY2 55 H
156
U3R24 PVGS SG31 All Data Page 3 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 85 30 2.36 112 WAR 28 0.28 P20 VS2
-0.93 VS3 TEH 0.61 NYAX2 67 H
38 31 85 30 0.78 107 PCT 21 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 64 C
134 31 85 30 0.25 135 PCT 10 P2 VS4 0.93 TEH TEC 0.61 CBAY2 64 C
134 31 87 30 0.48 117 PCT 16 P2 VS4 0.98 TEH TEC 0.61 CBAY2 64 C
135 31 87 30 0.31 143 PCT 12 P2 VS3
-0.82 TEH TEC 0.61 CBAY2 64 C
135 31 89 30 0.24 124 PCT 10 P2 VS3
-0.77 TEH TEC 0.61 CBAY2 64 C
136 31 99 30 0.26 127 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 64 C
141 31 111 30 0.21 141 PCT 7
P2 BW2
-0.99 TEC TEH 0.61 CBAY2 53 H
128 31 115 30 0.38 144 PCT 12 P2 BW1 0.8 TEC TEH 0.61 CBAY2 53 H
126 31 98 31 0.29 121 PCT 11 P2 VS2 0.85 TEH TEC 0.61 CBAY2 64 C
124 31 110 31 0.19 129 PCT 7
P2 VS4
-1 TEC TEH 0.61 CBAY2 53 H
122 31 53 32 0.35 129 PCT 12 P2 BW1 1.04 TEH TEC 0.61 CBAY2 24 C
35 31 77 32 0.29 133 PCT 10 P2 VS2
-0.68 TEH TEC 0.61 CBAY2 24 C
47 31 93 32 0.35 94 PCT 11 P2 VS2 0.84 TEH TEC 0.61 CBAY2 66 C
152 31 107 32 0.24 131 PCT 11 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 55 H
151 31 110 33 0.27 126 PCT 12 P2 VS2
-0.76 TEC TEH 0.61 CBAY2 55 H
141 31 120 33 2.46 114 WAR 29 0.26 P16 VS4 0.83 VS3 TEC 0.61 NYAX2 266 C
20 31 120 33 1.03 100 PCT 27 P2 VS4 0.88 TEC TEH 0.61 CBAY2 55 H
64 31 5
34 0.25 60 PCT 12 P2 VS3 0.77 TEC TEH 0.61 CBAY2 51 H
97 31 27 34 0.34 136 PCT 10 P2 08C
-0.94 TEH TEC 0.61 CBAY2 18 C
213 31 125 34 0.22 40 PCT 8
P2 BW1
-0.46 TEC TEH 0.61 CBAY2 53 H
47 31 90 35 0.24 96 PCT 10 P2 10C
-1.24 TEH TEC 0.61 CBAY2 64 C
107 31 94 35 0.39 113 PCT 14 P2 VS2 0.9 TEH TEC 0.61 CBAY2 64 C
105 31 100 35 0.5 77 PCT 16 P2 VS4 0.39 TEH TEC 0.61 CBAY2 64 C
102 31 122 35 0.41 18 PCT 16 P2 VS1 0.9 TEC TEH 0.61 CBAY2 55 H
62 31 122 35 0.24 117 PCT 10 P2 10C
-0.29 TEC TEH 0.61 CBAY2 55 H
62 31 69 36 0.35 111 PCT 11 P2 VS3 0.91 TEH TEC 0.61 CBAY2 20 C
237 31 71 36 0.33 127 PCT 10 P2 VS2 0.69 TEH TEC 0.61 CBAY2 20 C
238 31 105 36 0.22 125 PCT 10 P2 VS2
-0.79 TEC TEH 0.61 CBAY2 55 H
137 31 109 36 0.22 120 PCT 10 P2 BW1 2.38 TEC TEH 0.61 CBAY2 55 H
135 31 115 36 0.37 53 PCT 15 P2 VS3
-0.95 TEC TEH 0.61 CBAY2 55 H
132 31 127 36 0.34 155 PCT 11 P2 VS2
-1.01 TEC TEH 0.61 CBAY2 53 H
45 31 129 36 2.02 185 DNT P1 TSH 1.04 TEC TEH 0.61 CBAY2 53 H
37 31 129 36 NDF P14 TSH 1.04 01H TEH 0.61 NYAX2 67 H
28 31 14 37 0.43 131 PCT 11 P2 08C 0.74 TEH TEC 0.61 CBAY2 20 C
206 31 102 37 2.79 110 WAR 30 0.32 P20 VS3
-0.67 VS3 TEH 0.61 NYAX2 67 H
23 31 102 37 1.19 118 PCT 26 P2 VS3
-0.65 TEH TEC 0.61 CBAY2 66 C
115 31 112 37 0.29 88 PCT 13 P2 BW1 1.48 TEC TEH 0.61 CBAY2 55 H
123 31 112 37 0.23 36 PCT 10 P2 BW1 2.41 TEC TEH 0.61 CBAY2 55 H
123 31 128 37 0.31 74 PCT 10 P2 VS3
-0.6 TEC TEH 0.61 CBAY2 53 H
44 31 130 37 0.34 142 PCT 13 P2 VS1
-0.74 TEH TEC 0.61 CBAY2 68 C
48 31 27 38 0.31 124 PCT 11 P2 08C 0.74 TEH TEC 0.61 CBAY2 18 C
143 31 41 38 0.25 111 PCT 10 P2 BW1
-0.86 TEH TEC 0.61 CBAY2 18 C
150
U3R24 PVGS SG31 All Data Page 4 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 105 38 0.3 104 PCT 11 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 2
C 17 31 125 38 0.21 111 PCT 10 P2 BW2 0.94 TEC TEH 0.61 CBAY2 55 H
59 31 127 38 0.63 146 PLP 187 TSH 1.15 01H TEH 0.61 NYAX2 67 H
20 31 54 39 0.26 104 PCT 10 P2 BW1 1.36 TEH TEC 0.61 CBAY2 18 C
113 31 54 39 0.25 75 PCT 10 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 18 C
113 31 132 39 0.39 75 PCT 12 P2 11C 0
TEC TEH 0.61 CBAY2 53 H
34 31 134 39 0.21 107 PCT 7
P2 05H
-0.2 TEC TEH 0.61 CBAY2 53 H
40 31 85 40 0.49 53 PCT 14 P2 BW2 0.87 TEH TEC 0.61 CBAY2 66 C
105 31 89 40 0.53 72 PCT 15 P2 VS2 0.71 TEH TEC 0.61 CBAY2 66 C
107 31 93 40 0.32 98 PCT 10 P2 BW1 0.9 TEH TEC 0.61 CBAY2 66 C
109 31 119 40 0.35 50 PCT 14 P2 BW1 0.82 TEC TEH 0.61 CBAY2 55 H
111 31 121 40 0.33 75 PCT 14 P2 BW1 0.76 TEC TEH 0.61 CBAY2 55 H
110 31 127 40 0.25 140 PCT 11 P2 VS1 0.35 TEC TEH 0.61 CBAY2 55 H
57 31 127 40 0.22 96 PCT 10 P2 VS4 0.83 TEC TEH 0.61 CBAY2 55 H
57 31 133 40 0.29 153 PCT 10 P2 BW1 0.79 TEC TEH 0.61 CBAY2 53 H
33 31 135 40 0.19 145 PCT 7
P2 07H
-0.35 TEC TEH 0.61 CBAY2 53 H
39 31 10 41 0.31 75 PCT 13 P2 08H
-0.82 TEC TEH 0.61 CBAY2 51 H
84 31 10 41 0.25 100 PCT 12 P2 07C 0.84 TEC TEH 0.61 CBAY2 51 H
84 31 14 41 0.32 118 PCT 10 P2 08C 0.76 TEH TEC 0.61 CBAY2 20 C
134 31 136 41 0.29 153 PCT 10 P2 BW2
-0.91 TEC TEH 0.61 CBAY2 53 H
29 31 15 42 0.37 106 PCT 13 P2 08C 0.72 TEH TEC 0.61 CBAY2 18 C
67 31 27 42 0.34 129 PCT 11 P2 08C 0.77 TEH TEC 0.61 CBAY2 18 C
72 31 133 42 0.37 120 PCT 15 P2 VS1 0.78 TEC TEH 0.61 CBAY2 55 H
51 31 76 43 0.6 118 PCT 17 P2 09H 0.92 TEH TEC 0.61 CBAY2 18 C
26 31 90 43 0.27 152 PCT 11 P2 BW1
-0.77 TEH TEC 0.61 CBAY2 64 C
64 31 100 43 0.28 122 PCT 11 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 64 C
59 31 124 43 2.48 101 WAR 29 0.46 P23 VS4
-0.95 VS3 TEC 0.61 NYAX2 262 C
67 31 124 43 1.33 123 WAR 22 P22 VS5
-0.86 VS3 TEC 0.61 NYAX2 262 C
67 31 124 43 0.86 113 PCT 21 P2 VS4
-0.86 TEC TEH 0.61 CBAY2 53 H
63 31 124 43 1.22 107 WAR 21 0
P18 VS3 0.81 VS3 TEC 0.61 NYAX2 262 C
67 31 124 43 0.69 97 PCT 19 P2 VS3 0.86 TEC TEH 0.61 CBAY2 53 H
63 31 124 43 0.94 124 WAR 19 P11 VS3
-0.75 VS3 TEC 0.61 NYAX2 262 C
67 31 124 43 0.43 75 PCT 13 P2 VS3
-1.03 TEC TEH 0.61 CBAY2 53 H
63 31 124 43 0.38 120 PCT 12 P2 VS1 0.84 TEC TEH 0.61 CBAY2 53 H
63 31 124 43 0.26 159 PCT 9
P2 VS5
-0.81 TEC TEH 0.61 CBAY2 53 H
63 31 126 43 0.19 136 PCT 7
P2 VS3
-0.95 TEC TEH 0.61 CBAY2 53 H
64 31 134 43 0.3 134 PCT 13 P2 VS4 0.78 TEC TEH 0.61 CBAY2 55 H
33 31 47 44 0.34 138 PCT 11 P2 BW1 0.92 TEH TEC 0.61 CBAY2 20 C
77 31 127 44 0.34 103 PCT 14 P2 VS4
-0.39 TEC TEH 0.61 CBAY2 55 H
85 31 129 44 3.08 180 DNT P1 VS1 1.49 TEC TEH 0.61 CBAY2 55 H
84 31 129 44 NDF P12 VS1 1.49 VS3 TEH 0.61 NYAX2 67 H
9 31 133 44 2.09 181 DNT P1 VS1 1.23 TEC TEH 0.61 CBAY2 55 H
35 31 133 44 NDF P19 VS1 1.23 VS3 TEH 0.61 NYAX2 67 H
10
U3R24 PVGS SG31 All Data Page 5 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 48 45 0.33 121 PCT 10 P2 BW2 1.03 TEH TEC 0.61 CBAY2 20 C
37 31 66 45 0.36 96 PCT 11 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 20 C
28 31 72 45 0.34 99 PCT 11 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 20 C
25 31 90 45 0.59 127 PCT 17 P2 VS3 1.17 TEH TEC 0.61 CBAY2 66 C
79 31 108 45 0.25 85 PCT 11 P2 VS3 1.22 TEC TEH 0.61 CBAY2 55 H
73 31 126 45 0.36 133 PCT 14 P2 VS2
-0.75 TEC TEH 0.61 CBAY2 55 H
81 31 126 45 0.26 137 PCT 11 P2 VS3
-0.82 TEC TEH 0.61 CBAY2 55 H
81 31 113 46 0.29 147 NQI 3
10H 19.57 TEC TEH 0.61 CBAY2 41 H
30 31 113 46 NDF P23 10H 19.57 VS3 TEH 0.61 NYAX2 67 H
8 31 121 46 0.47 118 PCT 16 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 41 H
34 31 88 47 0.35 133 PCT 13 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 64 C
43 31 98 47 0.36 141 PCT 13 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 64 C
38 31 122 47 0.26 92 PCT 10 P2 VS3 1.03 TEC TEH 0.61 CBAY2 41 H
20 31 124 47 0.27 30 PCT 10 P2 VS1
-0.77 TEC TEH 0.61 CBAY2 41 H
19 31 144 47 0.35 133 PCT 10 P2 11H 0.69 TEC TEH 0.61 CBAY2 33 H
142 31 144 47 1.89 176 DNT P1 TSH 0.87 TEC TEH 0.61 CBAY2 33 H
142 31 144 47 NDF 62 TSH 0.87 01H TEH 0.61 NYAX2 65 H
54 31 45 48 0.3 56 PCT 12 P2 BW2 0.98 TEH TEC 0.61 CBAY2 14 C
135 31 53 48 0.28 116 PCT 11 P2 VS3 0.95 TEH TEC 0.61 CBAY2 18 C
6 31 93 48 0.3 59 PCT 10 P2 10H 0.85 TEH TEC 0.61 CBAY2 66 C
66 31 113 48 0.36 139 PCT 14 P2 BW1 0.44 TEC TEH 0.61 CBAY2 43 H
32 31 115 48 0.31 145 PCT 13 P2 BW1 0.43 TEC TEH 0.61 CBAY2 43 H
33 31 115 48 0.27 150 PCT 12 P2 VS4 0.9 TEC TEH 0.61 CBAY2 43 H
33 31 115 48 0.23 125 PCT 10 P2 VS3
-0.78 TEC TEH 0.61 CBAY2 43 H
33 31 117 48 0.35 131 PCT 14 P2 VS3
-1.19 TEC TEH 0.61 CBAY2 43 H
34 31 119 48 0.22 123 PCT 10 P2 VS3
-1.04 TEC TEH 0.61 CBAY2 43 H
35 31 121 48 0.26 157 PCT 11 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 43 H
36 31 143 48 0.55 142 PCT 13 P2 11H 0.68 TEC TEH 0.61 CBAY2 33 H
144 31 90 49 0.48 100 PCT 15 P2 10C
-1.69 TEH TEC 0.61 CBAY2 66 C
55 31 114 49 0.35 153 PCT 14 P2 VS1 0.82 TEC TEH 0.61 CBAY2 43 H
24 31 118 49 0.39 139 PCT 15 P2 VS4
-0.97 TEC TEH 0.61 CBAY2 43 H
22 31 85 50 0.4 135 PCT 11 P2 09H 0.18 TEH TEC 0.61 CBAY2 64 C
23 31 95 50 0.51 134 PCT 14 P2 10H 0.76 TEH TEC 0.61 CBAY2 64 C
28 31 97 50 0.48 153 PCT 10 P2 10H 0.78 TEH TEC 0.61 CBAY2 64 C
29 31 105 50 0.47 157 PCT 12 P2 10H 0.81 TEH TEC 0.61 CBAY2 64 C
33 31 125 50 0.32 91 PCT 12 P2 VS3
-1 TEC TEH 0.61 CBAY2 37 H
307 31 96 51 0.32 134 PCT 12 P2 VS4
-0.71 TEH TEC 0.61 CBAY2 64 C
15 31 96 51 0.38 139 PCT 10 P2 10H 0.78 TEH TEC 0.61 CBAY2 64 C
15 31 116 51 0.29 98 PCT 11 P2 BW1 0.82 TEC TEH 0.61 CBAY2 37 H
293 31 134 51 0.21 123 PCT 9
P2 VS1 0.71 TEC TEH 0.61 CBAY2 37 H
285 31 142 51 0.23 89 PCT 11 P2 VS2
-0.83 TEC TEH 0.61 CBAY2 35 H
143 31 144 51 0.48 90 PCT 18 P2 VS2
-0.93 TEC TEH 0.61 CBAY2 35 H
138 31 144 51 0.39 119 PCT 16 P2 VS2 1.03 TEC TEH 0.61 CBAY2 35 H
138
U3R24 PVGS SG31 All Data Page 6 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 59 52 0.28 117 PCT 11 P2 BW1 0.89 TEH TEC 0.61 CBAY2 14 C
55 31 71 52 0.33 81 PCT 12 P2 VS2
-0.94 TEH TEC 0.61 CBAY2 14 C
49 31 97 52 0.66 141 PCT 13 P2 10H 0.94 TEH TEC 0.61 CBAY2 66 C
44 31 125 52 0.43 113 PCT 16 P2 VS3
-1.05 TEC TEH 0.61 CBAY2 39 H
317 31 125 52 0.23 134 PCT 10 P2 VS2
-0.79 TEC TEH 0.61 CBAY2 39 H
317 31 127 52 0.34 143 PCT 14 P2 VS1
-0.88 TEC TEH 0.61 CBAY2 43 H
5 31 131 52 2.87 115 WAR 30 0.46 P12 VS2
-0.78 VS3 TEH 0.61 NYAX2 67 H
7 31 131 52 2.58 115 WAR 29 0.59 P12 VS3
-0.87 VS3 TEH 0.61 NYAX2 67 H
7 31 131 52 0.99 123 PCT 27 P2 VS2
-0.78 TEC TEH 0.61 CBAY2 43 H
7 31 131 52 0.86 126 PCT 25 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 43 H
7 31 131 52 0.52 142 PCT 18 P2 VS4
-0.76 TEC TEH 0.61 CBAY2 43 H
7 31 131 52 0.39 148 PCT 15 P2 VS5
-0.69 TEC TEH 0.61 CBAY2 43 H
7 31 137 52 0.34 151 PCT 14 P2 VS1
-0.85 TEC TEH 0.61 CBAY2 43 H
10 31 92 53 0.44 137 PCT 14 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 66 C
30 31 124 53 0.38 129 PCT 15 P2 VS2
-0.81 TEC TEH 0.61 CBAY2 39 H
297 31 130 53 0.37 137 PCT 15 P2 VS2
-0.7 TEC TEH 0.61 CBAY2 39 H
295 31 134 53 0.39 133 PCT 15 P2 VS1
-0.86 TEC TEH 0.61 CBAY2 39 H
293 31 9
54 NDF P43 07H 10.59 08H TEH 0.61 NYAX2 65 H
46 31 9
54 2.53 90 MBM 6
07H 10.59 TEC TEH 0.61 CBAY2 49 H
40 31 97 54 0.36 81 PCT 11 P2 10H 0.76 TEH TEC 0.61 CBAY2 62 C
145 31 121 54 0.36 124 PCT 13 P2 VS2
-0.93 TEC TEH 0.61 CBAY2 37 H
270 31 125 54 2.15 112 WAR 27 0.37 P12 VS3
-0.96 VS3 TEH 0.61 NYAX2 67 H
6 31 125 54 0.97 110 PCT 25 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 37 H
272 31 127 54 0.37 80 PCT 13 P2 VS4
-0.38 TEC TEH 0.61 CBAY2 37 H
273 31 56 55 0.57 57 PCT 16 P2 BW1
-1.71 TEH TEC 0.61 CBAY2 12 C
226 31 98 55 0.43 73 PCT 13 P2 10H 0.78 TEH TEC 0.61 CBAY2 62 C
135 31 116 55 0.22 145 PCT 9
P2 VS2
-0.84 TEC TEH 0.61 CBAY2 37 H
258 31 118 55 0.32 98 PCT 12 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 37 H
257 31 126 55 2.59 106 WAR 29 0.4 P23 VS4
-1.12 VS3 TEC 0.61 NYAX2 262 C
64 31 126 55 1.18 111 PCT 27 P2 VS3 1.23 TEC TEH 0.61 CBAY2 37 H
251 31 126 55 1.99 99 WAR 26 0.51 P19 VS3 1.04 VS3 TEC 0.61 NYAX2 262 C
64 31 126 55 0.83 116 PCT 23 P2 VS4
-1.25 TEC TEH 0.61 CBAY2 37 H
251 31 126 55 0.59 125 PCT 18 P2 VS3 0.96 TEC TEH 0.61 CBAY2 37 H
251 31 126 55 0.3 139 PCT 11 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 37 H
251 31 126 55 0.16 142 PCT 7
P2 VS1 0.25 TEC TEH 0.61 CBAY2 37 H
251 31 126 55 PAC VS3 TEH 0.61 NYAX2 67 H
5 31 136 55 0.25 109 PCT 10 P2 VS1 0.89 TEC TEH 0.61 CBAY2 37 H
246 31 152 55 7.64 182 DNT P1 TSH 0.8 TEC TEH 0.61 CBAY2 33 H
134 31 152 55 NDF P29 TSH 0.8 01H TEH 0.61 NYAX2 65 H
53 31 47 56 0.33 101 PCT 12 P2 VS3 0.75 TEH TEC 0.61 CBAY2 10 C
258 31 89 56 0.36 73 PCT 12 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 62 C
122 31 119 56 0.26 119 PCT 11 P2 VS2 0.73 TEC TEH 0.61 CBAY2 39 H
275 31 125 56 0.26 87 PCT 11 P2 VS3
-1.05 TEC TEH 0.61 CBAY2 39 H
278
U3R24 PVGS SG31 All Data Page 7 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 125 56 0.26 70 PCT 11 P2 BW2 0.89 TEC TEH 0.61 CBAY2 39 H
278 31 127 56 0.22 71 PCT 10 P2 VS3
-1.1 TEC TEH 0.61 CBAY2 39 H
279 31 127 56 0.23 68 PCT 10 P2 VS4 0.89 TEC TEH 0.61 CBAY2 39 H
279 31 133 56 5.14 180 DNT P1 10H 11.06 TEC TEH 0.61 CBAY2 39 H
282 31 133 56 NDF P42 10H 11.06 11H TEH 0.61 NYAX2 65 H
60 31 82 57 0.53 77 PCT 15 P2 VS2 0.82 TEH TEC 0.61 CBAY2 62 C
101 31 84 57 0.35 125 PCT 11 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 62 C
102 31 94 57 0.36 96 PCT 12 P2 10H 0.79 TEH TEC 0.61 CBAY2 62 C
106 31 124 57 NDF P30 BW1 0.57 VS3 TEH 0.61 NYAX2 65 H
59 31 132 57 0.25 138 PCT 11 P2 VS1 0.71 TEC TEH 0.61 CBAY2 39 H
253 31 142 57 0.36 125 PCT 14 P2 VS1 0.78 TEC TEH 0.61 CBAY2 39 H
248 31 152 57 0.26 71 PCT 10 P2 11C
-0.05 TEC TEH 0.61 CBAY2 33 H
132 31 79 58 0.39 106 PCT 12 P2 VS2
-0.98 TEH TEC 0.61 CBAY2 12 C
169 31 87 58 0.31 48 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 62 C
98 31 89 58 0.4 71 PCT 13 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 62 C
97 31 95 58 0.29 102 PCT 10 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 62 C
94 31 97 58 0.39 110 PCT 12 P2 BW1 0.85 TEH TEC 0.61 CBAY2 62 C
93 31 105 58 0.29 86 PCT 10 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 62 C
89 31 109 58 0.3 89 PCT 12 P2 BW1
-1.84 TEC TEH 0.61 CBAY2 37 H
222 31 125 58 0.46 74 PCT 15 P2 VS3
-0.99 TEC TEH 0.61 CBAY2 37 H
230 31 8
59 0.34 30 PCT 11 P2 08C 0.58 TEC TEH 0.61 CBAY2 51 H
26 31 48 59 0.38 54 PCT 12 P2 BW1 0.82 TEH TEC 0.61 CBAY2 12 C
150 31 66 59 0.4 157 PCT 12 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 12 C
159 31 92 59 0.44 74 PCT 13 P2 VS2 0.76 TEH TEC 0.61 CBAY2 62 C
81 31 124 59 1.18 101 PCT 27 P2 VS4
-0.99 TEC TEH 0.61 CBAY2 37 H
212 31 124 59 1.61 119 WAR 24 0.26 P31 VS4
-0.87 VS3 TEC 0.61 NYAX2 262 C
61 31 124 59 1.39 108 WAR 22 0.47 P23 VS4
-0.95 VS3 TEC 0.61 NYAX2 262 C
61 31 126 59 3.16 104 WAR 32 0.28 P23 VS4
-1.17 VS3 TEC 0.61 NYAX2 262 C
63 31 126 59 1.25 109 PCT 28 P2 VS4
-1.12 TEC TEH 0.61 CBAY2 37 H
211 31 128 59 1.55 106 PCT 31 P2 VS2 0.7 TEC TEH 0.61 CBAY2 37 H
210 31 128 59 2.01 109 WAR 27 0.42 P13 VS2 1
VS3 TEH 0.61 NYAX2 65 H
58 31 128 59 PID P2 VS2 0.7 TEH TEC 0.61 CBAY2 68 C
47 31 144 59 0.36 131 PCT 13 P2 VS2 1.15 TEC TEH 0.61 CBAY2 37 H
202 31 144 59 0.29 140 PCT 11 P2 VS3
-0.6 TEC TEH 0.61 CBAY2 37 H
202 31 146 59 0.27 143 PCT 10 P2 VS1
-0.85 TEC TEH 0.61 CBAY2 37 H
201 31 154 59 0.51 109 PCT 17 P2 VS4 0.33 TEC TEH 0.61 CBAY2 33 H
130 31 17 60 0.31 129 PCT 10 P2 08C 0.76 TEH TEC 0.61 CBAY2 10 C
202 31 67 60 0.5 155 PCT 16 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 10 C
177 31 85 60 0.28 128 PCT 11 P2 BW1 0.88 TEH TEC 0.61 CBAY2 64 C
184 31 85 60 0.26 131 PCT 10 P2 BW1 0.91 TEH TEC 0.61 CBAY2 64 C
183 31 89 60 0.31 82 PCT 10 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 62 C
66 31 109 60 0.25 136 PCT 11 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 39 H
226 31 121 60 0.26 138 PCT 11 P2 VS4
-0.79 TEC TEH 0.61 CBAY2 39 H
232
U3R24 PVGS SG31 All Data Page 8 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 121 60 0.21 135 PCT 10 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 39 H
232 31 123 60 0.39 108 PCT 15 P2 VS3
-1.08 TEC TEH 0.61 CBAY2 39 H
233 31 145 60 0.42 114 PCT 16 P2 VS3 0.35 TEC TEH 0.61 CBAY2 39 H
244 31 149 60 0.26 108 PCT 12 P2 VS2
-1.04 TEC TEH 0.61 CBAY2 35 H
150 31 54 61 0.22 82 PCT 9
P2 BW1
-1.24 TEH TEC 0.61 CBAY2 10 C
157 31 56 61 0.46 106 PCT 15 P2 BW1
-1.58 TEH TEC 0.61 CBAY2 10 C
158 31 62 61 0.4 64 PCT 13 P2 VS2
-0.71 TEH TEC 0.61 CBAY2 10 C
161 31 66 61 0.57 100 PCT 17 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 10 C
163 31 82 61 0.47 105 PCT 14 P2 VS4 0.42 TEH TEC 0.61 CBAY2 62 C
47 31 88 61 0.6 101 PCT 17 P2 VS2 0.78 TEH TEC 0.61 CBAY2 62 C
50 31 96 61 0.76 136 PCT 15 P2 10H 0.54 TEH TEC 0.61 CBAY2 62 C
54 31 122 61 0.39 103 PCT 15 P2 VS3 1.11 TEC TEH 0.61 CBAY2 39 H
215 31 126 61 0.33 68 PCT 13 P2 VS1 0.38 TEC TEH 0.61 CBAY2 39 H
213 31 134 61 NDF 134 11C 0.42 11C TEC 0.61 NYAX2 262 C
65 31 142 61 0.34 118 PCT 14 P2 VS3 0.91 TEC TEH 0.61 CBAY2 39 H
205 31 144 61 0.71 110 PCT 22 P2 VS4
-0.89 TEC TEH 0.61 CBAY2 39 H
204 31 144 61 1.41 109 WAR 22 0.23 P29 VS4
-0.77 VS3 TEC 0.61 NYAX2 262 C
66 31 144 61 0.25 85 PCT 11 P2 BW1 0.86 TEC TEH 0.61 CBAY2 39 H
204 31 150 61 0.27 127 PCT 12 P2 VS3 0.79 TEC TEH 0.61 CBAY2 35 H
151 31 152 61 0.28 93 PCT 12 P2 VS1 0.84 TEC TEH 0.61 CBAY2 35 H
128 31 152 61 0.2 117 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 35 H
128 31 47 62 0.38 88 PCT 12 P2 VS3 0.78 TEH TEC 0.61 CBAY2 12 C
113 31 87 62 0.46 87 PCT 14 P2 VS2
-0.93 TEH TEC 0.61 CBAY2 62 C
44 31 99 62 0.66 144 PCT 13 P2 10H 0.69 TEH TEC 0.61 CBAY2 66 C
22 31 101 62 0.41 98 PCT 13 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 62 C
39 31 121 62 0.52 109 PCT 17 P2 VS2 0.73 TEC TEH 0.61 CBAY2 37 H
185 31 121 62 0.42 124 PCT 15 P2 VS3 0.83 TEC TEH 0.61 CBAY2 37 H
185 31 139 62 0.35 90 PCT 13 P2 VS2
-0.96 TEC TEH 0.61 CBAY2 37 H
194 31 155 62 1.92 178 DNT P1 09C
-1.12 TEC TEH 0.61 CBAY2 33 H
156 31 155 62 NDF 184 09C
-1.12 11C TEC 0.61 NYAX2 262 C
68 31 28 63 0.3 94 PCT 10 P2 BW1
-0.83 TEH TEC 0.61 CBAY2 12 C
70 31 50 63 0.42 111 PCT 12 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 12 C
81 31 62 63 0.43 119 PCT 13 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 12 C
87 31 94 63 0.75 126 PCT 18 P2 10H 0.71 TEH TEC 0.61 CBAY2 62 C
28 31 100 63 0.34 85 PCT 11 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 62 C
36 31 126 63 0.25 142 PCT 10 P2 VS1 0.33 TEC TEH 0.61 CBAY2 37 H
165 31 128 63 0.19 123 PCT 8
P2 VS2 0.78 TEC TEH 0.61 CBAY2 37 H
164 31 136 63 0.29 145 PCT 11 P2 VS1
-0.64 TEC TEH 0.61 CBAY2 37 H
160 31 136 63 0.27 105 PCT 10 P2 VS1
-0.1 TEC TEH 0.61 CBAY2 37 H
160 31 138 63 0.32 106 PCT 12 P2 VS1 0.73 TEC TEH 0.61 CBAY2 37 H
159 31 71 64 0.32 117 PCT 11 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 10 C
105 31 97 64 0.39 98 PCT 12 P2 VS3
-0.86 TEH TEC 0.61 CBAY2 62 C
20 31 105 64 0.45 112 PCT 16 P2 VS2
-0.95 TEC TEH 0.61 CBAY2 39 H
178
U3R24 PVGS SG31 All Data Page 9 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 107 64 0.45 113 PCT 16 P2 VS3
-0.97 TEC TEH 0.61 CBAY2 39 H
179 31 107 64 0.33 121 PCT 14 P2 VS2
-1.05 TEC TEH 0.61 CBAY2 39 H
179 31 109 64 0.37 123 PCT 15 P2 VS2
-1 TEC TEH 0.61 CBAY2 39 H
180 31 117 64 0.34 113 PCT 14 P2 VS3
-1.24 TEC TEH 0.61 CBAY2 39 H
184 31 119 64 0.24 118 PCT 11 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 39 H
185 31 159 64 4.93 183 DNT P1 TSH 0.98 TEC TEH 0.61 CBAY2 33 H
125 31 159 64 NDF P23 TSH 0.98 01H TEH 0.61 NYAX2 65 H
52 31 12 65 0.26 93 PCT 10 P2 08C 0.07 TEH TEC 0.61 CBAY2 10 C
64 31 90 65 0.35 59 PCT 11 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 66 C
19 31 122 65 0.23 138 PCT 10 P2 VS4
-0.89 TEC TEH 0.61 CBAY2 39 H
168 31 124 65 0.5 113 PCT 18 P2 VS2 0.71 TEC TEH 0.61 CBAY2 39 H
167 31 124 65 0.32 120 PCT 13 P2 VS3
-0.69 TEC TEH 0.61 CBAY2 39 H
167 31 126 65 4.46 97 WAR 37 0.6 P23 VS4
-1.09 VS3 TEC 0.61 NYAX2 262 C
60 31 126 65 1.42 99 PCT 32 P2 VS4
-1.22 TEC TEH 0.61 CBAY2 39 H
166 31 126 65 3.16 106 WAR 32 0.42 P3 VS3
-0.63 VS3 TEC 0.61 NYAX2 262 C
60 31 126 65 1.04 124 PCT 27 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 39 H
166 31 126 65 0.65 90 PCT 21 P2 VS1 0.23 TEC TEH 0.61 CBAY2 39 H
166 31 126 65 0.76 120 WAR 17 0.22 P13 VS1 0.57 VS3 TEH 0.61 NYAX2 65 H
57 31 126 65 PAC VS3 TEH 0.61 NYAX2 65 H
57 31 126 65 PID P2 VS4
-1.22 TEH TEC 0.61 CBAY2 68 C
46 31 140 65 0.29 142 PCT 12 P2 VS1
-0.66 TEC TEH 0.61 CBAY2 39 H
159 31 142 65 0.31 125 PCT 13 P2 VS1
-0.89 TEC TEH 0.61 CBAY2 39 H
158 31 101 66 3.11 177 DNT P1 10C 14.19 TEH TEC 0.61 CBAY2 66 C
10 31 121 66 0.26 143 PCT 10 P2 VS4
-0.74 TEC TEH 0.61 CBAY2 37 H
136 31 153 66 0.25 60 PCT 10 P2 VS1
-0.93 TEC TEH 0.61 CBAY2 37 H
152 31 46 67 0.42 119 PCT 12 P2 VS3 0.84 TEH TEC 0.61 CBAY2 8
C 165 31 92 67 0.42 114 PCT 13 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 62 C
10 31 98 67 0.49 101 PCT 15 P2 VS2
-0.77 TEH TEC 0.61 CBAY2 62 C
7 31 118 67 0.49 130 PCT 16 P2 VS3
-0.36 TEC TEH 0.61 CBAY2 37 H
123 31 118 67 0.19 127 PCT 8
P2 VS2 1.03 TEC TEH 0.61 CBAY2 37 H
123 31 126 67 2.36 108 WAR 28 0.54 P22 VS4
-1.14 VS3 TEC 0.61 NYAX2 262 C
59 31 126 67 0.84 112 PCT 23 P2 VS4
-1.15 TEC TEH 0.61 CBAY2 37 H
119 31 126 67 1.4 117 WAR 22 P2 VS3
-0.72 VS3 TEC 0.61 NYAX2 262 C
59 31 126 67 0.44 94 PCT 15 P2 VS1 0.33 TEC TEH 0.61 CBAY2 37 H
119 31 126 67 0.42 129 PCT 14 P2 VS3
-0.72 TEC TEH 0.61 CBAY2 37 H
119 31 128 67 3.02 104 WAR 31 0.64 P23 VS4
-1.09 VS3 TEC 0.61 NYAX2 262 C
56 31 128 67 1.26 112 PCT 28 P2 VS2 0.78 TEC TEH 0.61 CBAY2 37 H
118 31 128 67 2.11 109 WAR 27 0.51 P13 VS2 0.98 VS3 TEH 0.61 NYAX2 65 H
56 31 128 67 0.92 115 PCT 24 P2 VS4
-0.79 TEC TEH 0.61 CBAY2 37 H
118 31 128 67 1.25 110 WAR 21 P2 VS3
-0.64 VS3 TEC 0.61 NYAX2 262 C
56 31 128 67 0.4 115 PCT 14 P2 VS3
-0.64 TEC TEH 0.61 CBAY2 37 H
118 31 128 67 0.28 135 PCT 11 P2 VS1 0.74 TEC TEH 0.61 CBAY2 37 H
118 31 128 67 PAC VS3 TEH 0.61 NYAX2 65 H
56
U3R24 PVGS SG31 All Data Page 10 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 130 67 3.63 100 WAR 34 0.57 P23 VS4
-0.79 VS3 TEC 0.61 NYAX2 262 C
55 31 130 67 1.16 106 PCT 27 P2 VS4
-0.79 TEC TEH 0.61 CBAY2 37 H
117 31 130 67 1.09 120 WAR 20 P2 VS3
-0.75 VS3 TEC 0.61 NYAX2 262 C
55 31 130 67 0.54 118 PCT 17 P2 VS2 0.81 TEC TEH 0.61 CBAY2 37 H
117 31 130 67 0.33 133 PCT 12 P2 VS3
-0.74 TEC TEH 0.61 CBAY2 37 H
117 31 140 67 0.3 134 PCT 11 P2 VS2
-0.83 TEC TEH 0.61 CBAY2 37 H
112 31 156 67 0.2 64 PCT 10 P2 BW2 0.89 TEC TEH 0.61 CBAY2 35 H
119 31 158 67 0.25 41 PCT 10 P2 BW1 0.89 TEC TEH 0.61 CBAY2 33 H
123 31 43 68 0.26 106 PCT 10 P2 BW1 0.87 TEH TEC 0.61 CBAY2 10 C
47 31 63 68 0.33 127 PCT 12 P2 BW1 0.88 TEH TEC 0.61 CBAY2 10 C
37 31 87 68 0.37 79 PCT 13 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 50 C
27 31 89 68 0.28 81 PCT 11 P2 VS2
-0.77 TEH TEC 0.61 CBAY2 50 C
26 31 91 68 0.5 61 PCT 16 P2 BW2 0.49 TEH TEC 0.61 CBAY2 50 C
25 31 91 68 0.24 113 PCT 10 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 50 C
25 31 97 68 0.39 97 PCT 14 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 50 C
21 31 125 68 0.24 94 PCT 11 P2 VS2
-1.09 TEC TEH 0.61 CBAY2 39 H
138 31 157 68 NDF 191 11C 19.99 VS3 TEC 0.61 NYAX2 262 C
69 31 92 69 0.44 135 PCT 12 P2 10H 0.33 TEH TEC 0.61 CBAY2 50 C
11 31 92 69 0.24 95 PCT 10 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 50 C
11 31 92 69 0.17 111 PCT 8
P2 09H 0.86 TEH TEC 0.61 CBAY2 50 C
11 31 120 69 0.27 118 PCT 12 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 39 H
120 31 122 69 0.4 56 PCT 15 P2 VS1 0.41 TEC TEH 0.61 CBAY2 39 H
119 31 128 69 1.7 98 WAR 24 0.32 P27 VS3
-0.67 VS3 TEH 0.61 NYAX2 65 H
55 31 128 69 0.67 116 PCT 21 P2 VS3
-0.59 TEC TEH 0.61 CBAY2 39 H
116 31 128 69 1.09 127 WAR 20 0.28 P21 VS2
-0.58 VS3 TEH 0.61 NYAX2 65 H
55 31 128 69 0.31 131 PCT 13 P2 VS2
-0.77 TEC TEH 0.61 CBAY2 39 H
116 31 132 69 0.31 115 PCT 13 P2 VS2 0.88 TEC TEH 0.61 CBAY2 39 H
114 31 148 69 0.27 133 PCT 12 P2 VS3 0.68 TEC TEH 0.61 CBAY2 39 H
106 31 162 69 0.4 68 PCT 14 P2 07H 0.75 TEC TEH 0.61 CBAY2 33 H
116 31 162 69 1.9 181 DNT P1 TSH 0.79 TEC TEH 0.61 CBAY2 33 H
116 31 162 69 NDF P1 TSH 0.79 01H TEH 0.61 NYAX2 65 H
51 31 57 70 0.32 52 PCT 10 P2 VS3
-1.01 TEH TEC 0.61 CBAY2 8
C 27 31 89 70 0.44 82 PCT 13 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 8
C 42 31 113 70 0.46 109 PCT 15 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 37 H
83 31 125 70 0.29 115 PCT 11 P2 VS2
-1.01 TEC TEH 0.61 CBAY2 37 H
89 31 159 70 2.12 177 DNT P1 09C
-1.08 TEC TEH 0.61 CBAY2 35 H
116 31 159 70 NDF 88 09C
-1.07 11C TEC 0.61 NYAX2 262 C
70 31 50 71 0.36 66 PCT 11 P2 BW2 0.9 TEH TEC 0.61 CBAY2 8
C 86 31 54 71 0.26 131 PCT 8
P2 09H
-1.46 TEH TEC 0.61 CBAY2 8
C 84 31 72 71 0.32 80 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 8
C 75 31 128 71 0.24 101 PCT 10 P2 VS1 0.73 TEC TEH 0.61 CBAY2 37 H
71 31 158 71 0.34 68 PCT 14 P2 BW2
-0.82 TEC TEH 0.61 CBAY2 35 H
120 31 162 71 0.33 63 PCT 12 P2 BW1 1.1 TEC TEH 0.61 CBAY2 33 H
111
U3R24 PVGS SG31 All Data Page 11 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 45 72 0.5 131 PCT 14 P2 BW1 0.64 TEH TEC 0.61 CBAY2 8
C 111 31 89 72 0.31 85 PCT 12 P2 VS3
-0.81 TEH TEC 0.61 CBAY2 6
C 35 31 99 72 122.63 20 OXP 2
TEH 22.23 TEC TEH 0.61 CBAY2 37 H
175 31 99 72 NDF P19 TEH 21.72 01H TEH 0.61 NYAX2 65 H
49 31 99 72 NDF P11 TEH 21.72 01H TEH 0.61 NYAX2 65 H
37 31 121 72 0.33 109 PCT 14 P2 VS2
-0.85 TEC TEH 0.61 CBAY2 39 H
85 31 161 72 2.46 178 DNT P1 09C
-1.2 TEC TEH 0.61 CBAY2 33 H
114 31 161 72 NDF 136 09C
-1.2 11C TEC 0.61 NYAX2 262 C
71 31 80 73 0.54 98 PCT 18 P2 VS3 0.92 TEH TEC 0.61 CBAY2 6
C 61 31 114 73 0.32 120 PCT 13 P2 VS2 0.76 TEC TEH 0.61 CBAY2 39 H
78 31 130 73 0.36 111 PCT 14 P2 VS3
-0.76 TEC TEH 0.61 CBAY2 39 H
70 31 47 74 0.43 78 PCT 15 P2 BW2 0.92 TEH TEC 0.61 CBAY2 6
C 106 31 47 74 NDF P37 08H 20.3 26.7 VS3 TEH 0.61 NYAX2 65 H
45 31 47 74 2.61 108 PRX P8 08H 20.3 26.7 TEH TEC 0.61 CBAY2 6
C 106 31 51 74 0.58 92 PCT 15 P2 VS3 0.76 TEH TEC 0.61 CBAY2 8
C 114 31 51 74 0.42 95 PCT 12 P2 BW1
-0.87 TEH TEC 0.61 CBAY2 8
C 114 31 125 74 0.22 127 PCT 9
P2 VS3
-0.97 TEC TEH 0.61 CBAY2 37 H
40 31 127 74 0.26 107 PCT 10 P2 VS3 0.28 TEC TEH 0.61 CBAY2 37 H
41 31 157 74 0.19 137 PCT 8
P2 VS5
-0.66 TEC TEH 0.61 CBAY2 37 H
56 31 161 74 0.28 84 PCT 12 P2 VS5
-0.79 TEC TEH 0.61 CBAY2 35 H
110 31 165 74 0.38 70 PCT 14 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 33 H
108 31 165 74 0.26 77 PCT 10 P2 BW2 0.89 TEC TEH 0.61 CBAY2 33 H
108 31 165 74 NDF 155 FDP 27.9 01C TEC 0.61 NYAX2 264 C
29 31 32 75 0.44 42 PCT 12 P2 08C 0.77 TEH TEC 0.61 CBAY2 6
C 163 31 46 75 0.28 73 PCT 11 P2 BW2 0.87 TEH TEC 0.61 CBAY2 6
C 156 31 86 75 0.51 144 PCT 11 P2 09H 0.84 TEC TEH 0.61 CBAY2 13 H
96 31 94 75 0.39 130 PCT 11 P2 10H 0.61 TEC TEH 0.61 CBAY2 13 H
92 31 128 75 NDF 170 10H 32.23 VS3 TEH 0.61 NYAX2 65 H
34 31 140 75 0.18 66 PCT 8
P2 BW1
-0.91 TEC TEH 0.61 CBAY2 37 H
18 31 160 75 0.25 97 PCT 11 P2 VS1 0.87 TEC TEH 0.61 CBAY2 35 H
113 31 162 75 0.2 109 PCT 10 P2 VS4 0.71 TEC TEH 0.61 CBAY2 35 H
109 31 164 75 2.78 114 WAR 30 0.2 P19 BW2 0.89 VS3 TEC 0.61 NYAX2 268 C
11 31 164 75 1.34 101 PCT 29 P2 BW2 0.89 TEC TEH 0.61 CBAY2 33 H
104 31 164 75 0.36 114 PCT 13 P2 10H 0.75 TEC TEH 0.61 CBAY2 33 H
104 31 164 75 NDF P28 FDP 27.87 VS3 TEC 0.61 NYAX2 268 C
11 31 21 76 0.37 53 PCT 14 P2 VS3
-0.87 TEH TEC 0.61 CBAY2 6
C 108 31 35 76 0.28 52 PCT 10 P2 04H 0.89 TEH TEC 0.61 CBAY2 6
C 115 31 47 76 0.5 101 PCT 17 P2 BW2 0.9 TEH TEC 0.61 CBAY2 6
C 121 31 97 76 0.41 142 PCT 11 P2 10H 0.75 TEC TEH 0.61 CBAY2 15 H
45 31 99 76 0.23 124 PCT 11 P2 BW1 0.84 TEC TEH 0.61 CBAY2 15 H
46 31 141 76 0.23 63 PCT 10 P2 BW1 0.89 TEC TEH 0.61 CBAY2 39 H
47 31 163 76 0.24 116 PCT 11 P2 BW2 0.97 TEC TEH 0.61 CBAY2 35 H
108 31 165 76 2.34 108 WAR 28 0.43 P15 BW2 0.79 VS3 TEC 0.61 NYAX2 268 C
10
U3R24 PVGS SG31 All Data Page 12 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 165 76 0.91 79 PCT 24 P2 BW2 0.79 TEC TEH 0.61 CBAY2 33 H
103 31 24 77 0.31 101 PCT 11 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 13 H
31 31 42 77 0.61 131 PCT 18 P2 BW1
-0.94 TEC TEH 0.61 CBAY2 13 H
39 31 46 77 0.32 108 PCT 14 P2 BW2 0.87 TEC TEH 0.61 CBAY2 15 H
25 31 48 77 0.36 111 PCT 12 P2 BW2 0.84 TEC TEH 0.61 CBAY2 13 H
42 31 52 77 0.28 43 PCT 10 P2 09H
-0.85 TEC TEH 0.61 CBAY2 15 H
30 31 52 77 PBC TEC TEH 0.61 CBAY2 13 H
55 31 110 77 0.49 119 PCT 18 P2 VS1 0.74 TEC TEH 0.61 CBAY2 15 H
54 31 112 77 0.42 134 PCT 16 P2 VS2 0.86 TEC TEH 0.61 CBAY2 15 H
53 31 116 77 0.59 110 PCT 20 P2 VS2 0.79 TEC TEH 0.61 CBAY2 39 H
31 31 116 77 0.71 119 WAR 16 0.43 P13 VS2 1.09 VS3 TEH 0.61 NYAX2 65 H
33 31 128 77 0.6 110 PCT 20 P2 VS3
-0.66 TEC TEH 0.61 CBAY2 39 H
25 31 128 77 0.72 111 WAR 16 0.35 P28 VS3
-0.44 VS3 TEH 0.61 NYAX2 65 H
32 31 156 77 NDF P20 11C 20.53 VS3 TEC 0.61 NYAX2 264 C
38 31 164 77 2.12 118 WAR 27 0.17 P18 BW2 0.82 VS3 TEC 0.61 NYAX2 268 C
13 31 164 77 0.72 94 PCT 21 P2 BW2 0.82 TEC TEH 0.61 CBAY2 33 H
101 31 164 77 0.32 123 PCT 11 P2 10H 0.68 TEC TEH 0.61 CBAY2 33 H
101 31 166 77 2.36 115 WAR 28 0.23 P18 BW2 0.92 VS3 TEC 0.61 NYAX2 268 C
12 31 166 77 0.78 62 PCT 22 P2 BW2 0.92 TEC TEH 0.61 CBAY2 33 H
102 31 25 78 0.29 108 PCT 10 P2 BW1 1.01 TEC TEH 0.61 CBAY2 13 H
32 31 31 78 0.33 118 PCT 11 P2 08H 0.83 TEC TEH 0.61 CBAY2 13 H
26 31 41 78 0.51 124 PCT 16 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 13 H
38 31 45 78 0.35 98 PCT 12 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 9
H 37 31 47 78 0.6 85 PCT 18 P2 BW2 0.89 TEC TEH 0.61 CBAY2 9
H 38 31 49 78 0.65 113 PCT 18 P2 BW2 0.87 TEC TEH 0.61 CBAY2 9
H 39 31 49 78 0.49 120 PCT 14 P2 09H
-1.43 TEC TEH 0.61 CBAY2 9
H 39 31 51 78 0.75 43 PCT 16 P2 09H
-0.85 TEC TEH 0.61 CBAY2 9
H 40 31 89 78 0.33 101 PCT 11 P2 09H 0.66 TEC TEH 0.61 CBAY2 9
H 59 31 97 78 0.35 108 PCT 12 P2 VS2
-0.82 TEC TEH 0.61 CBAY2 9
H 63 31 159 78 0.35 46 PCT 13 P2 BW2
-0.95 TEC TEH 0.61 CBAY2 37 H
7 31 161 78 0.32 108 PCT 12 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 37 H
8 31 163 78 0.47 114 PCT 18 P2 BW2
-1.01 TEC TEH 0.61 CBAY2 35 H
103 31 163 78 0.34 115 PCT 14 P2 BW2 0.89 TEC TEH 0.61 CBAY2 35 H
103 31 165 78 0.61 112 PCT 19 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 33 H
100 31 30 79 0.51 139 PCT 12 P2 08C 0.81 TEC TEH 0.61 CBAY2 13 H
27 31 32 79 0.47 106 PCT 15 P2 BW1
-0.95 TEC TEH 0.61 CBAY2 13 H
29 31 34 79 0.29 90 PCT 10 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 13 H
23 31 38 79 0.27 115 PCT 12 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 15 H
14 31 42 79 0.4 130 PCT 16 P2 VS3
-0.71 TEC TEH 0.61 CBAY2 15 H
27 31 42 79 0.33 117 PCT 13 P2 08H 0.03 TEC TEH 0.61 CBAY2 15 H
27 31 42 79 0.28 124 PCT 12 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 15 H
27 31 48 79 0.66 92 PCT 19 P2 BW2 0.92 TEC TEH 0.61 CBAY2 9
H 34 31 76 79 2.15 104 WAR 27 0.34 P12 VS2 0.79 VS3 TEH 0.61 NYAX2 65 H
15
U3R24 PVGS SG31 All Data Page 13 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 76 79 0.89 100 PCT 23 P2 VS2 0.83 TEC TEH 0.61 CBAY2 9
H 20 31 122 79 0.16 14 PCT 7
P2 VS1 0.85 TEC TEH 0.61 CBAY2 33 H
230 31 158 79 0.8 82 PCT 22 P2 BW2 0.92 TEC TEH 0.61 CBAY2 33 H
212 31 158 79 1.36 121 WAR 22 0.2 P18 BW2 0.92 VS3 TEC 0.61 NYAX2 264 C
33 31 162 79 1.28 113 WAR 21 0.17 P32 BW2
-0.85 VS3 TEC 0.61 NYAX2 264 C
14 31 162 79 0.55 109 PCT 20 P2 BW2
-0.82 TEC TEH 0.61 CBAY2 35 H
102 31 164 79 0.19 76 PCT 8
P2 VS2
-0.86 TEC TEH 0.61 CBAY2 33 H
96 31 166 79 0.43 79 PCT 15 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 33 H
99 31 166 79 0.4 141 PCT 11 P2 10H 0.7 TEC TEH 0.61 CBAY2 33 H
99 31 39 80 0.85 124 PCT 25 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 15 H
13 31 39 80 1.19 123 WAR 21 0.34 P10 BW1
-0.79 VS3 TEH 0.61 NYAX2 65 H
44 31 39 80 PID P2 BW1
-0.79 TEH TEC 0.61 CBAY2 68 C
35 31 43 80 0.21 73 PCT 10 P2 BW2 0.92 TEC TEH 0.61 CBAY2 15 H
24 31 45 80 0.3 84 PCT 11 P2 BW2 0.92 TEC TEH 0.61 CBAY2 13 H
10 31 49 80 0.31 56 PCT 13 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 11 H
38 31 53 80 0.23 75 PCT 10 P2 BW1
-0.68 TEC TEH 0.61 CBAY2 11 H
40 31 61 80 0.22 104 PCT 10 P2 VS2
-0.98 TEC TEH 0.61 CBAY2 11 H
44 31 103 80 2.03 107 WAR 27 0.41 P21 VS3
-0.7 VS3 TEH 0.61 NYAX2 65 H
14 31 103 80 0.68 120 PCT 22 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 15 H
33 31 105 80 0.44 121 PCT 17 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 15 H
34 31 107 80 0.23 105 PCT 11 P2 VS3
-0.91 TEC TEH 0.61 CBAY2 15 H
35 31 121 80 0.33 91 PCT 14 P2 VS3 0.76 TEC TEH 0.61 CBAY2 35 H
236 31 155 80 0.3 99 PCT 12 P2 BW2 0.89 TEC TEH 0.61 CBAY2 39 H
5 31 157 80 0.46 105 PCT 17 P2 BW2 0.81 TEC TEH 0.61 CBAY2 39 H
6 31 163 80 0.43 79 PCT 17 P2 BW2 0.84 TEC TEH 0.61 CBAY2 35 H
101 31 36 81 1.24 87 WAR 21 0.42 P24 BW1 1.05 VS3 TEH 0.61 NYAX2 65 H
41 31 36 81 0.73 108 PCT 20 P2 BW1 0.96 TEC TEH 0.61 CBAY2 13 H
21 31 36 81 PID P2 BW1 0.96 TEH TEC 0.61 CBAY2 68 C
34 31 44 81 0.55 94 PCT 17 P2 VS3 0.9 TEC TEH 0.61 CBAY2 13 H
9 31 78 81 0.24 112 PCT 11 P2 VS3 0.69 TEC TEH 0.61 CBAY2 11 H
20 31 90 81 0.2 112 PCT 9
P2 10H
-1.13 TEC TEH 0.61 CBAY2 11 H
71 31 98 81 0.18 61 PCT 9
P2 BW1 0.87 TEC TEH 0.61 CBAY2 11 H
67 31 122 81 0.24 124 PCT 11 P2 VS1
-1 TEC TEH 0.61 CBAY2 35 H
227 31 122 81 0.19 23 PCT 9
P2 VS1 0.75 TEC TEH 0.61 CBAY2 35 H
227 31 168 81 0.26 82 PCT 11 P2 BW2
-0.82 TEC TEH 0.61 CBAY2 33 H
97 31 39 82 1.01 121 PCT 27 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 15 H
10 31 39 82 1.88 111 WAR 26 0.34 P9 BW1
-0.86 VS3 TEH 0.61 NYAX2 65 H
42 31 39 82 PID P2 BW1
-0.86 TEH TEC 0.61 CBAY2 68 C
33 31 41 82 0.31 136 PCT 13 P2 BW2
-0.78 TEC TEH 0.61 CBAY2 15 H
11 31 45 82 0.41 120 PCT 14 P2 BW1 0.84 TEC TEH 0.61 CBAY2 13 H
7 31 45 82 0.43 96 PCT 14 P2 BW2 0.92 TEC TEH 0.61 CBAY2 13 H
7 31 47 82 1.15 126 WAR 21 0.32 P13 BW2 1.2 VS3 TEC 0.61 NYAX2 262 C
47 31 47 82 0.68 112 PCT 19 P2 BW2 1.05 TEC TEH 0.61 CBAY2 9
H 19
U3R24 PVGS SG31 All Data Page 14 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 47 82 0.37 127 PCT 13 P2 BW1 0.81 TEC TEH 0.61 CBAY2 9
H 19 31 51 82 0.44 109 PCT 14 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 9
H 17 31 97 82 0.49 125 PCT 14 P2 10H 0.76 TEC TEH 0.61 CBAY2 9
H 87 31 121 82 0.3 94 PCT 12 P2 VS4
-0.87 TEC TEH 0.61 CBAY2 33 H
190 31 165 82 0.54 120 PCT 19 P2 BW2 0.86 TEC TEH 0.61 CBAY2 35 H
99 31 167 82 0.42 50 PCT 15 P2 BW2 0.86 TEC TEH 0.61 CBAY2 33 H
93 31 44 83 0.3 69 PCT 11 P2 BW2 0.9 TEC TEH 0.61 CBAY2 13 H
6 31 46 83 0.42 81 PCT 13 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 5
H 293 31 50 83 1.85 110 WAR 25 0.52 P28 VS3
-0.84 VS3 TEH 0.61 NYAX2 61 H
53 31 50 83 0.71 106 PCT 19 P2 VS3
-0.83 TEC TEH 0.61 CBAY2 5
H 291 31 50 83 0.69 106 PCT 18 P2 09H
-0.13 TEC TEH 0.61 CBAY2 5
H 291 31 118 83 1.66 102 WAR 24 0.43 P28 VS3
-0.2 VS3 TEH 0.61 NYAX2 65 H
31 31 118 83 0.83 101 PCT 23 P2 VS3
-0.39 TEC TEH 0.61 CBAY2 33 H
181 31 158 83 0.29 124 PCT 11 P2 BW2 0.81 TEC TEH 0.61 CBAY2 33 H
161 31 168 83 0.32 71 PCT 12 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 33 H
88 31 37 84 0.3 115 PCT 11 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 13 H
18 31 41 84 1.23 115 PCT 27 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 13 H
13 31 41 84 1.95 110 WAR 26 0.37 P8 BW1
-0.92 VS3 TEH 0.61 NYAX2 65 H
43 31 41 84 0.23 85 PCT 9
P2 08H
-1.07 TEC TEH 0.61 CBAY2 13 H
13 31 41 84 PID P2 BW1
-0.92 TEH TEC 0.61 CBAY2 68 C
31 31 43 84 0.33 106 PCT 12 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 13 H
8 31 43 84 0.31 141 PCT 11 P2 BW1 0.87 TEC TEH 0.61 CBAY2 13 H
8 31 45 84 0.34 121 PCT 14 P2 BW1 0.63 TEC TEH 0.61 CBAY2 15 H
8 31 45 84 0.28 94 PCT 12 P2 BW1 0.97 TEC TEH 0.61 CBAY2 15 H
8 31 45 84 0.25 147 PCT 11 P2 VS3 0.71 TEC TEH 0.61 CBAY2 15 H
8 31 47 84 2.09 109 WAR 27 0.47 P23 BW1 0.88 VS3 TEH 0.61 NYAX2 61 H
52 31 47 84 0.94 118 PCT 26 P2 BW1 0.79 TEC TEH 0.61 CBAY2 15 H
7 31 47 84 1.73 132 WAR 25 0.63 P24 BW1 0.4 VS3 TEH 0.61 NYAX2 61 H
52 31 47 84 0.53 129 PCT 19 P2 BW2 0.87 TEC TEH 0.61 CBAY2 15 H
7 31 47 84 0.38 90 PCT 15 P2 BW1 0.21 TEC TEH 0.61 CBAY2 15 H
7 31 47 84 0.23 119 PCT 10 P2 08H 0.05 TEC TEH 0.61 CBAY2 15 H
7 31 47 84 0.21 44 PCT 10 P2 BW2 0.18 TEC TEH 0.61 CBAY2 15 H
7 31 47 84 PID P2 BW1 0.79 TEH TEC 0.61 CBAY2 68 C
32 31 49 84 0.38 130 PCT 13 P2 08H 0.73 TEC TEH 0.61 CBAY2 11 H
19 31 53 84 0.32 109 PCT 13 P2 VS3 0.8 TEC TEH 0.61 CBAY2 11 H
17 31 109 84 0.21 113 PCT 10 P2 VS2
-0.99 TEC TEH 0.61 CBAY2 15 H
74 31 163 84 0.22 71 PCT 10 P2 VS5 0.85 TEC TEH 0.61 CBAY2 35 H
207 31 38 85 0.42 117 PCT 14 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 13 H
17 31 40 85 1.89 108 WAR 26 0.37 P21 VS3
-0.62 VS3 TEH 0.61 NYAX2 65 H
40 31 40 85 0.71 110 PCT 20 P2 VS3
-0.75 TEC TEH 0.61 CBAY2 13 H
14 31 40 85 0.23 80 PCT 9
P2 08H 0.03 TEC TEH 0.61 CBAY2 13 H
14 31 40 85 PID P2 VS3
-0.75 TEH TEC 0.61 CBAY2 68 C
30 31 44 85 0.21 64 PCT 10 P2 08C
-0.9 TEC TEH 0.61 CBAY2 15 H
9
U3R24 PVGS SG31 All Data Page 15 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 46 85 2.42 285 WAR 28 0.94 P8 BW1
-0.8 VS3 TEH 0.61 NYAX2 61 H
51 31 46 85 0.93 121 PCT 26 P2 BW1
-0.78 TEC TEH 0.61 CBAY2 15 H
6 31 46 85 0.25 123 PCT 11 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 15 H
6 31 46 85 PID P2 BW1
-0.78 TEH TEC 0.61 CBAY2 68 C
29 31 48 85 0.45 93 PCT 17 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 7
H 329 31 52 85 0.35 140 PCT 14 P2 VS3 0.66 TEC TEH 0.61 CBAY2 7
H 327 31 84 85 0.22 108 PCT 10 P2 BW1
-0.78 TEC TEH 0.61 CBAY2 11 H
97 31 90 85 0.24 84 PCT 11 P2 BW1
-0.77 TEC TEH 0.61 CBAY2 11 H
94 31 98 85 0.39 134 PCT 12 P2 10H 0.6 TEC TEH 0.61 CBAY2 11 H
90 31 116 85 0.52 119 PCT 19 P2 VS2 0.69 TEC TEH 0.61 CBAY2 35 H
180 31 116 85 0.26 110 PCT 12 P2 VS3 0.95 TEC TEH 0.61 CBAY2 35 H
180 31 118 85 0.23 120 PCT 11 P2 VS2 0.79 TEC TEH 0.61 CBAY2 35 H
179 31 120 85 0.23 105 PCT 11 P2 VS2 0.71 TEC TEH 0.61 CBAY2 35 H
178 31 122 85 0.82 116 PCT 25 P2 VS4 0.51 TEC TEH 0.61 CBAY2 35 H
177 31 122 85 0.46 91 PCT 18 P2 VS2 0.99 TEC TEH 0.61 CBAY2 35 H
177 31 122 85 0.83 89 WAR 18 0.32 P7 VS4 0.47 VS3 TEC 0.61 NYAX2 262 C
53 31 142 85 0.26 81 PCT 12 P2 VS4
-0.92 TEC TEH 0.61 CBAY2 35 H
167 31 164 85 0.3 79 PCT 13 P2 VS2 0.83 TEC TEH 0.61 CBAY2 35 H
94 31 168 85 0.28 62 PCT 11 P2 VS1 0.96 TEC TEH 0.61 CBAY2 33 H
90 31 41 86 0.51 127 PCT 16 P2 08C 0.82 TEC TEH 0.61 CBAY2 7
H 231 31 43 86 0.34 120 PCT 14 P2 BW2
-0.89 TEC TEH 0.61 CBAY2 7
H 232 31 43 86 0.4 141 PCT 12 P2 08H 0.8 TEC TEH 0.61 CBAY2 7
H 232 31 43 86 0.36 138 PCT 11 P2 06H 0.74 TEC TEH 0.61 CBAY2 7
H 232 31 45 86 2.5 111 WAR 29 0.2 P24 BW1 0.9 VS3 TEH 0.61 NYAX2 61 H
48 31 45 86 1.01 122 PCT 27 P2 BW1 0.86 TEC TEH 0.61 CBAY2 7
H 233 31 45 86 PID P2 BW1 0.86 TEH TEC 0.61 CBAY2 68 C
25 31 47 86 1.76 104 WAR 25 0.2 P24 BW1 0.9 VS3 TEH 0.61 NYAX2 61 H
49 31 47 86 0.58 117 PCT 20 P2 BW1 0.89 TEC TEH 0.61 CBAY2 7
H 234 31 47 86 PID P2 BW1 0.89 TEH TEC 0.61 CBAY2 68 C
26 31 49 86 1.81 119 WAR 25 0.17 P13 BW2 0.96 VS3 TEC 0.61 NYAX2 262 C
46 31 49 86 0.6 102 PCT 20 P2 BW2 0.87 TEC TEH 0.61 CBAY2 7
H 235 31 49 86 0.54 116 PCT 19 P2 BW1 0.83 TEC TEH 0.61 CBAY2 7
H 235 31 49 86 PID P2 BW1 0.83 TEH TEC 0.61 CBAY2 68 C
27 31 51 86 1.62 125 WAR 24 0.23 P23 BW1
-0.85 VS3 TEH 0.61 NYAX2 61 H
50 31 51 86 0.62 119 PCT 20 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 7
H 236 31 51 86 0.22 48 PCT 10 P2 BW2
-0.8 TEC TEH 0.61 CBAY2 7
H 236 31 51 86 PID P2 BW1
-0.85 TEH TEC 0.61 CBAY2 68 C
28 31 61 86 0.22 98 PCT 10 P2 09H 0.76 TEC TEH 0.61 CBAY2 7
H 241 31 63 86 0.39 112 PCT 15 P2 VS3 0.9 TEC TEH 0.61 CBAY2 7
H 242 31 65 86 0.52 135 PCT 15 P2 09H 0.68 TEC TEH 0.61 CBAY2 7
H 243 31 91 86 0.26 59 PCT 10 P2 BW2 0.85 TEC TEH 0.61 CBAY2 9
H 104 31 111 86 0.24 128 PCT 11 P2 BW1
-1.55 TEC TEH 0.61 CBAY2 35 H
91 31 115 86 0.46 111 PCT 17 P2 VS3 0.79 TEC TEH 0.61 CBAY2 35 H
89
U3R24 PVGS SG31 All Data Page 16 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 115 86 0.45 95 PCT 17 P2 VS4
-0.82 TEC TEH 0.61 CBAY2 35 H
89 31 121 86 0.25 109 PCT 11 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 35 H
86 31 127 86 0.23 51 PCT 11 P2 VS4 0.82 TEC TEH 0.61 CBAY2 35 H
83 31 153 86 0.29 97 PCT 13 P2 VS1
-0.87 TEC TEH 0.61 CBAY2 35 H
70 31 40 87 0.28 97 PCT 12 P2 VS3 0.84 TEC TEH 0.61 CBAY2 7
H 230 31 46 87 0.3 111 PCT 13 P2 BW1
-0.8 TEC TEH 0.61 CBAY2 7
H 228 31 52 87 0.28 106 PCT 12 P2 VS3 0.58 TEC TEH 0.61 CBAY2 7
H 225 31 56 87 0.24 107 PCT 11 P2 BW1
-1.73 TEC TEH 0.61 CBAY2 7
H 223 31 88 87 0.33 106 PCT 12 P2 VS2 0.74 TEC TEH 0.61 CBAY2 9
H 117 31 118 87 1.73 100 WAR 25 0.45 P12 VS3 0.84 VS3 TEH 0.61 NYAX2 63 H
50 31 118 87 0.66 66 PCT 21 P2 VS3 0.84 TEC TEH 0.61 CBAY2 31 H
93 31 124 87 0.29 121 PCT 12 P2 VS3
-0.64 TEC TEH 0.61 CBAY2 31 H
95 31 124 87 0.23 44 PCT 10 P2 VS3 0.86 TEC TEH 0.61 CBAY2 31 H
95 31 166 87 0.24 52 PCT 11 P2 BW2 0.89 TEC TEH 0.61 CBAY2 35 H
60 31 43 88 0.63 99 PCT 18 P2 BW2 0.51 TEC TEH 0.61 CBAY2 5
H 217 31 45 88 0.69 111 PCT 19 P2 BW1 0.79 TEC TEH 0.61 CBAY2 5
H 218 31 45 88 0.51 128 PCT 15 P2 BW2
-0.8 TEC TEH 0.61 CBAY2 5
H 218 31 45 88 0.41 75 PCT 13 P2 BW2 0.97 TEC TEH 0.61 CBAY2 5
H 218 31 47 88 2.28 108 WAR 28 0.23 P13 BW2 1.12 VS3 TEC 0.61 NYAX2 262 C
45 31 47 88 2.16 106 WAR 27 0.37 P23 BW1 0.88 VS3 TEH 0.61 NYAX2 61 H
47 31 47 88 1.05 101 PCT 25 P2 BW2 0.89 TEC TEH 0.61 CBAY2 5
H 219 31 47 88 0.72 128 PCT 19 P2 BW1 0.79 TEC TEH 0.61 CBAY2 5
H 219 31 47 88 0.27 119 PCT 10 P2 VS3
-1.02 TEC TEH 0.61 CBAY2 5
H 219 31 47 88 PID P2 BW1 0.79 TEH TEC 0.61 CBAY2 68 C
24 31 53 88 0.59 100 PCT 17 P2 VS3
-0.95 TEC TEH 0.61 CBAY2 5
H 222 31 57 88 1.88 102 WAR 26 0.68 P28 VS3 0.75 VS3 TEH 0.61 NYAX2 61 H
46 31 57 88 0.69 120 PCT 19 P2 VS3 0.82 TEC TEH 0.61 CBAY2 5
H 224 31 59 88 0.3 108 PCT 10 P2 BW2 0.86 TEC TEH 0.61 CBAY2 5
H 225 31 75 88 0.36 113 PCT 14 P2 VS3
-0.83 TEC TEH 0.61 CBAY2 7
H 308 31 77 88 NDF 124 09C 23.36 VS3 TEC 0.61 NYAX2 262 C
43 31 79 88 0.33 132 PCT 11 P2 09H 0.75 TEC TEH 0.61 CBAY2 11 H
109 31 91 88 0.27 85 PCT 12 P2 10C
-1.93 TEC TEH 0.61 CBAY2 11 H
103 31 97 88 0.21 103 PCT 10 P2 BW2 0.89 TEC TEH 0.61 CBAY2 11 H
100 31 103 88 0.38 127 PCT 15 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 15 H
88 31 125 88 0.51 80 PCT 17 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 33 H
80 31 48 89 0.52 112 PCT 15 P2 09H
-1.12 TEC TEH 0.61 CBAY2 5
H 216 31 54 89 0.33 87 PCT 11 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 5
H 213 31 64 89 0.45 135 PCT 12 P2 09H 0.78 TEC TEH 0.61 CBAY2 5
H 208 31 68 89 0.33 129 PCT 11 P2 VS3 0.7 TEC TEH 0.61 CBAY2 5
H 206 31 82 89 0.26 134 PCT 11 P2 VS2 0.65 TEC TEH 0.61 CBAY2 11 H
113 31 84 89 0.28 92 PCT 12 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 11 H
114 31 86 89 0.43 69 PCT 16 P2 BW1
-0.77 TEC TEH 0.61 CBAY2 11 H
115 31 88 89 0.3 91 PCT 13 P2 VS2 0.57 TEC TEH 0.61 CBAY2 11 H
116
U3R24 PVGS SG31 All Data Page 17 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 98 89 0.41 103 PCT 15 P2 10H 0.79 TEC TEH 0.61 CBAY2 11 H
121 31 102 89 0.22 135 PCT 10 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 15 H
90 31 128 89 0.31 151 PCT 11 P2 VS1 0.74 TEC TEH 0.61 CBAY2 29 H
98 31 128 89 0.24 119 PCT 9
P2 VS3
-0.7 TEC TEH 0.61 CBAY2 29 H
98 31 130 89 0.39 118 PCT 13 P2 VS1 0.74 TEC TEH 0.61 CBAY2 29 H
99 31 160 89 0.26 94 PCT 11 P2 VS1 0.81 TEC TEH 0.61 CBAY2 33 H
52 31 166 89 2.77 113 WAR 30 0.26 P16 BW2 1.32 VS3 TEC 0.61 NYAX2 264 C
5 31 166 89 1.24 66 PCT 28 P2 BW2 0.86 TEC TEH 0.61 CBAY2 33 H
55 31 166 89 NDF 78 11C 32.27 VS3 TEC 0.61 NYAX2 264 C
5 31 168 89 NDF 15 11C 29.27 VS3 TEC 0.61 NYAX2 264 C
8 31 170 89 2.4 111 WAR 28 0.23 P17 BW2 0.87 VS3 TEC 0.61 NYAX2 268 C
14 31 170 89 0.82 113 PCT 23 P2 BW2 0.87 TEC TEH 0.61 CBAY2 33 H
57 31 47 90 0.26 148 PCT 11 P2 BW1 1.13 TEC TEH 0.61 CBAY2 7
H 198 31 49 90 0.29 141 PCT 12 P2 BW1 0.92 TEC TEH 0.61 CBAY2 7
H 199 31 51 90 0.41 99 PCT 16 P2 BW1
-0.8 TEC TEH 0.61 CBAY2 7
H 200 31 51 90 0.29 81 PCT 12 P2 VS3
-0.91 TEC TEH 0.61 CBAY2 7
H 200 31 53 90 0.22 92 PCT 10 P2 VS3 0.8 TEC TEH 0.61 CBAY2 7
H 201 31 63 90 0.22 109 PCT 10 P2 BW2 1.06 TEC TEH 0.61 CBAY2 7
H 206 31 75 90 NDF P12 09H 13.86 17.98 VS3 TEH 0.61 NYAX2 63 H
44 31 75 90 1.95 268 PRX P8 09H 13.58 17.78 TEC TEH 0.61 CBAY2 7
H 212 31 77 90 NDF P32 09H 13.56 20.96 VS3 TEH 0.61 NYAX2 63 H
45 31 77 90 1.71 271 PRX P8 09H 13.56 20.96 TEC TEH 0.61 CBAY2 7
H 213 31 89 90 0.45 108 PCT 14 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 13 H
133 31 97 90 0.4 143 PCT 11 P2 09H 0.72 TEC TEH 0.61 CBAY2 11 H
123 31 111 90 0.22 50 PCT 10 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 31 H
89 31 127 90 0.46 46 PCT 17 P2 VS3
-1.05 TEC TEH 0.61 CBAY2 31 H
81 31 147 90 0.15 19 PCT 7
P2 BW1 0.91 TEC TEH 0.61 CBAY2 31 H
71 31 169 90 0.35 79 PCT 15 P2 BW2
-0.91 TEC TEH 0.61 CBAY2 35 H
33 31 48 91 2.68 104 WAR 30 0.9 P23 BW1 0.87 VS3 TEH 0.61 NYAX2 61 H
45 31 48 91 1.76 110 WAR 25 0.74 P8 BW1
-0.84 VS3 TEH 0.61 NYAX2 61 H
45 31 48 91 0.84 123 PCT 24 P2 BW1 0.84 TEC TEH 0.61 CBAY2 7
H 197 31 48 91 0.63 110 PCT 21 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 7
H 197 31 48 91 0.29 112 PCT 12 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 7
H 197 31 48 91 PID P2 BW1 0.84 TEH TEC 0.61 CBAY2 68 C
23 31 52 91 0.26 136 PCT 11 P2 VS3
-0.82 TEC TEH 0.61 CBAY2 7
H 195 31 58 91 0.37 113 PCT 15 P2 BW1
-0.7 TEC TEH 0.61 CBAY2 7
H 192 31 80 91 0.32 100 PCT 11 P2 VS3 0.75 TEC TEH 0.61 CBAY2 13 H
140 31 82 91 0.33 117 PCT 11 P2 VS2 0.75 TEC TEH 0.61 CBAY2 13 H
141 31 88 91 0.21 113 PCT 8
P2 BW1
-0.99 TEC TEH 0.61 CBAY2 13 H
144 31 96 91 0.23 76 PCT 9
P2 10H 0.81 TEC TEH 0.61 CBAY2 13 H
148 31 158 91 0.32 70 PCT 14 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 35 H
26 31 158 91 0.23 44 PCT 11 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 35 H
26 31 160 91 0.33 138 PCT 14 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 35 H
27
U3R24 PVGS SG31 All Data Page 18 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 162 91 0.29 52 PCT 13 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 35 H
28 31 164 91 0.3 40 PCT 13 P2 BW2
-0.82 TEC TEH 0.61 CBAY2 35 H
29 31 170 91 0.32 70 PCT 14 P2 BW2 0.92 TEC TEH 0.61 CBAY2 35 H
32 31 51 92 1.29 107 WAR 22 0.3 P8 BW1
-0.95 VS3 TEH 0.61 NYAX2 61 H
44 31 51 92 0.76 92 PCT 20 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 5
H 190 31 51 92 PID P2 BW1
-0.85 TEH TEC 0.61 CBAY2 68 C
22 31 53 92 0.34 88 PCT 11 P2 VS3 0.88 TEC TEH 0.61 CBAY2 5
H 191 31 65 92 0.56 137 PCT 13 P2 09H 0.78 TEC TEH 0.61 CBAY2 5
H 197 31 97 92 0.37 116 PCT 14 P2 10H 0.86 TEC TEH 0.61 CBAY2 15 H
103 31 105 92 0.27 146 PCT 12 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 15 H
99 31 119 92 0.23 136 PCT 9
P2 VS2
-0.98 TEC TEH 0.61 CBAY2 29 H
87 31 161 92 0.18 67 PCT 8
P2 VS2
-1.09 TEC TEH 0.61 CBAY2 33 H
32 31 165 92 0.38 46 PCT 14 P2 BW2 0.89 TEC TEH 0.61 CBAY2 33 H
30 31 52 93 0.39 96 PCT 13 P2 BW2 0.86 TEC TEH 0.61 CBAY2 5
H 188 31 58 93 0.32 33 PCT 11 P2 BW2 0.54 TEC TEH 0.61 CBAY2 5
H 185 31 60 93 1.33 73 PCT 28 P2 VS4
-1 TEC TEH 0.61 CBAY2 5
H 184 31 60 93 1.74 101 WAR 25 0.17 P29 VS4
-1 VS3 TEC 0.61 NYAX2 262 C
44 31 84 93 0.2 101 PCT 10 P2 09H 0.79 TEC TEH 0.61 CBAY2 15 H
118 31 90 93 0.41 97 PCT 16 P2 10H
-1.04 TEC TEH 0.61 CBAY2 15 H
121 31 108 93 0.36 157 PCT 10 P2 09H 0.71 TEC TEH 0.61 CBAY2 15 H
130 31 114 93 0.45 140 PCT 15 P2 VS4 0.73 TEC TEH 0.61 CBAY2 29 H
54 31 158 93 0.26 102 PCT 11 P2 VS4 0.53 TEC TEH 0.61 CBAY2 33 H
21 31 160 93 0.38 78 PCT 14 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 33 H
22 31 51 94 0.29 98 PCT 12 P2 BW1
-0.8 TEC TEH 0.61 CBAY2 7
H 169 31 53 94 0.22 118 PCT 10 P2 VS3 0.84 TEC TEH 0.61 CBAY2 7
H 170 31 57 94 0.25 138 PCT 11 P2 BW1 0.31 TEC TEH 0.61 CBAY2 7
H 172 31 61 94 0.24 107 PCT 11 P2 BW2 0.9 TEC TEH 0.61 CBAY2 7
H 174 31 65 94 0.29 116 PCT 12 P2 VS4 0.83 TEC TEH 0.61 CBAY2 7
H 176 31 67 94 0.25 92 PCT 11 P2 BW1 0.85 TEC TEH 0.61 CBAY2 7
H 177 31 67 94 0.26 80 PCT 11 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 7
H 177 31 69 94 0.32 121 PCT 13 P2 BW1 0.88 TEC TEH 0.61 CBAY2 7
H 178 31 69 94 0.3 67 PCT 12 P2 VS4 0.79 TEC TEH 0.61 CBAY2 7
H 178 31 71 94 0.27 86 PCT 12 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 7
H 179 31 111 94 1.41 105 PCT 32 P2 VS2
-0.85 TEC TEH 0.61 CBAY2 31 H
52 31 111 94 3.32 97 WAR 32 0.55 P12 VS2
-0.85 VS3 TEH 0.61 NYAX2 63 H
40 31 111 94 0.48 94 PCT 17 P2 VS3 0.64 TEC TEH 0.61 CBAY2 31 H
52 31 111 94 PID P2 VS2
-0.85 TEH TEC 0.61 CBAY2 68 C
43 31 139 94 0.2 29 PCT 9
P2 BW1 0.92 TEC TEH 0.61 CBAY2 31 H
38 31 167 94 0.37 136 PCT 15 P2 BW2
-0.8 TEC TEH 0.61 CBAY2 35 H
7 31 50 95 1.51 118 WAR 23 0.52 P12 VS3 0.71 VS3 TEH 0.61 NYAX2 61 H
43 31 50 95 0.58 117 PCT 20 P2 VS3 0.71 TEC TEH 0.61 CBAY2 7
H 168 31 50 95 0.54 108 PCT 19 P2 BW2 0.97 TEC TEH 0.61 CBAY2 7
H 168 31 50 95 PID P2 VS3 0.71 TEH TEC 0.61 CBAY2 68 C
21
U3R24 PVGS SG31 All Data Page 19 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 56 95 0.32 62 PCT 13 P2 BW2 1.93 TEC TEH 0.61 CBAY2 7
H 165 31 56 95 0.23 131 PCT 10 P2 BW1
-1.73 TEC TEH 0.61 CBAY2 7
H 165 31 58 95 0.29 112 PCT 12 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 7
H 164 31 60 95 0.24 110 PCT 11 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 7
H 163 31 66 95 0.33 131 PCT 11 P2 09H 0.71 TEC TEH 0.61 CBAY2 7
H 160 31 70 95 0.31 75 PCT 13 P2 08H
-0.1 TEC TEH 0.61 CBAY2 7
H 158 31 72 95 0.28 108 PCT 12 P2 VS3 0.32 TEC TEH 0.61 CBAY2 7
H 157 31 128 95 0.47 92 PCT 17 P2 VS3 0.73 TEC TEH 0.61 CBAY2 31 H
24 31 130 95 0.28 59 PCT 12 P2 VS2 0.81 TEC TEH 0.61 CBAY2 31 H
25 31 61 96 0.28 55 PCT 10 P2 BW2 0.91 TEC TEH 0.61 CBAY2 5
H 169 31 65 96 0.27 94 PCT 10 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 5
H 171 31 71 96 0.3 93 PCT 10 P2 VS3
-0.91 TEC TEH 0.61 CBAY2 5
H 174 31 97 96 0.32 135 PCT 14 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 15 H
140 31 99 96 0.3 113 PCT 13 P2 VS3
-1.11 TEC TEH 0.61 CBAY2 15 H
139 31 107 96 0.3 137 PCT 13 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 15 H
135 31 111 96 2.06 99 WAR 27 0.54 P12 VS2
-0.9 VS3 TEH 0.61 NYAX2 63 H
31 31 111 96 0.79 116 PCT 24 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 15 H
133 31 121 96 0.46 131 PCT 15 P2 VS2
-0.93 TEC TEH 0.61 CBAY2 29 H
49 31 48 97 0.5 121 PCT 15 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 5
H 164 31 48 97 0.46 76 PCT 14 P2 VS3 0.95 TEC TEH 0.61 CBAY2 5
H 164 31 50 97 0.39 94 PCT 13 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 5
H 163 31 54 97 1.85 102 WAR 25 0.47 P28 VS3
-0.87 VS3 TEH 0.61 NYAX2 61 H
42 31 54 97 0.78 108 PCT 21 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 5
H 161 31 54 97 0.33 52 PCT 11 P2 09H 0.81 TEC TEH 0.61 CBAY2 5
H 161 31 54 97 PID P2 VS3
-0.9 TEH TEC 0.61 CBAY2 68 C
20 31 60 97 0.36 119 PCT 12 P2 VS2
-0.96 TEC TEH 0.61 CBAY2 5
H 158 31 64 97 0.29 84 PCT 10 P2 VS2 0.95 TEC TEH 0.61 CBAY2 5
H 156 31 66 97 0.25 92 PCT 9
P2 VS3 0.52 TEC TEH 0.61 CBAY2 5
H 155 31 76 97 NDF P14 09H 10.15 16.37 VS3 TEH 0.61 NYAX2 63 H
30 31 76 97 1.55 270 PRX P8 09H 10.54 16.64 TEC TEH 0.61 CBAY2 15 H
151 31 78 97 0.28 107 PCT 12 P2 VS3 0.59 TEC TEH 0.61 CBAY2 15 H
152 31 82 97 0.21 129 PCT 10 P2 VS3 0.82 TEC TEH 0.61 CBAY2 15 H
154 31 90 97 0.43 97 PCT 17 P2 10H
-1.27 TEC TEH 0.61 CBAY2 15 H
158 31 98 97 0.27 62 PCT 11 P2 10H 0.78 TEC TEH 0.61 CBAY2 15 H
162 31 106 97 0.36 128 PCT 15 P2 VS2 0.75 TEC TEH 0.61 CBAY2 15 H
166 31 114 97 0.39 129 PCT 13 P2 VS2 0.76 TEC TEH 0.61 CBAY2 29 H
17 31 118 97 0.36 128 PCT 12 P2 VS3 0.97 TEC TEH 0.61 CBAY2 29 H
19 31 130 97 0.49 137 PCT 16 P2 VS3
-0.95 TEC TEH 0.61 CBAY2 29 H
25 31 132 97 0.24 146 PCT 9
P2 VS1 0.67 TEC TEH 0.61 CBAY2 29 H
26 31 148 97 0.33 127 PCT 12 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 29 H
34 31 57 98 0.34 84 PCT 14 P2 BW1 1.95 TEC TEH 0.61 CBAY2 7
H 144 31 59 98 0.42 120 PCT 16 P2 VS2
-1.14 TEC TEH 0.61 CBAY2 7
H 145 31 67 98 0.34 135 PCT 14 P2 VS2 0.96 TEC TEH 0.61 CBAY2 7
H 149
U3R24 PVGS SG31 All Data Page 20 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 71 98 0.38 99 PCT 15 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 7
H 151 31 73 98 0.28 121 PCT 11 P2 06H 0.81 TEC TEH 0.61 CBAY2 7
H 152 31 91 98 0.61 154 PCT 12 P2 09H 0.61 TEC TEH 0.61 CBAY2 13 H
198 31 111 98 0.2 35 PCT 9
P2 BW1
-0.84 TEC TEH 0.61 CBAY2 31 H
15 31 131 98 0.27 61 PCT 12 P2 BW1 0.89 TEC TEH 0.61 CBAY2 31 H
5 31 131 98 0.25 126 PCT 11 P2 BW1
-0.95 TEC TEH 0.61 CBAY2 31 H
5 31 56 99 0.3 100 PCT 12 P2 BW1
-1.69 TEC TEH 0.61 CBAY2 7
H 137 31 58 99 0.23 139 PCT 10 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 7
H 136 31 62 99 0.27 133 PCT 11 P2 VS2
-0.66 TEC TEH 0.61 CBAY2 7
H 134 31 68 99 0.37 115 PCT 14 P2 VS3 0.6 TEC TEH 0.61 CBAY2 7
H 131 31 70 99 0.28 103 PCT 12 P2 VS4 0.38 TEC TEH 0.61 CBAY2 7
H 130 31 72 99 0.24 126 PCT 11 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 7
H 129 31 76 99 0.84 140 PCT 19 P2 09H 0.78 TEC TEH 0.61 CBAY2 7
H 127 31 90 99 0.47 122 PCT 13 P2 10C
-1.74 TEC TEH 0.61 CBAY2 13 H
210 31 94 99 0.41 141 PCT 10 P2 09H 0.75 TEC TEH 0.61 CBAY2 13 H
212 31 124 99 0.36 111 PCT 14 P2 VS1 0.72 TEC TEH 0.61 CBAY2 27 H
97 31 126 99 0.48 111 PCT 17 P2 VS3
-0.67 TEC TEH 0.61 CBAY2 27 H
98 31 128 99 0.31 132 PCT 13 P2 VS1 0.59 TEC TEH 0.61 CBAY2 27 H
99 31 160 99 0.29 92 PCT 12 P2 BW2 0.94 TEC TEH 0.61 CBAY2 31 H
261 31 168 99 0.37 76 PCT 14 P2 03C 0.85 TEC TEH 0.61 CBAY2 31 H
265 31 49 100 0.39 132 PCT 13 P2 BW1 0.87 TEC TEH 0.61 CBAY2 5
H 137 31 55 100 0.27 112 PCT 10 P2 BW1
-1.49 TEC TEH 0.61 CBAY2 5
H 140 31 57 100 0.28 109 PCT 10 P2 VS3 0.84 TEC TEH 0.61 CBAY2 5
H 141 31 61 100 0.28 90 PCT 10 P2 VS4 0.83 TEC TEH 0.61 CBAY2 5
H 143 31 65 100 0.3 98 PCT 10 P2 BW1 0.8 TEC TEH 0.61 CBAY2 5
H 145 31 107 100 0.34 122 PCT 14 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 15 H
172 31 109 100 0.21 131 PCT 10 P2 VS3
-1.06 TEC TEH 0.61 CBAY2 15 H
171 31 169 100 0.6 140 PCT 15 P2 04C 0.88 TEC TEH 0.61 CBAY2 29 H
251 31 171 100 NDF P32 11C 31.27 VS3 TEC 0.61 NYAX2 264 C
40 31 48 101 0.34 140 PCT 11 P2 BW1 0.68 TEC TEH 0.61 CBAY2 5
H 228 31 50 101 0.52 97 PCT 16 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 5
H 136 31 52 101 0.55 109 PCT 16 P2 VS3
-0.92 TEC TEH 0.61 CBAY2 5
H 135 31 52 101 0.33 109 PCT 11 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 5
H 135 31 54 101 2.68 99 WAR 30 0.83 P7 BW1
-1.34 VS3 TEH 0.61 NYAX2 61 H
41 31 54 101 0.99 103 PCT 24 P2 BW1
-1.33 TEC TEH 0.61 CBAY2 5
H 134 31 54 101 0.39 100 PCT 13 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 5
H 134 31 54 101 PID P2 BW1
-1.33 TEH TEC 0.61 CBAY2 68 C
18 31 64 101 0.29 104 PCT 10 P2 VS3 0.78 TEC TEH 0.61 CBAY2 5
H 129 31 66 101 2.07 106 WAR 27 0.56 P4 VS3 0.74 VS3 TEH 0.61 NYAX2 61 H
54 31 66 101 1.13 119 PCT 26 P2 VS3 0.75 TEC TEH 0.61 CBAY2 5
H 128 31 74 101 0.48 124 PCT 13 P2 09H
-0.3 TEC TEH 0.61 CBAY2 5
H 124 31 74 101 0.44 136 PCT 10 P2 08H 0.71 TEC TEH 0.61 CBAY2 5
H 124 31 74 101 0.25 138 PCT 9
P2 09H 0.73 TEC TEH 0.61 CBAY2 5
H 124
U3R24 PVGS SG31 All Data Page 21 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 76 101 1.67 113 WAR 24 0.59 P21 09H 0.86 09H TEH 0.61 NYAX2 63 H
21 31 76 101 0.73 121 PCT 22 P2 09H 0.86 TEC TEH 0.61 CBAY2 15 H
188 31 80 101 0.29 120 PCT 13 P2 VS2 0.77 TEC TEH 0.61 CBAY2 15 H
190 31 84 101 0.24 123 PCT 12 P2 09H 0.74 TEC TEH 0.61 CBAY2 15 H
192 31 96 101 0.52 153 PCT 11 P2 09H 0.72 TEC TEH 0.61 CBAY2 15 H
198 31 96 101 0.31 31 PCT 11 P2 10H 0.82 TEC TEH 0.61 CBAY2 15 H
198 31 106 101 0.23 99 PCT 11 P2 VS2 0.69 TEC TEH 0.61 CBAY2 15 H
203 31 118 101 0.46 125 PCT 15 P2 VS3 0.56 TEC TEH 0.61 CBAY2 25 H
94 31 120 101 0.27 99 PCT 10 P2 VS2 0.74 TEC TEH 0.61 CBAY2 25 H
95 31 122 101 0.25 39 PCT 10 P2 VS1 0.57 TEC TEH 0.61 CBAY2 25 H
96 31 130 101 0.26 115 PCT 10 P2 VS4 0.61 TEC TEH 0.61 CBAY2 25 H
100 31 65 102 0.23 100 PCT 10 P2 VS3
-1.05 TEC TEH 0.61 CBAY2 7
H 121 31 111 102 0.2 90 PCT 9
P2 VS2
-1.11 TEC TEH 0.61 CBAY2 27 H
90 31 165 102 0.16 74 PCT 8
P2 11H 0.35 TEC TEH 0.61 CBAY2 31 H
246 31 50 103 0.23 79 PCT 10 P2 BW2 0.97 TEC TEH 0.61 CBAY2 7
H 114 31 52 103 0.42 92 PCT 16 P2 BW1 0.66 TEC TEH 0.61 CBAY2 7
H 113 31 54 103 0.45 122 PCT 16 P2 VS3
-0.97 TEC TEH 0.61 CBAY2 7
H 112 31 58 103 0.29 109 PCT 12 P2 BW1 0.57 TEC TEH 0.61 CBAY2 7
H 110 31 68 103 0.27 131 PCT 10 P2 09H 0.72 TEC TEH 0.61 CBAY2 7
H 105 31 72 103 0.26 123 PCT 10 P2 09H
-0.3 TEC TEH 0.61 CBAY2 7
H 103 31 74 103 0.43 97 PCT 16 P2 VS2
-0.91 TEC TEH 0.61 CBAY2 7
H 102 31 78 103 0.24 146 PCT 9
P2 09H 0.9 TEC TEH 0.61 CBAY2 17 H
20 31 90 103 1.25 113 PCT 28 P2 10C
-1.81 TEC TEH 0.61 CBAY2 17 H
26 31 90 103 2.2 103 WAR 27 0.17 P22 10C
-1.51 10C TEC 0.61 NYAX2 262 C
36 31 96 103 0.22 141 PCT 8
P2 BW1
-0.92 TEC TEH 0.61 CBAY2 17 H
29 31 102 103 0.58 129 PCT 17 P2 VS2 0.61 TEC TEH 0.61 CBAY2 17 H
32 31 122 103 0.41 103 PCT 15 P2 VS3 0.84 TEC TEH 0.61 CBAY2 27 H
60 31 126 103 0.25 100 PCT 11 P2 VS3
-0.72 TEC TEH 0.61 CBAY2 27 H
62 31 132 103 0.31 59 PCT 13 P2 VS1 0.77 TEC TEH 0.61 CBAY2 27 H
65 31 138 103 0.22 121 PCT 10 P2 VS2 0.68 TEC TEH 0.61 CBAY2 27 H
68 31 164 103 0.23 97 PCT 10 P2 BW2 0.89 TEC TEH 0.61 CBAY2 31 H
240 31 166 103 2.16 105 PLP 4
TSC 0.7 01C TEC 0.61 NYAX2 264 C
52 31 170 103 0.32 149 PCT 10 P2 11H 0.29 TEC TEH 0.61 CBAY2 31 H
243 31 49 104 0.65 102 PCT 18 P2 BW1
-0.81 TEC TEH 0.61 CBAY2 5
H 110 31 61 104 0.38 128 PCT 13 P2 BW2 0.86 TEC TEH 0.61 CBAY2 5
H 116 31 67 104 0.35 87 PCT 12 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 5
H 119 31 71 104 1.81 127 WAR 25 0.38 P6 VS4
-0.84 VS3 TEC 0.61 NYAX2 262 C
35 31 71 104 0.72 98 PCT 19 P2 VS4
-0.8 TEC TEH 0.61 CBAY2 5
H 121 31 87 104 0.23 107 PCT 11 P2 BW1 0.9 TEC TEH 0.61 CBAY2 19 H
16 31 127 104 0.28 93 PCT 11 P2 VS3
-1.12 TEC TEH 0.61 CBAY2 25 H
84 31 48 105 0.28 59 PCT 10 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 5
H 109 31 48 105 0.27 131 PCT 10 P2 BW1 0.79 TEC TEH 0.61 CBAY2 5
H 109 31 52 105 0.34 92 PCT 11 P2 VS3 0.84 TEC TEH 0.61 CBAY2 5
H 107
U3R24 PVGS SG31 All Data Page 22 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 60 105 0.36 105 PCT 12 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 5
H 104 31 76 105 0.83 137 PCT 20 P2 09H 0.7 TEC TEH 0.61 CBAY2 19 H
22 31 76 105 1.04 110 WAR 20 0.26 P20 09H 0.7 VS3 TEH 0.61 NYAX2 63 H
17 31 76 105 NDF P6 09H 8.78 15.2 VS3 TEH 0.61 NYAX2 63 H
17 31 76 105 NDF P26 09H 20.41 24.3 VS3 TEH 0.61 NYAX2 63 H
17 31 76 105 1.91 274 PRX P8 09H 8.86 15.3 TEC TEH 0.61 CBAY2 19 H
22 31 92 105 0.27 68 PCT 12 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 19 H
30 31 98 105 0.38 112 PCT 15 P2 10H 0.81 TEC TEH 0.61 CBAY2 19 H
33 31 98 105 0.32 100 PCT 13 P2 BW1 1
TEC TEH 0.61 CBAY2 19 H
33 31 116 105 2.07 99 WAR 27 0.49 P12 VS2 0.89 VS3 TEH 0.61 NYAX2 63 H
18 31 116 105 0.86 106 PCT 23 P2 VS2 0.89 TEC TEH 0.61 CBAY2 25 H
56 31 116 105 0.25 144 PCT 10 P2 VS1
-0.79 TEC TEH 0.61 CBAY2 25 H
56 31 124 105 0.3 142 PCT 11 P2 VS1 0.67 TEC TEH 0.61 CBAY2 25 H
60 31 150 105 0.24 130 PCT 9
P2 BW1
-0.84 TEC TEH 0.61 CBAY2 29 H
217 31 49 106 0.29 96 PCT 12 P2 BW2 0.99 TEC TEH 0.61 CBAY2 7
H 86 31 59 106 0.31 133 PCT 13 P2 BW2 0.92 TEC TEH 0.61 CBAY2 7
H 91 31 61 106 0.34 129 PCT 14 P2 BW2
-0.07 TEC TEH 0.61 CBAY2 7
H 92 31 65 106 0.22 127 PCT 10 P2 VS4 0.8 TEC TEH 0.61 CBAY2 7
H 94 31 75 106 0.42 101 PCT 16 P2 VS2
-1.01 TEC TEH 0.61 CBAY2 7
H 99 31 79 106 0.44 123 PCT 14 P2 VS2 0.72 TEC TEH 0.61 CBAY2 17 H
52 31 81 106 0.3 136 PCT 11 P2 VS2 0.72 TEC TEH 0.61 CBAY2 17 H
51 31 93 106 0.38 118 PCT 13 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 17 H
45 31 95 106 0.34 131 PCT 12 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 17 H
44 31 95 106 0.46 153 PCT 10 P2 09H 0.78 TEC TEH 0.61 CBAY2 17 H
44 31 99 106 0.22 106 PCT 8
P2 BW1 0.92 TEC TEH 0.61 CBAY2 17 H
42 31 103 106 0.5 117 PCT 16 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 17 H
40 31 109 106 0.39 130 PCT 13 P2 VS3
-1.03 TEC TEH 0.61 CBAY2 17 H
37 31 119 106 0.26 54 PCT 11 P2 VS2
-0.98 TEC TEH 0.61 CBAY2 27 H
50 31 48 107 0.41 91 PCT 16 P2 VS3 0.82 TEC TEH 0.61 CBAY2 7
H 85 31 50 107 0.26 121 PCT 11 P2 08H 0.66 TEC TEH 0.61 CBAY2 7
H 84 31 52 107 0.26 111 PCT 11 P2 VS3 0.79 TEC TEH 0.61 CBAY2 7
H 83 31 56 107 0.23 85 PCT 10 P2 BW2
-1.6 TEC TEH 0.61 CBAY2 7
H 81 31 60 107 0.34 114 PCT 14 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 7
H 79 31 62 107 0.3 104 PCT 12 P2 BW2 0.88 TEC TEH 0.61 CBAY2 7
H 78 31 66 107 0.42 128 PCT 13 P2 09H 0.62 TEC TEH 0.61 CBAY2 7
H 76 31 88 107 0.33 120 PCT 12 P2 BW1 0.98 TEC TEH 0.61 CBAY2 17 H
58 31 92 107 0.3 118 PCT 11 P2 BW1
-0.9 TEC TEH 0.61 CBAY2 17 H
60 31 94 107 0.22 125 PCT 8
P2 BW1
-0.94 TEC TEH 0.61 CBAY2 17 H
61 31 98 107 0.19 95 PCT 7
P2 BW1 1.08 TEC TEH 0.61 CBAY2 17 H
63 31 100 107 0.5 136 PCT 12 P2 10H 0.65 TEC TEH 0.61 CBAY2 17 H
64 31 112 107 0.26 82 PCT 11 P2 BW1 1
TEC TEH 0.61 CBAY2 27 H
18 31 112 107 0.22 88 PCT 10 P2 VS4
-1.15 TEC TEH 0.61 CBAY2 27 H
18 31 118 107 0.2 116 PCT 9
P2 VS3
-0.46 TEC TEH 0.61 CBAY2 27 H
21
U3R24 PVGS SG31 All Data Page 23 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 124 107 0.3 87 PCT 12 P2 BW1 0.87 TEC TEH 0.61 CBAY2 27 H
24 31 132 107 0.22 107 PCT 10 P2 VS1 0.66 TEC TEH 0.61 CBAY2 27 H
28 31 160 107 0.27 78 PCT 11 P2 BW2 1.01 TEC TEH 0.61 CBAY2 31 H
214 31 47 108 2.2 105 WAR 27 0.81 P6 BW1
-0.79 VS3 TEH 0.61 NYAX2 61 H
40 31 47 108 0.97 95 PCT 23 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 5
H 229 31 47 108 0.28 111 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 5
H 229 31 47 108 PID P2 BW1
-0.79 TEH TEC 0.61 CBAY2 68 C
17 31 57 108 0.28 78 PCT 10 P2 BW2 1.85 TEC TEH 0.61 CBAY2 5
H 87 31 59 108 0.33 118 PCT 11 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 5
H 88 31 61 108 0.27 135 PCT 10 P2 BW2 0.88 TEC TEH 0.61 CBAY2 5
H 89 31 67 108 0.47 101 PCT 15 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 5
H 92 31 75 108 0.64 109 PCT 18 P2 VS2
-0.82 TEC TEH 0.61 CBAY2 5
H 96 31 85 108 0.21 108 PCT 10 P2 VS4
-0.74 TEC TEH 0.61 CBAY2 19 H
53 31 89 108 1.06 112 PCT 28 P2 VS2
-0.78 TEC TEH 0.61 CBAY2 19 H
52 31 89 108 2.24 104 WAR 28 0.53 P12 VS2
-0.78 VS3 TEH 0.61 NYAX2 63 H
13 31 99 108 0.24 61 PCT 11 P2 BW1 0.84 TEC TEH 0.61 CBAY2 19 H
47 31 103 108 0.72 112 PCT 23 P2 VS4 0.93 TEC TEH 0.61 CBAY2 19 H
45 31 103 108 1.3 297 WAR 22 0.23 P31 VS4 0.89 VS3 TEC 0.61 NYAX2 262 C
39 31 103 108 1.21 118 WAR 21 0.23 P31 VS4 0.54 VS3 TEC 0.61 NYAX2 262 C
39 31 103 108 0.34 99 PCT 14 P2 VS2
-0.97 TEC TEH 0.61 CBAY2 19 H
45 31 103 108 0.33 124 PCT 14 P2 VS4 0.59 TEC TEH 0.61 CBAY2 19 H
45 31 103 108 0.26 81 PCT 11 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 19 H
45 31 105 108 2.16 102 WAR 27 0.83 P12 VS3
-0.87 VS3 TEH 0.61 NYAX2 63 H
14 31 105 108 1.64 109 WAR 24 0.41 P28 VS2 1.01 VS3 TEH 0.61 NYAX2 63 H
14 31 105 108 0.75 110 PCT 23 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 19 H
44 31 105 108 0.53 116 PCT 19 P2 VS2 0.81 TEC TEH 0.61 CBAY2 19 H
44 31 105 108 0.36 98 PCT 15 P2 VS4
-0.94 TEC TEH 0.61 CBAY2 19 H
44 31 105 108 0.33 106 PCT 14 P2 VS3 1.01 TEC TEH 0.61 CBAY2 19 H
44 31 105 108 0.25 78 PCT 11 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 19 H
44 31 107 108 1.44 111 PCT 33 P2 VS4
-0.87 TEC TEH 0.61 CBAY2 19 H
43 31 107 108 3.17 101 WAR 32 0.65 P7 VS4
-0.98 VS3 TEC 0.61 NYAX2 262 C
40 31 107 108 PID P2 VS4
-0.87 TEH TEC 0.61 CBAY2 68 C
42 31 109 108 0.31 93 PCT 13 P2 VS3
-1 TEC TEH 0.61 CBAY2 19 H
42 31 109 108 0.25 60 PCT 11 P2 VS4 0.81 TEC TEH 0.61 CBAY2 19 H
42 31 111 108 0.36 94 PCT 15 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 19 H
41 31 113 108 1.13 155 PCT 17 P2 10H 0.76 TEC TEH 0.61 CBAY2 25 H
54 31 117 108 0.36 116 PCT 13 P2 VS2
-1.13 TEC TEH 0.61 CBAY2 25 H
52 31 171 108 1.23 113 PCT 27 P2 VS1
-0.78 TEC TEH 0.61 CBAY2 29 H
206 31 171 108 1.41 79 WAR 22 0.3 P5 VS1
-0.58 VS3 TEH 0.61 NYAX2 65 H
6 31 50 109 0.48 70 PCT 15 P2 VS3 0.89 TEC TEH 0.61 CBAY2 5
H 82 31 58 109 0.47 111 PCT 14 P2 VS3 0.98 TEC TEH 0.61 CBAY2 5
H 78 31 82 109 0.66 153 PCT 13 P2 09H 0.84 TEC TEH 0.61 CBAY2 19 H
61 31 92 109 3.63 103 WAR 34 0.94 P28 VS3
-0.74 VS3 TEH 0.61 NYAX2 63 H
12
U3R24 PVGS SG31 All Data Page 24 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 92 109 1.39 112 PCT 32 P2 VS3
-0.74 TEC TEH 0.61 CBAY2 19 H
66 31 92 109 0.27 124 PCT 12 P2 BW2
-0.82 TEC TEH 0.61 CBAY2 19 H
66 31 92 109 PID P2 VS3
-0.74 TEH TEC 0.61 CBAY2 68 C
41 31 98 109 0.41 111 PCT 16 P2 VS4
-0.97 TEC TEH 0.61 CBAY2 19 H
69 31 98 109 0.27 104 PCT 12 P2 BW1 1
TEC TEH 0.61 CBAY2 19 H
69 31 98 109 0.25 51 PCT 11 P2 BW2 0.89 TEC TEH 0.61 CBAY2 19 H
69 31 102 109 0.32 77 PCT 13 P2 VS2 0.84 TEC TEH 0.61 CBAY2 19 H
71 31 112 109 0.24 90 PCT 11 P2 VS4
-0.97 TEC TEH 0.61 CBAY2 19 H
76 31 116 109 0.27 94 PCT 11 P2 VS2 0.86 TEC TEH 0.61 CBAY2 25 H
19 31 118 109 0.24 117 PCT 10 P2 VS4 0.36 TEC TEH 0.61 CBAY2 25 H
20 31 122 109 0.44 113 PCT 15 P2 VS2 0.81 TEC TEH 0.61 CBAY2 25 H
22 31 122 109 0.26 97 PCT 10 P2 VS3 0.89 TEC TEH 0.61 CBAY2 25 H
22 31 122 109 0.23 136 PCT 9
P2 VS3 0.56 TEC TEH 0.61 CBAY2 25 H
22 31 130 109 0.41 117 PCT 14 P2 VS1 0.64 TEC TEH 0.61 CBAY2 25 H
26 31 130 109 0.41 111 PCT 14 P2 VS4
-0.7 TEC TEH 0.61 CBAY2 25 H
26 31 130 109 0.32 117 PCT 12 P2 VS3 0.94 TEC TEH 0.61 CBAY2 25 H
26 31 132 109 0.37 106 PCT 13 P2 VS3 0.86 TEC TEH 0.61 CBAY2 25 H
27 31 138 109 0.2 102 PCT 8
P2 BW1
-0.82 TEC TEH 0.61 CBAY2 25 H
30 31 162 109 0.35 138 PCT 12 P2 BW2
-0.96 TEC TEH 0.61 CBAY2 29 H
201 31 170 109 NDF P2 11C 29.95 VS3 TEC 0.61 NYAX2 264 C
59 31 51 110 0.42 131 PCT 16 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 7
H 57 31 61 110 0.26 104 PCT 11 P2 BW2
-0.78 TEC TEH 0.61 CBAY2 7
H 62 31 63 110 0.27 127 PCT 11 P2 BW2 0.96 TEC TEH 0.61 CBAY2 7
H 63 31 65 110 0.22 74 PCT 10 P2 VS2
-0.85 TEC TEH 0.61 CBAY2 7
H 64 31 67 110 0.21 133 PCT 10 P2 BW1 0.86 TEC TEH 0.61 CBAY2 7
H 65 31 75 110 0.22 120 PCT 10 P2 VS3 0.84 TEC TEH 0.61 CBAY2 7
H 69 31 83 110 0.54 130 PCT 14 P2 08H 0.73 TEC TEH 0.61 CBAY2 17 H
83 31 83 110 0.25 140 PCT 9
P2 09H
-0.28 TEC TEH 0.61 CBAY2 17 H
83 31 87 110 0.63 127 PCT 16 P2 09H 0.74 TEC TEH 0.61 CBAY2 17 H
81 31 91 110 0.38 110 PCT 13 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 17 H
79 31 93 110 0.42 104 PCT 14 P2 VS2 0.77 TEC TEH 0.61 CBAY2 17 H
78 31 93 110 0.29 129 PCT 11 P2 VS3 0.72 TEC TEH 0.61 CBAY2 17 H
78 31 95 110 1.91 110 WAR 26 0.34 P7 VS4
-0.61 VS3 TEC 0.61 NYAX2 262 C
37 31 95 110 0.8 103 PCT 21 P2 VS4
-0.79 TEC TEH 0.61 CBAY2 17 H
77 31 95 110 0.48 110 PCT 14 P2 10H 0.77 TEC TEH 0.61 CBAY2 17 H
77 31 95 110 0.33 129 PCT 11 P2 VS2 0.74 TEC TEH 0.61 CBAY2 17 H
77 31 103 110 0.47 122 PCT 15 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 17 H
73 31 105 110 0.31 89 PCT 11 P2 VS4
-0.81 TEC TEH 0.61 CBAY2 17 H
72 31 107 110 0.23 137 PCT 9
P2 BW1
-1.5 TEC TEH 0.61 CBAY2 17 H
71 31 109 110 0.22 114 PCT 9
P2 VS3 0.31 TEC TEH 0.61 CBAY2 17 H
70 31 119 110 0.21 134 PCT 10 P2 VS1
-0.82 TEC TEH 0.61 CBAY2 27 H
13 31 127 110 0.28 106 PCT 12 P2 VS1 0.33 TEC TEH 0.61 CBAY2 27 H
9 31 167 110 0.36 108 PCT 14 P2 BW2 0.81 TEC TEH 0.61 CBAY2 31 H
198
U3R24 PVGS SG31 All Data Page 25 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 171 110 2.69 180 DNT P1 TSH 1.02 TEC TEH 0.61 CBAY2 31 H
196 31 171 110 NDF 111 TSH 1.01 01H TEH 0.61 NYAX2 65 H
5 31 50 111 0.28 142 PCT 12 P2 BW1 0.86 TEC TEH 0.61 CBAY2 7
H 56 31 50 111 0.22 109 PCT 10 P2 VS3 0.81 TEC TEH 0.61 CBAY2 7
H 56 31 52 111 0.18 112 PCT 9
P2 09H 0.79 TEC TEH 0.61 CBAY2 7
H 55 31 98 111 0.23 95 PCT 9
P2 BW1 1.05 TEC TEH 0.61 CBAY2 17 H
95 31 102 111 0.44 123 PCT 14 P2 VS2 0.76 TEC TEH 0.61 CBAY2 17 H
96 31 114 111 0.23 116 PCT 11 P2 VS2 0.71 TEC TEH 0.61 CBAY2 23 H
279 31 126 111 0.27 100 PCT 12 P2 VS3
-0.67 TEC TEH 0.61 CBAY2 23 H
285 31 128 111 0.27 95 PCT 12 P2 VS1 0.67 TEC TEH 0.61 CBAY2 23 H
286 31 128 111 0.22 73 PCT 10 P2 VS5
-0.85 TEC TEH 0.61 CBAY2 23 H
286 31 162 111 0.58 82 PCT 19 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 31 H
191 31 53 112 0.31 124 PCT 11 P2 BW1
-0.55 TEC TEH 0.61 CBAY2 5
H 58 31 59 112 0.35 123 PCT 12 P2 VS3 0.83 TEC TEH 0.61 CBAY2 5
H 61 31 59 112 0.33 96 PCT 11 P2 BW2 0.91 TEC TEH 0.61 CBAY2 5
H 61 31 65 112 0.66 114 PCT 18 P2 BW2 0.91 TEC TEH 0.61 CBAY2 5
H 64 31 65 112 0.43 141 PCT 10 P2 09H 0.75 TEC TEH 0.61 CBAY2 5
H 64 31 85 112 0.31 103 PCT 13 P2 VS2 0.64 TEC TEH 0.61 CBAY2 19 H
90 31 95 112 0.51 113 PCT 18 P2 10H
-0.17 TEC TEH 0.61 CBAY2 19 H
85 31 103 112 0.51 116 PCT 17 P2 10H 0.83 TEC TEH 0.61 CBAY2 19 H
81 31 103 112 0.24 125 PCT 11 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 19 H
81 31 107 112 0.25 141 PCT 11 P2 BW1
-1.61 TEC TEH 0.61 CBAY2 19 H
79 31 117 112 0.51 125 PCT 17 P2 VS2
-1.06 TEC TEH 0.61 CBAY2 25 H
15 31 123 112 0.28 119 PCT 11 P2 VS1 0.62 TEC TEH 0.61 CBAY2 25 H
12 31 159 112 0.29 67 PCT 11 P2 BW2 0.94 TEC TEH 0.61 CBAY2 29 H
190 31 161 112 0.29 135 PCT 11 P2 BW2
-0.91 TEC TEH 0.61 CBAY2 29 H
189 31 165 112 0.58 115 PCT 17 P2 BW2
-0.91 TEC TEH 0.61 CBAY2 29 H
187 31 167 112 0.26 87 PCT 10 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 29 H
186 31 169 112 0.43 95 PCT 14 P2 BW2 0.89 TEC TEH 0.61 CBAY2 29 H
185 31 169 112 0.29 70 PCT 11 P2 BW2
-0.95 TEC TEH 0.61 CBAY2 29 H
185 31 56 113 0.37 93 PCT 12 P2 VS3 0.81 TEC TEH 0.61 CBAY2 5
H 53 31 58 113 0.4 68 PCT 13 P2 BW2
-0.71 TEC TEH 0.61 CBAY2 5
H 52 31 78 113 0.24 118 PCT 11 P2 VS3 0.77 TEC TEH 0.61 CBAY2 19 H
96 31 98 113 1.33 117 WAR 22 0.2 P4 10H 0.69 10H TEH 0.61 NYAX2 63 H
11 31 98 113 0.61 124 PCT 18 P2 10H 0.68 TEC TEH 0.61 CBAY2 19 H
101 31 128 113 0.55 148 PCT 10 P2 10C
-0.25 TEC TEH 0.61 CBAY2 21 H
300 31 168 113 0.39 130 PCT 13 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 29 H
182 31 170 113 0.76 109 PCT 21 P2 BW2 0.94 TEC TEH 0.61 CBAY2 29 H
183 31 170 113 1.25 97 WAR 21 0.14 P9 BW2 1.32 VS3 TEC 0.61 NYAX2 264 C
60 31 49 114 2.92 107 WAR 31 0.2 P22 BW1 0.87 VS3 TEH 0.61 NYAX2 61 H
39 31 49 114 0.96 120 PCT 26 P2 BW1 0.93 TEC TEH 0.61 CBAY2 7
H 28 31 49 114 PID P2 BW1 0.93 TEH TEC 0.61 CBAY2 68 C
16 31 57 114 0.29 132 PCT 12 P2 BW1 1.06 TEC TEH 0.61 CBAY2 7
H 32
U3R24 PVGS SG31 All Data Page 26 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 61 114 0.29 113 PCT 12 P2 BW2 0.85 TEC TEH 0.61 CBAY2 7
H 34 31 63 114 0.31 107 PCT 13 P2 BW1 1.22 TEC TEH 0.61 CBAY2 7
H 35 31 85 114 0.44 108 PCT 14 P2 VS2
-0.73 TEC TEH 0.61 CBAY2 21 H
9 31 93 114 0.27 144 PCT 10 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 21 H
13 31 99 114 0.61 138 PCT 14 P2 10H 0.77 TEC TEH 0.61 CBAY2 21 H
16 31 99 114 PBC TEC TEH 0.61 CBAY2 29 H
16 31 117 114 0.34 85 PCT 14 P2 VS2
-1.36 TEC TEH 0.61 CBAY2 23 H
276 31 119 114 0.23 114 PCT 11 P2 VS2 0.81 TEC TEH 0.61 CBAY2 23 H
275 31 133 114 0.26 135 PCT 12 P2 BW1
-0.75 TEC TEH 0.61 CBAY2 23 H
268 31 155 114 0.24 42 PCT 10 P2 VS2
-0.95 TEC TEH 0.61 CBAY2 31 H
179 31 163 114 0.3 72 PCT 12 P2 BW2 0.92 TEC TEH 0.61 CBAY2 31 H
175 31 169 114 0.43 83 PCT 16 P2 BW2 0.77 TEC TEH 0.61 CBAY2 31 H
173 31 46 115 2.64 113 WAR 29 0.23 P32 VS3 0.67 VS3 TEC 0.61 NYAX2 262 C
34 31 46 115 0.88 118 PCT 25 P2 VS3 0.79 TEC TEH 0.61 CBAY2 7
H 25 31 46 115 0.89 94 PCT 25 P2 BW2 1.01 TEC TEH 0.61 CBAY2 7
H 25 31 46 115 1.66 111 WAR 24 0.32 P14 BW2 1
VS3 TEC 0.61 NYAX2 262 C
34 31 46 115 1.15 121 WAR 21 0.32 P30 BW2
-0.38 VS3 TEC 0.61 NYAX2 262 C
34 31 46 115 0.35 117 PCT 14 P2 BW1
-0.96 TEC TEH 0.61 CBAY2 7
H 25 31 46 115 0.36 119 PCT 14 P2 BW2
-0.92 TEC TEH 0.61 CBAY2 7
H 25 31 46 115 PID P2 VS3 0.79 TEH TEC 0.61 CBAY2 68 C
15 31 48 115 0.36 129 PCT 14 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 7
H 24 31 60 115 0.27 73 PCT 12 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 7
H 18 31 96 115 0.37 128 PCT 12 P2 VS3 0.64 TEC TEH 0.61 CBAY2 21 H
25 31 98 115 0.21 94 PCT 8
P2 BW1 0.97 TEC TEH 0.61 CBAY2 21 H
24 31 114 115 0.41 110 PCT 16 P2 VS2 0.86 TEC TEH 0.61 CBAY2 23 H
244 31 116 115 0.35 104 PCT 14 P2 VS2 0.74 TEC TEH 0.61 CBAY2 23 H
245 31 126 115 0.72 139 PCT 18 P2 10H 0.68 TEC TEH 0.61 CBAY2 23 H
250 31 130 115 0.42 134 PCT 16 P2 VS1 0.56 TEC TEH 0.61 CBAY2 23 H
252 31 166 115 0.26 52 PCT 11 P2 BW2 0.91 TEC TEH 0.61 CBAY2 31 H
169 31 168 115 2.05 93 WAR 27 0.17 P9 BW2 1.06 VS3 TEC 0.61 NYAX2 266 C
5 31 168 115 0.94 83 PCT 26 P2 BW2 0.96 TEC TEH 0.61 CBAY2 31 H
171 31 170 115 0.35 29 PCT 12 P2 BW2 0.87 TEC TEH 0.61 CBAY2 29 H
184 31 170 115 0.32 129 PCT 11 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 29 H
184 31 43 116 0.66 118 PCT 18 P2 BW2 1.03 TEC TEH 0.61 CBAY2 5
H 26 31 45 116 0.29 130 PCT 10 P2 BW2 0.92 TEC TEH 0.61 CBAY2 5
H 27 31 47 116 0.67 110 PCT 19 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 5
H 29 31 47 116 0.3 125 PCT 10 P2 BW2 0.92 TEC TEH 0.61 CBAY2 5
H 29 31 49 116 0.44 109 PCT 14 P2 BW1 0.89 TEC TEH 0.61 CBAY2 5
H 30 31 59 116 0.36 114 PCT 12 P2 VS3 0.85 TEC TEH 0.61 CBAY2 5
H 35 31 61 116 0.36 135 PCT 12 P2 BW2 0.91 TEC TEH 0.61 CBAY2 5
H 36 31 63 116 0.67 89 PCT 19 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 5
H 37 31 63 116 0.28 128 PCT 10 P2 BW2 0.94 TEC TEH 0.61 CBAY2 5
H 37 31 93 116 2.83 99 WAR 30 0.34 P7 VS4
-0.68 VS3 TEC 0.61 NYAX2 262 C
38
U3R24 PVGS SG31 All Data Page 27 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 93 116 1.15 102 PCT 29 P2 VS4
-0.82 TEC TEH 0.61 CBAY2 23 H
14 31 113 116 0.38 64 PCT 13 P2 VS1
-0.91 TEC TEH 0.61 CBAY2 21 H
290 31 117 116 0.3 137 PCT 11 P2 VS2
-1.08 TEC TEH 0.61 CBAY2 21 H
288 31 165 116 0.2 31 PCT 8
P2 BW2 0.92 TEC TEH 0.61 CBAY2 29 H
166 31 167 116 0.42 80 PCT 16 P2 VS5 0.88 TEC TEH 0.61 CBAY2 31 H
170 31 167 116 0.32 75 PCT 13 P2 VS4 0.74 TEC TEH 0.61 CBAY2 31 H
170 31 40 117 0.33 117 PCT 11 P2 VS3 0.88 TEC TEH 0.61 CBAY2 5
H 231 31 42 117 0.59 121 PCT 17 P2 VS3 0.72 TEC TEH 0.61 CBAY2 5
H 230 31 42 117 0.34 127 PCT 12 P2 BW2
-0.98 TEC TEH 0.61 CBAY2 5
H 230 31 42 117 0.46 135 PCT 11 P2 08C
-0.23 TEC TEH 0.61 CBAY2 5
H 230 31 44 117 0.63 116 PCT 18 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 5
H 24 31 44 117 0.43 98 PCT 14 P2 VS3 0.72 TEC TEH 0.61 CBAY2 5
H 24 31 46 117 0.33 107 PCT 11 P2 VS3 0.82 TEC TEH 0.61 CBAY2 5
H 23 31 86 117 0.25 104 PCT 11 P2 BW1
-0.93 TEC TEH 0.61 CBAY2 23 H
28 31 98 117 0.23 135 PCT 10 P2 VS2 0.74 TEC TEH 0.61 CBAY2 23 H
23 31 102 117 0.25 113 PCT 11 P2 VS2 0.74 TEC TEH 0.61 CBAY2 23 H
21 31 106 117 0.2 76 PCT 9
P2 BW1
-1.22 TEC TEH 0.61 CBAY2 23 H
19 31 114 117 2.07 116 WAR 27 0.35 P4 VS3
-0.83 VS3 TEH 0.61 NYAX2 63 H
8 31 114 117 0.83 110 PCT 22 P2 VS3
-0.83 TEC TEH 0.61 CBAY2 21 H
255 31 118 117 0.27 135 PCT 10 P2 VS3
-0.42 TEC TEH 0.61 CBAY2 21 H
257 31 120 117 0.37 138 PCT 12 P2 VS1 0.9 TEC TEH 0.61 CBAY2 21 H
258 31 124 117 2.5 110 WAR 29 0.4 P4 VS3
-0.88 VS3 TEH 0.61 NYAX2 63 H
7 31 124 117 1.1 121 PCT 25 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 21 H
259 31 124 117 0.45 101 PCT 14 P2 VS1 0.72 TEC TEH 0.61 CBAY2 21 H
259 31 128 117 0.31 125 PCT 11 P2 VS1 0.72 TEC TEH 0.61 CBAY2 21 H
261 31 142 117 0.46 110 PCT 14 P2 VS3
-0.95 TEC TEH 0.61 CBAY2 21 H
268 31 166 117 3.03 97 WAR 31 0.23 P9 BW2 0.89 VS3 TEC 0.61 NYAX2 266 C
6 31 166 117 1.47 114 PCT 30 P2 BW2 0.89 TEC TEH 0.61 CBAY2 29 H
162 31 166 117 PID P2 BW2 0.89 TEH TEC 0.61 CBAY2 68 C
40 31 168 117 2.69 110 WAR 30 0.26 P25 BW2
-0.88 VS3 TEC 0.61 NYAX2 266 C
7 31 168 117 1.4 97 PCT 29 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 29 H
163 31 39 118 0.64 119 PCT 18 P2 VS3 0.72 TEC TEH 0.61 CBAY2 5
H 232 31 43 118 0.59 109 PCT 17 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 5
H 233 31 43 118 0.31 88 PCT 11 P2 BW2 0.87 TEC TEH 0.61 CBAY2 5
H 233 31 43 118 0.39 137 PCT 10 P2 08C
-0.15 TEC TEH 0.61 CBAY2 5
H 233 31 45 118 0.3 128 PCT 10 P2 08C
-0.98 TEC TEH 0.61 CBAY2 5
H 234 31 49 118 0.36 127 PCT 12 P2 BW2 0.92 TEC TEH 0.61 CBAY2 5
H 236 31 49 118 0.29 131 PCT 10 P2 BW1 0.84 TEC TEH 0.61 CBAY2 5
H 236 31 53 118 0.37 112 PCT 15 P2 VS3 0.84 TEC TEH 0.61 CBAY2 3
H 77 31 59 118 0.4 122 PCT 16 P2 BW2 0.89 TEC TEH 0.61 CBAY2 3
H 80 31 69 118 0.25 138 PCT 11 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 7
H 5
31 101 118 0.24 52 PCT 9
P2 BW1 0.92 TEC TEH 0.61 CBAY2 21 H
46 31 107 118 0.27 101 PCT 10 P2 VS3
-1.04 TEC TEH 0.61 CBAY2 21 H
49
U3R24 PVGS SG31 All Data Page 28 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 111 118 0.25 97 PCT 9
P2 VS4
-1.05 TEC TEH 0.61 CBAY2 21 H
51 31 169 118 0.47 129 PCT 13 P2 05H 0.83 TEC TEH 0.61 CBAY2 29 H
164 31 40 119 0.54 132 PCT 15 P2 08C
-0.2 TEC TEH 0.61 CBAY2 7
H 247 31 42 119 0.92 111 PCT 26 P2 BW1
-0.94 TEC TEH 0.61 CBAY2 7
H 246 31 42 119 1.2 83 WAR 21 0.34 P7 BW1
-0.92 VS3 TEH 0.61 NYAX2 61 H
37 31 42 119 PID P2 BW1
-0.94 TEH TEC 0.61 CBAY2 68 C
13 31 44 119 0.61 97 PCT 20 P2 BW1
-0.94 TEC TEH 0.61 CBAY2 7
H 245 31 44 119 0.8 73 WAR 17 0.25 P7 BW1
-0.94 VS3 TEH 0.61 NYAX2 61 H
38 31 44 119 0.41 141 PCT 11 P2 08H 0.7 TEC TEH 0.61 CBAY2 7
H 245 31 44 119 0.23 89 PCT 10 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 7
H 245 31 44 119 PID P2 BW1
-0.94 TEH TEC 0.61 CBAY2 68 C
14 31 50 119 0.4 91 PCT 16 P2 BW2 0.88 TEC TEH 0.61 CBAY2 3
H 75 31 60 119 0.25 130 PCT 11 P2 BW1 0.81 TEC TEH 0.61 CBAY2 3
H 70 31 90 119 0.55 105 PCT 16 P2 10H
-1.08 TEC TEH 0.61 CBAY2 21 H
63 31 114 119 0.21 135 PCT 10 P2 VS1
-0.96 TEC TEH 0.61 CBAY2 23 H
209 31 116 119 0.26 108 PCT 12 P2 VS3 0.69 TEC TEH 0.61 CBAY2 23 H
210 31 124 119 0.3 145 PCT 13 P2 VS1 0.95 TEC TEH 0.61 CBAY2 23 H
214 31 144 119 0.25 118 PCT 11 P2 VS2 0.43 TEC TEH 0.61 CBAY2 23 H
224 31 166 119 0.26 61 PCT 11 P2 BW2 0.99 TEC TEH 0.61 CBAY2 31 H
149 31 168 119 0.33 66 PCT 13 P2 BW2 0.91 TEC TEH 0.61 CBAY2 31 H
150 31 37 120 0.45 128 PCT 17 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 7
H 248 31 37 120 0.42 123 PCT 16 P2 VS3 0.3 TEC TEH 0.61 CBAY2 7
H 248 31 45 120 0.53 103 PCT 18 P2 BW2 0.9 TEC TEH 0.61 CBAY2 7
H 249 31 45 120 0.22 125 PCT 10 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 7
H 249 31 47 120 0.23 95 PCT 10 P2 VS3 0.8 TEC TEH 0.61 CBAY2 7
H 250 31 53 120 0.26 78 PCT 10 P2 BW2
-0.48 TEC TEH 0.61 CBAY2 1
H 78 31 89 120 0.43 121 PCT 16 P2 VS2
-0.76 TEC TEH 0.61 CBAY2 23 H
39 31 91 120 0.24 90 PCT 11 P2 BW1
-0.95 TEC TEH 0.61 CBAY2 23 H
40 31 40 121 0.18 127 PCT 7
P2 05H 0.71 TEC TEH 0.61 CBAY2 5
H 240 31 46 121 0.34 81 PCT 11 P2 BW2 0.82 TEC TEH 0.61 CBAY2 5
H 237 31 48 121 0.3 79 PCT 11 P2 BW2 0.94 TEC TEH 0.61 CBAY2 1
H 75 31 52 121 0.28 111 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 1
H 73 31 62 121 0.28 87 PCT 10 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 1
H 68 31 64 121 0.23 144 PCT 9
P2 09H 0.62 TEC TEH 0.61 CBAY2 1
H 67 31 74 121 0.44 96 PCT 14 P2 VS2 0.8 TEC TEH 0.61 CBAY2 1
H 62 31 98 121 0.24 86 PCT 11 P2 BW2 0.87 TEC TEH 0.61 CBAY2 23 H
56 31 104 121 0.2 136 PCT 10 P2 BW1
-0.9 TEC TEH 0.61 CBAY2 23 H
53 31 112 121 0.45 144 PCT 10 P2 10H 0.73 TEC TEH 0.61 CBAY2 21 H
215 31 164 121 0.55 83 PCT 17 P2 BW2 0.82 TEC TEH 0.61 CBAY2 29 H
142 31 166 121 1.4 112 PCT 29 P2 BW2 0.79 TEC TEH 0.61 CBAY2 29 H
143 31 166 121 2.49 126 WAR 29 0.23 P10 BW2 0.92 VS3 TEC 0.61 NYAX2 266 C
8 31 168 121 0.36 118 PCT 12 P2 BW2 0.89 TEC TEH 0.61 CBAY2 29 H
144 31 168 121 0.21 112 PCT 8
P2 10H 0.62 TEC TEH 0.61 CBAY2 29 H
144
U3R24 PVGS SG31 All Data Page 29 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 35 122 2.19 110 WAR 27 0.36 P7 BW1
-0.86 VS3 TEH 0.61 NYAX2 61 H
36 31 35 122 0.91 103 PCT 23 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 5
H 242 31 35 122 PID P2 BW1
-0.86 TEH TEC 0.61 CBAY2 68 C
12 31 39 122 2.1 111 WAR 27 0.31 P7 BW1
-0.83 VS3 TEH 0.61 NYAX2 61 H
35 31 39 122 2
111 WAR 26 0.62 P29 BW2
-0.35 VS3 TEC 0.61 NYAX2 262 C
30 31 39 122 0.99 115 PCT 24 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 5
H 244 31 39 122 0.95 120 PCT 23 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 5
H 244 31 39 122 0.75 131 PCT 17 P2 08H 0.68 TEC TEH 0.61 CBAY2 5
H 244 31 39 122 PID P2 BW2
-0.87 TEH TEC 0.61 CBAY2 68 C
11 31 47 122 1.65 123 WAR 24 0.4 P14 BW2 1.12 VS3 TEC 0.61 NYAX2 262 C
29 31 47 122 0.76 113 PCT 20 P2 BW2 0.5 TEC TEH 0.61 CBAY2 5
H 247 31 47 122 PID P2 BW2 0.5 TEH TEC 0.61 CBAY2 68 C
10 31 57 122 0.31 119 PCT 13 P2 VS3 0.9 TEC TEH 0.61 CBAY2 3
H 51 31 59 122 0.3 123 PCT 13 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 3
H 52 31 71 122 3.66 117 WAR 34 0.53 P12 VS2
-0.91 VS3 TEH 0.61 NYAX2 61 H
28 31 71 122 1.47 112 PCT 33 P2 VS2
-0.91 TEC TEH 0.61 CBAY2 3
H 58 31 71 122 PID P2 VS2
-0.91 TEH TEC 0.61 CBAY2 68 C
9 31 91 122 0.18 60 PCT 8
P2 10H
-1.64 TEC TEH 0.61 CBAY2 23 H
74 31 111 122 0.21 74 PCT 10 P2 BW2
-0.48 TEC TEH 0.61 CBAY2 23 H
84 31 165 122 0.31 94 PCT 13 P2 BW2 0.86 TEC TEH 0.61 CBAY2 31 H
131 31 167 122 0.43 84 PCT 16 P2 BW2 0.89 TEC TEH 0.61 CBAY2 31 H
130 31 32 123 0.46 109 PCT 17 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 7
H 260 31 32 123 0.48 132 PCT 17 P2 BW1 0.98 TEC TEH 0.61 CBAY2 7
H 260 31 32 123 0.26 123 PCT 11 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 7
H 260 31 34 123 0.32 103 PCT 13 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 7
H 259 31 34 123 0.25 146 PCT 11 P2 BW1 0.9 TEC TEH 0.61 CBAY2 7
H 259 31 36 123 0.22 76 PCT 10 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 7
H 258 31 46 123 0.25 70 PCT 11 P2 BW2 0.85 TEC TEH 0.61 CBAY2 7
H 253 31 54 123 0.44 115 PCT 17 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 3
H 45 31 62 123 0.39 134 PCT 15 P2 BW1 0.84 TEC TEH 0.61 CBAY2 3
H 41 31 110 123 0.28 124 PCT 12 P2 VS2 0.72 TEC TEH 0.61 CBAY2 23 H
86 31 120 123 0.21 96 PCT 10 P2 VS2 0.71 TEC TEH 0.61 CBAY2 23 H
177 31 126 123 1.39 111 PCT 32 P2 VS3
-0.54 TEC TEH 0.61 CBAY2 23 H
180 31 126 123 3.07 98 WAR 31 0.7 P28 VS3
-0.83 VS3 TEH 0.61 NYAX2 63 H
6 31 126 123 0.68 117 PCT 22 P2 VS3
-0.98 TEC TEH 0.61 CBAY2 23 H
180 31 126 123 0.51 118 PCT 18 P2 VS2 0.91 TEC TEH 0.61 CBAY2 23 H
180 31 126 123 0.46 125 PCT 17 P2 VS3 0.91 TEC TEH 0.61 CBAY2 23 H
180 31 126 123 0.23 94 PCT 10 P2 VS5
-0.87 TEC TEH 0.61 CBAY2 23 H
180 31 126 123 PID P2 VS3
-0.54 TEH TEC 0.61 CBAY2 68 C
39 31 132 123 0.26 130 PCT 12 P2 VS1 0.74 TEC TEH 0.61 CBAY2 23 H
183 31 162 123 0.68 114 PCT 22 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 31 H
126 31 162 123 1.29 114 WAR 22 0.61 P23 BW2
-0.83 VS3 TEC 0.61 NYAX2 266 C
11 31 166 123 1.47 89 WAR 23 0.18 P9 BW2 0.81 VS3 TEC 0.61 NYAX2 266 C
10
U3R24 PVGS SG31 All Data Page 30 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 166 123 0.65 127 PCT 21 P2 BW2 0.86 TEC TEH 0.61 CBAY2 31 H
128 31 168 123 0.41 121 PCT 15 P2 BW2 0.96 TEC TEH 0.61 CBAY2 31 H
129 31 33 124 0.53 124 PCT 18 P2 BW2
-0.79 TEC TEH 0.61 CBAY2 7
H 261 31 33 124 0.43 124 PCT 16 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 7
H 261 31 35 124 1.48 116 WAR 23 0.26 P8 BW1
-0.87 VS3 TEH 0.61 NYAX2 61 H
32 31 35 124 0.67 101 PCT 21 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 7
H 262 31 35 124 0.36 134 PCT 14 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 7
H 262 31 35 124 PID P2 BW1
-0.87 TEH TEC 0.61 CBAY2 68 C
6 31 37 124 0.34 88 PCT 14 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 7
H 263 31 37 124 0.27 131 PCT 12 P2 BW2
-0.8 TEC TEH 0.61 CBAY2 7
H 263 31 39 124 2.05 116 WAR 27 0.29 P7 BW1
-0.85 VS3 TEH 0.61 NYAX2 61 H
33 31 39 124 0.7 127 PCT 22 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 7
H 264 31 39 124 0.36 140 PCT 14 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 7
H 264 31 39 124 PID P2 BW1
-0.87 TEH TEC 0.61 CBAY2 68 C
7 31 41 124 2.73 105 WAR 30 0.34 P7 BW1
-0.85 VS3 TEH 0.61 NYAX2 61 H
34 31 41 124 1.2 101 PCT 29 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 7
H 265 31 41 124 0.45 108 PCT 17 P2 BW2 0.89 TEC TEH 0.61 CBAY2 7
H 265 31 41 124 0.33 118 PCT 13 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 7
H 265 31 41 124 PID P2 BW1
-0.87 TEH TEC 0.61 CBAY2 68 C
8 31 57 124 0.52 111 PCT 16 P2 VS3 0.82 TEC TEH 0.61 CBAY2 1
H 52 31 61 124 0.28 83 PCT 10 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 1
H 54 31 63 124 0.31 47 PCT 11 P2 BW1 1.21 TEC TEH 0.61 CBAY2 1
H 55 31 87 124 0.63 135 PCT 14 P2 09H 0.73 TEC TEH 0.61 CBAY2 21 H
74 31 99 124 0.32 106 PCT 11 P2 VS3
-1.15 TEC TEH 0.61 CBAY2 21 H
80 31 99 124 0.23 146 PCT 9
P2 09H 0.8 TEC TEH 0.61 CBAY2 21 H
80 31 111 124 0.26 123 PCT 12 P2 VS2
-0.82 TEC TEH 0.61 CBAY2 23 H
173 31 133 124 2.7 114 WAR 30 0.57 P4 VS3
-0.9 VS3 TEH 0.61 NYAX2 63 H
5 31 133 124 1.11 118 PCT 26 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 21 H
204 31 133 124 0.27 89 PCT 10 P2 VS2
-0.94 TEC TEH 0.61 CBAY2 21 H
204 31 163 124 2.24 94 WAR 28 0.86 P9 BW2 0.84 VS3 TEC 0.61 NYAX2 266 C
12 31 163 124 0.82 73 PCT 22 P2 BW2 0.86 TEC TEH 0.61 CBAY2 29 H
128 31 165 124 0.41 61 PCT 14 P2 BW2 0.81 TEC TEH 0.61 CBAY2 29 H
127 31 167 124 0.46 78 PCT 15 P2 BW2 0.86 TEC TEH 0.61 CBAY2 29 H
126 31 28 125 0.33 120 PCT 11 P2 BW1 0.92 TEC TEH 0.61 CBAY2 5
H 258 31 62 125 0.28 134 PCT 10 P2 BW1 0.86 TEC TEH 0.61 CBAY2 1
H 40 31 98 125 0.28 92 PCT 10 P2 BW1 1.02 TEC TEH 0.61 CBAY2 21 H
92 31 124 125 0.67 116 PCT 19 P2 VS1 0.77 TEC TEH 0.61 CBAY2 21 H
183 31 128 125 0.37 118 PCT 12 P2 VS2 0.68 TEC TEH 0.61 CBAY2 21 H
185 31 152 125 0.35 154 PCT 12 P2 VS1
-0.84 TEC TEH 0.61 CBAY2 29 H
118 31 162 125 0.3 105 PCT 11 P2 VS4 0.71 TEC TEH 0.61 CBAY2 29 H
123 31 164 125 0.37 37 PCT 13 P2 BW2 0.91 TEC TEH 0.61 CBAY2 29 H
124 31 166 125 1.54 113 PCT 31 P2 BW2 0.43 TEC TEH 0.61 CBAY2 29 H
125 31 166 125 2.68 114 WAR 30 0.23 P10 BW2 0.09 VS3 TEC 0.61 NYAX2 266 C
9
U3R24 PVGS SG31 All Data Page 31 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 166 125 PID P2 BW2 0.43 TEH TEC 0.61 CBAY2 68 C
38 31 27 126 0.67 129 PCT 16 P2 08H 0.76 TEC TEH 0.61 CBAY2 5
H 260 31 27 126 0.29 118 PCT 10 P2 08C
-0.78 TEC TEH 0.61 CBAY2 5
H 260 31 31 126 0.36 103 PCT 12 P2 VS3 0.68 TEC TEH 0.61 CBAY2 5
H 262 31 39 126 0.34 128 PCT 12 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 5
H 266 31 39 126 0.37 74 PCT 12 P2 BW2 0.95 TEC TEH 0.61 CBAY2 5
H 266 31 43 126 0.63 87 PCT 18 P2 BW2 0.95 TEC TEH 0.61 CBAY2 5
H 268 31 57 126 0.33 101 PCT 14 P2 BW1
-1.92 TEC TEH 0.61 CBAY2 3
H 23 31 63 126 0.33 114 PCT 14 P2 VS3 1.07 TEC TEH 0.61 CBAY2 3
H 26 31 65 126 0.48 79 PCT 18 P2 VS2
-1.01 TEC TEH 0.61 CBAY2 3
H 27 31 65 126 0.46 107 PCT 17 P2 BW2 0.93 TEC TEH 0.61 CBAY2 3
H 27 31 69 126 0.37 122 PCT 15 P2 VS3
-0.86 TEC TEH 0.61 CBAY2 3
H 29 31 73 126 0.28 120 PCT 12 P2 BW1 0.93 TEC TEH 0.61 CBAY2 3
H 31 31 75 126 0.45 99 PCT 17 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 3
H 32 31 133 126 0.41 91 PCT 16 P2 VS1 0.79 TEC TEH 0.61 CBAY2 23 H
162 31 133 126 0.23 124 PCT 11 P2 VS3
-0.82 TEC TEH 0.61 CBAY2 23 H
162 31 165 126 0.21 57 PCT 10 P2 BW2 0.96 TEC TEH 0.61 CBAY2 31 H
109 31 34 127 0.35 102 PCT 14 P2 BW2
-0.89 TEC TEH 0.61 CBAY2 7
H 277 31 36 127 0.36 121 PCT 14 P2 BW2
-0.93 TEC TEH 0.61 CBAY2 7
H 276 31 46 127 0.33 136 PCT 13 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 7
H 271 31 48 127 0.25 76 PCT 11 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 7
H 270 31 54 127 0.29 112 PCT 12 P2 09H
-0.08 TEC TEH 0.61 CBAY2 3
H 17 31 56 127 0.28 67 PCT 12 P2 BW1
-1.63 TEC TEH 0.61 CBAY2 3
H 16 31 90 127 0.41 77 PCT 16 P2 10C
-1.36 TEC TEH 0.61 CBAY2 23 H
131 31 94 127 0.23 69 PCT 11 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 23 H
129 31 106 127 0.36 137 PCT 11 P2 09H 0.75 TEC TEH 0.61 CBAY2 23 H
123 31 110 127 0.26 128 PCT 12 P2 VS4
-0.76 TEC TEH 0.61 CBAY2 23 H
121 31 116 127 0.29 125 PCT 12 P2 VS2 0.71 TEC TEH 0.61 CBAY2 23 H
139 31 126 127 0.37 113 PCT 15 P2 VS1 0.54 TEC TEH 0.61 CBAY2 23 H
144 31 126 127 0.37 96 PCT 15 P2 VS4
-0.92 TEC TEH 0.61 CBAY2 23 H
144 31 126 127 0.31 129 PCT 13 P2 VS3
-0.8 TEC TEH 0.61 CBAY2 23 H
144 31 130 127 0.37 122 PCT 15 P2 VS1 0.66 TEC TEH 0.61 CBAY2 23 H
146 31 132 127 0.37 127 PCT 15 P2 VS1 0.79 TEC TEH 0.61 CBAY2 23 H
147 31 142 127 0.26 84 PCT 11 P2 BW2 0.87 TEC TEH 0.61 CBAY2 23 H
152 31 152 127 0.24 104 PCT 11 P2 VS1
-0.88 TEC TEH 0.61 CBAY2 31 H
101 31 158 127 0.23 91 PCT 11 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 31 H
104 31 166 127 0.2 146 PCT 10 P2 BW2 0.86 TEC TEH 0.61 CBAY2 31 H
108 31 41 128 0.37 120 PCT 14 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 7
H 291 31 41 128 0.26 101 PCT 11 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 7
H 291 31 53 128 0.38 107 PCT 13 P2 BW1
-0.66 TEC TEH 0.61 CBAY2 1
H 22 31 57 128 0.32 109 PCT 11 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 1
H 24 31 59 128 0.47 112 PCT 15 P2 BW2
-0.77 TEC TEH 0.61 CBAY2 1
H 25 31 69 128 0.38 81 PCT 13 P2 VS3
-1.03 TEC TEH 0.61 CBAY2 1
H 30
U3R24 PVGS SG31 All Data Page 32 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 91 128 0.38 105 PCT 12 P2 10C
-1.68 TEC TEH 0.61 CBAY2 21 H
111 31 127 128 0.44 85 PCT 14 P2 BW2 0.84 TEC TEH 0.61 CBAY2 21 H
168 31 153 128 1.1 61 MBM 6
FDP 15.1 TEC TEH 0.61 CBAY2 29 H
114 31 42 129 0.24 122 PCT 10 P2 08C
-0.9 TEC TEH 0.61 CBAY2 7
H 297 31 58 129 0.24 120 PCT 9
P2 BW1
-0.65 TEC TEH 0.61 CBAY2 1
H 14 31 82 129 0.25 79 PCT 9
P2 BW1
-0.83 TEC TEH 0.61 CBAY2 21 H
135 31 94 129 0.28 120 PCT 10 P2 VS2 0.2 TEC TEH 0.61 CBAY2 21 H
129 31 126 129 0.47 128 PCT 15 P2 VS3
-0.7 TEC TEH 0.61 CBAY2 21 H
146 31 128 129 0.48 129 PCT 15 P2 VS1 0.67 TEC TEH 0.61 CBAY2 21 H
147 31 130 129 0.52 130 PCT 16 P2 VS1 0.69 TEC TEH 0.61 CBAY2 21 H
148 31 162 129 0.42 66 PCT 14 P2 BW2 0.86 TEC TEH 0.61 CBAY2 29 H
106 31 164 129 0.34 62 PCT 12 P2 BW2 0.89 TEC TEH 0.61 CBAY2 29 H
107 31 9
130 0.32 86 PCT 10 P2 06H 0
TEH TEC 0.61 CBAY2 202 C
7 31 25 130 0.32 14 PCT 10 P2 08C 0.68 TEH TEC 0.61 CBAY2 226 C
257 31 49 130 0.37 136 PCT 11 P2 BW1 0.79 TEH TEC 0.61 CBAY2 226 C
245 31 59 130 0.29 138 PCT 9
P2 BW2 0.45 TEH TEC 0.61 CBAY2 226 C
240 31 63 130 0.21 156 PCT 7
P2 BW2 0.47 TEH TEC 0.61 CBAY2 226 C
238 31 65 130 0.28 128 PCT 9
P2 BW2 1.22 TEH TEC 0.61 CBAY2 226 C
237 31 81 130 0.52 145 PCT 11 P2 09H 0.77 TEH TEC 0.61 CBAY2 244 C
12 31 91 130 0.29 119 PCT 10 P2 VS2
-0.78 TEH TEC 0.61 CBAY2 244 C
63 31 101 130 0.22 102 PCT 8
P2 BW1 0.98 TEH TEC 0.61 CBAY2 244 C
68 31 103 130 0.37 126 PCT 12 P2 VS3
-0.77 TEH TEC 0.61 CBAY2 244 C
69 31 107 130 0.38 146 PCT 12 P2 10H 0.67 TEH TEC 0.61 CBAY2 244 C
71 31 133 130 0.34 148 PCT 12 P2 VS1
-0.71 TEC TEH 0.61 CBAY2 47 H
39 31 133 130 0.3 155 PCT 11 P2 VS2
-1.07 TEC TEH 0.61 CBAY2 47 H
39 31 161 130 0.34 120 PCT 12 P2 BW2 0.84 TEC TEH 0.61 CBAY2 41 H
118 31 165 130 0.39 133 PCT 14 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 41 H
179 31 4
131 0.43 107 PCT 12 P2 06C
-0.98 TEH TEC 0.61 CBAY2 202 C
10 31 6
131 0.21 129 PCT 7
P2 01C
-0.2 TEH TEC 0.61 CBAY2 202 C
9 31 18 131 1.1 88 PLP 7
FDP 1.38 TEH TEC 0.61 CBAY2 226 C
213 31 18 131 NDF 47 FDP 1.38 01C TEC 0.61 NYAX2 262 C
31 31 42 131 0.34 124 PCT 11 P2 BW2
-0.97 TEH TEC 0.61 CBAY2 226 C
225 31 74 131 0.17 138 PCT 6
P2 08H 0.75 TEH TEC 0.61 CBAY2 244 C
18 31 98 131 1.71 120 WAR 24 0.31 P7 VS4 0.63 VS3 TEC 0.61 NYAX2 266 C
15 31 98 131 1.23 116 WAR 21 0.37 P7 VS3
-1.01 VS3 TEC 0.61 NYAX2 266 C
15 31 98 131 0.67 115 PCT 18 P2 VS4 0.89 TEH TEC 0.61 CBAY2 244 C
80 31 98 131 0.34 116 PCT 12 P2 VS3
-0.69 TEH TEC 0.61 CBAY2 244 C
80 31 126 131 0.25 54 PCT 10 P2 VS4 1.05 TEC TEH 0.61 CBAY2 47 H
56 31 156 131 1.98 107 WAR 26 0.23 P23 BW2
-0.88 VS3 TEC 0.61 NYAX2 266 C
13 31 156 131 0.88 124 PCT 25 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 43 H
137 31 5
132 0.42 42 PCT 13 P2 BW2
-0.71 TEH TEC 0.61 CBAY2 202 C
18 31 7
132 0.55 140 PCT 15 P2 BW2
-0.57 TEH TEC 0.61 CBAY2 202 C
19 31 33 132 0.27 104 PCT 10 P2 VS3
-0.65 TEH TEC 0.61 CBAY2 228 C
264
U3R24 PVGS SG31 All Data Page 33 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 43 132 0.27 139 PCT 10 P2 08H 0.78 TEH TEC 0.61 CBAY2 228 C
259 31 93 132 0.25 76 PCT 9
P2 10H 0.79 TEH TEC 0.61 CBAY2 246 C
50 31 159 132 0.37 63 PCT 14 P2 BW2 0.91 TEC TEH 0.61 CBAY2 41 H
120 31 161 132 0.32 134 PCT 12 P2 BW2 0.89 TEC TEH 0.61 CBAY2 41 H
116 31 163 132 0.26 89 PCT 11 P2 BW2 0.91 TEC TEH 0.61 CBAY2 43 H
81 31 8
133 0.44 132 PCT 14 P2 BW2 1.43 TEH TEC 0.61 CBAY2 204 C
6 31 48 133 0.29 98 PCT 10 P2 VS3 0.93 TEH TEC 0.61 CBAY2 228 C
238 31 92 133 0.55 127 PCT 14 P2 10H 1.37 TEH TEC 0.61 CBAY2 246 C
65 31 92 133 0.4 76 PCT 13 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 246 C
65 31 96 133 0.73 142 PCT 15 P2 09H 0.69 TEH TEC 0.61 CBAY2 246 C
63 31 98 133 0.31 82 PCT 11 P2 VS3
-0.68 TEH TEC 0.61 CBAY2 246 C
62 31 130 133 0.43 149 PCT 15 P2 VS1 0.66 TEC TEH 0.61 CBAY2 47 H
36 31 142 133 0.31 125 PCT 11 P2 VS1 0.73 TEC TEH 0.61 CBAY2 45 H
24 31 160 133 0.58 75 PCT 18 P2 BW2 0.84 TEC TEH 0.61 CBAY2 41 H
115 31 162 133 0.27 98 PCT 12 P2 BW2 0.99 TEC TEH 0.61 CBAY2 43 H
80 31 17 134 0.74 161 PCT 10 P2 06H 0.78 TEH TEC 0.61 CBAY2 226 C
206 31 47 134 0.37 148 PCT 11 P2 08C 0.76 TEH TEC 0.61 CBAY2 226 C
191 31 55 134 0.35 116 PCT 11 P2 VS3
-1.19 TEH TEC 0.61 CBAY2 226 C
187 31 65 134 0.18 160 PCT 6
P2 09H 0.8 TEH TEC 0.61 CBAY2 226 C
182 31 89 134 0.29 113 PCT 10 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 244 C
90 31 91 134 0.61 125 PCT 17 P2 VS3
-0.71 TEH TEC 0.61 CBAY2 244 C
91 31 91 134 0.33 109 PCT 11 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 244 C
91 31 97 134 0.24 149 PCT 9
P2 10H 0.69 TEH TEC 0.61 CBAY2 244 C
94 31 111 134 0.49 109 PCT 15 P2 BW2
-0.77 TEH TEC 0.61 CBAY2 244 C
101 31 113 134 0.52 162 PCT 11 P2 09C 0.82 TEC TEH 0.61 CBAY2 47 H
65 31 115 134 0.32 153 PCT 12 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 47 H
64 31 121 134 0.28 156 PCT 11 P2 VS3
-0.8 TEC TEH 0.61 CBAY2 47 H
61 31 48 135 0.46 124 PCT 12 P2 09C
-1.14 TEH TEC 0.61 CBAY2 226 C
173 31 102 135 0.69 143 PCT 13 P2 10H 0.67 TEH TEC 0.61 CBAY2 244 C
106 31 112 135 0.47 143 PCT 16 P2 VS2 0.78 TEC TEH 0.61 CBAY2 47 H
66 31 122 135 0.19 38 PCT 8
P2 VS1 0.84 TEC TEH 0.61 CBAY2 47 H
71 31 124 135 0.37 143 PCT 13 P2 VS1 0.71 TEC TEH 0.61 CBAY2 47 H
72 31 128 135 0.39 145 PCT 14 P2 VS2 0.78 TEC TEH 0.61 CBAY2 47 H
34 31 144 135 0.4 145 PCT 15 P2 VS2 0.73 TEC TEH 0.61 CBAY2 43 H
207 31 7
136 2.84 176 DNT P1 08H 6.41 TEH TEC 0.61 CBAY2 202 C
27 31 63 136 0.41 121 PCT 13 P2 VS3 0.98 TEH TEC 0.61 CBAY2 228 C
193 31 69 136 0.69 137 PCT 15 P2 09H 0.69 TEH TEC 0.61 CBAY2 246 C
17 31 89 136 0.34 57 PCT 12 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 246 C
74 31 97 136 0.29 78 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 246 C
78 31 159 136 0.24 82 PCT 11 P2 VS2 0.63 TEC TEH 0.61 CBAY2 43 H
77 31 8
137 0.33 145 PCT 11 P2 BW1
-0.68 TEH TEC 0.61 CBAY2 202 C
41 31 38 137 0.37 135 PCT 12 P2 VS3 0.89 TEH TEC 0.61 CBAY2 228 C
176 31 46 137 NDF 23 TSC 0.79 01C TEC 0.61 NYAX2 262 C
28
U3R24 PVGS SG31 All Data Page 34 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 50 137 0.3 113 PCT 11 P2 VS3 0.81 TEH TEC 0.61 CBAY2 228 C
182 31 60 137 0.31 109 PCT 11 P2 VS3
-0.9 TEH TEC 0.61 CBAY2 228 C
187 31 126 137 0.24 114 PCT 9
P2 VS3 1.36 TEC TEH 0.61 CBAY2 45 H
84 31 158 137 0.39 141 PCT 15 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 43 H
76 31 160 137 0.4 38 PCT 14 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 41 H
182 31 13 138 0.56 121 PCT 15 P2 BW1 0.07 TEH TEC 0.61 CBAY2 226 C
153 31 25 138 0.52 98 PCT 15 P2 BW1
-0.91 TEH TEC 0.61 CBAY2 226 C
147 31 37 138 0.29 115 PCT 9
P2 08H
-0.23 TEH TEC 0.61 CBAY2 226 C
141 31 53 138 0.43 130 PCT 13 P2 BW1
-0.55 TEH TEC 0.61 CBAY2 226 C
133 31 107 138 0.53 127 PCT 14 P2 09H 0.7 TEH TEC 0.61 CBAY2 244 C
127 31 121 138 NDF 123 10C 26.75 VS3 TEC 0.61 NYAX2 266 C
16 31 157 138 0.48 121 PCT 17 P2 BW2 0.78 TEC TEH 0.61 CBAY2 43 H
75 31 10 139 0.32 146 PCT 10 P2 BW1
-0.75 TEH TEC 0.61 CBAY2 202 C
54 31 52 139 0.38 143 PCT 12 P2 BW1
-0.75 TEH TEC 0.61 CBAY2 226 C
120 31 64 139 0.36 147 PCT 11 P2 BW1 0.89 TEH TEC 0.61 CBAY2 226 C
126 31 106 139 0.71 142 PCT 14 P2 09H 0.7 TEH TEC 0.61 CBAY2 244 C
132 31 140 139 0.42 144 PCT 16 P2 VS1 0.81 TEC TEH 0.61 CBAY2 43 H
203 31 156 139 0.32 86 PCT 13 P2 BW2 0.86 TEC TEH 0.61 CBAY2 43 H
74 31 156 139 0.23 125 PCT 10 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 43 H
74 31 25 140 0.42 99 PCT 14 P2 BW1
-1.02 TEH TEC 0.61 CBAY2 228 C
155 31 53 140 0.63 84 PCT 18 P2 BW1
-0.61 TEH TEC 0.61 CBAY2 228 C
141 31 57 140 0.3 71 PCT 11 P2 VS3 1.06 TEH TEC 0.61 CBAY2 228 C
139 31 59 140 0.4 105 PCT 13 P2 VS3 0.99 TEH TEC 0.61 CBAY2 228 C
138 31 63 140 0.29 79 PCT 10 P2 VS3 0.99 TEH TEC 0.61 CBAY2 228 C
136 31 65 140 0.33 60 PCT 11 P2 VS2
-0.93 TEH TEC 0.61 CBAY2 228 C
135 31 103 140 0.45 137 PCT 11 P2 10H 0.72 TEH TEC 0.61 CBAY2 246 C
109 31 60 141 0.28 106 PCT 10 P2 VS3 0.98 TEH TEC 0.61 CBAY2 228 C
130 31 62 141 0.33 130 PCT 11 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 228 C
131 31 112 141 0.29 126 PCT 11 P2 VS2 0.75 TEC TEH 0.61 CBAY2 45 H
96 31 128 141 0.35 139 PCT 12 P2 VS3
-0.72 TEC TEH 0.61 CBAY2 45 H
104 31 130 141 0.44 147 PCT 15 P2 VS2 0.81 TEC TEH 0.61 CBAY2 47 H
14 31 130 141 0.36 147 PCT 13 P2 VS1 0.66 TEC TEH 0.61 CBAY2 47 H
14 31 130 141 0.36 159 PCT 13 P2 VS3
-0.77 TEC TEH 0.61 CBAY2 47 H
14 31 132 141 0.32 141 PCT 12 P2 VS1
-0.84 TEC TEH 0.61 CBAY2 47 H
7 31 49 142 0.38 116 PCT 12 P2 BW1 0.4 TEH TEC 0.61 CBAY2 226 C
80 31 55 142 0.48 116 PCT 14 P2 BW1 1.68 TEH TEC 0.61 CBAY2 226 C
77 31 59 142 0.51 108 PCT 14 P2 VS3 0.99 TEH TEC 0.61 CBAY2 226 C
75 31 71 142 0.28 144 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 244 C
145 31 79 142 0.31 147 PCT 11 P2 VS2 0.83 TEH TEC 0.61 CBAY2 244 C
149 31 105 142 0.47 130 PCT 14 P2 VS2 0.84 TEH TEC 0.61 CBAY2 244 C
162 31 105 142 0.42 142 PCT 10 P2 10H 0.68 TEH TEC 0.61 CBAY2 244 C
162 31 8
143 0.35 130 PCT 11 P2 BW1
-0.63 TEH TEC 0.61 CBAY2 202 C
70 31 36 143 NDF 7
08H 25.8 VS3 TEH 0.61 NYAX2 59 H
52
U3R24 PVGS SG31 All Data Page 35 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 36 143 NDF 130 VS3
-1.12 VS3 TEH 0.61 NYAX2 59 H
52 31 36 143 3.57 181 DNT P1 VS3
-0.99 TEH TEC 0.61 CBAY2 226 C
57 31 114 143 0.36 143 PCT 13 P2 VS2 0.78 TEC TEH 0.61 CBAY2 47 H
106 31 120 143 0.45 149 PCT 15 P2 VS2
-0.84 TEC TEH 0.61 CBAY2 47 H
103 31 120 143 0.4 131 PCT 14 P2 VS4
-0.81 TEC TEH 0.61 CBAY2 47 H
103 31 25 144 0.31 94 PCT 11 P2 BW1
-0.98 TEH TEC 0.61 CBAY2 228 C
98 31 41 144 0.23 129 PCT 9
P2 08C 0.74 TEH TEC 0.61 CBAY2 228 C
90 31 51 144 8.19 76 PLP 144 TSH 0.17 01H TEH 0.61 NYAX2 59 H
53 31 53 144 0.34 81 PCT 12 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 228 C
84 31 53 144 6.69 74 PLP 132 TSH 0.14 01H TEH 0.61 NYAX2 59 H
54 31 55 144 NDF 88 TSH 0.13 01H TEH 0.61 NYAX2 61 H
5 31 59 144 0.33 85 PCT 11 P2 VS3 1.02 TEH TEC 0.61 CBAY2 228 C
81 31 65 144 0.7 135 PCT 15 P2 09H 0.9 TEH TEC 0.61 CBAY2 228 C
78 31 87 144 0.22 96 PCT 8
P2 BW1
-0.7 TEH TEC 0.61 CBAY2 246 C
136 31 91 144 0.34 101 PCT 12 P2 VS3 0.15 TEH TEC 0.61 CBAY2 246 C
138 31 36 145 NDF 119 08H 25.98 VS3 TEH 0.61 NYAX2 59 H
51 31 38 145 NDF 91 08H 26.11 VS3 TEH 0.61 NYAX2 59 H
50 31 54 145 10.25 132 PLP 139 TSH 0.2 01H TEH 0.61 NYAX2 59 H
47 31 94 145 1.54 96 WAR 23 0.31 P12 VS2 0.78 VS3 TEH 0.61 NYAX2 59 H
29 31 94 145 0.8 96 PCT 21 P2 VS2 0.78 TEH TEC 0.61 CBAY2 254 C
108 31 94 145 0.4 76 PCT 14 P2 VS4
-0.69 TEH TEC 0.61 CBAY2 254 C
108 31 104 145 0.6 155 PCT 12 P2 09H 0.71 TEH TEC 0.61 CBAY2 254 C
103 31 114 145 1.01 119 PCT 25 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 45 H
120 31 114 145 0.75 88 WAR 17 0.4 P3 VS3
-0.83 VS3 TEH 0.61 NYAX2 59 H
28 31 126 145 0.28 146 PCT 10 P2 VS1 0.36 TEC TEH 0.61 CBAY2 45 H
114 31 128 145 0.51 153 PCT 17 P2 VS1 0.79 TEC TEH 0.61 CBAY2 47 H
11 31 128 145 0.27 151 PCT 10 P2 VS3
-0.77 TEC TEH 0.61 CBAY2 47 H
11 31 130 145 0.43 146 PCT 14 P2 VS1 0.61 TEC TEH 0.61 CBAY2 45 H
12 31 132 145 0.45 111 PCT 15 P2 VS1 0.79 TEC TEH 0.61 CBAY2 45 H
9 31 7
146 0.32 114 PCT 11 P2 BW2 0.86 TEH TEC 0.61 CBAY2 204 C
21 31 49 146 0.51 139 PCT 14 P2 BW1 0.9 TEH TEC 0.61 CBAY2 226 C
25 31 55 146 3.84 135 PLP 163 TSH 0.2 01H TEH 0.61 NYAX2 59 H
41 31 79 146 0.34 146 PCT 11 P2 VS2 0.7 TEH TEC 0.61 CBAY2 258 C
120 31 85 146 0.32 146 PCT 11 P2 VS2 0.77 TEH TEC 0.61 CBAY2 258 C
117 31 87 146 0.37 141 PCT 12 P2 VS2 0.83 TEH TEC 0.61 CBAY2 258 C
116 31 89 146 0.35 106 PCT 12 P2 VS2 0.78 TEH TEC 0.61 CBAY2 254 C
93 31 105 146 0.46 72 PCT 15 P2 VS2 0.82 TEH TEC 0.61 CBAY2 254 C
101 31 147 146 0.37 153 PCT 10 P2 11H 0.65 TEC TEH 0.61 CBAY2 41 H
102 31 28 147 0.3 134 PCT 11 P2 BW1
-0.91 TEH TEC 0.61 CBAY2 224 C
146 31 48 147 0.32 79 PCT 10 P2 09C
-1.09 TEH TEC 0.61 CBAY2 226 C
9 31 74 147 0.35 139 PCT 11 P2 VS2
-0.78 TEH TEC 0.61 CBAY2 258 C
109 31 88 147 0.25 89 PCT 10 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 254 C
92 31 94 147 0.42 101 PCT 14 P2 VS3
-0.81 TEH TEC 0.61 CBAY2 254 C
90
U3R24 PVGS SG31 All Data Page 36 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 94 147 0.25 104 PCT 10 P2 VS4 0.53 TEH TEC 0.61 CBAY2 254 C
90 31 110 147 0.47 134 PCT 14 P2 VS4
-0.68 TEH TEC 0.61 CBAY2 258 C
188 31 128 147 0.41 127 PCT 13 P2 VS3
-0.67 TEH TEC 0.61 CBAY2 258 C
180 31 152 147 0.27 39 PCT 10 P2 BW1 0.89 TEC TEH 0.61 CBAY2 41 H
66 31 25 148 0.39 60 PCT 13 P2 BW1
-0.96 TEH TEC 0.61 CBAY2 228 C
41 31 49 148 0.62 102 PCT 18 P2 BW1 0.59 TEH TEC 0.61 CBAY2 228 C
29 31 61 148 0.35 106 PCT 12 P2 VS3 0.84 TEH TEC 0.61 CBAY2 228 C
23 31 63 148 0.5 120 PCT 15 P2 VS3 1.06 TEH TEC 0.61 CBAY2 228 C
22 31 87 148 0.38 124 PCT 12 P2 VS2
-0.77 TEH TEC 0.61 CBAY2 258 C
95 31 89 148 0.25 91 PCT 10 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 254 C
75 31 105 148 3.08 103 WAR 31 0.4 P11 VS3
-0.71 VS3 TEH 0.61 NYAX2 59 H
27 31 105 148 1.43 89 PCT 29 P2 VS3
-0.72 TEH TEC 0.61 CBAY2 254 C
83 31 105 148 0.44 62 PCT 15 P2 VS2 0.87 TEH TEC 0.61 CBAY2 254 C
83 31 107 148 0.35 108 PCT 12 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 45 H
123 31 8
149 0.34 124 PCT 11 P2 BW1
-0.69 TEH TEC 0.61 CBAY2 202 C
75 31 46 149 0.24 143 PCT 9
P2 BW1 0.83 TEH TEC 0.61 CBAY2 228 C
9 31 78 149 0.42 144 PCT 13 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 258 C
90 31 88 149 0.27 119 PCT 10 P2 VS2
-0.72 TEH TEC 0.61 CBAY2 254 C
74 31 108 149 0.94 135 PCT 18 P2 10H 0.62 TEH TEC 0.61 CBAY2 258 C
209 31 114 149 1.37 127 PCT 28 P2 VS2 0.82 TEH TEC 0.61 CBAY2 258 C
206 31 114 149 1.08 52 WAR 20 0.23 P4 VS2 0.81 VS3 TEH 0.61 NYAX2 59 H
26 31 148 149 1.63 100 WAR 24 0.2 P14 11H 0.77 11H TEH 0.61 NYAX2 59 H
25 31 148 149 1.01 136 PCT 22 P2 11H 0.63 TEC TEH 0.61 CBAY2 43 H
84 31 148 149 1.18 104 WAR 21 0.2 P9 11H 0.63 11H TEH 0.61 NYAX2 59 H
25 31 47 150 0.35 48 PCT 12 P2 BW2 0.94 TEH TEC 0.61 CBAY2 224 C
119 31 49 150 0.38 75 PCT 12 P2 BW1 0.91 TEH TEC 0.61 CBAY2 224 C
118 31 51 150 0.36 64 PCT 12 P2 BW1
-0.94 TEH TEC 0.61 CBAY2 224 C
117 31 53 150 0.33 105 PCT 11 P2 VS3 1.02 TEH TEC 0.61 CBAY2 224 C
116 31 111 150 0.59 154 PCT 11 P2 10H 0.71 TEH TEC 0.61 CBAY2 258 C
212 31 117 150 0.35 128 PCT 12 P2 BW2
-0.92 TEH TEC 0.61 CBAY2 258 C
215 31 121 150 0.48 92 PCT 15 P2 BW2
-0.73 TEH TEC 0.61 CBAY2 258 C
217 31 125 150 0.54 122 PCT 16 P2 VS1 0.96 TEH TEC 0.61 CBAY2 258 C
219 31 143 150 0.27 107 PCT 10 P2 11H 0.72 TEC TEH 0.61 CBAY2 41 H
98 31 74 151 0.44 145 PCT 14 P2 VS2 0.73 TEH TEC 0.61 CBAY2 258 C
68 31 82 151 0.34 112 PCT 11 P2 09H 0.77 TEH TEC 0.61 CBAY2 258 C
72 31 98 151 0.44 82 PCT 15 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 254 C
50 31 98 151 0.43 118 PCT 14 P2 BW1 0.88 TEH TEC 0.61 CBAY2 254 C
50 31 100 151 0.4 112 PCT 14 P2 BW2
-0.79 TEH TEC 0.61 CBAY2 254 C
49 31 100 151 0.36 87 PCT 13 P2 VS2 0.87 TEH TEC 0.61 CBAY2 254 C
49 31 102 151 0.35 117 PCT 12 P2 BW2
-0.87 TEH TEC 0.61 CBAY2 254 C
48 31 106 151 0.28 129 PCT 11 P2 BW2
-1.29 TEH TEC 0.61 CBAY2 254 C
46 31 124 151 0.43 144 PCT 13 P2 BW2 0.82 TEH TEC 0.61 CBAY2 258 C
224 31 128 151 0.4 150 PCT 15 P2 VS2 0.66 TEC TEH 0.61 CBAY2 43 H
191
U3R24 PVGS SG31 All Data Page 37 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 128 151 0.35 151 PCT 14 P2 VS1 0.66 TEC TEH 0.61 CBAY2 43 H
191 31 142 151 0.49 101 PCT 16 P2 VS1 0.73 TEC TEH 0.61 CBAY2 41 H
97 31 41 152 0.35 125 PCT 12 P2 BW2
-0.79 TEH TEC 0.61 CBAY2 222 C
117 31 65 152 0.9 151 PCT 14 P2 09H 0.76 TEH TEC 0.61 CBAY2 222 C
105 31 67 152 0.29 102 PCT 10 P2 BW2 0.92 TEH TEC 0.61 CBAY2 258 C
64 31 89 152 0.52 103 PCT 16 P2 VS2 0.84 TEH TEC 0.61 CBAY2 254 C
37 31 105 152 0.58 142 PCT 13 P2 10H 0.75 TEH TEC 0.61 CBAY2 254 C
45 31 109 152 0.75 153 PCT 12 P2 09H 0.65 TEH TEC 0.61 CBAY2 258 C
234 31 113 152 0.28 143 PCT 10 P2 VS4 0.91 TEH TEC 0.61 CBAY2 258 C
236 31 129 152 0.23 134 PCT 10 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 43 H
167 31 149 152 0.2 28 PCT 8
P2 BW1 0.86 TEC TEH 0.61 CBAY2 41 H
77 31 58 153 0.42 106 PCT 13 P2 VS3 0.8 TEH TEC 0.61 CBAY2 222 C
101 31 60 153 0.49 111 PCT 15 P2 VS3 0.99 TEH TEC 0.61 CBAY2 222 C
102 31 62 153 0.3 120 PCT 10 P2 BW1 0.87 TEH TEC 0.61 CBAY2 222 C
103 31 62 153 0.3 118 PCT 10 P2 VS3
-0.93 TEH TEC 0.61 CBAY2 222 C
103 31 82 153 0.41 147 PCT 13 P2 VS2 0.75 TEH TEC 0.61 CBAY2 258 C
51 31 92 153 0.29 141 PCT 11 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 254 C
34 31 106 153 0.46 94 PCT 15 P2 BW2
-1.44 TEH TEC 0.61 CBAY2 254 C
27 31 128 153 0.33 152 PCT 13 P2 VS3
-0.66 TEC TEH 0.61 CBAY2 43 H
166 31 132 153 0.33 65 PCT 12 P2 VS1 0.81 TEC TEH 0.61 CBAY2 41 H
152 31 132 153 0.31 89 PCT 12 P2 VS3
-0.82 TEC TEH 0.61 CBAY2 41 H
152 31 134 153 0.25 156 PCT 11 P2 VS1 0.79 TEC TEH 0.61 CBAY2 43 H
159 31 27 154 0.32 61 PCT 11 P2 BW2
-0.79 TEH TEC 0.61 CBAY2 224 C
72 31 59 154 0.48 84 PCT 15 P2 VS3 1.01 TEH TEC 0.61 CBAY2 224 C
56 31 101 154 0.31 77 PCT 11 P2 BW1 0.41 TEH TEC 0.61 CBAY2 254 C
24 31 107 154 0.45 131 PCT 12 P2 10H 0.3 TEH TEC 0.61 CBAY2 254 C
26 31 121 154 0.51 115 PCT 15 P2 BW2
-0.87 TEH TEC 0.61 CBAY2 258 C
259 31 127 154 0.48 151 PCT 15 P2 BW2 0.96 TEH TEC 0.61 CBAY2 258 C
262 31 143 154 0.21 147 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 43 H
89 31 8
155 0.64 83 PCT 18 P2 BW1
-0.74 TEH TEC 0.61 CBAY2 204 C
50 31 48 155 0.41 151 PCT 10 P2 08C
-1 TEH TEC 0.61 CBAY2 224 C
42 31 50 155 0.42 120 PCT 12 P2 09C
-0.99 TEH TEC 0.61 CBAY2 224 C
43 31 102 155 0.43 116 PCT 14 P2 BW2
-0.82 TEH TEC 0.61 CBAY2 254 C
9 31 116 155 0.39 107 PCT 12 P2 BW2 0.9 TEH TEC 0.61 CBAY2 258 C
269 31 118 155 0.53 121 PCT 16 P2 BW2 0.98 TEH TEC 0.61 CBAY2 258 C
268 31 134 155 0.29 154 PCT 12 P2 VS1 0.71 TEC TEH 0.61 CBAY2 43 H
110 31 134 155 0.23 101 PCT 10 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 43 H
110 31 59 156 0.65 123 PCT 18 P2 VS3 0.97 TEH TEC 0.61 CBAY2 222 C
53 31 67 156 0.37 141 PCT 12 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 258 C
23 31 89 156 0.25 154 PCT 9
P2 VS2 0.82 TEH TEC 0.61 CBAY2 258 C
12 31 89 156 0.18 64 PCT 7
P2 09H
-0.05 TEH TEC 0.61 CBAY2 258 C
12 31 101 156 0.68 147 PCT 12 P2 09H 0.71 TEH TEC 0.61 CBAY2 258 C
7 31 107 156 0.42 120 PCT 13 P2 BW1
-1.54 TEH TEC 0.61 CBAY2 258 C
273
U3R24 PVGS SG31 All Data Page 38 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 113 156 0.84 145 PCT 15 P2 10H 0.85 TEH TEC 0.61 CBAY2 258 C
276 31 131 156 0.29 151 PCT 12 P2 BW2 0.86 TEC TEH 0.61 CBAY2 43 H
162 31 48 157 0.46 76 PCT 14 P2 08C
-0.03 TEH TEC 0.61 CBAY2 222 C
41 31 56 157 0.74 124 PCT 19 P2 VS3 0.86 TEH TEC 0.61 CBAY2 222 C
45 31 82 157 0.3 122 PCT 10 P2 VS4 0.27 TEH TEC 0.61 CBAY2 258 C
165 31 86 157 0.64 134 PCT 14 P2 09H 0.69 TEH TEC 0.61 CBAY2 258 C
167 31 92 157 0.45 160 PCT 14 P2 10H 1.42 TEH TEC 0.61 CBAY2 260 C
8 31 96 157 0.28 141 PCT 10 P2 VS3
-0.69 TEH TEC 0.61 CBAY2 260 C
10 31 96 157 0.27 152 PCT 10 P2 VS4
-0.69 TEH TEC 0.61 CBAY2 260 C
10 31 102 157 0.43 128 PCT 11 P2 10H 0.72 TEH TEC 0.61 CBAY2 258 C
169 31 132 157 0.46 144 PCT 17 P2 VS1 0.74 TEC TEH 0.61 CBAY2 43 H
108 31 138 157 0.21 150 PCT 10 P2 VS3 0.83 TEC TEH 0.61 CBAY2 43 H
56 31 140 157 0.4 145 PCT 12 P2 11H 0.6 TEC TEH 0.61 CBAY2 43 H
92 31 144 157 NDF 175 TSC 1.05 01C TEC 0.61 NYAX2 262 C
23 31 144 157 3.81 180 DNT P1 TSC 0.87 TEC TEH 0.61 CBAY2 41 H
82 31 49 158 0.39 126 PCT 13 P2 BW1 1.03 TEH TEC 0.61 CBAY2 220 C
270 31 61 158 0.27 100 PCT 10 P2 VS4 0.85 TEH TEC 0.61 CBAY2 220 C
264 31 73 158 0.35 118 PCT 12 P2 BW1 1.04 TEH TEC 0.61 CBAY2 250 C
154 31 77 158 0.38 148 PCT 13 P2 VS2 0.75 TEH TEC 0.61 CBAY2 250 C
152 31 85 158 0.29 127 PCT 10 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 250 C
148 31 91 158 0.36 96 PCT 12 P2 VS2 0.43 TEH TEC 0.61 CBAY2 250 C
145 31 91 158 0.29 139 PCT 10 P2 BW1 0
TEH TEC 0.61 CBAY2 250 C
145 31 99 158 0.39 127 PCT 13 P2 VS2 0.82 TEH TEC 0.61 CBAY2 250 C
141 31 101 158 0.28 120 PCT 10 P2 BW1 0.85 TEH TEC 0.61 CBAY2 250 C
140 31 103 158 0.4 134 PCT 13 P2 VS3 0.93 TEH TEC 0.61 CBAY2 250 C
139 31 105 158 0.47 135 PCT 15 P2 VS2 0.89 TEH TEC 0.61 CBAY2 250 C
138 31 107 158 0.36 145 PCT 12 P2 VS4
-0.9 TEH TEC 0.61 CBAY2 260 C
137 31 111 158 0.3 130 PCT 10 P2 VS3
-0.9 TEH TEC 0.61 CBAY2 260 C
34 31 113 158 0.3 142 PCT 10 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 260 C
33 31 115 158 0.7 132 PCT 19 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 260 C
32 31 117 158 0.55 145 PCT 16 P2 VS1
-0.86 TEH TEC 0.61 CBAY2 260 C
31 31 127 158 NDF 158 TSH
-1.94 01H TEH 0.61 NYAX2 59 H
22 31 127 158 19.95 5
OXP 2
TSH
-1.94 TEH TEC 0.61 CBAY2 260 C
26 31 129 158 0.22 120 PCT 10 P2 VS1 0.74 TEC TEH 0.61 CBAY2 43 H
164 31 131 158 0.22 146 PCT 10 P2 VS3
-0.97 TEC TEH 0.61 CBAY2 43 H
107 31 30 159 0.24 134 PCT 9
P2 VS3
-0.63 TEH TEC 0.61 CBAY2 220 C
242 31 48 159 0.23 142 PCT 9
P2 BW1
-0.85 TEH TEC 0.61 CBAY2 220 C
251 31 80 159 0.38 140 PCT 12 P2 VS2 0.77 TEH TEC 0.61 CBAY2 250 C
125 31 82 159 0.68 121 PCT 19 P2 VS2 0.77 TEH TEC 0.61 CBAY2 250 C
126 31 102 159 0.28 152 PCT 10 P2 VS4
-0.64 TEH TEC 0.61 CBAY2 250 C
135 31 112 159 1.53 111 PCT 29 P2 VS3
-1.07 TEH TEC 0.61 CBAY2 260 C
39 31 112 159 2.18 101 WAR 27 0.26 P3 VS3
-0.98 VS3 TEH 0.61 NYAX2 59 H
21 31 112 159 0.3 147 PCT 10 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 260 C
39
U3R24 PVGS SG31 All Data Page 39 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 118 159 0.5 131 PCT 15 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 260 C
41 31 124 159 0.55 97 PCT 16 P2 VS3
-1.21 TEH TEC 0.61 CBAY2 260 C
44 31 124 159 0.5 131 PCT 15 P2 VS2 0.98 TEH TEC 0.61 CBAY2 260 C
44 31 124 159 0.3 149 PCT 10 P2 VS3 0.83 TEH TEC 0.61 CBAY2 260 C
44 31 126 159 0.58 106 PCT 17 P2 VS1 0.44 TEH TEC 0.61 CBAY2 260 C
45 31 128 159 0.23 159 PCT 10 P2 VS1 0.89 TEC TEH 0.61 CBAY2 43 H
165 31 132 159 0.27 126 PCT 11 P2 VS1 0.48 TEC TEH 0.61 CBAY2 41 H
147 31 57 160 0.26 152 PCT 9
P2 VS3
-0.88 TEH TEC 0.61 CBAY2 218 C
264 31 75 160 0.3 115 PCT 10 P2 BW1 1.1 TEH TEC 0.61 CBAY2 248 C
152 31 77 160 0.42 133 PCT 13 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 248 C
151 31 91 160 0.44 106 PCT 13 P2 BW1
-0.91 TEH TEC 0.61 CBAY2 248 C
144 31 95 160 0.56 139 PCT 13 P2 10H 0.67 TEH TEC 0.61 CBAY2 248 C
142 31 95 160 0.28 137 PCT 9
P2 10H
-0.15 TEH TEC 0.61 CBAY2 248 C
142 31 99 160 2.29 286 WAR 28 0.4 P11 VS3
-0.72 VS3 TEH 0.61 NYAX2 59 H
20 31 99 160 1.26 106 PCT 26 P2 VS3
-0.65 TEH TEC 0.61 CBAY2 248 C
140 31 99 160 0.31 144 PCT 10 P2 VS4 0.72 TEH TEC 0.61 CBAY2 248 C
140 31 101 160 1.46 111 PCT 28 P2 VS3
-0.85 TEH TEC 0.61 CBAY2 248 C
139 31 101 160 1.28 96 WAR 21 0.26 P3 VS3
-1.03 VS3 TEH 0.61 NYAX2 59 H
19 31 103 160 0.59 144 PCT 16 P2 BW2 0.93 TEH TEC 0.61 CBAY2 248 C
138 31 125 160 0.27 128 PCT 10 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 260 C
47 31 137 160 0.23 132 PCT 10 P2 BW2 0.96 TEC TEH 0.61 CBAY2 43 H
95 31 80 161 0.4 132 PCT 12 P2 VS2
-0.88 TEH TEC 0.61 CBAY2 248 C
121 31 82 161 0.37 125 PCT 12 P2 VS2
-0.11 TEH TEC 0.61 CBAY2 248 C
122 31 82 161 0.3 138 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 248 C
122 31 90 161 0.28 139 PCT 10 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 248 C
126 31 98 161 0.53 140 PCT 11 P2 10H 0.69 TEH TEC 0.61 CBAY2 248 C
130 31 98 161 0.3 145 PCT 10 P2 VS3
-0.64 TEH TEC 0.61 CBAY2 248 C
130 31 100 161 1.13 143 PCT 19 P2 09H 0.63 TEH TEC 0.61 CBAY2 248 C
131 31 124 161 0.62 133 PCT 17 P2 VS3
-0.78 TEH TEC 0.61 CBAY2 260 C
63 31 128 161 1.37 101 WAR 22 0.2 P12 VS1 0.69 VS3 TEH 0.61 NYAX2 59 H
23 31 128 161 0.62 142 PCT 20 P2 VS1 0.69 TEC TEH 0.61 CBAY2 43 H
104 31 35 162 0.66 139 PCT 14 P2 08H 0.9 TEH TEC 0.61 CBAY2 220 C
221 31 57 162 0.36 76 PCT 12 P2 BW1 1.94 TEH TEC 0.61 CBAY2 220 C
211 31 79 162 0.71 145 PCT 13 P2 09H 0.66 TEH TEC 0.61 CBAY2 250 C
114 31 87 162 0.58 135 PCT 17 P2 VS4 0.86 TEH TEC 0.61 CBAY2 250 C
110 31 91 162 0.44 137 PCT 14 P2 BW1 1.19 TEH TEC 0.61 CBAY2 250 C
108 31 93 162 0.37 107 PCT 12 P2 BW1 0.8 TEH TEC 0.61 CBAY2 250 C
107 31 93 162 0.26 145 PCT 9
P2 09H 0.75 TEH TEC 0.61 CBAY2 250 C
107 31 95 162 0.61 141 PCT 13 P2 09H 0.74 TEH TEC 0.61 CBAY2 250 C
106 31 103 162 0.49 129 PCT 13 P2 10H 0.61 TEH TEC 0.61 CBAY2 250 C
102 31 111 162 0.44 143 PCT 10 P2 10C 0.7 TEH TEC 0.61 CBAY2 260 C
74 31 117 162 0.43 109 PCT 13 P2 VS3
-1.22 TEH TEC 0.61 CBAY2 260 C
71 31 123 162 0.31 144 PCT 11 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 260 C
68
U3R24 PVGS SG31 All Data Page 40 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 125 162 0.5 115 PCT 15 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 260 C
67 31 125 162 0.46 121 PCT 14 P2 VS3
-1.06 TEH TEC 0.61 CBAY2 260 C
67 31 135 162 0.35 137 PCT 14 P2 BW1 0.84 TEC TEH 0.61 CBAY2 43 H
97 31 32 163 NDF 10 TSH
-1 01H TEH 0.61 NYAX2 59 H
31 31 32 163 69.31 10 OXP 2
TSH
-1.17 TEH TEC 0.61 CBAY2 220 C
188 31 60 163 0.33 30 PCT 11 P2 VS2
-0.94 TEH TEC 0.61 CBAY2 220 C
202 31 82 163 0.62 143 PCT 12 P2 09C 0.86 TEH TEC 0.61 CBAY2 250 C
89 31 92 163 0.38 113 PCT 12 P2 BW1
-0.74 TEH TEC 0.61 CBAY2 250 C
94 31 92 163 0.34 139 PCT 12 P2 VS2 0.74 TEH TEC 0.61 CBAY2 250 C
94 31 94 163 0.54 137 PCT 16 P2 VS2 0.74 TEH TEC 0.61 CBAY2 250 C
95 31 96 163 0.68 134 PCT 19 P2 VS4
-0.67 TEH TEC 0.61 CBAY2 250 C
96 31 96 163 0.58 126 PCT 17 P2 VS2 0.84 TEH TEC 0.61 CBAY2 250 C
96 31 110 163 0.35 144 PCT 12 P2 VS3 0.91 TEH TEC 0.61 CBAY2 260 C
77 31 112 163 0.38 142 PCT 12 P2 VS3 0.86 TEH TEC 0.61 CBAY2 260 C
78 31 116 163 0.5 136 PCT 15 P2 VS3 0.72 TEH TEC 0.61 CBAY2 260 C
80 31 126 163 0.44 148 PCT 14 P2 BW1 0.87 TEH TEC 0.61 CBAY2 260 C
85 31 128 163 0.23 158 PCT 10 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 43 H
103 31 132 163 0.52 136 PCT 18 P2 VS1
-0.77 TEC TEH 0.61 CBAY2 43 H
50 31 132 163 0.47 138 PCT 17 P2 VS4
-0.81 TEC TEH 0.61 CBAY2 43 H
50 31 134 163 0.37 113 PCT 15 P2 BW1 0.86 TEC TEH 0.61 CBAY2 43 H
98 31 134 163 0.24 132 PCT 11 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 43 H
98 31 47 164 0.36 110 PCT 11 P2 BW1 0.77 TEH TEC 0.61 CBAY2 218 C
214 31 85 164 0.36 130 PCT 12 P2 BW2
-0.88 TEH TEC 0.61 CBAY2 248 C
104 31 91 164 0.38 146 PCT 12 P2 BW1 0.96 TEH TEC 0.61 CBAY2 248 C
101 31 91 164 0.36 98 PCT 11 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 248 C
101 31 93 164 0.44 129 PCT 11 P2 09H 0.69 TEH TEC 0.61 CBAY2 248 C
100 31 99 164 1.45 117 WAR 23 0.31 P11 VS3
-1.21 VS3 TEH 0.61 NYAX2 59 H
18 31 99 164 0.76 118 PCT 20 P2 VS3
-1.21 TEH TEC 0.61 CBAY2 248 C
97 31 107 164 0.22 149 PCT 8
P2 10H 0.57 TEH TEC 0.61 CBAY2 248 C
93 31 109 164 0.5 83 PCT 15 P2 BW1
-0.94 TEH TEC 0.61 CBAY2 260 C
94 31 113 164 0.51 57 PCT 15 P2 VS1
-0.81 TEH TEC 0.61 CBAY2 260 C
92 31 117 164 0.4 100 PCT 13 P2 VS3
-1.24 TEH TEC 0.61 CBAY2 260 C
90 31 123 164 0.52 109 PCT 15 P2 VS3
-1.19 TEH TEC 0.61 CBAY2 260 C
87 31 125 164 0.29 124 PCT 10 P2 BW1 0.95 TEH TEC 0.61 CBAY2 260 C
86 31 133 164 0.21 145 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 43 H
99 31 18 165 NDF 10 TSH 0
01H TEH 0.61 NYAX2 59 H
30 31 18 165 29.74 82 DTI P5 TSH 0
TEH TEC 0.61 CBAY2 236 C
213 31 50 165 0.26 135 PCT 9
P2 09H 0.79 TEH TEC 0.61 CBAY2 218 C
197 31 54 165 0.27 96 PCT 9
P2 BW1
-1.23 TEH TEC 0.61 CBAY2 218 C
199 31 56 165 0.31 141 PCT 10 P2 BW1
-1.58 TEH TEC 0.61 CBAY2 218 C
200 31 62 165 0.37 64 PCT 12 P2 VS3 0.69 TEH TEC 0.61 CBAY2 218 C
203 31 70 165 0.43 127 PCT 13 P2 BW2
-0.93 TEH TEC 0.61 CBAY2 248 C
73 31 70 165 0.34 147 PCT 11 P2 VS2 0.62 TEH TEC 0.61 CBAY2 248 C
73
U3R24 PVGS SG31 All Data Page 41 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 72 165 0.41 112 PCT 13 P2 BW2
-0.84 TEH TEC 0.61 CBAY2 248 C
74 31 76 165 0.35 143 PCT 11 P2 VS3 0.84 TEH TEC 0.61 CBAY2 248 C
76 31 80 165 0.49 132 PCT 15 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 248 C
78 31 84 165 0.34 108 PCT 11 P2 BW2
-0.92 TEH TEC 0.61 CBAY2 248 C
80 31 98 165 0.4 144 PCT 13 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 248 C
87 31 102 165 0.41 130 PCT 13 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 248 C
89 31 104 165 0.5 119 PCT 15 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 248 C
90 31 104 165 0.38 117 PCT 12 P2 BW1
-0.86 TEH TEC 0.61 CBAY2 248 C
90 31 118 165 0.44 111 PCT 14 P2 VS5 0.85 TEH TEC 0.61 CBAY2 260 C
99 31 130 165 0.15 84 PCT 7
P2 BW1
-0.19 TEC TEH 0.61 CBAY2 41 H
84 31 134 165 NDF P54 TSH 0.96 01H TEH 0.61 NYAX2 59 H
24 31 134 165 NDF 167 TSC 0.99 01C TEC 0.61 NYAX2 262 C
15 31 134 165 4.14 183 DNT P1 TSH 0.98 TEC TEH 0.61 CBAY2 41 H
46 31 134 165 5.44 181 DNT P1 TSC 0.93 TEC TEH 0.61 CBAY2 41 H
46 31 39 166 0.45 143 PCT 10 P2 08C 0.77 TEH TEC 0.61 CBAY2 220 C
163 31 45 166 0.37 130 PCT 10 P2 08C
-1.05 TEH TEC 0.61 CBAY2 220 C
160 31 49 166 0.56 110 PCT 17 P2 BW1 0.85 TEH TEC 0.61 CBAY2 220 C
158 31 51 166 0.34 113 PCT 12 P2 BW1 0.85 TEH TEC 0.61 CBAY2 220 C
157 31 71 166 0.42 136 PCT 13 P2 BW1 0.79 TEH TEC 0.61 CBAY2 250 C
81 31 73 166 0.28 140 PCT 10 P2 BW1 0.96 TEH TEC 0.61 CBAY2 250 C
80 31 91 166 0.7 98 PCT 19 P2 10C
-1.64 TEH TEC 0.61 CBAY2 250 C
71 31 97 166 0.4 90 PCT 13 P2 10H
-0.18 TEH TEC 0.61 CBAY2 250 C
68 31 99 166 0.41 117 PCT 13 P2 VS3
-1.3 TEH TEC 0.61 CBAY2 250 C
67 31 111 166 0.27 150 PCT 10 P2 BW1
-0.96 TEH TEC 0.61 CBAY2 260 C
108 31 115 166 0.37 131 PCT 12 P2 BW1 0.41 TEH TEC 0.61 CBAY2 260 C
106 31 117 166 0.29 40 PCT 10 P2 VS3
-1.16 TEH TEC 0.61 CBAY2 260 C
105 31 123 166 0.32 116 PCT 12 P2 VS3
-1.13 TEC TEH 0.61 CBAY2 47 H
131 31 125 166 0.28 116 PCT 11 P2 VS3
-1.11 TEC TEH 0.61 CBAY2 47 H
116 31 44 167 0.38 135 PCT 13 P2 BW1 0.92 TEH TEC 0.61 CBAY2 220 C
137 31 70 167 0.3 138 PCT 10 P2 VS2 0.67 TEH TEC 0.61 CBAY2 250 C
45 31 80 167 0.35 137 PCT 12 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 250 C
50 31 82 167 0.28 122 PCT 10 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 250 C
51 31 110 167 0.53 146 PCT 16 P2 BW1 0.73 TEH TEC 0.61 CBAY2 260 C
112 31 112 167 0.42 101 PCT 13 P2 BW1
-1.06 TEH TEC 0.61 CBAY2 260 C
113 31 124 167 0.62 153 PCT 12 P2 10H 0.67 TEC TEH 0.61 CBAY2 47 H
117 31 9
168 0.54 146 PCT 10 P2 07C 0.76 TEH TEC 0.61 CBAY2 206 C
10 31 23 168 0.52 147 PCT 11 P2 08H
-0.57 TEH TEC 0.61 CBAY2 218 C
171 31 47 168 0.34 67 PCT 11 P2 08C
-1.09 TEH TEC 0.61 CBAY2 218 C
159 31 59 168 0.26 138 PCT 9
P2 BW1 0.87 TEH TEC 0.61 CBAY2 218 C
153 31 63 168 0.3 104 PCT 10 P2 VS3 1.27 TEH TEC 0.61 CBAY2 218 C
151 31 79 168 0.42 144 PCT 13 P2 VS2 0.77 TEH TEC 0.61 CBAY2 248 C
64 31 81 168 0.3 149 PCT 10 P2 VS2 0.74 TEH TEC 0.61 CBAY2 248 C
63 31 87 168 0.36 130 PCT 12 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 248 C
60
U3R24 PVGS SG31 All Data Page 42 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 99 168 0.46 120 PCT 14 P2 VS3
-1.11 TEH TEC 0.61 CBAY2 248 C
54 31 101 168 0.3 139 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 248 C
53 31 109 168 0.81 160 PCT 14 P2 09H 0.73 TEH TEC 0.61 CBAY2 260 C
123 31 117 168 0.35 127 PCT 12 P2 VS3
-1.16 TEH TEC 0.61 CBAY2 260 C
119 31 117 168 0.6 144 PCT 12 P2 10C 0.83 TEH TEC 0.61 CBAY2 260 C
119 31 129 168 0.38 143 PCT 13 P2 VS3 0.61 TEC TEH 0.61 CBAY2 45 H
126 31 129 168 0.27 104 PCT 10 P2 VS3
-0.05 TEC TEH 0.61 CBAY2 45 H
126 31 129 168 0.16 136 PCT 7
P2 VS1
-0.85 TEC TEH 0.61 CBAY2 45 H
126 31 54 169 0.32 127 PCT 11 P2 VS3
-1.12 TEH TEC 0.61 CBAY2 218 C
132 31 56 169 0.3 73 PCT 10 P2 BW1
-1.49 TEH TEC 0.61 CBAY2 218 C
133 31 62 169 0.49 103 PCT 14 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 218 C
136 31 66 169 0.33 120 PCT 11 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 248 C
29 31 70 169 0.34 143 PCT 11 P2 VS2 0.57 TEH TEC 0.61 CBAY2 248 C
31 31 92 169 0.2 119 PCT 7
P2 VS2
-0.81 TEH TEC 0.61 CBAY2 248 C
42 31 96 169 0.41 108 PCT 13 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 248 C
43 31 96 169 0.42 141 PCT 13 P2 VS2 0.84 TEH TEC 0.61 CBAY2 248 C
43 31 96 169 0.33 96 PCT 11 P2 BW1 0.18 TEH TEC 0.61 CBAY2 248 C
43 31 102 169 0.49 126 PCT 14 P2 VS3 0.54 TEH TEC 0.61 CBAY2 248 C
46 31 106 169 0.28 87 PCT 10 P2 10C 0.72 TEH TEC 0.61 CBAY2 248 C
48 31 128 169 0.65 99 PCT 19 P2 VS3
-1.13 TEC TEH 0.61 CBAY2 45 H
127 31 128 169 NDF 155 TSC 0.94 01C TEC 0.61 NYAX2 262 C
14 31 128 169 4.58 183 DNT P1 TSC 0.94 TEC TEH 0.61 CBAY2 45 H
127 31 49 170 0.34 122 PCT 12 P2 BW1 0.82 TEH TEC 0.61 CBAY2 220 C
101 31 51 170 0.56 148 PCT 12 P2 09H 0.76 TEH TEC 0.61 CBAY2 220 C
100 31 79 170 0.28 141 PCT 10 P2 BW1 0.86 TEH TEC 0.61 CBAY2 250 C
38 31 81 170 0.38 139 PCT 12 P2 VS2 0.84 TEH TEC 0.61 CBAY2 250 C
37 31 83 170 0.35 137 PCT 12 P2 BW1 0.93 TEH TEC 0.61 CBAY2 250 C
36 31 87 170 0.34 91 PCT 11 P2 BW1 0.88 TEH TEC 0.61 CBAY2 250 C
34 31 89 170 NDF 11 09H 33.28 VS3 TEH 0.61 NYAX2 59 H
17 31 95 170 0.26 70 PCT 10 P2 BW2 0.57 TEH TEC 0.61 CBAY2 250 C
31 31 97 170 0.27 69 PCT 10 P2 VS3
-1.04 TEH TEC 0.61 CBAY2 250 C
30 31 99 170 0.38 121 PCT 13 P2 VS3
-1.2 TEH TEC 0.61 CBAY2 250 C
29 31 99 170 0.34 138 PCT 12 P2 VS4 1.11 TEH TEC 0.61 CBAY2 250 C
29 31 101 170 0.3 101 PCT 10 P2 BW1 0.88 TEH TEC 0.61 CBAY2 250 C
28 31 103 170 0.37 92 PCT 12 P2 BW1 0.95 TEH TEC 0.61 CBAY2 250 C
27 31 119 170 0.69 157 PCT 12 P2 09H 0.73 TEC TEH 0.61 CBAY2 47 H
127 31 121 170 0.44 153 PCT 10 P2 10H 0.82 TEC TEH 0.61 CBAY2 47 H
120 31 32 171 0.76 151 PCT 13 P2 08C 0.81 TEH TEC 0.61 CBAY2 220 C
74 31 34 171 0.54 145 PCT 12 P2 08C 0.78 TEH TEC 0.61 CBAY2 220 C
75 31 70 171 0.36 137 PCT 12 P2 VS2 0.81 TEH TEC 0.61 CBAY2 250 C
8 31 90 171 0.69 141 PCT 14 P2 09H 0.67 TEH TEC 0.61 CBAY2 250 C
18 31 94 171 0.66 143 PCT 13 P2 09H 0.69 TEH TEC 0.61 CBAY2 250 C
19 31 94 171 0.33 117 PCT 11 P2 VS3 0.56 TEH TEC 0.61 CBAY2 250 C
19
U3R24 PVGS SG31 All Data Page 43 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 114 171 0.66 137 PCT 15 P2 10H
-0.05 TEC TEH 0.61 CBAY2 47 H
139 31 122 171 0.25 143 PCT 10 P2 05C 0.78 TEC TEH 0.61 CBAY2 45 H
140 31 15 172 0.51 135 PCT 12 P2 08H
-0.3 TEH TEC 0.61 CBAY2 218 C
108 31 31 172 0.18 153 PCT 7
P2 VS3
-0.8 TEH TEC 0.61 CBAY2 218 C
100 31 47 172 0.33 70 PCT 11 P2 BW2 0.62 TEH TEC 0.61 CBAY2 218 C
92 31 63 172 0.32 113 PCT 11 P2 BW1 0.4 TEH TEC 0.61 CBAY2 218 C
84 31 87 172 0.34 56 PCT 11 P2 BW1 0.89 TEH TEC 0.61 CBAY2 242 C
13 31 89 172 0.57 125 PCT 16 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 248 C
24 31 89 172 0.28 130 PCT 10 P2 VS4 0.94 TEH TEC 0.61 CBAY2 248 C
24 31 93 172 0.36 55 PCT 11 P2 10H 0.71 TEH TEC 0.61 CBAY2 242 C
46 31 105 172 0.36 86 PCT 12 P2 BW1
-1.06 TEH TEC 0.61 CBAY2 242 C
87 31 105 172 0.28 133 PCT 10 P2 BW1
-0.59 TEH TEC 0.61 CBAY2 242 C
87 31 105 172 0.3 143 PCT 10 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 242 C
87 31 111 172 0.33 86 PCT 11 P2 BW1
-0.89 TEH TEC 0.61 CBAY2 260 C
135 31 113 172 0.13 147 PCT 6
P2 BW1 0.74 TEC TEH 0.61 CBAY2 47 H
138 31 56 173 0.44 125 PCT 13 P2 BW1
-1.49 TEH TEC 0.61 CBAY2 218 C
78 31 56 173 0.18 146 PCT 7
P2 VS3
-0.87 TEH TEC 0.61 CBAY2 218 C
78 31 72 173 0.34 90 PCT 11 P2 BW1 1.03 TEH TEC 0.61 CBAY2 248 C
13 31 88 173 0.33 135 PCT 11 P2 VS4
-0.51 TEH TEC 0.61 CBAY2 248 C
17 31 88 173 0.31 121 PCT 10 P2 VS2 0.82 TEH TEC 0.61 CBAY2 248 C
17 31 92 173 0.36 76 PCT 12 P2 VS3 0.82 TEH TEC 0.61 CBAY2 242 C
45 31 96 173 1.77 113 WAR 25 0.18 P11 VS3 0.58 VS3 TEH 0.61 NYAX2 59 H
16 31 96 173 0.88 123 PCT 21 P2 VS3 0.49 TEH TEC 0.61 CBAY2 242 C
105 31 98 173 0.67 131 PCT 18 P2 VS4
-0.56 TEH TEC 0.61 CBAY2 248 C
18 31 108 173 0.99 137 PCT 18 P2 10H 0.71 TEH TEC 0.61 CBAY2 248 C
21 31 108 173 0.29 138 PCT 10 P2 VS3
-0.74 TEH TEC 0.61 CBAY2 248 C
21 31 114 173 0.41 159 PCT 13 P2 VS1 0.88 TEH TEC 0.61 CBAY2 242 C
112 31 19 174 0.27 107 PCT 10 P2 08C
-0.05 TEH TEC 0.61 CBAY2 220 C
56 31 35 174 0.34 20 PCT 10 P2 05C 0.81 TEH TEC 0.61 CBAY2 220 C
48 31 49 174 0.31 42 PCT 11 P2 BW1 0.91 TEH TEC 0.61 CBAY2 220 C
41 31 57 174 0.34 73 PCT 12 P2 VS3 1.1 TEH TEC 0.61 CBAY2 220 C
37 31 61 174 0.38 76 PCT 13 P2 BW1 0.67 TEH TEC 0.61 CBAY2 220 C
35 31 63 174 0.29 93 PCT 10 P2 VS3 1.1 TEH TEC 0.61 CBAY2 220 C
34 31 65 174 0.4 48 PCT 13 P2 BW2 0.94 TEH TEC 0.61 CBAY2 220 C
33 31 89 174 0.33 137 PCT 11 P2 VS2 0.77 TEH TEC 0.61 CBAY2 240 C
9 31 89 174 0.29 146 PCT 10 P2 BW1
-0.75 TEH TEC 0.61 CBAY2 240 C
9 31 93 174 0.33 62 PCT 11 P2 VS2 0.81 TEH TEC 0.61 CBAY2 242 C
49 31 99 174 0.37 82 PCT 12 P2 VS3
-1.44 TEH TEC 0.61 CBAY2 240 C
127 31 99 174 0.73 165 PCT 10 P2 09H 0.8 TEH TEC 0.61 CBAY2 240 C
127 31 101 174 0.3 48 PCT 10 P2 VS2
-0.72 TEH TEC 0.61 CBAY2 242 C
90 31 115 174 0.42 144 PCT 10 P2 09H 0.8 TEC TEH 0.61 CBAY2 45 H
149 31 115 174 0.2 120 PCT 8
P2 VS1 0.84 TEC TEH 0.61 CBAY2 45 H
149 31 24 175 0.42 135 PCT 12 P2 08C
-0.98 TEH TEC 0.61 CBAY2 220 C
10
U3R24 PVGS SG31 All Data Page 44 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 38 175 0.52 131 PCT 13 P2 08C 0.69 TEH TEC 0.61 CBAY2 220 C
17 31 40 175 0.39 136 PCT 10 P2 08C
-1.07 TEH TEC 0.61 CBAY2 220 C
18 31 78 175 0.31 147 PCT 10 P2 VS2 0.78 TEH TEC 0.61 CBAY2 236 C
281 31 80 175 0.34 153 PCT 11 P2 VS2 0.84 TEH TEC 0.61 CBAY2 236 C
284 31 82 175 0.66 119 PCT 18 P2 VS2 0.76 TEH TEC 0.61 CBAY2 238 C
317 31 92 175 0.45 22 PCT 13 P2 10H 1.45 TEH TEC 0.61 CBAY2 242 C
50 31 98 175 0.54 94 PCT 15 P2 BW1
-1.39 TEH TEC 0.61 CBAY2 240 C
128 31 98 175 0.31 99 PCT 10 P2 BW1
-0.08 TEH TEC 0.61 CBAY2 240 C
128 31 100 175 0.41 140 PCT 13 P2 VS3 0.49 TEH TEC 0.61 CBAY2 242 C
103 31 106 175 0.78 139 PCT 15 P2 10H 0.71 TEH TEC 0.61 CBAY2 240 C
108 31 118 175 0.25 129 PCT 10 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 45 H
136 31 63 176 0.25 107 PCT 9
P2 BW1
-0.77 TEH TEC 0.61 CBAY2 218 C
31 31 79 176 1.69 122 WAR 24 0.34 P7 VS4
-0.83 VS3 TEC 0.61 NYAX2 262 C
13 31 79 176 0.66 149 PCT 18 P2 VS4
-0.6 TEH TEC 0.61 CBAY2 236 C
285 31 85 176 0.32 85 PCT 10 P2 VS3
-1.23 TEH TEC 0.61 CBAY2 240 C
6 31 87 176 1.75 115 WAR 25 0.34 P28 VS2 0.82 VS3 TEH 0.61 NYAX2 59 H
15 31 87 176 0.83 129 PCT 20 P2 VS2 0.74 TEH TEC 0.61 CBAY2 240 C
11 31 89 176 0.37 57 PCT 12 P2 BW1 0.86 TEH TEC 0.61 CBAY2 242 C
42 31 91 176 0.43 91 PCT 13 P2 BW2
-0.87 TEH TEC 0.61 CBAY2 242 C
51 31 91 176 0.37 102 PCT 12 P2 BW1
-0.58 TEH TEC 0.61 CBAY2 242 C
51 31 97 176 0.36 92 PCT 11 P2 VS3
-1.2 TEH TEC 0.61 CBAY2 240 C
129 31 99 176 0.65 126 PCT 18 P2 VS3
-1.23 TEH TEC 0.61 CBAY2 242 C
102 31 103 176 0.45 75 PCT 14 P2 VS3
-1.22 TEH TEC 0.61 CBAY2 240 C
112 31 54 177 0.24 146 PCT 8
P2 VS3
-0.98 TEH TEC 0.61 CBAY2 218 C
25 31 56 177 0.4 129 PCT 12 P2 VS3
-1.04 TEH TEC 0.61 CBAY2 218 C
26 31 58 177 0.32 130 PCT 10 P2 BW1
-1.69 TEH TEC 0.61 CBAY2 218 C
27 31 60 177 0.37 66 PCT 12 P2 BW1
-0.76 TEH TEC 0.61 CBAY2 218 C
28 31 94 177 0.38 150 PCT 12 P2 VS2 0.83 TEH TEC 0.61 CBAY2 240 C
53 31 98 177 0.42 138 PCT 13 P2 BW2 1.04 TEH TEC 0.61 CBAY2 242 C
101 31 49 178 0.54 150 PCT 15 P2 09H 1.09 TEH TEC 0.61 CBAY2 230 C
25 31 75 178 0.37 127 PCT 12 P2 VS2 0.79 TEH TEC 0.61 CBAY2 236 C
278 31 77 178 0.4 99 PCT 12 P2 VS3
-1.1 TEH TEC 0.61 CBAY2 236 C
287 31 81 178 3.07 112 WAR 31 0.23 P31 BW2 0.93 VS3 TEC 0.61 NYAX2 262 C
12 31 81 178 1.43 92 PCT 28 P2 BW2 0.91 TEH TEC 0.61 CBAY2 242 C
10 31 101 178 0.41 129 PCT 13 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 240 C
125 31 101 178 0.31 97 PCT 10 P2 VS3
-1.02 TEH TEC 0.61 CBAY2 240 C
125 31 105 178 0.54 112 PCT 16 P2 VS4 0.73 TEH TEC 0.61 CBAY2 250 C
6 31 113 178 0.49 28 PCT 11 P2 04C 0.8 TEC TEH 0.61 CBAY2 45 H
150 31 56 179 0.33 138 PCT 10 P2 BW1
-1.57 TEH TEC 0.61 CBAY2 230 C
67 31 82 179 0.56 123 PCT 16 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 236 C
309 31 82 179 0.68 137 PCT 14 P2 09C
-0.28 TEH TEC 0.61 CBAY2 236 C
309 31 82 179 0.29 150 PCT 10 P2 VS2 0.84 TEH TEC 0.61 CBAY2 236 C
309 31 82 179 0.29 115 PCT 10 P2 VS3 0.61 TEH TEC 0.61 CBAY2 236 C
309
U3R24 PVGS SG31 All Data Page 45 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 96 179 0.43 43 PCT 13 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 242 C
99 31 104 179 0.45 136 PCT 14 P2 VS3
-0.73 TEH TEC 0.61 CBAY2 250 C
5 31 106 179 0.34 115 PCT 10 P2 03C 0.85 TEH TEC 0.61 CBAY2 248 C
10 31 110 179 0.3 80 PCT 11 P2 VS3
-1.08 TEC TEH 0.61 CBAY2 45 H
144 31 43 180 0.46 142 PCT 10 P2 08C 0.82 TEH TEC 0.61 CBAY2 230 C
78 31 47 180 0.32 131 PCT 10 P2 BW2 0.93 TEH TEC 0.61 CBAY2 230 C
76 31 49 180 0.33 145 PCT 10 P2 BW1 0.48 TEH TEC 0.61 CBAY2 230 C
75 31 51 180 0.42 144 PCT 12 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 230 C
74 31 67 180 0.37 110 PCT 12 P2 VS3 1.03 TEH TEC 0.61 CBAY2 238 C
28 31 79 180 0.17 151 PCT 7
P2 VS3
-0.95 TEH TEC 0.61 CBAY2 242 C
16 31 85 180 0.43 115 PCT 13 P2 VS4 1
TEH TEC 0.61 CBAY2 242 C
38 31 89 180 0.4 83 PCT 12 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 240 C
44 31 89 180 0.25 130 PCT 9
P2 BW1
-1.02 TEH TEC 0.61 CBAY2 240 C
44 31 91 180 0.3 115 PCT 10 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 240 C
56 31 103 180 1.9 103 WAR 26 0.2 P11 VS3
-1.19 VS3 TEH 0.61 NYAX2 59 H
13 31 103 180 0.88 127 PCT 21 P2 VS3
-1.19 TEH TEC 0.61 CBAY2 248 C
6 31 105 180 1.8 107 WAR 25 0.24 P11 VS3
-1.06 VS3 TEH 0.61 NYAX2 59 H
14 31 105 180 0.82 120 PCT 20 P2 VS3
-1.06 TEH TEC 0.61 CBAY2 248 C
7 31 107 180 0.56 116 PCT 16 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 248 C
8 31 107 180 0.27 142 PCT 9
P2 05C 0.9 TEH TEC 0.61 CBAY2 248 C
8 31 109 180 0.31 118 PCT 11 P2 VS3 0.05 TEC TEH 0.61 CBAY2 45 H
143 31 56 181 0.31 33 PCT 11 P2 BW1
-1.48 TEH TEC 0.61 CBAY2 238 C
34 31 74 181 0.29 136 PCT 10 P2 BW1 0.9 TEH TEC 0.61 CBAY2 236 C
290 31 82 181 0.36 131 PCT 11 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 240 C
16 31 88 181 0.33 141 PCT 11 P2 VS3
-0.87 TEH TEC 0.61 CBAY2 240 C
43 31 90 181 0.37 128 PCT 12 P2 VS3
-1.12 TEH TEC 0.61 CBAY2 240 C
57 31 94 181 0.33 135 PCT 11 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 242 C
97 31 94 181 0.29 111 PCT 10 P2 VS3 0.46 TEH TEC 0.61 CBAY2 242 C
97 31 98 181 1.2 104 PCT 25 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 240 C
122 31 98 181 1.6 94 WAR 24 0.59 P3 VS3
-1.05 VS3 TEH 0.61 NYAX2 59 H
12 31 100 181 1.28 104 PCT 26 P2 VS3
-1.26 TEH TEC 0.61 CBAY2 240 C
102 31 100 181 1.69 101 WAR 24 0.32 P4 VS3
-0.88 VS3 TEH 0.61 NYAX2 59 H
11 31 106 181 1.2 118 WAR 21 0.25 P3 VS3
-1.11 VS3 TEH 0.61 NYAX2 59 H
10 31 106 181 0.83 112 PCT 21 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 248 C
5 31 106 181 0.59 134 PCT 13 P2 05C 0.82 TEH TEC 0.61 CBAY2 248 C
5 31 106 181 0.31 95 PCT 10 P2 VS3
-0.39 TEH TEC 0.61 CBAY2 248 C
5 31 75 182 0.48 93 PCT 15 P2 VS2
-0.98 TEH TEC 0.61 CBAY2 238 C
310 31 77 182 0.33 36 PCT 11 P2 VS2
-0.88 TEH TEC 0.61 CBAY2 242 C
18 31 79 182 0.35 133 PCT 11 P2 VS3
-0.85 TEH TEC 0.61 CBAY2 236 C
306 31 81 182 0.38 88 PCT 12 P2 VS3
-1.22 TEH TEC 0.61 CBAY2 240 C
17 31 83 182 0.32 61 PCT 11 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 242 C
36 31 85 182 0.33 101 PCT 11 P2 VS4 0.88 TEH TEC 0.61 CBAY2 242 C
57 31 87 182 0.58 100 PCT 16 P2 VS3
-1.07 TEH TEC 0.61 CBAY2 240 C
42
U3R24 PVGS SG31 All Data Page 46 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 87 182 0.37 37 PCT 12 P2 09C
-1 TEH TEC 0.61 CBAY2 240 C
42 31 95 182 0.37 98 PCT 12 P2 VS3
-1.2 TEH TEC 0.61 CBAY2 240 C
78 31 99 182 0.69 114 PCT 18 P2 VS3
-1.52 TEH TEC 0.61 CBAY2 240 C
101 31 103 182 0.43 129 PCT 13 P2 VS3
-1.15 TEH TEC 0.61 CBAY2 242 C
107 31 4
183 0.24 147 PCT 9
P2 07C 0.76 TEH TEC 0.61 CBAY2 210 C
29 31 10 183 0.45 75 PCT 14 P2 07H
-0.99 TEH TEC 0.61 CBAY2 212 C
6 31 82 183 0.32 67 PCT 11 P2 VS4
-0.62 TEH TEC 0.61 CBAY2 242 C
35 31 88 183 0.43 107 PCT 13 P2 VS2 0.47 TEH TEC 0.61 CBAY2 240 C
59 31 94 183 0.58 148 PCT 11 P2 09H 0.31 TEH TEC 0.61 CBAY2 240 C
77 31 102 183 0.63 132 PCT 14 P2 04C 0.77 TEH TEC 0.61 CBAY2 240 C
138 31 13 184 0.22 75 PCT 8
P2 08H 0.25 TEH TEC 0.61 CBAY2 238 C
58 31 49 184 0.32 86 PCT 11 P2 BW2
-0.91 TEH TEC 0.61 CBAY2 238 C
76 31 59 184 0.63 102 PCT 18 P2 BW2 0.92 TEH TEC 0.61 CBAY2 238 C
81 31 81 184 0.35 49 PCT 12 P2 VS4
-0.65 TEH TEC 0.61 CBAY2 242 C
34 31 83 184 0.26 31 PCT 9
P2 BW1 1.24 TEH TEC 0.61 CBAY2 242 C
59 31 97 184 0.44 76 PCT 13 P2 VS3
-1.17 TEH TEC 0.61 CBAY2 240 C
136 31 99 184 2.17 109 WAR 27 0.29 P11 VS3
-1.43 VS3 TEH 0.61 NYAX2 59 H
9 31 99 184 1.08 106 PCT 24 P2 VS3
-1.11 TEH TEC 0.61 CBAY2 240 C
135 31 80 185 0.74 130 PCT 16 P2 09H 0.69 TEH TEC 0.61 CBAY2 242 C
33 31 96 185 0.42 137 PCT 13 P2 BW1 0.89 TEH TEC 0.61 CBAY2 240 C
133 31 98 185 0.41 93 PCT 13 P2 VS3
-1.16 TEH TEC 0.61 CBAY2 240 C
134 31 47 186 0.41 114 PCT 13 P2 BW1
-0.83 TEH TEC 0.61 CBAY2 236 C
78 31 49 186 0.31 146 PCT 10 P2 BW1 0.69 TEH TEC 0.61 CBAY2 236 C
79 31 51 186 0.29 133 PCT 10 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 236 C
80 31 77 186 0.66 91 PCT 18 P2 VS3
-1.14 TEH TEC 0.61 CBAY2 240 C
21 31 81 186 2.53 106 WAR 29 0.35 P8 VS4
-0.88 VS3 TEC 0.61 NYAX2 262 C
11 31 81 186 1.17 77 PCT 25 P2 VS4
-0.73 TEH TEC 0.61 CBAY2 242 C
61 31 81 186 0.31 62 PCT 11 P2 VS2 0.82 TEH TEC 0.61 CBAY2 242 C
61 31 83 186 0.49 120 PCT 14 P2 BW1 0.97 TEH TEC 0.61 CBAY2 240 C
38 31 95 186 0.45 119 PCT 13 P2 04C 0.87 TEH TEC 0.61 CBAY2 240 C
132 31 95 186 NDF P12 TSH 2.51 01H TEH 0.61 NYAX2 59 H
8 31 95 186 7.01 181 DNT P1 TSH 2.51 TEH TEC 0.61 CBAY2 240 C
132 31 76 187 0.34 150 PCT 11 P2 VS2 0.67 TEH TEC 0.61 CBAY2 240 C
22 31 82 187 0.43 82 PCT 13 P2 VS3 0.68 TEH TEC 0.61 CBAY2 240 C
37 31 84 187 0.29 110 PCT 10 P2 VS2 0.6 TEH TEC 0.61 CBAY2 240 C
63 31 92 187 0.53 143 PCT 11 P2 05C 0.77 TEH TEC 0.61 CBAY2 240 C
114 31 53 188 0.43 85 PCT 14 P2 BW2
-1.04 TEH TEC 0.61 CBAY2 238 C
135 31 63 188 0.27 100 PCT 10 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 238 C
140 31 77 188 0.44 129 PCT 13 P2 VS3
-1.08 TEH TEC 0.61 CBAY2 242 C
30 31 79 188 0.37 130 PCT 12 P2 VS3
-0.95 TEH TEC 0.61 CBAY2 242 C
63 31 81 188 0.49 135 PCT 11 P2 09C
-0.25 TEH TEC 0.61 CBAY2 240 C
36 31 81 188 0.32 89 PCT 10 P2 VS2
-1.06 TEH TEC 0.61 CBAY2 240 C
36 31 87 188 0.31 135 PCT 10 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 242 C
95
U3R24 PVGS SG31 All Data Page 47 of 47 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 31 89 188 0.88 95 PCT 21 P2 VS3
-1.1 TEH TEC 0.61 CBAY2 240 C
72 31 89 188 0.93 110 WAR 19 0.2 P12 VS3
-1.1 VS3 TEH 0.61 NYAX2 59 H
7 31 58 189 0.73 106 PCT 19 P2 VS3
-0.94 TEH TEC 0.61 CBAY2 238 C
147 31 73 190 0.32 74 PCT 10 P2 VS3
-1.16 TEH TEC 0.61 CBAY2 240 C
25 31 75 190 0.31 102 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 242 C
28 31 77 190 0.78 102 PCT 20 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 240 C
31 31 77 190 0.9 119 WAR 18 0.14 P12 VS3
-1.09 VS3 TEH 0.61 NYAX2 59 H
5 31 52 191 0.25 42 PCT 9
P2 09H 0.39 TEH TEC 0.61 CBAY2 236 C
149 31 58 191 0.36 142 PCT 12 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 236 C
146 31 77 192 2.49 289 WAR 29 0.23 P12 VS3
-1.09 VS3 TEH 0.61 NYAX2 59 H
6 31 77 192 1.55 104 PCT 29 P2 VS3
-0.97 TEH TEC 0.61 CBAY2 240 C
32 31 56 195 0.25 133 PCT 9
P2 09C 0.74 TEH TEC 0.61 CBAY2 236 C
202 31 51 196 0.27 92 PCT 10 P2 03C 0.02 TEH TEC 0.61 CBAY2 238 C
254 31 58 197 0.39 128 PCT 11 P2 03C 0.8 TEH TEC 0.61 CBAY2 228 C
329 31 36 199 0.49 139 PCT 10 P2 08C 0.74 TEH TEC 0.61 CBAY2 226 C
286 31 43 200 0.38 127 PCT 11 P2 08C
-1.09 TEH TEC 0.61 CBAY2 228 C
289 31 29 202 0.34 68 PCT 11 P2 08C
-0.98 TEH TEC 0.61 CBAY2 226 C
264
APPENDIX C STEAM GENERATOR 32
SUMMARY
DATA SHEETS
U3R24 PVGS SG32 All Data Page 1 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 3
24 0.69 54 PLP 7
07H 6.96 TEH TEC 0.61 CBAY2 22 C
60 32 3
24 4.44 119 PLP 24 07H 7.05 08H TEH 0.61 NYAX2 49 H
18 32 3
62 0.23 77 PCT 9
P2 06C 0.79 TEH TEC 0.61 CBAY2 22 C
157 32 3
176 0.32 41 PCT 10 P2 07C 0.7 TEH TEC 0.61 CBAY2 204 C
64 32 3
176 0.34 54 PCT 11 P2 04C 0.8 TEH TEC 0.61 CBAY2 204 C
64 32 4
131 0.27 128 PCT 10 P2 08C 0.61 TEH TEC 0.61 CBAY2 206 C
74 32 5
178 0.44 129 PCT 11 P2 07C 0.73 TEH TEC 0.61 CBAY2 204 C
62 32 6
157 0.37 108 PCT 11 P2 08H 0.38 TEH TEC 0.61 CBAY2 204 C
111 32 6
165 0.43 120 PCT 12 P2 04C 0.73 TEH TEC 0.61 CBAY2 204 C
91 32 7
34 0.28 83 PCT 10 P2 BW2 1.09 TEH TEC 0.61 CBAY2 22 C
84 32 8
65 0.27 101 PCT 9
P2 06H 0.85 TEH TEC 0.61 CBAY2 24 C
163 32 8
69 0.43 56 PCT 14 P2 BW1
-0.59 TEH TEC 0.61 CBAY2 22 C
167 32 8
69 0.33 57 PCT 12 P2 BW1 0.9 TEH TEC 0.61 CBAY2 22 C
167 32 8
131 0.42 36 PCT 14 P2 BW2 1.29 TEH TEC 0.61 CBAY2 206 C
75 32 8
159 0.39 117 PCT 11 P2 08C 0.67 TEH TEC 0.61 CBAY2 204 C
109 32 8
175 0.29 100 PCT 10 P2 07C 0.8 TEH TEC 0.61 CBAY2 204 C
70 32 8
183 0.5 145 PCT 10 P2 07C 0.68 TEH TEC 0.61 CBAY2 204 C
53 32 9
8 0.35 129 PCT 10 P2 05H 0.77 TEH TEC 0.61 CBAY2 24 C
24 32 9
130 1.72 101 WAR 24 0.22 P3 BW1 1.21 07H VS3 0.58 NPUFZ 57 H
9 32 9
130 1.01 134 PCT 25 P2 BW1 1.11 TEH TEC 0.61 CBAY2 206 C
73 32 10 67 0.5 88 PCT 15 P2 BW1
-0.69 TEH TEC 0.61 CBAY2 24 C
161 32 10 171 0.25 153 PCT 10 P2 BW1
-0.76 TEH TEC 0.61 CBAY2 202 C
124 32 11 10 0.48 133 PCT 12 P2 05H 0.75 TEH TEC 0.61 CBAY2 6
C 22 32 11 34 0.31 111 PCT 11 P2 06C 0.89 TEH TEC 0.61 CBAY2 10 C
263 32 11 74 0.8 147 PCT 16 P2 08C 0.72 TEH TEC 0.61 CBAY2 18 C
197 32 11 132 0.63 113 PCT 17 P2 BW2 1.25 TEH TEC 0.61 CBAY2 224 C
189 32 11 162 0.24 125 PCT 10 P2 07C 0.77 TEH TEC 0.61 CBAY2 214 C
207 32 11 162 0.24 154 PCT 10 P2 06C 0.65 TEH TEC 0.61 CBAY2 214 C
207 32 11 162 0.34 143 PCT 12 P2 04C 0.81 TEH TEC 0.61 CBAY2 214 C
207 32 11 176 0.5 136 PCT 12 P2 07C 0.75 TEH TEC 0.61 CBAY2 212 C
344 32 12 27 0.31 82 PCT 11 P2 05C 0.8 TEH TEC 0.61 CBAY2 10 C
156 32 12 61 0.34 157 PCT 10 P2 06H 0.61 TEH TEC 0.61 CBAY2 18 C
21 32 12 171 0.45 138 PCT 12 P2 07C 0.75 TEH TEC 0.61 CBAY2 214 C
57 32 12 179 0.27 107 PCT 10 P2 04C 0.8 TEH TEC 0.61 CBAY2 210 C
265 32 13 132 0.41 79 PCT 12 P2 BW2 1.22 TEH TEC 0.61 CBAY2 224 C
146 32 13 198 0.25 76 PCT 10 P2 BW1 0.99 TEH TEC 0.61 CBAY2 210 C
62 32 14 17 0.21 90 PCT 8
P2 08H
-0.98 TEH TEC 0.61 CBAY2 12 C
14 32 14 73 0.38 57 PCT 12 P2 08C 0.75 TEH TEC 0.61 CBAY2 18 C
188 32 15 130 0.25 104 PCT 8
P2 BW1 0.49 TEC TEH 0.61 CBAY2 5
H 113 32 15 166 0.26 154 PCT 10 P2 08C 0.75 TEH TEC 0.61 CBAY2 214 C
154 32 15 174 0.58 137 PCT 14 P2 06C 0.78 TEH TEC 0.61 CBAY2 214 C
54 32 15 196 0.28 102 PCT 10 P2 03C 0.81 TEH TEC 0.61 CBAY2 212 C
85
U3R24 PVGS SG32 All Data Page 2 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 16 35 0.35 130 PCT 10 P2 06C 0.87 TEH TEC 0.61 CBAY2 10 C
266 32 16 137 0.3 52 PCT 10 P2 06H 0.81 TEH TEC 0.61 CBAY2 222 C
133 32 16 163 0.47 146 PCT 11 P2 08C 0.5 TEH TEC 0.61 CBAY2 214 C
159 32 16 171 0.59 140 PCT 14 P2 04C 0.82 TEH TEC 0.61 CBAY2 214 C
59 32 17 182 0.21 109 PCT 8
P2 08C
-1.04 TEH TEC 0.61 CBAY2 210 C
261 32 18 69 0.27 110 PCT 11 P2 BW2 0.97 TEH TEC 0.61 CBAY2 18 C
135 32 18 75 0.33 139 PCT 12 P2 BW1 1.01 TEH TEC 0.61 CBAY2 18 C
203 32 19 74 0.51 131 PCT 17 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 18 C
201 32 19 128 0.43 109 PCT 13 P2 BW1
-1.1 TEC TEH 0.61 CBAY2 5
H 117 32 20 153 0.31 73 PCT 10 P2 BW1 0.42 TEH TEC 0.61 CBAY2 216 C
276 32 23 34 0.93 124 PCT 20 P2 08H 0.59 TEH TEC 0.61 CBAY2 10 C
257 32 23 34 1.57 111 WAR 24 0.14 P30 08H 0.55 08H TEH 0.61 NYAX2 59 H
7 32 23 56 0.26 94 PCT 10 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 14 C
197 32 23 132 0.23 68 PCT 10 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 222 C
100 32 23 152 0.34 64 PCT 10 P2 BW1
-0.76 TEH TEC 0.61 CBAY2 220 C
34 32 24 5
0.21 84 PCT 7
P2 03C 0.8 TEH TEC 0.61 CBAY2 4
C 78 32 24 23 0.42 69 PCT 14 P2 VS3
-0.96 TEH TEC 0.61 CBAY2 10 C
107 32 24 33 0.93 135 PCT 22 P2 VS3 0.8 TEH TEC 0.61 CBAY2 12 C
235 32 24 33 1.99 108 WAR 26 0.18 P32 VS3 0.83 VS3 TEH 0.61 NYAX2 58 H
11 32 24 37 0.34 138 PCT 11 P2 BW1 1.07 TEH TEC 0.61 CBAY2 12 C
292 32 24 49 0.26 137 PCT 10 P2 VS3 0.86 TEH TEC 0.61 CBAY2 14 C
100 32 24 57 0.26 117 PCT 10 P2 BW1 0.88 TEH TEC 0.61 CBAY2 14 C
210 32 24 65 0.49 116 PCT 16 P2 VS3 0.91 TEH TEC 0.61 CBAY2 18 C
83 32 24 169 0.4 113 PCT 12 P2 BW2 1
TEH TEC 0.61 CBAY2 216 C
65 32 25 24 0.58 137 PCT 17 P2 VS3
-0.97 TEH TEC 0.61 CBAY2 12 C
107 32 25 126 0.28 99 PCT 9
P2 07H
-1.11 TEC TEH 0.61 CBAY2 7
H 122 32 25 126 0.34 97 PCT 10 P2 07C
-0.99 TEC TEH 0.61 CBAY2 7
H 122 32 25 168 0.35 138 PCT 11 P2 BW1 0.52 TEH TEC 0.61 CBAY2 216 C
103 32 26 27 0.27 138 PCT 10 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 10 C
163 32 28 79 0.35 121 PCT 11 P2 VS3
-0.32 TEC TEH 0.61 CBAY2 1
H 113 32 28 125 0.46 69 PCT 13 P2 BW1 0.68 TEC TEH 0.61 CBAY2 5
H 123 32 28 125 0.37 62 PCT 11 P2 BW2 0.95 TEC TEH 0.61 CBAY2 5
H 123 32 28 135 0.37 98 PCT 11 P2 05C 0.79 TEH TEC 0.61 CBAY2 224 C
170 32 28 155 0.31 61 PCT 12 P2 08C
-0.95 TEH TEC 0.61 CBAY2 214 C
268 32 29 2
0.34 108 PCT 12 P2 02C
-1 TEH TEC 0.61 CBAY2 2
C 61 32 30 79 0.59 94 PCT 16 P2 BW1
-0.75 TEC TEH 0.61 CBAY2 1
H 118 32 30 125 0.51 121 PCT 14 P2 VS3
-0.8 TEC TEH 0.61 CBAY2 5
H 129 32 30 129 0.36 124 PCT 11 P2 VS3
-0.8 TEC TEH 0.61 CBAY2 7
H 130 32 31 80 0.86 103 PCT 20 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 1
H 119 32 31 80 1.68 122 WAR 24 0.17 P17 BW1
-0.85 VS3 TEH 0.61 NYAX2 49 H
28 32 31 80 TBP TEH TEC 0.61 CBAY2 54 C
9 32 31 80 PID P2 BW1
-0.85 TEH TEC 0.61 CBAY2 54 C
9
U3R24 PVGS SG32 All Data Page 3 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 31 126 0.62 133 PCT 13 P2 08H 0.7 TEC TEH 0.61 CBAY2 5
H 133 32 31 126 0.99 99 PCT 22 P2 BW2 0.99 TEC TEH 0.61 CBAY2 5
H 133 32 31 126 PID P2 BW2 0.99 TEH TEC 0.61 CBAY2 54 C
30 32 31 126 1.88 100 WAR 26 0.32 P19 BW2 0.99 VS3 TEC 0.61 NYAX2 254 C
64 32 31 138 0.25 128 PCT 10 P2 VS3
-0.97 TEH TEC 0.61 CBAY2 222 C
146 32 31 146 0.35 139 PCT 11 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 224 C
44 32 31 162 0.25 150 PCT 10 P2 08C 0.76 TEH TEC 0.61 CBAY2 214 C
197 32 31 198 0.17 119 PCT 7
P2 VS3
-0.79 TEH TEC 0.61 CBAY2 210 C
53 32 32 137 0.4 99 PCT 14 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 222 C
125 32 32 145 0.23 94 PCT 10 P2 VS3
-0.96 TEH TEC 0.61 CBAY2 222 C
183 32 32 163 0.37 119 PCT 12 P2 08C 0.73 TEH TEC 0.61 CBAY2 214 C
168 32 32 163 0.47 148 PCT 10 P2 07C 0.61 TEH TEC 0.61 CBAY2 214 C
168 32 32 167 0.48 142 PCT 11 P2 08C 0.75 TEH TEC 0.61 CBAY2 214 C
117 32 33 34 0.72 155 PCT 12 P2 08H 0.77 TEH TEC 0.61 CBAY2 10 C
252 32 33 74 0.33 117 PCT 11 P2 VS3 0.61 TEH TEC 0.61 CBAY2 20 C
214 32 33 80 0.78 152 PCT 12 P2 06H 0.81 TEC TEH 0.61 CBAY2 1
H 121 32 33 124 0.33 140 PCT 11 P2 BW2 0.13 TEC TEH 0.61 CBAY2 5
H 135 32 33 124 0.59 129 PCT 16 P2 BW2 0.85 TEC TEH 0.61 CBAY2 5
H 135 32 33 166 0.51 150 PCT 10 P2 08C 0.72 TEH TEC 0.61 CBAY2 214 C
145 32 34 77 0.29 79 PCT 10 P2 VS3 0.76 TEC TEH 0.61 CBAY2 1
H 88 32 34 79 0.32 125 PCT 11 P2 08H 0.65 TEC TEH 0.61 CBAY2 1
H 105 32 34 81 0.41 129 PCT 11 P2 08C 0.75 TEC TEH 0.61 CBAY2 1
H 122 32 34 123 0.28 114 PCT 9
P2 07H
-1.07 TEC TEH 0.61 CBAY2 5
H 136 32 34 141 0.23 97 PCT 10 P2 VS3
-0.94 TEH TEC 0.61 CBAY2 222 C
152 32 35 60 0.24 106 PCT 10 P2 BW2
-0.91 TEH TEC 0.61 CBAY2 18 C
10 32 35 82 0.48 132 PCT 14 P2 BW1 0.3 TEC TEH 0.61 CBAY2 1
H 123 32 35 82 0.29 140 PCT 10 P2 VS3 0.78 TEC TEH 0.61 CBAY2 1
H 123 32 35 124 1.17 95 PCT 23 P2 BW2 0.85 TEC TEH 0.61 CBAY2 7
H 135 32 35 124 0.41 130 PCT 10 P2 06C
-0.97 TEC TEH 0.61 CBAY2 7
H 135 32 35 124 PID P2 BW2 0.85 TEH TEC 0.61 CBAY2 54 C
29 32 35 124 2.32 117 WAR 28 0.28 P5 BW2 0.89 VS3 TEC 0.61 NYAX2 254 C
63 32 35 166 0.4 139 PCT 10 P2 08C 0.74 TEH TEC 0.61 CBAY2 214 C
144 32 35 176 0.32 117 PCT 10 P2 08C 0.8 TEH TEC 0.61 CBAY2 212 C
331 32 35 198 0.24 133 PCT 9
P2 VS3
-0.7 TEH TEC 0.61 CBAY2 210 C
51 32 36 19 2.42 180 DNT P1 VS3
-1.54 TEH TEC 0.61 CBAY2 4
C 22 32 36 19 NDF P1 VS3
-1.38 VS3 TEH 0.61 NYAX2 49 H
8 32 36 21 4.35 180 DNT P1 VS3
-1.49 TEH TEC 0.61 CBAY2 12 C
70 32 36 21 NDF P32 VS3
-1.37 VS3 TEH 0.61 NYAX2 49 H
7 32 36 81 0.4 83 PCT 12 P2 06H 0.79 TEC TEH 0.61 CBAY2 1
H 103 32 36 83 0.52 116 PCT 15 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 1
H 124 32 36 123 0.58 134 PCT 12 P2 07H 0.77 TEC TEH 0.61 CBAY2 7
H 136 32 37 34 0.92 154 PCT 13 P2 08H 0.7 TEH TEC 0.61 CBAY2 10 C
250
U3R24 PVGS SG32 All Data Page 4 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 37 66 0.42 98 PCT 14 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 20 C
124 32 37 76 0.3 142 PCT 10 P2 BW1
-0.9 TEC TEH 0.61 CBAY2 1
H 19 32 37 80 1.04 110 PCT 22 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 1
H 91 32 37 80 1.88 118 WAR 26 0.17 P16 BW1
-0.88 VS3 TEH 0.61 NYAX2 49 H
27 32 37 80 PID P2 BW1
-0.88 TEH TEC 0.61 CBAY2 54 C
10 32 37 84 0.76 113 PCT 19 P2 BW1 0.14 TEC TEH 0.61 CBAY2 1
H 125 32 37 84 0.59 126 PCT 14 P2 08C 0.83 TEC TEH 0.61 CBAY2 1
H 125 32 37 124 0.6 79 PCT 15 P2 BW2 0.87 TEC TEH 0.61 CBAY2 7
H 143 32 37 126 0.7 126 PCT 18 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 5
H 142 32 37 132 0.37 133 PCT 14 P2 08C 0.68 TEH TEC 0.61 CBAY2 222 C
106 32 37 142 0.23 107 PCT 10 P2 BW2
-0.85 TEH TEC 0.61 CBAY2 222 C
177 32 38 79 0.33 141 PCT 10 P2 VS3 0.83 TEC TEH 0.61 CBAY2 3
H 98 32 38 81 0.32 84 PCT 10 P2 VS3 0.77 TEC TEH 0.61 CBAY2 1
H 92 32 38 119 0.31 89 PCT 10 P2 08C
-0.96 TEC TEH 0.61 CBAY2 5
H 137 32 38 121 0.48 95 PCT 13 P2 BW1 0.69 TEC TEH 0.61 CBAY2 7
H 172 32 38 121 0.44 137 PCT 10 P2 05C
-0.12 TEC TEH 0.61 CBAY2 7
H 172 32 39 80 0.48 130 PCT 14 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 3
H 97 32 39 84 0.48 70 PCT 14 P2 BW1 0.27 TEC TEH 0.61 CBAY2 1
H 100 32 39 120 0.54 138 PCT 14 P2 BW1
-0.95 TEC TEH 0.61 CBAY2 7
H 171 32 39 124 0.48 101 PCT 14 P2 05C
-1.01 TEC TEH 0.61 CBAY2 5
H 144 32 40 61 0.38 75 PCT 14 P2 BW2 1.03 TEH TEC 0.61 CBAY2 18 C
35 32 40 81 0.66 144 PCT 12 P2 08H 0.71 TEC TEH 0.61 CBAY2 3
H 96 32 40 83 0.56 133 PCT 13 P2 08H 0.66 TEC TEH 0.61 CBAY2 1
H 94 32 40 121 0.42 43 PCT 12 P2 BW1 0.9 TEC TEH 0.61 CBAY2 7
H 146 32 40 145 0.36 149 PCT 13 P2 BW1 0.81 TEH TEC 0.61 CBAY2 222 C
179 32 40 145 0.24 85 PCT 10 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 222 C
179 32 41 62 0.46 122 PCT 14 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 20 C
65 32 41 64 0.43 146 PCT 15 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 18 C
61 32 41 74 0.27 117 PCT 10 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 20 C
246 32 41 80 0.41 149 PCT 12 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 1
H 45 32 41 84 0.43 120 PCT 13 P2 VS3 0.69 TEC TEH 0.61 CBAY2 1
H 95 32 41 86 0.89 114 PCT 21 P2 VS3 0.79 TEC TEH 0.61 CBAY2 1
H 98 32 41 86 2.04 113 WAR 27 0.29 P8 VS3 0.53 VS3 TEH 0.61 NYAX2 49 H
29 32 41 86 TBP TEH TEC 0.61 CBAY2 54 C
13 32 41 86 PID P2 VS3 0.79 TEH TEC 0.61 CBAY2 54 C
13 32 41 118 0.59 130 PCT 13 P2 08H 0.77 TEC TEH 0.61 CBAY2 7
H 169 32 41 118 0.5 119 PCT 14 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 7
H 169 32 41 138 0.25 114 PCT 10 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 222 C
49 32 41 190 0.27 138 PCT 10 P2 BW1
-0.91 TEH TEC 0.61 CBAY2 210 C
149 32 41 198 0.24 70 PCT 9
P2 VS3
-0.72 TEH TEC 0.61 CBAY2 210 C
48 32 42 37 0.35 129 PCT 12 P2 BW1 0.84 TEH TEC 0.61 CBAY2 12 C
301 32 42 81 0.32 138 PCT 10 P2 VS3
-0.79 TEC TEH 0.61 CBAY2 3
H 90
U3R24 PVGS SG32 All Data Page 5 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 42 83 0.36 117 PCT 11 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 3
H 94 32 42 139 0.23 113 PCT 10 P2 VS3
-0.82 TEH TEC 0.61 CBAY2 222 C
45 32 42 175 0.73 153 PCT 13 P2 08C 0.84 TEH TEC 0.61 CBAY2 214 C
22 32 42 179 0.38 68 PCT 13 P2 BW2
-0.88 TEH TEC 0.61 CBAY2 210 C
280 32 43 4
2.06 175 DNT P1 TSC 0.8 TEH TEC 0.61 CBAY2 4
C 56 32 43 4
NDF P16 TSC 0.74 01C TEC 0.61 NYAX2 256 C
57 32 43 64 0.3 82 PCT 11 P2 BW1
-0.87 TEH TEC 0.61 CBAY2 18 C
60 32 43 82 0.33 130 PCT 10 P2 VS3 0.74 TEC TEH 0.61 CBAY2 3
H 48 32 43 84 0.86 111 PCT 20 P2 BW2
-0.77 TEC TEH 0.61 CBAY2 3
H 93 32 43 84 PID P2 BW2
-0.77 TEH TEC 0.61 CBAY2 54 C
11 32 43 84 1.98 99 WAR 26 0.41 P15 BW2
-0.77 VS3 TEC 0.61 NYAX2 256 C
9 32 43 86 0.77 132 PCT 19 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 1
H 97 32 43 86 0.35 135 PCT 11 P2 BW2 0.92 TEC TEH 0.61 CBAY2 1
H 97 32 43 88 0.4 126 PCT 12 P2 BW1
-0.88 TEC TEH 0.61 CBAY2 3
H 118 32 43 118 0.58 125 PCT 15 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 7
H 149 32 43 122 0.5 62 PCT 14 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 5
H 171 32 43 128 0.55 66 PCT 14 P2 08H
-0.99 TEC TEH 0.61 CBAY2 5
H 181 32 43 158 0.36 135 PCT 13 P2 05C 0.76 TEH TEC 0.61 CBAY2 214 C
241 32 43 160 0.38 72 PCT 12 P2 BW2 0.93 TEH TEC 0.61 CBAY2 216 C
200 32 43 174 0.73 144 PCT 16 P2 08C 0.87 TEH TEC 0.61 CBAY2 214 C
40 32 43 184 0.28 139 PCT 10 P2 BW1 0.95 TEH TEC 0.61 CBAY2 212 C
226 32 43 194 0.31 119 PCT 11 P2 BW1
-0.91 TEH TEC 0.61 CBAY2 210 C
97 32 44 83 0.68 154 PCT 13 P2 08H 0.66 TEC TEH 0.61 CBAY2 1
H 59 32 44 85 0.47 122 PCT 13 P2 BW1 0.95 TEC TEH 0.61 CBAY2 3
H 92 32 44 91 0.39 101 PCT 12 P2 08H 0.66 TEC TEH 0.61 CBAY2 1
H 127 32 44 117 0.63 111 PCT 16 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 7
H 150 32 44 179 0.26 90 PCT 10 P2 BW2
-0.92 TEH TEC 0.61 CBAY2 210 C
281 32 45 64 0.33 114 PCT 12 P2 BW1 0.97 TEH TEC 0.61 CBAY2 18 C
59 32 45 72 1.06 129 PCT 22 P2 08H 0.73 TEH TEC 0.61 CBAY2 18 C
168 32 45 72 1.81 118 WAR 25 0.39 P29 08H 0.53 08H TEH 0.61 NYAX2 49 H
25 32 45 72 1.41 121 WAR 22 0.34 P24 08H 0.61 08H TEH 0.61 NYAX2 49 H
25 32 45 76 0.45 144 PCT 13 P2 BW2 0.87 TEC TEH 0.61 CBAY2 1
H 23 32 45 80 0.35 115 PCT 11 P2 BW2 0.95 TEC TEH 0.61 CBAY2 1
H 47 32 45 82 0.35 72 PCT 11 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 3
H 49 32 45 114 0.48 127 PCT 13 P2 VS3 0.77 TEC TEH 0.61 CBAY2 7
H 167 32 45 116 0.65 120 PCT 16 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 7
H 151 32 45 122 0.5 128 PCT 13 P2 08H 0.59 TEC TEH 0.61 CBAY2 7
H 182 32 45 122 0.59 50 PCT 15 P2 BW1 0.89 TEC TEH 0.61 CBAY2 7
H 182 32 45 132 0.69 132 PCT 16 P2 08H 0.63 TEC TEH 0.61 CBAY2 7
H 279 32 45 134 2.11 118 WAR 27 0.26 P16 BW1
-0.77 VS3 TEH 0.61 NYAX2 53 H
25 32 45 134 0.72 110 PCT 21 P2 BW1
-0.77 TEH TEC 0.61 CBAY2 222 C
74 32 45 138 0.28 104 PCT 11 P2 VS3
-0.64 TEH TEC 0.61 CBAY2 222 C
51
U3R24 PVGS SG32 All Data Page 6 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 45 142 0.34 127 PCT 13 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 222 C
28 32 45 152 0.2 82 PCT 7
P2 BW1
-0.9 TEH TEC 0.61 CBAY2 220 C
23 32 46 53 NDF P6 08C 35.12 VS3 TEC 0.61 NYAX2 256 C
12 32 46 61 0.27 126 PCT 11 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 18 C
38 32 46 75 0.4 116 PCT 12 P2 VS3 0.89 TEC TEH 0.61 CBAY2 1
H 14 32 46 89 0.6 97 PCT 16 P2 BW2 0.95 TEC TEH 0.61 CBAY2 3
H 113 32 46 91 0.48 61 PCT 14 P2 BW1 0.93 TEC TEH 0.61 CBAY2 3
H 116 32 46 119 0.53 91 PCT 15 P2 BW1 0.81 TEC TEH 0.61 CBAY2 5
H 170 32 46 137 0.33 116 PCT 10 P2 VS3 0.86 TEH TEC 0.61 CBAY2 224 C
113 32 46 163 0.29 122 PCT 11 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 214 C
175 32 46 171 0.24 34 PCT 10 P2 BW1
-0.96 TEH TEC 0.61 CBAY2 214 C
74 32 46 171 0.25 73 PCT 10 P2 BW1 0.91 TEH TEC 0.61 CBAY2 214 C
74 32 47 74 0.3 111 PCT 11 P2 VS3
-0.91 TEH TEC 0.61 CBAY2 20 C
243 32 47 78 0.36 127 PCT 11 P2 BW2 0.95 TEC TEH 0.61 CBAY2 3
H 23 32 47 80 0.44 94 PCT 13 P2 BW2 0.92 TEC TEH 0.61 CBAY2 1
H 48 32 47 82 0.41 148 PCT 12 P2 BW2 0.97 TEC TEH 0.61 CBAY2 3
H 50 32 47 90 0.92 111 PCT 21 P2 BW2 0.85 TEC TEH 0.61 CBAY2 3
H 114 32 47 90 PID P2 BW2 0.85 TEH TEC 0.61 CBAY2 54 C
14 32 47 90 1.77 115 WAR 25 0.17 P2 BW2 0.85 VS3 TEC 0.61 NYAX2 256 C
7 32 47 114 0.61 103 PCT 16 P2 VS3 0.79 TEC TEH 0.61 CBAY2 7
H 153 32 47 114 0.83 116 PCT 19 P2 BW2 0.96 TEC TEH 0.61 CBAY2 7
H 153 32 47 118 0.34 148 PCT 11 P2 BW1
-0.97 TEC TEH 0.61 CBAY2 5
H 169 32 47 118 0.45 128 PCT 13 P2 BW2 0.89 TEC TEH 0.61 CBAY2 5
H 169 32 47 120 0.77 110 PCT 18 P2 BW2 0.86 TEC TEH 0.61 CBAY2 7
H 184 32 47 122 0.86 102 PCT 20 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 7
H 218 32 47 122 0.34 98 PCT 10 P2 BW2 0.91 TEC TEH 0.61 CBAY2 7
H 218 32 47 122 1.5 113 WAR 23 0.21 P16 BW1
-0.92 VS3 TEH 0.61 NYAX2 53 H
27 32 47 122 PID P2 BW1
-0.92 TEH TEC 0.61 CBAY2 54 C
24 32 47 124 0.85 103 PCT 20 P2 BW2 1.02 TEC TEH 0.61 CBAY2 5
H 185 32 47 124 0.8 140 WAR 17 0.35 P5 BW2 0.98 VS3 TEC 0.61 NYAX2 254 C
61 32 47 142 0.38 75 PCT 14 P2 BW1
-0.83 TEH TEC 0.61 CBAY2 222 C
29 32 47 150 0.28 67 PCT 9
P2 BW1 0.87 TEH TEC 0.61 CBAY2 220 C
85 32 47 194 0.18 79 PCT 7
P2 VS3
-0.75 TEH TEC 0.61 CBAY2 210 C
95 32 48 43 0.38 103 PCT 13 P2 VS3
-0.78 TEH TEC 0.61 CBAY2 14 C
56 32 48 67 0.28 97 PCT 10 P2 BW2 0.99 TEH TEC 0.61 CBAY2 20 C
156 32 48 69 0.25 132 PCT 10 P2 VS3 0.96 TEH TEC 0.61 CBAY2 18 C
150 32 48 77 0.37 114 PCT 11 P2 09C
-1.37 TEC TEH 0.61 CBAY2 3
H 14 32 48 83 0.42 131 PCT 13 P2 BW2 0.89 TEC TEH 0.61 CBAY2 1
H 61 32 48 85 0.4 130 PCT 12 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 3
H 64 32 48 85 0.46 105 PCT 13 P2 BW2 0.95 TEC TEH 0.61 CBAY2 3
H 64 32 48 87 0.33 139 PCT 11 P2 VS3 0.81 TEC TEH 0.61 CBAY2 1
H 128 32 48 89 0.28 69 PCT 9
P2 06H 0.78 TEC TEH 0.61 CBAY2 3
H 119
U3R24 PVGS SG32 All Data Page 7 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 48 89 1.23 108 PCT 24 P2 BW2 0.93 TEC TEH 0.61 CBAY2 3
H 119 32 48 89 PID P2 BW2 0.93 TEH TEC 0.61 CBAY2 54 C
12 32 48 89 2.04 93 WAR 27 0.71 P1 BW2 0.93 VS3 TEC 0.61 NYAX2 256 C
8 32 48 91 0.73 85 PCT 18 P2 BW1 0
TEC TEH 0.61 CBAY2 3
H 115 32 48 91 0.55 133 PCT 15 P2 VS3 0.91 TEC TEH 0.61 CBAY2 3
H 115 32 48 91 0.71 103 PCT 18 P2 BW2 0.93 TEC TEH 0.61 CBAY2 3
H 115 32 48 117 0.79 111 PCT 19 P2 BW1 0.87 TEC TEH 0.61 CBAY2 5
H 168 32 48 139 0.36 93 PCT 13 P2 VS3
-0.73 TEH TEC 0.61 CBAY2 222 C
42 32 48 141 0.32 107 PCT 10 P2 BW2 1.02 TEH TEC 0.61 CBAY2 224 C
89 32 48 143 0.41 109 PCT 15 P2 BW2 0.91 TEH TEC 0.61 CBAY2 222 C
21 32 48 149 0.34 136 PCT 12 P2 BW1 0.88 TEH TEC 0.61 CBAY2 218 C
60 32 48 159 0.34 129 PCT 11 P2 05C 0.78 TEH TEC 0.61 CBAY2 214 C
226 32 49 78 0.8 148 PCT 13 P2 09H
-0.98 TEC TEH 0.61 CBAY2 3
H 24 32 49 80 0.3 127 PCT 10 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 1
H 49 32 49 80 0.47 51 PCT 14 P2 BW2
-0.74 TEC TEH 0.61 CBAY2 1
H 49 32 49 82 0.3 80 PCT 10 P2 BW1
-0.77 TEC TEH 0.61 CBAY2 3
H 51 32 49 82 0.34 87 PCT 11 P2 BW2
-0.83 TEC TEH 0.61 CBAY2 3
H 51 32 49 82 0.34 88 PCT 10 P2 BW2 0.97 TEC TEH 0.61 CBAY2 3
H 51 32 49 90 0.39 103 PCT 11 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 7
H 19 32 49 90 0.51 72 PCT 14 P2 BW2
-0.74 TEC TEH 0.61 CBAY2 7
H 19 32 49 106 0.32 50 PCT 10 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 5
H 72 32 49 106 0.67 123 PCT 17 P2 BW2 0.99 TEC TEH 0.61 CBAY2 5
H 72 32 49 112 0.32 127 PCT 10 P2 BW1 0.78 TEC TEH 0.61 CBAY2 7
H 155 32 49 112 0.44 99 PCT 12 P2 BW2
-0.74 TEC TEH 0.61 CBAY2 7
H 155 32 49 114 0.58 108 PCT 16 P2 VS3 0.79 TEC TEH 0.61 CBAY2 5
H 151 32 49 116 0.35 60 PCT 11 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 5
H 167 32 49 120 0.34 29 PCT 10 P2 BW1 0.94 TEC TEH 0.61 CBAY2 7
H 216 32 49 124 0.9 74 PCT 21 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 5
H 222 32 49 124 1.43 110 WAR 23 0.2 P21 BW2
-0.81 VS3 TEC 0.61 NYAX2 254 C
62 32 49 130 0.47 134 PCT 13 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 9
H 5
32 49 136 0.32 48 PCT 10 P2 VS3 0.99 TEH TEC 0.61 CBAY2 224 C
121 32 49 142 0.37 123 PCT 14 P2 VS3
-0.7 TEH TEC 0.61 CBAY2 222 C
30 32 49 158 0.25 151 PCT 10 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 214 C
238 32 49 158 0.25 118 PCT 10 P2 BW2 0.9 TEH TEC 0.61 CBAY2 214 C
238 32 49 162 NDF 87 TSH 0.81 01H TEH 0.61 NYAX2 53 H
17 32 49 166 0.29 76 PCT 11 P2 BW1 1.03 TEH TEC 0.61 CBAY2 214 C
137 32 49 182 0.32 157 PCT 12 P2 09H
-1.96 TEH TEC 0.61 CBAY2 210 C
245 32 49 184 0.28 91 PCT 10 P2 VS3 0.88 TEH TEC 0.61 CBAY2 212 C
223 32 50 67 0.35 145 PCT 12 P2 BW2 1.02 TEH TEC 0.61 CBAY2 20 C
157 32 50 75 1.27 135 PCT 21 P2 08H 0.69 TEC TEH 0.61 CBAY2 1
H 12 32 50 75 1.51 110 WAR 23 0.23 P23 08H 0.68 09H TEH 0.61 NYAX2 49 H
26 32 50 81 0.24 92 PCT 8
P2 08H
-0.38 TEC TEH 0.61 CBAY2 3
H 45
U3R24 PVGS SG32 All Data Page 8 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 50 89 0.6 145 PCT 11 P2 08H 0.66 TEC TEH 0.61 CBAY2 3
H 120 32 50 89 0.54 114 PCT 15 P2 BW2 0.87 TEC TEH 0.61 CBAY2 3
H 120 32 50 93 0.75 100 PCT 18 P2 BW1
-0.75 TEC TEH 0.61 CBAY2 7
H 20 32 50 93 2.22 111 PCT 33 P2 VS3
-0.73 TEC TEH 0.61 CBAY2 7
H 20 32 50 93 1.34 111 WAR 22 P31 BW1
-0.75 VS3 TEH 0.61 NYAX2 51 H
25 32 50 93 3.6 113 WAR 34 0.38 P8 VS3
-0.73 VS3 TEH 0.61 NYAX2 51 H
25 32 50 93 TBP TEH TEC 0.61 CBAY2 54 C
15 32 50 93 PID P2 VS3
-0.73 TEH TEC 0.61 CBAY2 54 C
15 32 50 105 0.74 96 PCT 18 P2 BW1 0.74 TEC TEH 0.61 CBAY2 5
H 71 32 50 107 0.87 86 PCT 20 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 5
H 138 32 50 107 TBP TEH TEC 0.61 CBAY2 54 C
23 32 50 107 PID P2 BW2
-0.81 TEH TEC 0.61 CBAY2 54 C
23 32 50 107 1.76 108 WAR 25 0.46 P17 BW2
-0.81 VS3 TEC 0.61 NYAX2 256 C
6 32 50 117 0.39 40 PCT 11 P2 BW1 0.81 TEC TEH 0.61 CBAY2 7
H 187 32 50 129 0.58 114 PCT 15 P2 VS3
-0.79 TEC TEH 0.61 CBAY2 9
H 6
32 50 133 1.16 111 WAR 21 0.18 P9 09H 1.14 09H TEH 0.61 NYAX2 53 H
26 32 50 133 0.83 113 PCT 19 P2 09H 1.38 TEH TEC 0.61 CBAY2 224 C
134 32 50 133 0.32 73 PCT 10 P2 VS3 0.86 TEH TEC 0.61 CBAY2 224 C
134 32 50 135 0.63 134 PCT 17 P2 09H 1.34 TEH TEC 0.61 CBAY2 222 C
64 32 50 197 0.3 118 PCT 10 P2 BW1 0
TEH TEC 0.61 CBAY2 212 C
56 32 50 199 2.67 182 DNT P1 08C 27.67 TEH TEC 0.61 CBAY2 210 C
40 32 51 38 0.27 37 PCT 10 P2 09H 0.78 TEH TEC 0.61 CBAY2 10 C
298 32 51 48 0.57 28 PCT 15 P2 09H 0.86 TEH TEC 0.61 CBAY2 14 C
73 32 51 66 0.28 140 PCT 10 P2 09H 0.91 TEH TEC 0.61 CBAY2 20 C
117 32 51 74 0.29 106 PCT 10 P2 VS3 0.86 TEH TEC 0.61 CBAY2 20 C
241 32 51 76 0.39 119 PCT 12 P2 VS3 0.78 TEC TEH 0.61 CBAY2 1
H 26 32 51 78 0.66 138 PCT 13 P2 08H 0.69 TEC TEH 0.61 CBAY2 3
H 25 32 51 78 0.36 119 PCT 11 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 3
H 25 32 51 84 0.42 68 PCT 13 P2 BW1 0.94 TEC TEH 0.61 CBAY2 1
H 78 32 51 86 0.49 127 PCT 14 P2 VS3 0.76 TEC TEH 0.61 CBAY2 3
H 83 32 51 88 0.52 92 PCT 15 P2 BW2
-0.78 TEC TEH 0.61 CBAY2 5
H 16 32 51 90 0.41 52 PCT 12 P2 BW2
-0.7 TEC TEH 0.61 CBAY2 7
H 18 32 51 92 0.57 38 PCT 15 P2 BW1 0.92 TEC TEH 0.61 CBAY2 5
H 35 32 51 92 0.78 81 PCT 19 P2 BW2
-0.7 TEC TEH 0.61 CBAY2 5
H 35 32 51 94 0.77 115 PCT 18 P2 BW1
-0.81 TEC TEH 0.61 CBAY2 7
H 38 32 51 96 0.51 113 PCT 14 P2 BW1
-0.78 TEC TEH 0.61 CBAY2 5
H 86 32 51 98 0.54 109 PCT 15 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 5
H 84 32 51 104 1.49 128 PCT 27 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 5
H 70 32 51 104 1.37 118 WAR 22 0.23 P32 BW1
-0.76 VS3 TEH 0.61 NYAX2 51 H
30 32 51 104 1.25 114 WAR 21 0.17 P16 BW1
-0.76 VS3 TEH 0.61 NYAX2 51 H
30 32 51 104 PID P2 BW1
-0.87 TEH TEC 0.61 CBAY2 54 C
20 32 51 106 0.47 101 PCT 14 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 5
H 73
U3R24 PVGS SG32 All Data Page 9 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 51 106 0.37 104 PCT 11 P2 VS3
-0.91 TEC TEH 0.61 CBAY2 5
H 73 32 51 108 1.26 103 PCT 24 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 7
H 163 32 51 108 1.17 89 PCT 24 P2 BW2 0.34 TEC TEH 0.61 CBAY2 7
H 163 32 51 108 1.66 102 WAR 24 0.2 P31 BW1
-0.82 VS3 TEH 0.61 NYAX2 51 H
54 32 51 108 PID P2 BW1
-0.85 TEH TEC 0.61 CBAY2 54 C
22 32 51 108 1.99 119 WAR 26 0.2 P2 BW2 0.87 VS3 TEC 0.61 NYAX2 256 C
5 32 51 120 0.44 61 PCT 13 P2 09H
-0.48 TEC TEH 0.61 CBAY2 5
H 189 32 51 122 1.36 97 PCT 26 P2 BW1 0.91 TEC TEH 0.61 CBAY2 5
H 220 32 51 122 2.57 103 WAR 29 0.23 P31 BW1 0.87 VS3 TEH 0.61 NYAX2 53 H
28 32 51 128 0.69 137 PCT 17 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 9
H 7
32 51 130 0.43 103 PCT 12 P2 09H 0.81 TEC TEH 0.61 CBAY2 9
H 37 32 51 132 0.32 48 PCT 10 P2 BW2 0.93 TEC TEH 0.61 CBAY2 11 H
5 32 51 136 0.39 124 PCT 10 P2 09H
-0.81 TEH TEC 0.61 CBAY2 224 C
122 32 51 140 0.33 84 PCT 10 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 224 C
99 32 51 152 0.52 73 PCT 14 P2 09H 0.83 TEH TEC 0.61 CBAY2 220 C
20 32 51 170 0.32 125 PCT 12 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 214 C
86 32 52 11 0.33 116 PCT 11 P2 VS3
-0.73 TEH TEC 0.61 CBAY2 6
C 43 32 52 87 0.55 118 PCT 14 P2 08H
-0.26 TEC TEH 0.61 CBAY2 1
H 130 32 52 89 0.34 121 PCT 10 P2 VS3 0.74 TEC TEH 0.61 CBAY2 3
H 121 32 52 91 0.3 143 PCT 10 P2 VS3 0.77 TEC TEH 0.61 CBAY2 5
H 20 32 52 93 0.52 118 PCT 14 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 7
H 21 32 52 95 0.44 127 PCT 13 P2 VS3
-0.79 TEC TEH 0.61 CBAY2 5
H 37 32 52 99 0.44 130 PCT 11 P2 09H 0.78 TEC TEH 0.61 CBAY2 7
H 87 32 52 99 0.35 91 PCT 11 P2 BW2 0.89 TEC TEH 0.61 CBAY2 7
H 87 32 52 101 0.95 104 PCT 21 P2 VS3
-0.83 TEC TEH 0.61 CBAY2 7
H 84 32 52 101 2.07 114 WAR 27 0.34 P8 VS3
-0.81 VS3 TEH 0.61 NYAX2 51 H
29 32 52 101 PID P2 VS3
-0.83 TEH TEC 0.61 CBAY2 54 C
18 32 52 103 0.8 88 PCT 19 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 5
H 69 32 52 103 0.45 125 PCT 13 P2 BW1 0.76 TEC TEH 0.61 CBAY2 5
H 69 32 52 103 0.4 109 PCT 12 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 5
H 69 32 52 107 0.37 101 PCT 11 P2 09C 0.81 TEC TEH 0.61 CBAY2 7
H 162 32 52 163 0.3 150 PCT 11 P2 09H 0.82 TEH TEC 0.61 CBAY2 214 C
178 32 53 18 0.34 126 PCT 10 P2 09C 0.76 TEH TEC 0.61 CBAY2 10 C
47 32 53 38 0.48 71 PCT 15 P2 09H 0.76 TEH TEC 0.61 CBAY2 10 C
297 32 53 42 0.4 57 PCT 13 P2 09H 0.82 TEH TEC 0.61 CBAY2 14 C
18 32 53 52 0.31 129 PCT 10 P2 09H 0.72 TEH TEC 0.61 CBAY2 14 C
127 32 53 68 0.41 118 PCT 14 P2 VS3 0.83 TEH TEC 0.61 CBAY2 18 C
110 32 53 76 0.35 117 PCT 11 P2 VS3 0.71 TEC TEH 0.61 CBAY2 1
H 27 32 53 80 0.34 141 PCT 11 P2 VS3 0.74 TEC TEH 0.61 CBAY2 1
H 51 32 53 88 0.35 110 PCT 11 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 5
H 15 32 53 98 0.94 106 PCT 21 P2 BW1
-0.56 TEC TEH 0.61 CBAY2 7
H 86 32 53 98 1.43 113 WAR 23 0.26 P31 BW1
-0.56 VS3 TEH 0.61 NYAX2 51 H
26
U3R24 PVGS SG32 All Data Page 10 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 53 98 PID P2 BW1
-0.56 TEH TEC 0.61 CBAY2 54 C
16 32 53 106 0.43 101 PCT 12 P2 BW1
-0.45 TEC TEH 0.61 CBAY2 7
H 78 32 53 106 0.69 114 PCT 17 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 7
H 78 32 53 110 0.33 103 PCT 10 P2 06C
-1.04 TEC TEH 0.61 CBAY2 5
H 155 32 53 114 0.35 130 PCT 10 P2 VS3 0.8 TEC TEH 0.61 CBAY2 7
H 190 32 53 124 0.39 148 PCT 11 P2 VS3
-0.82 TEC TEH 0.61 CBAY2 7
H 271 32 53 126 0.54 112 PCT 15 P2 VS3 0.75 TEC TEH 0.61 CBAY2 9
H 9
32 53 134 0.35 99 PCT 13 P2 VS3 0.88 TEH TEC 0.61 CBAY2 222 C
78 32 53 194 0.41 141 PCT 10 P2 09H 0.64 TEH TEC 0.61 CBAY2 210 C
92 32 54 81 0.3 126 PCT 10 P2 BW2 1.59 TEC TEH 0.61 CBAY2 3
H 43 32 54 97 0.5 128 PCT 14 P2 VS3
-0.72 TEC TEH 0.61 CBAY2 7
H 41 32 54 101 0.68 30 PCT 13 P2 09H
-0.99 TEC TEH 0.61 CBAY2 5
H 68 32 54 101 0.74 112 PCT 18 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 5
H 68 32 54 103 0.8 97 PCT 19 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 5
H 76 32 54 105 0.58 126 PCT 15 P2 VS3
-0.81 TEC TEH 0.61 CBAY2 7
H 77 32 54 107 0.41 136 PCT 12 P2 VS3
-0.73 TEC TEH 0.61 CBAY2 7
H 159 32 54 109 0.89 129 PCT 20 P2 VS3
-0.79 TEC TEH 0.61 CBAY2 5
H 156 32 54 109 2.08 115 WAR 27 0.32 P8 VS3
-0.79 VS3 TEH 0.61 NYAX2 51 H
53 32 54 109 PID P2 VS3
-0.79 TEH TEC 0.61 CBAY2 54 C
21 32 54 111 0.53 85 PCT 15 P2 BW2 1.51 TEC TEH 0.61 CBAY2 5
H 162 32 54 117 0.41 123 PCT 12 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 5
H 192 32 55 24 0.27 84 PCT 10 P2 BW1
-1.2 TEH TEC 0.61 CBAY2 12 C
92 32 55 80 0.36 15 PCT 11 P2 BW2 1.6 TEC TEH 0.61 CBAY2 1
H 52 32 55 92 0.43 50 PCT 13 P2 BW2
-1.47 TEC TEH 0.61 CBAY2 5
H 33 32 55 98 0.63 124 PCT 16 P2 BW1
-1.52 TEC TEH 0.61 CBAY2 7
H 81 32 55 100 0.43 141 PCT 13 P2 BW1 1.88 TEC TEH 0.61 CBAY2 5
H 67 32 55 102 0.65 87 PCT 17 P2 BW2
-1.42 TEC TEH 0.61 CBAY2 5
H 77 32 55 130 0.35 136 PCT 10 P2 09C 0.75 TEC TEH 0.61 CBAY2 11 H
36 32 55 142 0.49 133 PCT 14 P2 09H 0.81 TEH TEC 0.61 CBAY2 222 C
33 32 55 198 0.38 35 PCT 10 P2 01C
-0.86 TEH TEC 0.61 CBAY2 210 C
41 32 56 75 0.31 104 PCT 10 P2 VS3
-0.98 TEC TEH 0.61 CBAY2 1
H 9
32 56 107 0.92 115 PCT 21 P2 VS3
-0.93 TEC TEH 0.61 CBAY2 5
H 158 32 56 107 2.02 120 WAR 27 0.23 P8 VS3
-0.93 VS3 TEH 0.61 NYAX2 51 H
56 32 56 107 PID P2 VS3
-0.93 TEH TEC 0.61 CBAY2 54 C
19 32 56 111 0.81 109 PCT 19 P2 VS3
-0.92 TEC TEH 0.61 CBAY2 7
H 193 32 56 139 0.39 94 PCT 14 P2 BW2
-1.82 TEH TEC 0.61 CBAY2 222 C
38 32 56 159 0.26 148 PCT 10 P2 VS3
-0.85 TEH TEC 0.61 CBAY2 214 C
230 32 56 175 1.67 114 WAR 24 0.43 P15 BW1
-1.79 VS3 TEH 0.61 NYAX2 53 H
6 32 56 175 0.67 102 PCT 20 P2 BW1
-1.79 TEH TEC 0.61 CBAY2 214 C
29 32 56 181 0.34 148 PCT 11 P2 BW1
-1.76 TEH TEC 0.61 CBAY2 212 C
264 32 56 191 0.4 134 PCT 14 P2 BW1
-1.74 TEH TEC 0.61 CBAY2 210 C
137 32 57 38 0.46 121 PCT 13 P2 09H 0.76 TEH TEC 0.61 CBAY2 10 C
295
U3R24 PVGS SG32 All Data Page 11 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 57 48 0.4 140 PCT 14 P2 BW1
-1.85 TEH TEC 0.61 CBAY2 14 C
70 32 57 76 0.82 91 PCT 20 P2 09H 0.69 TEC TEH 0.61 CBAY2 1
H 29 32 57 76 1.56 110 WAR 23 0.2 P11 09H 0.64 09H TEH 0.61 NYAX2 49 H
30 32 57 80 0.32 24 PCT 10 P2 BW2 1.98 TEC TEH 0.61 CBAY2 1
H 53 32 57 108 0.51 126 PCT 14 P2 VS3 0.69 TEC TEH 0.61 CBAY2 5
H 159 32 57 108 0.51 109 PCT 14 P2 BW2
-1.91 TEC TEH 0.61 CBAY2 5
H 159 32 57 110 0.32 132 PCT 10 P2 VS3 0.79 TEC TEH 0.61 CBAY2 7
H 194 32 57 114 0.53 144 PCT 15 P2 BW1
-1.91 TEC TEH 0.61 CBAY2 5
H 195 32 57 122 0.45 127 PCT 13 P2 VS3 0.71 TEC TEH 0.61 CBAY2 9
H 13 32 57 124 0.64 117 PCT 17 P2 VS3 0.74 TEC TEH 0.61 CBAY2 9
H 31 32 57 150 0.36 100 PCT 11 P2 VS3 0.91 TEH TEC 0.61 CBAY2 220 C
90 32 57 170 0.37 127 PCT 11 P2 09H 0.61 TEH TEC 0.61 CBAY2 214 C
83 32 57 178 0.21 113 PCT 8
P2 09H 0.8 TEH TEC 0.61 CBAY2 210 C
291 32 57 182 0.27 75 PCT 10 P2 BW2 2.5 TEH TEC 0.61 CBAY2 210 C
241 32 58 7
0.21 142 PCT 8
P2 BW1 1.21 TEH TEC 0.61 CBAY2 2
C 117 32 58 71 0.28 119 PCT 10 P2 BW2 0.89 TEH TEC 0.61 CBAY2 20 C
228 32 58 83 0.29 137 PCT 10 P2 BW1
-1.81 TEC TEH 0.61 CBAY2 1
H 66 32 58 99 0.44 52 PCT 13 P2 BW1
-0.71 TEC TEH 0.61 CBAY2 5
H 80 32 58 105 1.19 123 PCT 24 P2 BW1 2.55 TEC TEH 0.61 CBAY2 5
H 56 32 58 105 2.16 106 WAR 27 0.56 P16 BW1 2.55 VS3 TEH 0.61 NYAX2 51 H
31 32 58 105 PID P2 BW1 2.55 TEH TEC 0.61 CBAY2 54 C
17 32 58 117 0.48 136 PCT 13 P2 BW1 0.85 TEC TEH 0.61 CBAY2 7
H 243 32 58 117 0.48 113 PCT 13 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 7
H 243 32 58 121 0.62 126 PCT 16 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 9
H 14 32 58 127 0.56 120 PCT 15 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 11 H
33 32 58 133 0.33 50 PCT 11 P2 VS3
-0.96 TEH TEC 0.61 CBAY2 224 C
130 32 58 135 0.38 108 PCT 14 P2 VS3
-0.88 TEH TEC 0.61 CBAY2 222 C
60 32 58 137 0.34 68 PCT 11 P2 VS3
-0.94 TEH TEC 0.61 CBAY2 224 C
107 32 58 145 0.33 96 PCT 11 P2 VS3 0.99 TEH TEC 0.61 CBAY2 224 C
60 32 59 26 0.27 50 PCT 10 P2 BW2 0.85 TEH TEC 0.61 CBAY2 10 C
131 32 59 30 0.41 139 PCT 10 P2 09H 0.7 TEH TEC 0.61 CBAY2 10 C
184 32 59 34 0.3 112 PCT 11 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 10 C
239 32 59 38 0.51 131 PCT 13 P2 09H 0.84 TEH TEC 0.61 CBAY2 10 C
294 32 59 40 0.31 152 PCT 10 P2 BW2 0.89 TEH TEC 0.61 CBAY2 12 C
318 32 59 48 0.34 106 PCT 12 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 14 C
69 32 59 80 0.32 73 PCT 11 P2 VS3 0.75 TEC TEH 0.61 CBAY2 1
H 54 32 59 92 0.33 52 PCT 10 P2 BW2
-0.78 TEC TEH 0.61 CBAY2 5
H 31 32 59 106 0.41 81 PCT 12 P2 BW1
-0.82 TEC TEH 0.61 CBAY2 7
H 59 32 59 112 0.59 47 PCT 16 P2 BW1 0.97 TEC TEH 0.61 CBAY2 5
H 197 32 59 120 0.38 132 PCT 11 P2 VS3 0.7 TEC TEH 0.61 CBAY2 9
H 15 32 59 124 0.53 130 PCT 15 P2 VS3 0.7 TEC TEH 0.61 CBAY2 11 H
13 32 59 134 0.46 139 PCT 12 P2 09C 0.7 TEH TEC 0.61 CBAY2 222 C
81
U3R24 PVGS SG32 All Data Page 12 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 59 140 0.39 138 PCT 12 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 224 C
103 32 59 146 0.44 105 PCT 13 P2 VS3 0.92 TEH TEC 0.61 CBAY2 224 C
58 32 59 150 0.36 64 PCT 11 P2 VS3 0.99 TEH TEC 0.61 CBAY2 220 C
91 32 59 154 0.26 134 PCT 10 P2 BW1
-0.89 TEH TEC 0.61 CBAY2 218 C
15 32 59 172 0.41 80 PCT 12 P2 BW2 0.94 TEH TEC 0.61 CBAY2 216 C
35 32 60 35 0.29 107 PCT 10 P2 BW1
-1.21 TEH TEC 0.61 CBAY2 10 C
288 32 60 75 0.37 114 PCT 12 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 1
H 7
32 60 87 0.36 126 PCT 11 P2 VS2 0.88 TEC TEH 0.61 CBAY2 5
H 5
32 60 105 0.48 107 PCT 13 P2 VS2 0.9 TEC TEH 0.61 CBAY2 7
H 58 32 60 113 0.41 124 PCT 12 P2 VS2
-0.84 TEC TEH 0.61 CBAY2 5
H 211 32 60 115 0.41 112 PCT 12 P2 BW1
-0.6 TEC TEH 0.61 CBAY2 7
H 245 32 60 115 0.5 141 PCT 14 P2 VS2 0.85 TEC TEH 0.61 CBAY2 7
H 245 32 60 117 0.28 97 PCT 9
P2 VS4
-0.97 TEC TEH 0.61 CBAY2 7
H 264 32 60 135 0.27 121 PCT 11 P2 BW1
-0.71 TEH TEC 0.61 CBAY2 222 C
59 32 60 139 0.39 97 PCT 14 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 222 C
36 32 60 175 0.28 108 PCT 11 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 214 C
31 32 61 84 0.33 45 PCT 11 P2 VS3 0.62 TEC TEH 0.61 CBAY2 1
H 73 32 61 86 0.32 128 PCT 10 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 3
H 78 32 61 88 0.38 61 PCT 12 P2 BW2 0.92 TEC TEH 0.61 CBAY2 5
H 11 32 61 106 0.33 140 PCT 10 P2 VS3 0.73 TEC TEH 0.61 CBAY2 7
H 60 32 61 112 0.34 27 PCT 11 P2 BW1 0.89 TEC TEH 0.61 CBAY2 5
H 210 32 61 118 0.97 112 PCT 21 P2 VS3 0.78 TEC TEH 0.61 CBAY2 9
H 17 32 61 118 1.9 106 WAR 26 0.32 P8 VS3 0.78 VS3 TEH 0.61 NYAX2 53 H
29 32 61 176 0.28 118 PCT 10 P2 BW1 0.42 TEH TEC 0.61 CBAY2 212 C
318 32 62 15 0.59 150 PCT 10 P2 09H
-0.13 TEH TEC 0.61 CBAY2 8
C 11 32 62 67 0.34 120 PCT 12 P2 BW2 1.02 TEH TEC 0.61 CBAY2 20 C
163 32 62 99 1.27 108 PCT 25 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 5
H 47 32 62 99 2.22 113 WAR 27 0.42 P8 VS3
-0.94 VS3 TEH 0.61 NYAX2 51 H
27 32 62 109 0.41 94 PCT 12 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 5
H 200 32 62 125 0.54 100 PCT 15 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 11 H
146 32 62 129 0.45 129 PCT 13 P2 VS3
-0.83 TEC TEH 0.61 CBAY2 11 H
92 32 62 133 0.38 115 PCT 12 P2 VS3 0.9 TEH TEC 0.61 CBAY2 224 C
128 32 62 137 0.42 73 PCT 13 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 224 C
105 32 62 141 0.36 70 PCT 11 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 224 C
82 32 62 191 0.23 68 PCT 8
P2 VS3
-0.68 TEH TEC 0.61 CBAY2 228 C
276 32 63 8
0.24 111 PCT 8
P2 BW1
-0.74 TEH TEC 0.61 CBAY2 4
C 92 32 63 10 0.27 94 PCT 10 P2 VS3
-1.39 TEH TEC 0.61 CBAY2 2
C 119 32 63 38 0.26 115 PCT 10 P2 BW1
-0.87 TEH TEC 0.61 CBAY2 10 C
292 32 63 46 0.43 82 PCT 14 P2 BW1
-0.77 TEH TEC 0.61 CBAY2 16 C
71 32 63 84 0.36 69 PCT 11 P2 VS4 0.73 TEC TEH 0.61 CBAY2 1
H 72 32 63 98 0.46 147 PCT 13 P2 BW2
-0.3 TEC TEH 0.61 CBAY2 5
H 46 32 63 112 0.35 130 PCT 10 P2 BW2 0.54 TEC TEH 0.61 CBAY2 7
H 248
U3R24 PVGS SG32 All Data Page 13 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 63 120 0.56 112 PCT 15 P2 VS3 0.83 TEC TEH 0.61 CBAY2 11 H
17 32 63 126 0.31 133 PCT 10 P2 VS3 0.93 TEC TEH 0.61 CBAY2 11 H
96 32 63 132 0.37 120 PCT 13 P2 VS3 0.49 TEH TEC 0.61 CBAY2 226 C
109 32 64 55 0.36 80 PCT 12 P2 VS3 1.02 TEH TEC 0.61 CBAY2 16 C
238 32 64 101 0.84 100 PCT 19 P2 BW1
-0.75 TEC TEH 0.61 CBAY2 7
H 54 32 64 105 0.4 107 PCT 12 P2 BW1
-0.8 TEC TEH 0.61 CBAY2 7
H 201 32 64 109 0.32 137 PCT 10 P2 VS3 0.83 TEC TEH 0.61 CBAY2 5
H 207 32 64 111 0.35 117 PCT 11 P2 VS3 0.78 TEC TEH 0.61 CBAY2 7
H 249 32 64 133 0.43 138 PCT 13 P2 VS3 0.69 TEH TEC 0.61 CBAY2 228 C
133 32 65 36 0.4 143 PCT 13 P2 BW2
-0.84 TEH TEC 0.61 CBAY2 12 C
258 32 65 66 0.35 95 PCT 12 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 20 C
110 32 65 84 0.78 135 PCT 16 P2 09H 0.92 TEC TEH 0.61 CBAY2 1
H 71 32 65 88 0.68 138 PCT 13 P2 09H 0.76 TEC TEH 0.61 CBAY2 5
H 9
32 65 102 0.57 50 PCT 15 P2 VS4 0.83 TEC TEH 0.61 CBAY2 7
H 64 32 65 106 0.3 90 PCT 10 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 5
H 203 32 65 110 0.48 87 PCT 13 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 7
H 250 32 65 132 0.52 123 PCT 17 P2 09H 0.83 TEH TEC 0.61 CBAY2 226 C
110 32 65 166 0.31 55 PCT 12 P2 BW1 0.93 TEH TEC 0.61 CBAY2 234 C
49 32 65 176 0.41 92 PCT 13 P2 BW1
-0.02 TEH TEC 0.61 CBAY2 232 C
36 32 65 184 0.48 21 PCT 10 P2 09H
-0.7 TEH TEC 0.61 CBAY2 232 C
14 32 66 103 1.21 123 PCT 24 P2 BW1
-0.83 TEC TEH 0.61 CBAY2 7
H 199 32 66 103 1.94 106 WAR 26 0.2 P31 BW1
-0.83 VS3 TEH 0.61 NYAX2 51 H
28 32 66 115 0.39 153 PCT 12 P2 BW1
-0.84 TEC TEH 0.61 CBAY2 9
H 22 32 66 121 0.76 96 PCT 18 P2 09H
-0.17 TEC TEH 0.61 CBAY2 11 H
194 32 66 123 0.34 132 PCT 11 P2 VS3 0.75 TEC TEH 0.61 CBAY2 9
H 136 32 66 131 0.42 131 PCT 15 P2 09H 0.79 TEH TEC 0.61 CBAY2 226 C
139 32 66 159 NDF P15 TSC
-1.23 01C TEC 0.61 NYAX2 258 C
27 32 66 161 0.39 43 PCT 12 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 228 C
232 32 66 167 0.38 78 PCT 14 P2 BW2 0.89 TEH TEC 0.61 CBAY2 234 C
50 32 66 177 NDF 183 09H 6.27 11.99 VS3 TEH 0.61 NYAX2 53 H
5 32 66 177 1.38 283 PRX P8 09H 6.26 12.05 TEH TEC 0.61 CBAY2 232 C
37 32 66 187 0.5 82 PCT 15 P2 VS3
-0.73 TEH TEC 0.61 CBAY2 232 C
6 32 66 195 0.32 118 PCT 11 P2 01C 0.75 TEH TEC 0.61 CBAY2 226 C
288 32 67 74 0.31 104 PCT 11 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 20 C
233 32 67 98 0.58 80 PCT 15 P2 VS2
-0.89 TEC TEH 0.61 CBAY2 7
H 51 32 67 114 0.86 107 PCT 19 P2 09H 0.8 TEC TEH 0.61 CBAY2 11 H
238 32 67 118 0.72 147 PCT 12 P2 09H 0.78 TEC TEH 0.61 CBAY2 11 H
24 32 67 120 0.51 139 PCT 10 P2 09H
-0.2 TEC TEH 0.61 CBAY2 9
H 138 32 67 132 0.24 151 PCT 10 P2 BW1 0.84 TEH TEC 0.61 CBAY2 226 C
111 32 67 138 0.5 71 PCT 14 P2 09H 0.78 TEH TEC 0.61 CBAY2 228 C
71 32 67 144 0.26 82 PCT 11 P2 BW1 0.08 TEH TEC 0.61 CBAY2 222 C
198 32 67 144 0.25 95 PCT 10 P2 VS3
-0.82 TEH TEC 0.61 CBAY2 222 C
198
U3R24 PVGS SG32 All Data Page 14 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 67 154 0.38 128 PCT 12 P2 BW1 0.37 TEH TEC 0.61 CBAY2 228 C
195 32 67 164 0.46 66 PCT 14 P2 BW2 0.43 TEH TEC 0.61 CBAY2 236 C
57 32 67 166 0.17 100 PCT 7
P2 BW1 0.86 TEH TEC 0.61 CBAY2 234 C
94 32 67 166 0.25 37 PCT 10 P2 BW2 0.89 TEH TEC 0.61 CBAY2 234 C
94 32 67 168 0.29 141 PCT 11 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 234 C
51 32 67 176 0.35 120 PCT 13 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 234 C
13 32 67 180 0.32 52 PCT 11 P2 VS3 0.92 TEH TEC 0.61 CBAY2 232 C
29 32 68 53 0.42 131 PCT 11 P2 09H 0.75 TEH TEC 0.61 CBAY2 26 C
124 32 68 89 0.25 106 PCT 8
P2 09H 0.69 TEC TEH 0.61 CBAY2 7
H 8
32 68 101 0.59 104 PCT 16 P2 BW1
-0.73 TEC TEH 0.61 CBAY2 15 H
91 32 68 145 0.49 135 PCT 14 P2 09H 0.55 TEH TEC 0.61 CBAY2 228 C
33 32 68 169 4.47 183 DNT P1 VS4 0.61 TEH TEC 0.61 CBAY2 234 C
52 32 68 169 NDF P1 VS4 0.6 VS3 TEC 0.61 NYAX2 258 C
30 32 69 18 0.49 113 PCT 15 P2 VS3
-1.04 TEH TEC 0.61 CBAY2 26 C
18 32 69 90 0.54 88 PCT 15 P2 VS3
-1.04 TEC TEH 0.61 CBAY2 15 H
178 32 69 98 0.69 83 PCT 17 P2 BW1 0.9 TEC TEH 0.61 CBAY2 7
H 68 32 69 98 0.85 99 PCT 19 P2 VS4 0.97 TEC TEH 0.61 CBAY2 7
H 68 32 69 98 1.5 110 WAR 23 0.2 P21 VS4 0.85 VS3 TEC 0.61 NYAX2 254 C
50 32 69 124 1.56 116 PCT 27 P2 VS3
-0.65 TEC TEH 0.61 CBAY2 9
H 93 32 69 124 1.98 96 WAR 26 0.2 P24 VS3
-0.69 VS3 TEH 0.61 NYAX2 53 H
38 32 69 126 0.65 126 PCT 17 P2 VS3
-0.69 TEC TEH 0.61 CBAY2 11 H
99 32 69 134 0.52 77 PCT 15 P2 VS3
-0.94 TEH TEC 0.61 CBAY2 228 C
106 32 69 176 0.3 96 PCT 11 P2 BW1 0.83 TEH TEC 0.61 CBAY2 234 C
41 32 70 87 0.62 144 PCT 16 P2 VS2
-0.57 TEC TEH 0.61 CBAY2 13 H
215 32 70 103 0.56 107 PCT 15 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 13 H
48 32 70 111 0.32 112 PCT 10 P2 BW1
-0.9 TEC TEH 0.61 CBAY2 9
H 266 32 70 125 0.42 135 PCT 12 P2 VS3 0.7 TEC TEH 0.61 CBAY2 11 H
142 32 70 129 0.14 146 PCT 5
P2 VS3 0.62 TEC TEH 0.61 CBAY2 11 H
88 32 70 137 0.37 132 PCT 12 P2 09H 0.8 TEH TEC 0.61 CBAY2 228 C
98 32 70 167 0.35 91 PCT 11 P2 BW2
-0.81 TEH TEC 0.61 CBAY2 236 C
59 32 70 175 0.58 115 PCT 16 P2 VS2 0.56 TEH TEC 0.61 CBAY2 236 C
17 32 70 185 0.28 101 PCT 11 P2 VS2
-0.3 TEH TEC 0.61 CBAY2 230 C
33 32 71 10 0.37 128 PCT 10 P2 04C
-0.18 TEH TEC 0.61 CBAY2 28 C
11 32 71 14 0.43 106 PCT 13 P2 VS3
-0.91 TEH TEC 0.61 CBAY2 28 C
21 32 71 16 0.37 129 PCT 12 P2 VS2
-0.93 TEH TEC 0.61 CBAY2 26 C
16 32 71 38 0.3 133 PCT 10 P2 VS3 1.09 TEH TEC 0.61 CBAY2 28 C
212 32 71 52 0.32 138 PCT 11 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 26 C
130 32 71 58 0.28 72 PCT 10 P2 BW1
-0.85 TEH TEC 0.61 CBAY2 30 C
30 32 71 58 0.35 71 PCT 12 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 30 C
30 32 71 80 1.92 125 PCT 30 P2 VS2
-0.79 TEC TEH 0.61 CBAY2 13 H
261 32 71 80 3.18 302 WAR 32 0.4 P24 VS2
-0.72 VS3 TEH 0.61 NYAX2 49 H
38 32 71 80 PID P2 VS2
-0.79 TEH TEC 0.61 CBAY2 54 C
6
U3R24 PVGS SG32 All Data Page 15 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 71 98 0.39 139 PCT 12 P2 VS2
-0.88 TEC TEH 0.61 CBAY2 15 H
92 32 71 106 0.38 139 PCT 12 P2 VS2
-0.92 TEC TEH 0.61 CBAY2 15 H
7 32 71 122 0.58 115 PCT 16 P2 VS3
-1.19 TEC TEH 0.61 CBAY2 11 H
150 32 71 128 0.55 116 PCT 15 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 9
H 44 32 71 134 0.33 142 PCT 11 P2 BW1
-0.75 TEH TEC 0.61 CBAY2 228 C
107 32 71 140 0.21 98 PCT 9
P2 VS3
-0.74 TEH TEC 0.61 CBAY2 226 C
43 32 71 144 0.24 93 PCT 10 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 222 C
200 32 71 146 0.38 104 PCT 12 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 224 C
265 32 71 150 0.3 58 PCT 10 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 228 C
162 32 71 156 0.29 130 PCT 11 P2 VS2 0.61 TEH TEC 0.61 CBAY2 226 C
239 32 71 164 0.31 60 PCT 12 P2 BW2 0.52 TEH TEC 0.61 CBAY2 234 C
96 32 71 186 0.25 75 PCT 10 P2 VS2 0.51 TEH TEC 0.61 CBAY2 230 C
34 32 71 186 0.16 25 PCT 7
P2 VS4
-0.72 TEH TEC 0.61 CBAY2 230 C
34 32 71 188 0.29 145 PCT 11 P2 VS2 0.71 TEH TEC 0.61 CBAY2 230 C
14 32 71 194 0.24 96 PCT 10 P2 VS3
-0.76 TEH TEC 0.61 CBAY2 226 C
290 32 72 13 2.09 179 DNT P1 08H 6.58 TEH TEC 0.61 CBAY2 28 C
22 32 72 25 0.13 99 PCT 5
P2 07C 0.38 TEH TEC 0.61 CBAY2 28 C
79 32 72 37 0.43 117 PCT 13 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 28 C
211 32 72 43 0.28 83 PCT 10 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 26 C
65 32 72 51 0.35 113 PCT 12 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 26 C
131 32 72 79 0.69 130 PCT 15 P2 09H 0.74 TEC TEH 0.61 CBAY2 13 H
300 32 72 101 0.46 147 PCT 11 P2 09H 0.78 TEC TEH 0.61 CBAY2 15 H
89 32 72 109 0.3 142 PCT 10 P2 VS3 1.01 TEC TEH 0.61 CBAY2 11 H
326 32 72 149 0.52 122 PCT 15 P2 09H 0.83 TEH TEC 0.61 CBAY2 228 C
140 32 72 165 0.51 133 PCT 16 P2 BW2
-0.88 TEH TEC 0.61 CBAY2 234 C
97 32 72 167 0.35 103 PCT 11 P2 VS2
-0.9 TEH TEC 0.61 CBAY2 236 C
100 32 72 171 0.27 117 PCT 11 P2 VS2 0.73 TEH TEC 0.61 CBAY2 234 C
89 32 72 175 0.44 120 PCT 13 P2 VS2 0.69 TEH TEC 0.61 CBAY2 236 C
47 32 72 179 0.24 148 PCT 10 P2 VS3 0.98 TEH TEC 0.61 CBAY2 234 C
38 32 72 181 0.29 75 PCT 11 P2 VS2 0.81 TEH TEC 0.61 CBAY2 234 C
18 32 72 181 0.24 126 PCT 10 P2 VS3 1.02 TEH TEC 0.61 CBAY2 234 C
18 32 73 18 0.37 109 PCT 11 P2 VS3
-1.07 TEH TEC 0.61 CBAY2 28 C
29 32 73 42 0.45 138 PCT 11 P2 09H 0.76 TEH TEC 0.61 CBAY2 26 C
66 32 73 56 0.39 123 PCT 11 P2 09C
-0.31 TEH TEC 0.61 CBAY2 30 C
28 32 73 96 0.33 109 PCT 10 P2 09H
-0.22 TEC TEH 0.61 CBAY2 13 H
93 32 73 108 0.42 53 PCT 12 P2 BW1 0.96 TEC TEH 0.61 CBAY2 9
H 270 32 73 158 0.34 29 PCT 11 P2 BW2
-0.93 TEH TEC 0.61 CBAY2 228 C
224 32 73 160 0.29 88 PCT 11 P2 BW2
-0.83 TEH TEC 0.61 CBAY2 226 C
272 32 73 168 0.46 41 PCT 14 P2 BW2
-0.84 TEH TEC 0.61 CBAY2 236 C
99 32 73 182 0.31 112 PCT 12 P2 VS3 0.36 TEH TEC 0.61 CBAY2 234 C
19 32 73 186 0.29 72 PCT 10 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 232 C
23 32 73 188 0.25 108 PCT 10 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 230 C
36
U3R24 PVGS SG32 All Data Page 16 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 73 190 0.47 90 PCT 14 P2 BW1 0.85 TEH TEC 0.61 CBAY2 228 C
291 32 73 190 0.43 35 PCT 13 P2 VS3
-0.86 TEH TEC 0.61 CBAY2 228 C
291 32 74 13 0.3 129 PCT 10 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 26 C
13 32 74 15 0.44 139 PCT 13 P2 VS2 0.71 TEH TEC 0.61 CBAY2 28 C
46 32 74 17 0.35 142 PCT 11 P2 VS2 0.64 TEH TEC 0.61 CBAY2 28 C
28 32 74 17 0.22 83 PCT 8
P2 VS4
-0.89 TEH TEC 0.61 CBAY2 28 C
28 32 74 37 0.35 120 PCT 11 P2 VS2 0.84 TEH TEC 0.61 CBAY2 28 C
225 32 74 43 0.29 98 PCT 9
P2 VS2
-0.76 TEH TEC 0.61 CBAY2 28 C
265 32 74 47 0.48 121 PCT 14 P2 09C
-0.33 TEH TEC 0.61 CBAY2 26 C
118 32 74 95 0.45 120 PCT 13 P2 VS4 0.68 TEC TEH 0.61 CBAY2 13 H
130 32 74 99 0.57 143 PCT 12 P2 09H 0.69 TEC TEH 0.61 CBAY2 13 H
88 32 74 99 0.6 93 PCT 16 P2 VS2
-0.85 TEC TEH 0.61 CBAY2 13 H
88 32 74 103 0.73 150 PCT 12 P2 09C 0.78 TEC TEH 0.61 CBAY2 13 H
46 32 74 105 0.29 134 PCT 10 P2 VS4 0.69 TEC TEH 0.61 CBAY2 15 H
47 32 74 109 0.47 126 PCT 14 P2 VS2 0.7 TEC TEH 0.61 CBAY2 11 H
325 32 74 117 0.53 96 PCT 15 P2 VS3 0.9 TEC TEH 0.61 CBAY2 11 H
235 32 74 127 0.35 88 PCT 11 P2 VS3 0.82 TEC TEH 0.61 CBAY2 9
H 82 32 74 155 0.29 107 PCT 11 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 226 C
216 32 74 175 0.3 124 PCT 12 P2 VS2 0.79 TEH TEC 0.61 CBAY2 234 C
58 32 74 181 0.45 105 PCT 15 P2 VS4 0.69 TEH TEC 0.61 CBAY2 234 C
36 32 74 187 0.37 61 PCT 12 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 232 C
22 32 75 12 0.72 113 PCT 19 P2 VS3
-1.15 TEH TEC 0.61 CBAY2 26 C
12 32 75 12 0.5 126 PCT 15 P2 VS3 0.79 TEH TEC 0.61 CBAY2 26 C
12 32 75 12 1.44 116 WAR 23 0.26 P24 VS3
-1.39 VS3 TEH 0.61 NYAX2 49 H
52 32 75 12 1.48 297 WAR 23 0.4 P16 VS3 0.73 VS3 TEH 0.61 NYAX2 49 H
52 32 75 18 0.4 104 PCT 12 P2 VS3
-0.88 TEH TEC 0.61 CBAY2 28 C
44 32 75 58 0.37 133 PCT 10 P2 09C
-0.24 TEH TEC 0.61 CBAY2 36 C
72 32 75 96 0.76 121 PCT 18 P2 VS2 0.68 TEC TEH 0.61 CBAY2 13 H
94 32 75 106 0.6 97 PCT 16 P2 VS2 0.72 TEC TEH 0.61 CBAY2 15 H
9 32 75 108 0.38 110 PCT 12 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 9
H 271 32 75 114 0.53 115 PCT 15 P2 VS3 0.67 TEC TEH 0.61 CBAY2 11 H
242 32 75 118 0.35 122 PCT 11 P2 VS3 0.59 TEC TEH 0.61 CBAY2 11 H
198 32 75 126 0.55 140 PCT 15 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 11 H
102 32 75 156 0.38 82 PCT 14 P2 BW1 0.39 TEH TEC 0.61 CBAY2 226 C
237 32 75 158 0.36 62 PCT 11 P2 BW1 0.91 TEH TEC 0.61 CBAY2 228 C
223 32 75 162 0.31 38 PCT 10 P2 VS3 0.84 TEH TEC 0.61 CBAY2 228 C
254 32 75 166 0.36 101 PCT 11 P2 VS2 0.83 TEH TEC 0.61 CBAY2 236 C
149 32 75 168 0.28 53 PCT 11 P2 BW1 0.85 TEH TEC 0.61 CBAY2 234 C
100 32 75 172 0.39 125 PCT 12 P2 VS2 0.64 TEH TEC 0.61 CBAY2 236 C
64 32 75 172 0.92 110 PCT 22 P2 VS4
-0.8 TEH TEC 0.61 CBAY2 236 C
64 32 75 172 2.04 120 WAR 27 0.41 P27 VS4
-0.49 VS3 TEC 0.61 NYAX2 258 C
31 32 75 174 0.3 67 PCT 12 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 234 C
86
U3R24 PVGS SG32 All Data Page 17 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 75 180 0.45 119 PCT 13 P2 BW1 0.98 TEH TEC 0.61 CBAY2 236 C
22 32 75 182 0.34 121 PCT 12 P2 BW1 0.85 TEH TEC 0.61 CBAY2 234 C
35 32 75 182 0.25 117 PCT 10 P2 VS3 0.71 TEH TEC 0.61 CBAY2 234 C
35 32 75 188 0.27 58 PCT 9
P2 VS2
-0.87 TEH TEC 0.61 CBAY2 232 C
21 32 75 188 0.31 55 PCT 11 P2 VS2 0.86 TEH TEC 0.61 CBAY2 232 C
21 32 76 15 0.4 96 PCT 12 P2 VS4
-0.73 TEH TEC 0.61 CBAY2 28 C
26 32 76 43 0.22 114 PCT 8
P2 VS2
-0.72 TEH TEC 0.61 CBAY2 28 C
282 32 76 99 0.71 115 PCT 18 P2 VS3 0.77 TEC TEH 0.61 CBAY2 13 H
87 32 76 109 0.53 109 PCT 15 P2 VS3 0.75 TEC TEH 0.61 CBAY2 11 H
324 32 76 133 0.36 44 PCT 11 P2 VS2 0.78 TEH TEC 0.61 CBAY2 228 C
127 32 76 161 0.42 65 PCT 13 P2 VS2 0.75 TEH TEC 0.61 CBAY2 228 C
237 32 76 163 0.57 128 PCT 15 P2 09C
-0.78 TEH TEC 0.61 CBAY2 234 C
141 32 76 179 0.41 103 PCT 13 P2 VS2 0.79 TEH TEC 0.61 CBAY2 236 C
43 32 76 181 0.38 91 PCT 12 P2 VS2 0.86 TEH TEC 0.61 CBAY2 236 C
23 32 76 185 0.27 142 PCT 11 P2 VS2 0.66 TEH TEC 0.61 CBAY2 234 C
22 32 76 187 0.32 104 PCT 11 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 232 C
46 32 77 34 0.4 103 PCT 12 P2 BW2
-0.96 TEH TEC 0.61 CBAY2 28 C
228 32 77 50 0.28 151 PCT 10 P2 VS2 0.8 TEH TEC 0.61 CBAY2 36 C
11 32 77 60 0.36 110 PCT 12 P2 09C
-0.31 TEH TEC 0.61 CBAY2 34 C
70 32 77 94 0.31 126 PCT 10 P2 VS2 0.67 TEC TEH 0.61 CBAY2 15 H
138 32 77 104 0.97 281 PRX P8 09H 10.65 17.49 TEC TEH 0.61 CBAY2 13 H
11 32 77 104 0.41 131 PCT 12 P2 BW1
-0.87 TEC TEH 0.61 CBAY2 13 H
11 32 77 104 NDF P18 09H 10.65 17.49 VS3 TEH 0.61 NYAX2 51 H
39 32 77 106 0.43 148 PCT 13 P2 VS2 0.62 TEC TEH 0.61 CBAY2 15 H
10 32 77 120 0.55 126 PCT 15 P2 VS2 0.75 TEC TEH 0.61 CBAY2 9
H 143 32 77 124 0.35 137 PCT 11 P2 VS2 0.62 TEC TEH 0.61 CBAY2 9
H 97 32 77 142 0.37 46 PCT 12 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 228 C
44 32 77 158 0.39 45 PCT 12 P2 VS2 0.77 TEH TEC 0.61 CBAY2 228 C
222 32 77 164 0.48 133 PCT 16 P2 BW2 0.42 TEH TEC 0.61 CBAY2 234 C
140 32 77 166 0.43 133 PCT 13 P2 BW2 0.96 TEH TEC 0.61 CBAY2 236 C
107 32 77 170 0.41 105 PCT 14 P2 BW2
-0.89 TEH TEC 0.61 CBAY2 234 C
102 32 77 180 0.41 145 PCT 12 P2 BW1 0.9 TEH TEC 0.61 CBAY2 236 C
42 32 77 186 2.45 102 WAR 29 0.44 P7 VS3 0.88 VS3 TEH 0.61 NYAX2 53 H
4 32 77 186 0.96 114 PCT 24 P2 VS3 0.7 TEH TEC 0.61 CBAY2 234 C
23 32 77 188 0.38 67 PCT 12 P2 VS3
-0.87 TEH TEC 0.61 CBAY2 228 C
294 32 78 13 0.22 47 PCT 7
P2 BW1 0.71 TEH TEC 0.61 CBAY2 28 C
24 32 78 89 0.28 135 PCT 10 P2 BW1 0.93 TEC TEH 0.61 CBAY2 15 H
217 32 78 97 0.71 108 PCT 18 P2 VS2
-0.76 TEC TEH 0.61 CBAY2 15 H
130 32 78 103 0.82 150 PCT 13 P2 09H 0.86 TEC TEH 0.61 CBAY2 13 H
44 32 78 109 0.31 102 PCT 10 P2 VS2 0.69 TEC TEH 0.61 CBAY2 11 H
323 32 78 147 0.35 124 PCT 13 P2 VS2 0.84 TEH TEC 0.61 CBAY2 226 C
150 32 78 149 0.38 44 PCT 12 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 228 C
143
U3R24 PVGS SG32 All Data Page 18 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 78 155 0.26 88 PCT 11 P2 VS2 0.76 TEH TEC 0.61 CBAY2 226 C
218 32 78 157 0.29 58 PCT 10 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 228 C
206 32 78 167 0.48 122 PCT 14 P2 BW2 0.96 TEH TEC 0.61 CBAY2 236 C
108 32 78 169 0.32 110 PCT 10 P2 VS2 0.82 TEH TEC 0.61 CBAY2 236 C
146 32 78 169 0.42 88 PCT 13 P2 BW2 0.91 TEH TEC 0.61 CBAY2 236 C
146 32 78 177 0.3 95 PCT 11 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 234 C
83 32 78 177 0.29 101 PCT 11 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 234 C
83 32 78 187 0.41 58 PCT 12 P2 VS2
-0.82 TEH TEC 0.61 CBAY2 228 C
295 32 78 189 0.31 89 PCT 12 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 234 C
25 32 79 24 0.35 101 PCT 11 P2 VS4
-0.58 TEH TEC 0.61 CBAY2 28 C
135 32 79 102 1.49 125 PCT 25 P2 09H 0.61 TEC TEH 0.61 CBAY2 15 H
53 32 79 102 1.59 100 WAR 24 0.17 P21 09H 0.9 09H TEH 0.61 NYAX2 51 H
32 32 79 102 1.8 109 WAR 25 0.2 P26 09H 0.92 09H TEH 0.61 NYAX2 51 H
32 32 79 104 2.22 271 PRX P8 09H 12.07 18.59 TEC TEH 0.61 CBAY2 13 H
12 32 79 104 NDF P31 09H 12.07 18.59 VS3 TEH 0.61 NYAX2 51 H
40 32 79 140 0.38 140 PCT 10 P2 09H
-0.17 TEH TEC 0.61 CBAY2 226 C
47 32 79 142 0.32 71 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 228 C
45 32 79 144 0.4 131 PCT 14 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 222 C
204 32 79 146 0.33 47 PCT 11 P2 VS4
-0.59 TEH TEC 0.61 CBAY2 228 C
5 32 79 156 0.29 94 PCT 11 P2 VS2
-1.02 TEH TEC 0.61 CBAY2 226 C
235 32 79 160 0.25 128 PCT 10 P2 VS2 0.84 TEH TEC 0.61 CBAY2 226 C
269 32 79 164 0.34 69 PCT 11 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 236 C
154 32 79 164 0.32 58 PCT 10 P2 VS2 0.82 TEH TEC 0.61 CBAY2 236 C
154 32 79 168 0.77 78 PCT 19 P2 BW2 0.88 TEH TEC 0.61 CBAY2 236 C
109 32 79 180 0.25 102 PCT 10 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 234 C
63 32 79 182 0.8 91 PCT 20 P2 VS4
-0.54 TEH TEC 0.61 CBAY2 236 C
40 32 79 182 1.52 121 WAR 23 0.38 P27 VS4
-0.65 VS3 TEC 0.61 NYAX2 258 C
39 32 80 27 0.28 102 PCT 9
P2 VS2
-0.57 TEH TEC 0.61 CBAY2 28 C
180 32 80 123 0.72 106 PCT 18 P2 VS2
-0.73 TEC TEH 0.61 CBAY2 9
H 129 32 80 125 0.4 149 PCT 12 P2 VS2
-0.72 TEC TEH 0.61 CBAY2 11 H
137 32 80 143 0.33 115 PCT 13 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 226 C
29 32 80 151 0.32 115 PCT 12 P2 VS2
-0.69 TEH TEC 0.61 CBAY2 226 C
185 32 80 153 0.51 75 PCT 15 P2 VS2
-0.59 TEH TEC 0.61 CBAY2 228 C
175 32 80 167 0.23 102 PCT 9
P2 VS2
-0.71 TEH TEC 0.61 CBAY2 234 C
137 32 80 167 0.55 123 PCT 17 P2 BW2 0.9 TEH TEC 0.61 CBAY2 234 C
137 32 80 169 0.4 75 PCT 12 P2 BW2 1.1 TEH TEC 0.61 CBAY2 236 C
110 32 80 177 0.35 75 PCT 11 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 236 C
69 32 80 179 0.27 66 PCT 11 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 234 C
81 32 80 181 0.3 123 PCT 12 P2 VS4 0.67 TEH TEC 0.61 CBAY2 234 C
64 32 80 185 0.76 133 PCT 19 P2 VS4 0.75 TEH TEC 0.61 CBAY2 236 C
27 32 80 187 0.32 85 PCT 12 P2 VS2
-0.96 TEH TEC 0.61 CBAY2 234 C
30 32 80 187 0.43 114 PCT 15 P2 VS3
-0.74 TEH TEC 0.61 CBAY2 234 C
30
U3R24 PVGS SG32 All Data Page 19 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 80 187 0.59 109 PCT 18 P2 VS4 0.63 TEH TEC 0.61 CBAY2 234 C
30 32 81 14 0.58 116 PCT 16 P2 VS4 0.83 TEH TEC 0.61 CBAY2 28 C
67 32 81 18 0.39 108 PCT 12 P2 VS3
-1.23 TEH TEC 0.61 CBAY2 28 C
99 32 81 50 0.34 136 PCT 12 P2 VS2 0.68 TEH TEC 0.61 CBAY2 34 C
11 32 81 52 0.38 117 PCT 12 P2 VS3
-0.9 TEH TEC 0.61 CBAY2 36 C
66 32 81 82 0.33 130 PCT 11 P2 VS3
-1.09 TEC TEH 0.61 CBAY2 15 H
271 32 81 88 0.84 121 PCT 20 P2 VS3
-1.09 TEC TEH 0.61 CBAY2 13 H
181 32 81 88 1.66 296 WAR 24 0.17 P24 VS3
-1.03 VS3 TEH 0.61 NYAX2 49 H
39 32 81 90 0.24 111 PCT 9
P2 VS3
-1.09 TEC TEH 0.61 CBAY2 15 H
184 32 81 96 0.43 70 PCT 13 P2 VS2 0.62 TEC TEH 0.61 CBAY2 13 H
97 32 81 104 1.35 129 PCT 22 P2 09H 0.72 TEC TEH 0.61 CBAY2 13 H
13 32 81 104 1.25 113 WAR 21 0.23 P26 09H 0.7 09H TEH 0.61 NYAX2 51 H
41 32 81 104 1.41 103 WAR 22 0.23 P20 09H 0.72 09H TEH 0.61 NYAX2 51 H
41 32 81 108 1.48 128 PCT 24 P2 09H 0.81 TEC TEH 0.61 CBAY2 9
H 274 32 81 108 1.39 281 PRX P8 09H 13.73 20.6 TEC TEH 0.61 CBAY2 9
H 274 32 81 108 1.31 105 WAR 22 0.29 P26 09H 0.79 VS3 TEH 0.61 NYAX2 51 H
50 32 81 108 1.23 116 WAR 21 0.26 P20 09H 0.85 VS3 TEH 0.61 NYAX2 51 H
50 32 81 108 NDF 163 09H 13.25 20.49 VS3 TEH 0.61 NYAX2 51 H
50 32 81 118 0.29 147 PCT 10 P2 VS2 0.69 TEC TEH 0.61 CBAY2 11 H
201 32 81 120 0.31 143 PCT 10 P2 VS2 0.77 TEC TEH 0.61 CBAY2 9
H 145 32 81 122 0.49 123 PCT 14 P2 VS2 0.69 TEC TEH 0.61 CBAY2 11 H
155 32 81 142 0.34 59 PCT 11 P2 VS2
-0.78 TEH TEC 0.61 CBAY2 228 C
46 32 81 160 0.24 145 PCT 10 P2 VS2 0.89 TEH TEC 0.61 CBAY2 226 C
268 32 81 188 0.97 140 PCT 19 P2 09H 0.75 TEH TEC 0.61 CBAY2 234 C
29 32 81 190 0.22 74 PCT 9
P2 VS4
-0.78 TEH TEC 0.61 CBAY2 234 C
27 32 82 15 0.66 123 PCT 17 P2 VS3 1
TEH TEC 0.61 CBAY2 28 C
69 32 82 25 0.27 83 PCT 9
P2 VS4
-0.7 TEH TEC 0.61 CBAY2 28 C
182 32 82 77 0.48 126 PCT 11 P2 09H 0.75 TEC TEH 0.61 CBAY2 7
H 95 32 82 147 0.26 131 PCT 10 P2 VS2
-0.67 TEH TEC 0.61 CBAY2 226 C
152 32 82 163 0.24 85 PCT 10 P2 VS3 0.94 TEH TEC 0.61 CBAY2 234 C
142 32 83 14 0.45 140 PCT 10 P2 09H 0.6 TEH TEC 0.61 CBAY2 28 C
68 32 83 18 0.29 142 PCT 9
P2 VS2
-0.81 TEH TEC 0.61 CBAY2 28 C
106 32 83 24 0.32 60 PCT 10 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 28 C
183 32 83 66 0.24 120 PCT 8
P2 09H 0.82 TEH TEC 0.61 CBAY2 40 C
70 32 83 98 0.33 117 PCT 11 P2 VS2 0.64 TEC TEH 0.61 CBAY2 15 H
98 32 83 110 0.41 87 PCT 12 P2 VS4 0.26 TEC TEH 0.61 CBAY2 11 H
291 32 83 148 0.32 111 PCT 12 P2 VS2
-0.88 TEH TEC 0.61 CBAY2 226 C
164 32 83 150 0.41 76 PCT 12 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 228 C
156 32 83 178 0.69 90 PCT 18 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 236 C
89 32 83 182 0.26 113 PCT 10 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 234 C
78 32 83 182 0.31 92 PCT 12 P2 VS3
-0.81 TEH TEC 0.61 CBAY2 234 C
78 32 84 25 0.37 121 PCT 11 P2 VS4
-0.64 TEH TEC 0.61 CBAY2 28 C
199
U3R24 PVGS SG32 All Data Page 20 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 84 31 0.66 111 PCT 18 P2 BW2
-0.82 TEH TEC 0.61 CBAY2 26 C
78 32 84 37 0.28 118 PCT 10 P2 VS2 0.75 TEH TEC 0.61 CBAY2 26 C
108 32 84 39 0.32 90 PCT 11 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 26 C
143 32 84 39 0.27 139 PCT 10 P2 VS2 0.8 TEH TEC 0.61 CBAY2 26 C
143 32 84 41 0.33 120 PCT 11 P2 VS2
-0.71 TEH TEC 0.61 CBAY2 32 C
13 32 84 45 0.28 57 PCT 10 P2 VS2 0.75 TEH TEC 0.61 CBAY2 30 C
17 32 84 53 0.39 119 PCT 13 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 34 C
63 32 84 59 0.39 100 PCT 12 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 40 C
15 32 84 71 0.27 127 PCT 10 P2 09H 0.81 TEH TEC 0.61 CBAY2 38 C
111 32 84 95 0.5 130 PCT 14 P2 VS3 0.72 TEC TEH 0.61 CBAY2 13 H
125 32 84 105 0.29 144 PCT 10 P2 VS3 0.79 TEC TEH 0.61 CBAY2 15 H
42 32 84 117 0.38 131 PCT 12 P2 VS2 0.64 TEC TEH 0.61 CBAY2 11 H
230 32 84 143 0.2 123 PCT 9
P2 VS2
-1 TEH TEC 0.61 CBAY2 226 C
27 32 84 147 0.38 111 PCT 14 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 226 C
153 32 84 153 0.34 82 PCT 11 P2 VS2
-0.77 TEH TEC 0.61 CBAY2 228 C
177 32 84 153 0.33 106 PCT 11 P2 VS2 0.82 TEH TEC 0.61 CBAY2 228 C
177 32 84 163 0.43 79 PCT 15 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 234 C
182 32 84 165 0.29 93 PCT 11 P2 VS2 0.63 TEH TEC 0.61 CBAY2 234 C
144 32 84 181 0.43 98 PCT 13 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 236 C
73 32 84 183 0.27 94 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 234 C
77 32 84 183 0.25 135 PCT 10 P2 VS2 0.83 TEH TEC 0.61 CBAY2 234 C
77 32 84 183 0.51 123 PCT 16 P2 VS3 0.58 TEH TEC 0.61 CBAY2 234 C
77 32 84 183 0.32 106 PCT 12 P2 09C
-0.03 TEH TEC 0.61 CBAY2 234 C
77 32 84 185 0.31 95 PCT 12 P2 VS2 0.88 TEH TEC 0.61 CBAY2 234 C
68 32 84 187 0.35 125 PCT 11 P2 VS4 0.92 TEH TEC 0.61 CBAY2 236 C
35 32 85 18 0.31 107 PCT 10 P2 VS2
-0.66 TEH TEC 0.61 CBAY2 28 C
141 32 85 34 0.72 94 PCT 18 P2 BW2 0.52 TEH TEC 0.61 CBAY2 28 C
290 32 85 38 0.3 128 PCT 10 P2 VS2 0.75 TEH TEC 0.61 CBAY2 26 C
144 32 85 46 0.27 111 PCT 10 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 34 C
14 32 85 50 0.36 118 PCT 12 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 36 C
96 32 85 68 0.43 126 PCT 14 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 38 C
31 32 85 86 0.41 107 PCT 13 P2 BW1 0.85 TEC TEH 0.61 CBAY2 15 H
230 32 85 102 0.33 94 PCT 11 P2 VS2
-0.83 TEC TEH 0.61 CBAY2 15 H
56 32 85 108 0.31 93 PCT 10 P2 BW1 0.93 TEC TEH 0.61 CBAY2 9
H 276 32 85 152 0.36 133 PCT 13 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 226 C
198 32 85 160 0.37 136 PCT 14 P2 VS2
-0.81 TEH TEC 0.61 CBAY2 226 C
266 32 85 162 0.41 57 PCT 12 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 228 C
250 32 85 164 0.26 108 PCT 10 P2 09C
-0.28 TEH TEC 0.61 CBAY2 234 C
181 32 85 166 0.29 116 PCT 11 P2 VS2 0.86 TEH TEC 0.61 CBAY2 234 C
145 32 85 168 0.31 83 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 236 C
189 32 85 168 0.36 125 PCT 11 P2 VS2 0.79 TEH TEC 0.61 CBAY2 236 C
189 32 85 170 0.4 21 PCT 12 P2 BW1 0.88 TEH TEC 0.61 CBAY2 236 C
160
U3R24 PVGS SG32 All Data Page 21 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 85 182 0.35 70 PCT 11 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 236 C
74 32 85 182 0.22 138 PCT 8
P2 VS3
-0.99 TEH TEC 0.61 CBAY2 236 C
74 32 85 184 0.58 150 PCT 12 P2 09H 0.63 TEH TEC 0.61 CBAY2 234 C
76 32 85 188 0.32 83 PCT 10 P2 BW2
-0.86 TEH TEC 0.61 CBAY2 236 C
34 32 86 21 0.52 118 PCT 15 P2 VS3 0.75 TEH TEC 0.61 CBAY2 28 C
190 32 86 51 0.26 117 PCT 10 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 34 C
61 32 86 61 0.37 108 PCT 13 P2 VS2 0.93 TEH TEC 0.61 CBAY2 38 C
21 32 86 101 0.46 90 PCT 14 P2 VS2
-0.91 TEC TEH 0.61 CBAY2 15 H
82 32 86 109 0.2 89 PCT 7
P2 VS2 0.82 TEC TEH 0.61 CBAY2 11 H
319 32 86 121 0.24 94 PCT 8
P2 VS3 0.79 TEC TEH 0.61 CBAY2 11 H
184 32 86 143 0.26 72 PCT 10 P2 VS2 0.86 TEH TEC 0.61 CBAY2 226 C
26 32 86 149 0.36 46 PCT 11 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 228 C
147 32 86 159 0.33 93 PCT 12 P2 VS3 0.87 TEH TEC 0.61 CBAY2 226 C
256 32 86 161 0.39 44 PCT 12 P2 VS2
-0.88 TEH TEC 0.61 CBAY2 228 C
242 32 86 179 0.28 113 PCT 11 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 234 C
111 32 86 181 0.52 92 PCT 15 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 236 C
86 32 86 181 0.31 106 PCT 10 P2 VS2 0.79 TEH TEC 0.61 CBAY2 236 C
86 32 86 181 0.33 43 PCT 11 P2 BW2
-0.8 TEH TEC 0.61 CBAY2 236 C
86 32 86 183 0.27 85 PCT 9
P2 VS2
-0.73 TEH TEC 0.61 CBAY2 236 C
75 32 86 185 0.31 123 PCT 12 P2 VS2 0.73 TEH TEC 0.61 CBAY2 234 C
75 32 86 187 0.93 100 PCT 24 P2 VS4 0.82 TEH TEC 0.61 CBAY2 234 C
70 32 86 187 2.71 101 WAR 30 0.76 P20 VS4 1
VS3 TEC 0.61 NYAX2 258 C
40 32 87 20 0.49 121 PCT 14 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 28 C
189 32 87 86 0.54 73 PCT 15 P2 BW1 0.75 TEC TEH 0.61 CBAY2 15 H
231 32 87 100 0.69 143 PCT 13 P2 09H 0.81 TEC TEH 0.61 CBAY2 13 H
58 32 87 104 0.3 119 PCT 10 P2 BW1 0.86 TEC TEH 0.61 CBAY2 13 H
16 32 87 106 0.98 130 PCT 19 P2 09H 0.73 TEC TEH 0.61 CBAY2 15 H
15 32 87 106 1.49 106 WAR 23 0.22 P26 09H 0.68 09H TEH 0.61 NYAX2 51 H
45 32 87 138 0.19 24 PCT 7
P2 VS4 0.87 TEH TEC 0.61 CBAY2 228 C
83 32 87 146 0.28 88 PCT 9
P2 VS2
-0.74 TEH TEC 0.61 CBAY2 228 C
9 32 87 156 0.26 120 PCT 11 P2 VS3
-0.74 TEH TEC 0.61 CBAY2 226 C
231 32 87 160 0.62 122 PCT 19 P2 VS3
-0.86 TEH TEC 0.61 CBAY2 226 C
265 32 87 166 0.25 141 PCT 10 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 234 C
179 32 87 168 0.26 123 PCT 10 P2 VS3
-0.89 TEH TEC 0.61 CBAY2 234 C
147 32 87 170 0.32 50 PCT 10 P2 BW1 0.91 TEH TEC 0.61 CBAY2 236 C
187 32 87 170 0.7 96 PCT 18 P2 VS3
-1.12 TEH TEC 0.61 CBAY2 236 C
187 32 87 174 0.32 120 PCT 12 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 234 C
130 32 87 174 0.33 115 PCT 12 P2 VS3
-1.24 TEH TEC 0.61 CBAY2 234 C
130 32 87 178 0.44 77 PCT 13 P2 VS3
-0.97 TEH TEC 0.61 CBAY2 236 C
137 32 87 182 0.25 46 PCT 8
P2 VS2
-0.79 TEH TEC 0.61 CBAY2 236 C
85 32 87 182 0.4 85 PCT 12 P2 VS3
-0.88 TEH TEC 0.61 CBAY2 236 C
85 32 87 184 0.34 78 PCT 11 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 236 C
76
U3R24 PVGS SG32 All Data Page 22 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 87 184 0.56 125 PCT 16 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 236 C
76 32 88 21 0.21 76 PCT 7
P2 VS2
-0.77 TEH TEC 0.61 CBAY2 28 C
195 32 88 21 0.38 121 PCT 12 P2 VS4
-0.74 TEH TEC 0.61 CBAY2 28 C
195 32 88 37 0.35 126 PCT 12 P2 VS2
-0.68 TEH TEC 0.61 CBAY2 32 C
9 32 88 39 0.23 73 PCT 8
P2 VS4
-0.73 TEH TEC 0.61 CBAY2 36 C
21 32 88 41 0.4 117 PCT 13 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 30 C
13 32 88 77 0.68 106 PCT 17 P2 VS3 0.77 TEC TEH 0.61 CBAY2 7
H 98 32 88 89 0.7 130 PCT 15 P2 09H 0.72 TEC TEH 0.61 CBAY2 15 H
212 32 88 107 0.49 107 PCT 14 P2 VS2
-0.96 TEC TEH 0.61 CBAY2 9
H 300 32 88 109 0.34 77 PCT 11 P2 VS2 0.61 TEC TEH 0.61 CBAY2 11 H
318 32 88 115 0.35 101 PCT 11 P2 BW1 0.9 TEC TEH 0.61 CBAY2 9
H 214 32 88 115 0.27 123 PCT 9
P2 09C
-1.01 TEC TEH 0.61 CBAY2 9
H 214 32 88 117 0.31 87 PCT 10 P2 VS4
-0.92 TEC TEH 0.61 CBAY2 11 H
228 32 88 117 0.31 74 PCT 10 P2 VS4 0.97 TEC TEH 0.61 CBAY2 11 H
228 32 88 121 0.39 101 PCT 12 P2 VS3 0.82 TEC TEH 0.61 CBAY2 11 H
183 32 88 125 0.3 149 PCT 10 P2 VS2 0.74 TEC TEH 0.61 CBAY2 11 H
133 32 88 139 0.36 129 PCT 13 P2 VS2
-0.9 TEH TEC 0.61 CBAY2 226 C
59 32 88 147 0.3 134 PCT 12 P2 06H 0.68 TEH TEC 0.61 CBAY2 226 C
155 32 88 147 0.27 77 PCT 11 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 226 C
155 32 88 157 0.36 75 PCT 11 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 228 C
211 32 88 161 0.33 97 PCT 11 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 228 C
243 32 88 167 0.27 100 PCT 11 P2 VS2 0.72 TEH TEC 0.61 CBAY2 234 C
178 32 88 175 0.54 112 PCT 17 P2 VS3 0.69 TEH TEC 0.61 CBAY2 234 C
129 32 88 181 0.28 76 PCT 11 P2 VS2
-0.98 TEH TEC 0.61 CBAY2 234 C
113 32 89 18 0.24 136 PCT 8
P2 VS2
-0.79 TEH TEC 0.61 CBAY2 28 C
187 32 89 20 0.27 143 PCT 9
P2 09H 0.65 TEH TEC 0.61 CBAY2 28 C
194 32 89 34 0.3 129 PCT 10 P2 BW1 1.13 TEH TEC 0.61 CBAY2 26 C
148 32 89 46 0.29 16 PCT 11 P2 BW2 0.8 TEH TEC 0.61 CBAY2 42 C
37 32 89 48 0.31 80 PCT 11 P2 BW1 0.95 TEH TEC 0.61 CBAY2 34 C
58 32 89 56 0.32 44 PCT 11 P2 BW2 0.87 TEH TEC 0.61 CBAY2 34 C
158 32 89 86 0.49 50 PCT 14 P2 BW1 0.98 TEC TEH 0.61 CBAY2 15 H
232 32 89 88 0.56 114 PCT 15 P2 VS3
-1.02 TEC TEH 0.61 CBAY2 13 H
185 32 89 92 0.37 113 PCT 11 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 13 H
142 32 89 96 0.47 124 PCT 13 P2 BW1 0.84 TEC TEH 0.61 CBAY2 13 H
101 32 89 98 0.33 113 PCT 11 P2 VS4 1.1 TEC TEH 0.61 CBAY2 15 H
101 32 89 100 0.36 141 PCT 11 P2 BW1 0.97 TEC TEH 0.61 CBAY2 13 H
59 32 89 106 0.73 124 PCT 19 P2 VS3
-1.03 TEC TEH 0.61 CBAY2 15 H
16 32 89 106 0.62 103 PCT 17 P2 VS4 0.57 TEC TEH 0.61 CBAY2 15 H
16 32 89 108 0.31 88 PCT 10 P2 VS2
-0.82 TEC TEH 0.61 CBAY2 9
H 278 32 89 112 0.37 57 PCT 11 P2 BW2 1.06 TEC TEH 0.61 CBAY2 9
H 235 32 89 114 0.39 74 PCT 12 P2 BW1 0.82 TEC TEH 0.61 CBAY2 11 H
249 32 89 118 0.49 113 PCT 14 P2 VS3
-0.89 TEC TEH 0.61 CBAY2 11 H
205
U3R24 PVGS SG32 All Data Page 23 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 89 130 0.39 128 PCT 12 P2 VS2 0.77 TEC TEH 0.61 CBAY2 11 H
55 32 89 134 0.51 56 PCT 15 P2 BW1 0.97 TEH TEC 0.61 CBAY2 228 C
116 32 89 138 0.54 49 PCT 15 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 228 C
84 32 89 138 0.32 32 PCT 10 P2 BW2 0.77 TEH TEC 0.61 CBAY2 228 C
84 32 89 142 0.3 18 PCT 10 P2 BW1
-0.05 TEH TEC 0.61 CBAY2 228 C
50 32 89 144 0.31 137 PCT 12 P2 BW1 0.83 TEH TEC 0.61 CBAY2 226 C
9 32 89 152 0.27 86 PCT 11 P2 VS3
-0.89 TEH TEC 0.61 CBAY2 226 C
196 32 89 154 0.36 58 PCT 11 P2 VS3
-0.87 TEH TEC 0.61 CBAY2 228 C
184 32 89 160 0.34 91 PCT 13 P2 BW1 0.85 TEH TEC 0.61 CBAY2 226 C
264 32 89 160 0.27 124 PCT 11 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 226 C
264 32 89 162 0.34 38 PCT 11 P2 BW1 0.91 TEH TEC 0.61 CBAY2 228 C
248 32 89 166 0.3 69 PCT 10 P2 09H 0.78 TEH TEC 0.61 CBAY2 236 C
198 32 89 166 0.25 25 PCT 9
P2 BW1 0.91 TEH TEC 0.61 CBAY2 236 C
198 32 89 166 0.56 79 PCT 16 P2 VS3
-0.91 TEH TEC 0.61 CBAY2 236 C
198 32 89 166 0.44 69 PCT 13 P2 VS3 0.96 TEH TEC 0.61 CBAY2 236 C
198 32 89 166 0.29 109 PCT 10 P2 VS4
-0.66 TEH TEC 0.61 CBAY2 236 C
198 32 89 176 0.3 82 PCT 11 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 234 C
128 32 89 182 0.26 41 PCT 10 P2 VS2
-0.69 TEH TEC 0.61 CBAY2 234 C
114 32 89 184 0.29 100 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 236 C
83 32 89 188 0.48 114 PCT 16 P2 VS3
-0.92 TEH TEC 0.61 CBAY2 234 C
72 32 89 188 0.24 121 PCT 10 P2 VS4
-0.64 TEH TEC 0.61 CBAY2 234 C
72 32 90 25 0.41 119 PCT 12 P2 10C
-1.27 TEH TEC 0.61 CBAY2 26 C
84 32 90 105 0.21 117 PCT 8
P2 VS2 0.84 TEC TEH 0.61 CBAY2 15 H
39 32 90 111 1.41 127 PCT 23 P2 09H 0.82 TEC TEH 0.61 CBAY2 9
H 256 32 90 111 1.34 120 WAR 22 0.27 P26 09H 0.87 10H TEH 0.61 NYAX2 55 H
16 32 90 125 0.48 136 PCT 11 P2 09H 0.84 TEC TEH 0.61 CBAY2 11 H
132 32 90 141 0.3 70 PCT 10 P2 10C
-1.52 TEH TEC 0.61 CBAY2 228 C
54 32 90 151 0.3 155 PCT 11 P2 BW1
-0.76 TEH TEC 0.61 CBAY2 226 C
190 32 90 173 0.29 90 PCT 10 P2 BW2 0.8 TEH TEC 0.61 CBAY2 236 C
184 32 90 175 0.29 62 PCT 10 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 236 C
165 32 90 179 0.26 69 PCT 9
P2 VS2
-0.83 TEH TEC 0.61 CBAY2 236 C
120 32 90 181 0.3 110 PCT 10 P2 BW2 0.78 TEH TEC 0.61 CBAY2 236 C
134 32 91 46 0.27 85 PCT 10 P2 BW1 0.97 TEH TEC 0.61 CBAY2 34 C
56 32 91 90 0.32 51 PCT 11 P2 BW1
-0.86 TEC TEH 0.61 CBAY2 15 H
189 32 91 98 2.26 182 DNT P1 10C 1.22 TEC TEH 0.61 CBAY2 15 H
102 32 91 98 NDF P6 10C 1.22 10C TEC 0.61 NYAX2 254 C
49 32 91 106 0.35 74 PCT 11 P2 BW1 0.97 TEC TEH 0.61 CBAY2 15 H
17 32 91 130 0.19 146 PCT 7
P2 BW2 0.92 TEC TEH 0.61 CBAY2 11 H
56 32 91 144 0.25 134 PCT 10 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 226 C
10 32 91 154 0.51 27 PCT 15 P2 BW1 0.99 TEH TEC 0.61 CBAY2 228 C
183 32 91 156 0.62 151 PCT 13 P2 10H
-1.97 TEH TEC 0.61 CBAY2 226 C
229 32 91 158 0.33 76 PCT 10 P2 BW1 0.83 TEH TEC 0.61 CBAY2 228 C
215
U3R24 PVGS SG32 All Data Page 24 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 91 164 2.9 182 DNT P1 10C 1.19 TEH TEC 0.61 CBAY2 234 C
184 32 91 164 NDF 166 10C 1.12 10C TEC 0.61 NYAX2 258 C
28 32 91 166 2.57 177 DNT P1 10C 1.45 TEH TEC 0.61 CBAY2 236 C
231 32 91 166 NDF 22 10C 1.36 10C TEC 0.61 NYAX2 258 C
29 32 91 176 2.83 178 DNT P1 10C 1.89 TEH TEC 0.61 CBAY2 236 C
166 32 91 176 NDF P3 10C 1.32 10C TEC 0.61 NYAX2 258 C
32 32 91 182 1.98 178 DNT P1 10C 0.91 TEH TEC 0.61 CBAY2 236 C
133 32 91 182 NDF 86 10C 0.97 10C TEC 0.61 NYAX2 258 C
38 32 92 17 4.46 179 DNT P1 10H 1.11 TEH TEC 0.61 CBAY2 28 C
191 32 92 17 NDF P1 10H 1.13 10H TEH 0.61 NYAX2 49 H
51 32 92 21 0.51 121 PCT 15 P2 BW1 0.26 TEH TEC 0.61 CBAY2 26 C
35 32 92 29 0.29 114 PCT 10 P2 VS2 0.85 TEH TEC 0.61 CBAY2 26 C
100 32 92 97 0.76 136 PCT 16 P2 10H 1.04 TEC TEH 0.61 CBAY2 15 H
123 32 92 97 0.37 99 PCT 12 P2 VS3
-0.64 TEC TEH 0.61 CBAY2 15 H
123 32 92 99 0.59 138 PCT 12 P2 10H 1.08 TEC TEH 0.61 CBAY2 13 H
79 32 92 109 0.37 125 PCT 11 P2 VS4 0.97 TEC TEH 0.61 CBAY2 11 H
316 32 92 119 0.41 139 PCT 10 P2 10H 0.67 TEC TEH 0.61 CBAY2 9
H 169 32 92 121 0.36 93 PCT 11 P2 VS4
-0.86 TEC TEH 0.61 CBAY2 11 H
181 32 92 135 0.27 139 PCT 11 P2 10H 0.98 TEH TEC 0.61 CBAY2 226 C
93 32 92 163 0.31 127 PCT 10 P2 10C 1.13 TEH TEC 0.61 CBAY2 234 C
222 32 92 173 0.24 132 PCT 10 P2 VS3 0.69 TEH TEC 0.61 CBAY2 234 C
152 32 92 183 0.27 106 PCT 9
P2 BW2
-0.87 TEH TEC 0.61 CBAY2 236 C
132 32 92 187 2.88 177 DNT P1 10C 1.17 TEH TEC 0.61 CBAY2 236 C
80 32 92 187 NDF P13 10C 1.06 10C TEC 0.61 NYAX2 258 C
43 32 93 22 0.3 99 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 26 C
87 32 93 44 0.57 25 PCT 13 P2 10H 0.79 TEH TEC 0.61 CBAY2 34 C
54 32 93 102 0.9 106 PCT 21 P2 VS2 0.59 TEC TEH 0.61 CBAY2 15 H
60 32 93 102 1.77 110 WAR 25 0.28 P8 VS2 0.61 VS3 TEH 0.61 NYAX2 51 H
33 32 93 124 0.52 30 PCT 11 P2 10H
-0.86 TEC TEH 0.61 CBAY2 9
H 105 32 93 148 0.26 70 PCT 11 P2 10H 0.75 TEH TEC 0.61 CBAY2 226 C
159 32 93 148 0.26 96 PCT 10 P2 VS4
-0.82 TEH TEC 0.61 CBAY2 226 C
159 32 93 150 0.5 86 PCT 14 P2 BW1
-0.74 TEH TEC 0.61 CBAY2 228 C
151 32 93 156 0.27 139 PCT 11 P2 BW1
-0.74 TEH TEC 0.61 CBAY2 226 C
228 32 93 160 0.36 28 PCT 10 P2 10H
-0.83 TEH TEC 0.61 CBAY2 226 C
262 32 93 162 0.27 92 PCT 9
P2 10H
-0.77 TEH TEC 0.61 CBAY2 228 C
246 32 93 164 0.47 108 PCT 16 P2 VS2 0.72 TEH TEC 0.61 CBAY2 234 C
221 32 93 166 0.27 136 PCT 11 P2 VS2 0.67 TEH TEC 0.61 CBAY2 234 C
186 32 94 29 0.34 80 PCT 11 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 26 C
153 32 94 33 0.28 122 PCT 10 P2 BW1
-0.74 TEH TEC 0.61 CBAY2 36 C
27 32 94 53 0.25 114 PCT 10 P2 VS2 0.79 TEH TEC 0.61 CBAY2 34 C
212 32 94 61 0.49 116 PCT 15 P2 10H 0.79 TEH TEC 0.61 CBAY2 38 C
101 32 94 65 1.3 109 PCT 28 P2 VS3 0.75 TEH TEC 0.61 CBAY2 46 C
31
U3R24 PVGS SG32 All Data Page 25 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 94 65 0.95 125 WAR 19 0.17 P15 VS3 0.83 VS3 TEH 0.61 NYAX2 49 H
44 32 94 87 0.24 143 PCT 8
P2 VS2
-0.85 TEC TEH 0.61 CBAY2 13 H
204 32 94 89 0.62 88 PCT 17 P2 10H 0.8 TEC TEH 0.61 CBAY2 15 H
209 32 94 95 0.89 115 PCT 19 P2 10H 0.8 TEC TEH 0.61 CBAY2 13 H
120 32 94 99 0.64 126 PCT 16 P2 VS2
-0.8 TEC TEH 0.61 CBAY2 13 H
78 32 94 121 0.28 118 PCT 9
P2 VS3 0.82 TEC TEH 0.61 CBAY2 11 H
180 32 94 143 0.27 147 PCT 11 P2 10H 0.76 TEH TEC 0.61 CBAY2 226 C
15 32 94 163 0.33 141 PCT 11 P2 VS4
-0.84 TEH TEC 0.61 CBAY2 236 C
235 32 94 181 0.24 140 PCT 10 P2 BW1
-0.68 TEH TEC 0.61 CBAY2 234 C
123 32 95 22 0.5 118 PCT 14 P2 VS2
-0.73 TEH TEC 0.61 CBAY2 28 C
244 32 95 42 0.31 132 PCT 11 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 34 C
52 32 95 58 0.41 106 PCT 14 P2 VS2
-0.69 TEH TEC 0.61 CBAY2 38 C
41 32 95 94 0.19 76 PCT 7
P2 VS4 0.86 TEC TEH 0.61 CBAY2 15 H
147 32 95 100 0.32 113 PCT 10 P2 VS4 0.81 TEC TEH 0.61 CBAY2 13 H
62 32 95 110 1.04 107 PCT 22 P2 VS3
-0.7 TEC TEH 0.61 CBAY2 11 H
297 32 95 110 2.04 111 WAR 27 0.27 P22 VS3
-0.42 VS3 TEH 0.61 NYAX2 55 H
18 32 95 112 0.75 96 PCT 18 P2 VS3
-0.75 TEC TEH 0.61 CBAY2 9
H 238 32 95 126 0.59 147 PCT 12 P2 10H
-0.75 TEC TEH 0.61 CBAY2 11 H
112 32 95 146 0.31 135 PCT 10 P2 10H 0.45 TEH TEC 0.61 CBAY2 228 C
13 32 95 150 0.45 138 PCT 12 P2 09H 0.72 TEH TEC 0.61 CBAY2 238 C
16 32 95 150 0.29 69 PCT 11 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 238 C
16 32 95 152 0.3 55 PCT 12 P2 10H 0.78 TEH TEC 0.61 CBAY2 226 C
193 32 95 156 0.24 100 PCT 10 P2 VS4
-0.67 TEH TEC 0.61 CBAY2 226 C
227 32 95 166 0.24 127 PCT 10 P2 VS3
-0.78 TEH TEC 0.61 CBAY2 234 C
219 32 95 174 0.24 47 PCT 10 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 234 C
171 32 95 178 0.33 42 PCT 11 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 236 C
179 32 95 182 0.32 124 PCT 12 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 234 C
122 32 95 186 0.32 121 PCT 12 P2 VS3
-1.07 TEH TEC 0.61 CBAY2 234 C
119 32 96 29 0.4 99 PCT 12 P2 10H 0.78 TEH TEC 0.61 CBAY2 28 C
310 32 96 33 0.29 90 PCT 10 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 30 C
5 32 96 41 0.56 29 PCT 13 P2 10H 0.83 TEH TEC 0.61 CBAY2 34 C
51 32 96 45 0.28 53 PCT 10 P2 BW1
-0.83 TEH TEC 0.61 CBAY2 36 C
160 32 96 59 0.61 128 PCT 16 P2 10H 0.81 TEH TEC 0.61 CBAY2 38 C
99 32 96 63 0.4 32 PCT 11 P2 10H 0.83 TEH TEC 0.61 CBAY2 46 C
33 32 96 71 0.19 115 PCT 7
P2 10H 0.75 TEH TEC 0.61 CBAY2 48 C
53 32 96 87 0.57 123 PCT 15 P2 VS3 0.77 TEC TEH 0.61 CBAY2 13 H
203 32 96 89 0.47 139 PCT 14 P2 09H 0.67 TEC TEH 0.61 CBAY2 15 H
208 32 96 91 0.54 30 PCT 12 P2 10H 0.86 TEC TEH 0.61 CBAY2 13 H
160 32 96 93 0.6 131 PCT 14 P2 09H 0.68 TEC TEH 0.61 CBAY2 15 H
164 32 96 97 0.28 134 PCT 10 P2 VS2
-0.88 TEC TEH 0.61 CBAY2 15 H
121 32 96 107 0.74 73 PCT 18 P2 10H 0.84 TEC TEH 0.61 CBAY2 9
H 296 32 96 113 1.29 114 PCT 25 P2 VS2
-0.78 TEC TEH 0.61 CBAY2 11 H
269
U3R24 PVGS SG32 All Data Page 26 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 96 113 2.99 115 WAR 31 0.33 P8 VS2
-0.63 VS3 TEH 0.61 NYAX2 55 H
17 32 96 117 0.41 117 PCT 11 P2 09H 0.7 TEC TEH 0.61 CBAY2 11 H
225 32 96 117 0.58 155 PCT 11 P2 10H 0.79 TEC TEH 0.61 CBAY2 11 H
225 32 96 119 0.48 88 PCT 14 P2 10H 0.78 TEC TEH 0.61 CBAY2 9
H 167 32 96 125 0.69 150 PCT 12 P2 09H 0.76 TEC TEH 0.61 CBAY2 11 H
129 32 96 131 0.74 28 PCT 12 P2 10H 0.81 TEH TEC 0.61 CBAY2 240 C
242 32 96 155 0.52 40 PCT 13 P2 10H 0.78 TEH TEC 0.61 CBAY2 240 C
12 32 96 155 0.33 49 PCT 11 P2 VS2 0.84 TEH TEC 0.61 CBAY2 240 C
12 32 96 157 0.46 134 PCT 11 P2 09H 0.74 TEH TEC 0.61 CBAY2 236 C
270 32 96 167 0.21 107 PCT 9
P2 VS3
-0.93 TEH TEC 0.61 CBAY2 234 C
218 32 96 171 0.34 120 PCT 10 P2 10H 0.76 TEH TEC 0.61 CBAY2 236 C
226 32 96 179 0.43 93 PCT 13 P2 VS2 0.98 TEH TEC 0.61 CBAY2 236 C
178 32 96 185 0.36 121 PCT 11 P2 VS3
-1.01 TEH TEC 0.61 CBAY2 236 C
126 32 97 20 0.36 95 PCT 11 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 28 C
241 32 97 28 0.44 131 PCT 13 P2 VS2
-0.72 TEH TEC 0.61 CBAY2 28 C
309 32 97 34 0.25 90 PCT 10 P2 VS2
-0.92 TEH TEC 0.61 CBAY2 34 C
26 32 97 76 0.43 109 PCT 13 P2 VS4 0.8 TEC TEH 0.61 CBAY2 13 H
317 32 97 108 0.55 137 PCT 11 P2 09H 0.84 TEC TEH 0.61 CBAY2 9
H 282 32 97 110 0.3 129 PCT 10 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 11 H
298 32 97 124 0.28 138 PCT 9
P2 VS3 0.71 TEC TEH 0.61 CBAY2 9
H 107 32 97 128 0.45 46 PCT 11 P2 10H
-0.79 TEC TEH 0.61 CBAY2 9
H 57 32 97 138 27.6 62 DTI P5 TSC
-1.4 TEH TEC 0.61 CBAY2 238 C
239 32 97 138 NDF P19 TSC
-1.4 01C TEC 0.61 NYAX2 254 C
51 32 97 180 0.5 83 PCT 14 P2 VS2
-0.93 TEH TEC 0.61 CBAY2 236 C
177 32 97 180 0.58 92 PCT 16 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 236 C
177 32 97 182 0.38 122 PCT 12 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 236 C
171 32 98 25 0.33 120 PCT 11 P2 VS3 0.96 TEH TEC 0.61 CBAY2 26 C
157 32 98 29 0.24 136 PCT 9
P2 10H 0.8 TEH TEC 0.61 CBAY2 36 C
31 32 98 41 0.28 112 PCT 10 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 34 C
117 32 98 55 0.27 112 PCT 10 P2 BW1
-0.79 TEH TEC 0.61 CBAY2 38 C
44 32 98 59 0.71 148 PCT 13 P2 10H 0.86 TEH TEC 0.61 CBAY2 44 C
21 32 98 61 0.44 115 PCT 14 P2 10H 0.87 TEH TEC 0.61 CBAY2 46 C
35 32 98 95 0.68 99 PCT 17 P2 VS2
-0.98 TEC TEH 0.61 CBAY2 13 H
118 32 98 99 0.68 102 PCT 17 P2 VS2
-0.91 TEC TEH 0.61 CBAY2 13 H
76 32 98 103 0.76 89 PCT 18 P2 VS3 0.88 TEC TEH 0.61 CBAY2 13 H
34 32 98 103 0.33 93 PCT 10 P2 VS4 0.76 TEC TEH 0.61 CBAY2 13 H
34 32 98 133 0.17 93 PCT 7
P2 10H 0.85 TEH TEC 0.61 CBAY2 238 C
277 32 98 143 0.27 65 PCT 9
P2 10H 0.79 TEH TEC 0.61 CBAY2 240 C
166 32 98 155 0.24 108 PCT 10 P2 VS2 0.77 TEH TEC 0.61 CBAY2 234 C
264 32 98 161 0.22 121 PCT 9
P2 10H 0.65 TEH TEC 0.61 CBAY2 234 C
257 32 98 167 0.29 32 PCT 10 P2 BW1 1
TEH TEC 0.61 CBAY2 236 C
239 32 98 177 0.18 129 PCT 8
P2 10H 0.73 TEH TEC 0.61 CBAY2 234 C
168
U3R24 PVGS SG32 All Data Page 27 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 98 185 0.61 50 PCT 17 P2 VS3
-0.91 TEH TEC 0.61 CBAY2 236 C
127 32 99 20 0.32 123 PCT 10 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 28 C
242 32 99 28 0.27 134 PCT 10 P2 VS3 0.77 TEH TEC 0.61 CBAY2 36 C
32 32 99 32 0.26 65 PCT 10 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 34 C
28 32 99 34 0.55 127 PCT 16 P2 VS2
-0.66 TEH TEC 0.61 CBAY2 36 C
48 32 99 34 0.78 126 PCT 20 P2 VS3
-1.35 TEH TEC 0.61 CBAY2 36 C
48 32 99 34 1.44 276 WAR 23 0.2 P22 VS3
-1.04 VS3 TEH 0.61 NYAX2 49 H
48 32 99 40 0.36 116 PCT 13 P2 VS3
-1.24 TEH TEC 0.61 CBAY2 34 C
118 32 99 40 0.63 126 PCT 18 P2 VS3 0.84 TEH TEC 0.61 CBAY2 34 C
118 32 99 42 0.33 135 PCT 11 P2 VS3
-1.26 TEH TEC 0.61 CBAY2 36 C
163 32 99 44 0.62 125 PCT 18 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 42 C
18 32 99 54 0.28 132 PCT 10 P2 VS2
-1.04 TEH TEC 0.61 CBAY2 38 C
45 32 99 94 0.3 127 PCT 10 P2 VS4
-0.87 TEC TEH 0.61 CBAY2 15 H
149 32 99 104 0.26 135 PCT 9
P2 VS3 0.74 TEC TEH 0.61 CBAY2 13 H
22 32 99 104 0.31 104 PCT 10 P2 09C
-0.96 TEC TEH 0.61 CBAY2 13 H
22 32 99 140 0.35 44 PCT 12 P2 VS2 0.8 TEH TEC 0.61 CBAY2 240 C
181 32 99 142 0.26 109 PCT 10 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 238 C
206 32 99 174 0.32 75 PCT 10 P2 VS2
-0.88 TEH TEC 0.61 CBAY2 236 C
223 32 99 178 0.54 100 PCT 17 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 234 C
167 32 99 180 0.38 118 PCT 14 P2 VS3
-1.1 TEH TEC 0.61 CBAY2 234 C
159 32 99 182 0.31 134 PCT 10 P2 VS3
-1.19 TEH TEC 0.61 CBAY2 236 C
175 32 100 21 0.66 130 PCT 18 P2 VS3
-0.44 TEH TEC 0.61 CBAY2 26 C
92 32 100 23 0.55 124 PCT 16 P2 VS3
-0.42 TEH TEC 0.61 CBAY2 26 C
159 32 100 35 0.37 65 PCT 13 P2 VS3 1.03 TEH TEC 0.61 CBAY2 42 C
26 32 100 37 0.53 102 PCT 16 P2 10H 0.81 TEH TEC 0.61 CBAY2 34 C
47 32 100 41 0.27 141 PCT 9
P2 10H 0.78 TEH TEC 0.61 CBAY2 36 C
164 32 100 47 0.55 143 PCT 13 P2 10H 0.72 TEH TEC 0.61 CBAY2 34 C
205 32 100 47 0.32 111 PCT 12 P2 VS4 0.39 TEH TEC 0.61 CBAY2 34 C
205 32 100 53 0.27 65 PCT 10 P2 BW1
-0.82 TEH TEC 0.61 CBAY2 38 C
46 32 100 67 0.41 125 PCT 12 P2 10H 0.75 TEH TEC 0.61 CBAY2 48 C
57 32 100 101 1.44 107 PCT 27 P2 VS3 0.79 TEC TEH 0.61 CBAY2 15 H
75 32 100 101 2.53 110 WAR 29 0.17 P13 VS3 0.79 VS3 TEH 0.61 NYAX2 55 H
26 32 100 103 0.5 84 PCT 14 P2 VS4 0.49 TEC TEH 0.61 CBAY2 13 H
33 32 100 109 0.28 144 PCT 9
P2 VS2 0.74 TEC TEH 0.61 CBAY2 11 H
312 32 100 121 0.65 119 PCT 17 P2 VS2 0.76 TEC TEH 0.61 CBAY2 11 H
177 32 100 133 0.32 126 PCT 12 P2 BW1
-0.83 TEH TEC 0.61 CBAY2 238 C
278 32 100 135 0.57 39 PCT 12 P2 10H 0.82 TEH TEC 0.61 CBAY2 240 C
215 32 100 139 0.29 154 PCT 10 P2 10H 0.78 TEH TEC 0.61 CBAY2 240 C
185 32 100 147 0.25 73 PCT 10 P2 VS2 0.82 TEH TEC 0.61 CBAY2 238 C
48 32 100 153 0.31 90 PCT 10 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 240 C
19 32 100 173 0.24 129 PCT 10 P2 VS3 0.95 TEH TEC 0.61 CBAY2 234 C
197 32 101 24 0.36 115 PCT 11 P2 VS3
-0.88 TEH TEC 0.61 CBAY2 28 C
305
U3R24 PVGS SG32 All Data Page 28 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 101 26 0.49 100 PCT 15 P2 BW1 0.54 TEH TEC 0.61 CBAY2 36 C
34 32 101 28 0.38 107 PCT 12 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 26 C
167 32 101 30 0.29 94 PCT 11 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 34 C
30 32 101 30 0.36 134 PCT 13 P2 VS3 1.03 TEH TEC 0.61 CBAY2 34 C
30 32 101 38 0.27 104 PCT 10 P2 BW1
-0.72 TEH TEC 0.61 CBAY2 34 C
120 32 101 54 0.34 100 PCT 12 P2 VS4
-0.85 TEH TEC 0.61 CBAY2 38 C
94 32 101 58 0.44 118 PCT 15 P2 VS3 0.59 TEH TEC 0.61 CBAY2 46 C
38 32 101 84 0.32 92 PCT 10 P2 VS2 0.77 TEC TEH 0.61 CBAY2 13 H
234 32 101 114 0.29 143 PCT 10 P2 VS2 0.64 TEC TEH 0.61 CBAY2 11 H
255 32 101 122 0.29 142 PCT 9
P2 VS2 0.81 TEC TEH 0.61 CBAY2 11 H
165 32 101 130 0.3 146 PCT 10 P2 VS2 0.71 TEC TEH 0.61 CBAY2 11 H
61 32 101 132 0.3 52 PCT 10 P2 VS2 0.75 TEH TEC 0.61 CBAY2 240 C
239 32 101 148 0.31 105 PCT 11 P2 BW1
-0.7 TEH TEC 0.61 CBAY2 238 C
49 32 101 150 0.26 114 PCT 10 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 238 C
22 32 101 156 0.26 98 PCT 10 P2 10H
-0.88 TEH TEC 0.61 CBAY2 238 C
10 32 101 156 0.28 103 PCT 11 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 238 C
10 32 101 162 0.34 120 PCT 11 P2 BW1 1.06 TEH TEC 0.61 CBAY2 236 C
275 32 101 168 0.49 95 PCT 14 P2 VS2
-0.74 TEH TEC 0.61 CBAY2 236 C
262 32 101 170 0.52 112 PCT 15 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 236 C
242 32 101 174 0.29 105 PCT 11 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 234 C
198 32 101 178 0.29 67 PCT 10 P2 VS2
-0.83 TEH TEC 0.61 CBAY2 236 C
212 32 101 178 0.25 63 PCT 9
P2 VS3 0.86 TEH TEC 0.61 CBAY2 236 C
212 32 101 182 1.26 117 WAR 21 0.2 P22 VS3
-0.91 VS3 TEH 0.61 NYAX2 53 H
8 32 101 182 0.72 116 PCT 21 P2 VS3
-0.91 TEH TEC 0.61 CBAY2 234 C
161 32 102 21 1.31 122 PCT 27 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 26 C
161 32 102 21 2.9 109 WAR 31 0.29 P5 VS3
-0.82 VS3 TEH 0.61 NYAX2 49 H
49 32 102 25 0.37 116 PCT 12 P2 BW1 0.91 TEH TEC 0.61 CBAY2 36 C
35 32 102 27 0.28 91 PCT 10 P2 10H 0.86 TEH TEC 0.61 CBAY2 26 C
166 32 102 27 0.36 142 PCT 12 P2 BW1 1.04 TEH TEC 0.61 CBAY2 26 C
166 32 102 37 0.51 115 PCT 16 P2 VS3 1.01 TEH TEC 0.61 CBAY2 34 C
121 32 102 47 0.45 89 PCT 14 P2 VS3 0.73 TEH TEC 0.61 CBAY2 40 C
87 32 102 53 0.61 133 PCT 15 P2 10H 0.85 TEH TEC 0.61 CBAY2 38 C
93 32 102 67 0.28 51 PCT 11 P2 VS4 0.88 TEH TEC 0.61 CBAY2 46 C
50 32 102 69 0.32 83 PCT 12 P2 VS2 0.82 TEH TEC 0.61 CBAY2 46 C
78 32 102 83 1.47 118 PCT 27 P2 VS3 0.69 TEC TEH 0.61 CBAY2 13 H
243 32 102 83 2.37 112 WAR 28 0.36 P22 VS3 0.82 VS3 TEH 0.61 NYAX2 51 H
18 32 102 91 0.56 108 PCT 15 P2 VS3 0.87 TEC TEH 0.61 CBAY2 13 H
157 32 102 93 0.52 105 PCT 15 P2 VS3 0.82 TEC TEH 0.61 CBAY2 15 H
161 32 102 103 1.12 107 PCT 23 P2 VS3 0.82 TEC TEH 0.61 CBAY2 13 H
32 32 102 103 1.95 102 WAR 26 0.31 P22 VS3 0.73 VS3 TEH 0.61 NYAX2 55 H
25 32 102 105 0.32 132 PCT 11 P2 VS3 0.79 TEC TEH 0.61 CBAY2 15 H
33 32 102 111 0.3 139 PCT 10 P2 VS4
-0.78 TEC TEH 0.61 CBAY2 9
H 250
U3R24 PVGS SG32 All Data Page 29 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 102 115 0.75 116 PCT 18 P2 VS3
-0.87 TEC TEH 0.61 CBAY2 9
H 207 32 102 137 0.22 98 PCT 9
P2 09H 0.87 TEH TEC 0.61 CBAY2 238 C
245 32 102 139 0.37 31 PCT 12 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 240 C
186 32 102 143 0.32 51 PCT 11 P2 BW1
-0.8 TEH TEC 0.61 CBAY2 240 C
164 32 102 147 0.3 48 PCT 10 P2 VS3 0.9 TEH TEC 0.61 CBAY2 240 C
143 32 102 151 0.26 78 PCT 10 P2 VS3 0.95 TEH TEC 0.61 CBAY2 238 C
23 32 102 153 0.36 79 PCT 12 P2 VS3 0.86 TEH TEC 0.61 CBAY2 240 C
47 32 102 159 0.3 96 PCT 11 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 234 C
268 32 102 161 0.29 55 PCT 10 P2 VS3 0.98 TEH TEC 0.61 CBAY2 240 C
6 32 102 165 0.3 123 PCT 12 P2 BW1
-0.77 TEH TEC 0.61 CBAY2 234 C
253 32 102 171 0.61 99 PCT 17 P2 VS3 0.76 TEH TEC 0.61 CBAY2 236 C
243 32 102 183 1.85 89 WAR 25 0.33 P14 VS3
-0.86 VS3 TEH 0.61 NYAX2 53 H
9 32 102 183 0.97 114 PCT 24 P2 VS3
-1.07 TEH TEC 0.61 CBAY2 234 C
162 32 103 24 0.32 147 PCT 11 P2 BW1 0.79 TEH TEC 0.61 CBAY2 36 C
36 32 103 32 0.32 41 PCT 11 P2 BW2 0.91 TEH TEC 0.61 CBAY2 34 C
137 32 103 36 0.27 147 PCT 10 P2 VS2 0.87 TEH TEC 0.61 CBAY2 34 C
122 32 103 46 0.46 125 PCT 14 P2 BW1 0.9 TEH TEC 0.61 CBAY2 40 C
88 32 103 52 0.46 113 PCT 15 P2 VS2
-0.9 TEH TEC 0.61 CBAY2 38 C
92 32 103 52 0.31 106 PCT 12 P2 VS4
-0.69 TEH TEC 0.61 CBAY2 38 C
92 32 103 54 0.3 127 PCT 10 P2 VS4 0.91 TEH TEC 0.61 CBAY2 44 C
26 32 103 56 0.62 120 PCT 18 P2 VS3 0.75 TEH TEC 0.61 CBAY2 46 C
104 32 103 72 0.33 80 PCT 12 P2 BW1 1.01 TEH TEC 0.61 CBAY2 46 C
117 32 103 74 0.3 52 PCT 10 P2 05H 0.85 TEH TEC 0.61 CBAY2 46 C
106 32 103 92 0.38 117 PCT 11 P2 VS2
-1.04 TEC TEH 0.61 CBAY2 13 H
149 32 103 92 0.66 114 PCT 17 P2 VS3 0.52 TEC TEH 0.61 CBAY2 13 H
149 32 103 98 0.97 104 PCT 22 P2 VS3 0.51 TEC TEH 0.61 CBAY2 15 H
108 32 103 98 1.93 115 WAR 26 0.29 P6 VS3 0.53 VS3 TEH 0.61 NYAX2 55 H
27 32 103 100 0.34 128 PCT 11 P2 BW1
-0.8 TEC TEH 0.61 CBAY2 13 H
66 32 103 104 0.39 105 PCT 12 P2 VS2
-0.92 TEC TEH 0.61 CBAY2 13 H
24 32 103 106 0.28 150 PCT 10 P2 VS2 0.71 TEC TEH 0.61 CBAY2 15 H
23 32 103 106 0.84 123 PCT 20 P2 VS3 0.66 TEC TEH 0.61 CBAY2 15 H
23 32 103 106 1.13 104 WAR 20 P8 VS2 0.95 VS3 TEH 0.61 NYAX2 55 H
24 32 103 106 1.84 110 WAR 25 0.31 P5 VS3 0
VS3 TEH 0.61 NYAX2 55 H
24 32 103 108 0.31 133 PCT 10 P2 VS3 0.31 TEC TEH 0.61 CBAY2 9
H 285 32 103 110 0.38 147 PCT 12 P2 VS2 0.69 TEC TEH 0.61 CBAY2 11 H
301 32 103 126 0.39 144 PCT 12 P2 VS2 0.64 TEC TEH 0.61 CBAY2 11 H
116 32 103 140 0.32 57 PCT 11 P2 VS2
-0.78 TEH TEC 0.61 CBAY2 240 C
179 32 103 146 0.32 117 PCT 10 P2 10H 0.63 TEH TEC 0.61 CBAY2 228 C
19 32 103 168 0.24 147 PCT 10 P2 BW1
-0.78 TEH TEC 0.61 CBAY2 234 C
230 32 103 168 0.4 69 PCT 14 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 234 C
230 32 103 174 0.24 128 PCT 10 P2 VS4
-0.75 TEH TEC 0.61 CBAY2 234 C
211 32 103 176 0.27 118 PCT 11 P2 BW1
-0.69 TEH TEC 0.61 CBAY2 234 C
200
U3R24 PVGS SG32 All Data Page 30 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 103 178 0.4 82 PCT 12 P2 BW1
-0.84 TEH TEC 0.61 CBAY2 236 C
219 32 103 178 0.36 82 PCT 11 P2 VS3 0.91 TEH TEC 0.61 CBAY2 236 C
219 32 104 35 0.26 75 PCT 10 P2 BW2
-0.86 TEH TEC 0.61 CBAY2 34 C
123 32 104 47 0.32 114 PCT 10 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 40 C
117 32 104 47 0.22 129 PCT 8
P2 VS3 0.86 TEH TEC 0.61 CBAY2 40 C
117 32 104 51 0.34 121 PCT 12 P2 VS3 0.85 TEH TEC 0.61 CBAY2 38 C
91 32 104 63 0.33 62 PCT 12 P2 BW2
-0.88 TEH TEC 0.61 CBAY2 46 C
83 32 104 79 0.51 128 PCT 14 P2 VS2 0.77 TEC TEH 0.61 CBAY2 13 H
284 32 104 85 0.64 93 PCT 17 P2 VS3 0.82 TEC TEH 0.61 CBAY2 15 H
248 32 104 87 0.42 142 PCT 13 P2 VS3 0.82 TEC TEH 0.61 CBAY2 13 H
199 32 104 91 0.65 121 PCT 17 P2 VS2 0.77 TEC TEH 0.61 CBAY2 13 H
156 32 104 91 0.28 128 PCT 9
P2 VS4
-0.81 TEC TEH 0.61 CBAY2 13 H
156 32 104 113 0.3 47 PCT 10 P2 BW1
-0.89 TEC TEH 0.61 CBAY2 11 H
265 32 104 137 0.2 93 PCT 8
P2 VS2 0.86 TEH TEC 0.61 CBAY2 238 C
246 32 104 157 0.27 40 PCT 10 P2 VS2
-0.79 TEH TEC 0.61 CBAY2 240 C
23 32 104 161 0.24 99 PCT 10 P2 VS2
-0.8 TEH TEC 0.61 CBAY2 234 C
270 32 104 161 0.44 95 PCT 15 P2 VS3 1.05 TEH TEC 0.61 CBAY2 234 C
270 32 104 165 0.31 102 PCT 10 P2 BW1
-0.81 TEH TEC 0.61 CBAY2 236 C
278 32 104 169 0.34 113 PCT 13 P2 VS4 0.84 TEH TEC 0.61 CBAY2 234 C
231 32 104 171 0.31 61 PCT 10 P2 VS2
-0.89 TEH TEC 0.61 CBAY2 236 C
259 32 104 173 0.25 146 PCT 9
P2 09H
-0.3 TEH TEC 0.61 CBAY2 236 C
245 32 104 175 0.2 111 PCT 8
P2 VS4
-0.73 TEH TEC 0.61 CBAY2 234 C
210 32 105 26 0.45 122 PCT 15 P2 BW1 0.96 TEH TEC 0.61 CBAY2 34 C
34 32 105 36 0.46 126 PCT 14 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 36 C
169 32 105 52 0.59 142 PCT 17 P2 VS4
-0.64 TEH TEC 0.61 CBAY2 44 C
28 32 105 54 0.52 113 PCT 16 P2 VS3
-1.08 TEH TEC 0.61 CBAY2 46 C
102 32 105 58 0.3 130 PCT 11 P2 VS3
-1.11 TEH TEC 0.61 CBAY2 46 C
4 32 105 78 0.36 144 PCT 12 P2 VS2 0.66 TEC TEH 0.61 CBAY2 15 H
327 32 105 80 0.42 110 PCT 12 P2 VS3
-0.99 TEC TEH 0.61 CBAY2 13 H
278 32 105 92 0.93 119 PCT 21 P2 VS2
-0.73 TEC TEH 0.61 CBAY2 13 H
150 32 105 92 1
106 PCT 22 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 13 H
150 32 105 92 1.6 122 WAR 24 0.34 P23 VS2
-0.73 VS3 TEH 0.61 NYAX2 55 H
28 32 105 92 2.05 107 WAR 27 0.23 P22 VS3
-0.58 VS3 TEH 0.61 NYAX2 55 H
28 32 105 168 0.35 118 PCT 13 P2 BW1
-0.52 TEH TEC 0.61 CBAY2 234 C
250 32 105 168 0.34 89 PCT 12 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 234 C
250 32 105 170 0.3 146 PCT 11 P2 BW1
-0.5 TEH TEC 0.61 CBAY2 234 C
232 32 105 170 0.3 135 PCT 11 P2 VS3
-1.26 TEH TEC 0.61 CBAY2 234 C
232 32 105 178 0.36 119 PCT 13 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 234 C
202 32 106 31 0.33 103 PCT 12 P2 BW1
-1.26 TEH TEC 0.61 CBAY2 34 C
42 32 106 37 0.27 119 PCT 9
P2 VS2
-0.8 TEH TEC 0.61 CBAY2 36 C
184 32 106 37 0.35 125 PCT 12 P2 VS4 0.85 TEH TEC 0.61 CBAY2 36 C
184 32 106 53 1.11 103 PCT 26 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 46 C
101
U3R24 PVGS SG32 All Data Page 31 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 106 53 2.51 286 WAR 29 0.27 P1 VS2
-0.9 VS3 TEH 0.61 NYAX2 49 H
45 32 106 61 0.34 79 PCT 11 P2 VS3 0.88 TEH TEC 0.61 CBAY2 48 C
66 32 106 69 0.3 107 PCT 11 P2 BW2
-1.45 TEH TEC 0.61 CBAY2 46 C
120 32 106 77 0.33 122 PCT 10 P2 VS3 0.75 TEC TEH 0.61 CBAY2 7
H 107 32 106 99 0.2 79 PCT 7
P2 VS2 0.67 TEC TEH 0.61 CBAY2 13 H
72 32 106 99 0.26 93 PCT 9
P2 VS3 0.7 TEC TEH 0.61 CBAY2 13 H
72 32 106 107 0.57 126 PCT 15 P2 VS4
-0.7 TEC TEH 0.61 CBAY2 9
H 291 32 106 111 0.46 110 PCT 13 P2 VS4
-0.78 TEC TEH 0.61 CBAY2 9
H 248 32 106 119 0.45 93 PCT 13 P2 BW1 1.46 TEC TEH 0.61 CBAY2 9
H 162 32 106 147 0.35 37 PCT 12 P2 VS4
-0.69 TEH TEC 0.61 CBAY2 240 C
141 32 106 155 0.3 107 PCT 11 P2 BW1
-1.35 TEH TEC 0.61 CBAY2 238 C
27 32 106 159 0.3 105 PCT 10 P2 VS3
-0.9 TEH TEC 0.61 CBAY2 240 C
25 32 106 161 0.44 109 PCT 15 P2 BW1
-1.32 TEH TEC 0.61 CBAY2 238 C
5 32 106 165 0.33 50 PCT 11 P2 BW1
-1.29 TEH TEC 0.61 CBAY2 236 C
300 32 106 177 0.36 131 PCT 11 P2 09H 0.73 TEH TEC 0.61 CBAY2 234 C
208 32 107 46 0.53 112 PCT 17 P2 BW2
-1.41 TEH TEC 0.61 CBAY2 38 C
53 32 107 48 0.3 120 PCT 11 P2 BW1 1.67 TEH TEC 0.61 CBAY2 38 C
88 32 107 64 0.44 120 PCT 15 P2 VS3 0.55 TEH TEC 0.61 CBAY2 46 C
86 32 107 80 0.33 124 PCT 10 P2 VS4 0.79 TEC TEH 0.61 CBAY2 13 H
279 32 107 84 0.24 106 PCT 8
P2 09H 0.76 TEC TEH 0.61 CBAY2 13 H
237 32 107 86 0.29 135 PCT 10 P2 VS3 0.73 TEC TEH 0.61 CBAY2 15 H
241 32 107 92 0.25 150 PCT 9
P2 VS2
-0.84 TEC TEH 0.61 CBAY2 13 H
151 32 107 106 0.18 130 PCT 7
P2 VS4 0.76 TEC TEH 0.61 CBAY2 15 H
25 32 107 134 0.37 120 PCT 12 P2 09H 0.81 TEH TEC 0.61 CBAY2 238 C
268 32 107 134 0.25 118 PCT 10 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 238 C
268 32 107 140 0.29 64 PCT 10 P2 VS2
-0.9 TEH TEC 0.61 CBAY2 240 C
177 32 107 146 0.39 46 PCT 12 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 228 C
21 32 107 178 0.24 147 PCT 10 P2 10H
-0.86 TEH TEC 0.61 CBAY2 234 C
207 32 108 31 0.29 97 PCT 11 P2 VS2 0.74 TEH TEC 0.61 CBAY2 34 C
127 32 108 33 0.25 55 PCT 9
P2 VS2
-0.8 TEH TEC 0.61 CBAY2 36 C
172 32 108 73 0.35 94 PCT 11 P2 BW1 1.99 TEC TEH 0.61 CBAY2 13 H
321 32 108 179 0.3 115 PCT 11 P2 VS3
-1.11 TEH TEC 0.61 CBAY2 234 C
206 32 109 24 0.37 107 PCT 12 P2 VS3
-1.17 TEH TEC 0.61 CBAY2 36 C
38 32 109 24 0.39 82 PCT 13 P2 VS3 0.32 TEH TEC 0.61 CBAY2 36 C
38 32 109 52 0.26 32 PCT 10 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 42 C
63 32 109 54 0.84 78 PCT 22 P2 VS4 1.18 TEH TEC 0.61 CBAY2 42 C
105 32 109 54 1.84 120 WAR 25 0.2 P3 VS4 1.18 VS3 TEC 0.61 NYAX2 256 C
10 32 109 74 0.56 108 PCT 15 P2 VS4 0.92 TEC TEH 0.61 CBAY2 41 H
29 32 109 80 0.47 90 PCT 13 P2 VS3
-0.91 TEC TEH 0.61 CBAY2 13 H
280 32 109 84 0.53 85 PCT 15 P2 VS3
-1.07 TEC TEH 0.61 CBAY2 13 H
238 32 109 90 0.41 109 PCT 13 P2 VS3 0.26 TEC TEH 0.61 CBAY2 15 H
198 32 109 102 0.29 112 PCT 10 P2 VS2
-1.1 TEC TEH 0.61 CBAY2 15 H
67
U3R24 PVGS SG32 All Data Page 32 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 109 102 0.35 102 PCT 11 P2 VS4 0.93 TEC TEH 0.61 CBAY2 15 H
67 32 109 128 0.38 118 PCT 12 P2 VS3
-1.07 TEC TEH 0.61 CBAY2 9
H 63 32 109 132 0.32 50 PCT 11 P2 VS2 0.7 TEH TEC 0.61 CBAY2 240 C
236 32 109 166 0.98 130 WAR 19 P16 VS2
-0.84 VS3 TEH 0.61 NYAX2 53 H
15 32 109 166 1.25 117 WAR 21 0.29 P21 VS3
-1.2 VS3 TEH 0.61 NYAX2 53 H
15 32 109 166 0.24 110 PCT 10 P2 VS2
-0.84 TEH TEC 0.61 CBAY2 234 C
275 32 109 166 0.73 109 PCT 21 P2 VS3
-1.2 TEH TEC 0.61 CBAY2 234 C
275 32 109 168 0.36 131 PCT 11 P2 VS3
-1.24 TEH TEC 0.61 CBAY2 236 C
297 32 109 172 1.65 116 WAR 24 0.28 P21 VS3
-1.11 VS3 TEH 0.61 NYAX2 53 H
12 32 109 172 0.86 112 PCT 23 P2 VS3
-1.11 TEH TEC 0.61 CBAY2 234 C
246 32 109 176 0.34 112 PCT 11 P2 BW1
-0.1 TEH TEC 0.61 CBAY2 236 C
254 32 109 176 0.52 89 PCT 15 P2 BW1 1.03 TEH TEC 0.61 CBAY2 236 C
254 32 110 29 0.4 97 PCT 14 P2 VS4
-0.84 TEH TEC 0.61 CBAY2 34 C
129 32 110 47 0.29 112 PCT 10 P2 VS3 0.88 TEH TEC 0.61 CBAY2 44 C
33 32 110 61 0.28 76 PCT 11 P2 VS3 1.11 TEH TEC 0.61 CBAY2 46 C
89 32 110 85 0.38 110 PCT 12 P2 VS3 0.95 TEC TEH 0.61 CBAY2 15 H
245 32 110 91 1.04 102 PCT 22 P2 VS3 0.95 TEC TEH 0.61 CBAY2 13 H
153 32 110 91 2.14 103 WAR 27 0.23 P21 VS3 0.71 VS3 TEH 0.61 NYAX2 55 H
29 32 110 93 0.39 145 PCT 12 P2 VS2 0.76 TEC TEH 0.61 CBAY2 15 H
157 32 110 97 0.31 118 PCT 10 P2 VS2 0.91 TEC TEH 0.61 CBAY2 15 H
114 32 110 123 0.3 147 PCT 10 P2 BW1
-2.4 TEC TEH 0.61 CBAY2 9
H 114 32 110 123 0.33 91 PCT 10 P2 BW1 2.5 TEC TEH 0.61 CBAY2 9
H 114 32 110 153 0.22 150 PCT 9
P2 06H 0.78 TEH TEC 0.61 CBAY2 238 C
132 32 111 26 0.55 111 PCT 17 P2 VS3
-0.99 TEH TEC 0.61 CBAY2 34 C
37 32 111 28 0.92 99 PCT 20 P2 VS3 0.5 TEC TEH 0.61 CBAY2 45 H
25 32 111 28 0.96 294 WAR 19 0.11 P4 VS3 0.32 VS3 TEH 0.61 NYAX2 49 H
53 32 111 32 0.28 118 NQI 3
10H 12.07 TEH TEC 0.61 CBAY2 36 C
179 32 111 32 0.51 123 PCT 15 P2 VS3 0.68 TEH TEC 0.61 CBAY2 36 C
179 32 111 32 NDF P30 10H 12.07 VS3 TEH 0.61 NYAX2 49 H
54 32 111 32 0.96 89 WAR 19 0.29 P5 VS3 0.32 VS3 TEH 0.61 NYAX2 49 H
54 32 111 42 0.26 87 PCT 10 P2 BW2
-0.9 TEH TEC 0.61 CBAY2 38 C
57 32 111 70 0.65 115 PCT 16 P2 VS2
-0.86 TEC TEH 0.61 CBAY2 41 H
74 32 111 70 0.7 111 PCT 17 P2 VS3 0.92 TEC TEH 0.61 CBAY2 41 H
74 32 111 72 0.5 104 PCT 14 P2 VS2
-0.87 TEC TEH 0.61 CBAY2 41 H
31 32 111 96 0.42 119 PCT 13 P2 VS2
-0.83 TEC TEH 0.61 CBAY2 31 H
23 32 111 96 0.22 106 PCT 8
P2 VS4 0.72 TEC TEH 0.61 CBAY2 31 H
23 32 111 98 0.32 139 PCT 11 P2 VS2
-0.82 TEC TEH 0.61 CBAY2 15 H
112 32 111 106 0.18 87 PCT 7
P2 VS2
-0.96 TEC TEH 0.61 CBAY2 15 H
27 32 111 112 0.3 112 PCT 10 P2 BW2
-1.99 TEC TEH 0.61 CBAY2 19 H
235 32 111 138 0.32 111 PCT 11 P2 10H 0.76 TEH TEC 0.61 CBAY2 238 C
232 32 111 174 0.37 113 PCT 13 P2 10H 0.68 TEH TEC 0.61 CBAY2 234 C
244 32 112 33 0.3 131 PCT 11 P2 VS2
-0.92 TEH TEC 0.61 CBAY2 34 C
181
U3R24 PVGS SG32 All Data Page 33 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 112 33 0.29 147 PCT 11 P2 VS4
-0.68 TEH TEC 0.61 CBAY2 34 C
181 32 112 43 0.39 119 PCT 14 P2 BW1
-2 TEH TEC 0.61 CBAY2 38 C
83 32 112 51 0.35 28 PCT 12 P2 VS1
-1 TEH TEC 0.61 CBAY2 42 C
102 32 112 61 0.36 92 PCT 12 P2 VS2
-0.96 TEH TEC 0.61 CBAY2 48 C
89 32 112 77 0.36 97 PCT 11 P2 VS3 1.01 TEC TEH 0.61 CBAY2 7
H 110 32 112 95 0.6 124 PCT 16 P2 VS2 0.72 TEC TEH 0.61 CBAY2 29 H
34 32 112 109 0.44 113 PCT 13 P2 VS4
-0.91 TEC TEH 0.61 CBAY2 11 H
306 32 112 115 0.25 136 PCT 8
P2 VS4
-0.99 TEC TEH 0.61 CBAY2 19 H
234 32 112 131 0.28 38 PCT 10 P2 VS4
-0.83 TEH TEC 0.61 CBAY2 240 C
250 32 112 155 0.29 36 PCT 10 P2 VS2 0.75 TEH TEC 0.61 CBAY2 240 C
101 32 112 157 0.28 97 PCT 11 P2 VS2 0.9 TEH TEC 0.61 CBAY2 238 C
114 32 113 26 2.05 182 DNT P1 BW1 1.03 TEC TEH 0.61 CBAY2 45 H
29 32 113 26 0.43 66 PCT 12 P2 VS3
-1.14 TEC TEH 0.61 CBAY2 45 H
29 32 113 26 0.64 111 PCT 16 P2 VS3 0.45 TEC TEH 0.61 CBAY2 45 H
29 32 113 26 NDF P27 BW1 1.03 VS3 TEH 0.61 NYAX2 51 H
6 32 113 26 1.29 106 WAR 22 P5 VS3
-1.14 VS3 TEH 0.61 NYAX2 51 H
6 32 113 26 0.81 68 WAR 17 P29 VS3 0.45 VS3 TEH 0.61 NYAX2 51 H
6 32 113 28 0.51 101 PCT 14 P2 VS3 0.35 TEC TEH 0.61 CBAY2 45 H
26 32 113 34 0.4 126 PCT 13 P2 VS4 0.86 TEH TEC 0.61 CBAY2 34 C
192 32 113 38 0.32 104 PCT 11 P2 VS3
-1.05 TEH TEC 0.61 CBAY2 40 C
108 32 113 46 0.37 38 PCT 13 P2 VS1
-0.69 TEH TEC 0.61 CBAY2 46 C
169 32 113 90 0.7 102 PCT 17 P2 VS4 0.83 TEC TEH 0.61 CBAY2 29 H
95 32 113 92 0.3 43 PCT 10 P2 VS2
-0.95 TEC TEH 0.61 CBAY2 31 H
84 32 113 92 0.93 105 PCT 22 P2 VS4
-0.74 TEC TEH 0.61 CBAY2 31 H
84 32 113 92 1.8 106 WAR 25 0.37 P27 VS4
-0.78 VS3 TEC 0.61 NYAX2 254 C
47 32 113 114 0.45 129 PCT 13 P2 VS2 0.69 TEC TEH 0.61 CBAY2 17 H
223 32 113 130 0.33 129 PCT 10 P2 VS4 0.81 TEC TEH 0.61 CBAY2 17 H
5 32 113 140 0.51 98 PCT 15 P2 BW1 0.89 TEH TEC 0.61 CBAY2 240 C
174 32 113 140 0.23 26 PCT 8
P2 VS2
-0.78 TEH TEC 0.61 CBAY2 240 C
174 32 113 144 0.21 116 PCT 9
P2 06H 0.9 TEH TEC 0.61 CBAY2 238 C
185 32 113 156 0.27 60 PCT 11 P2 BW1 0.85 TEH TEC 0.61 CBAY2 238 C
116 32 113 164 0.29 138 PCT 10 P2 VS3
-1.03 TEH TEC 0.61 CBAY2 240 C
58 32 113 166 0.49 97 PCT 15 P2 BW1 0.44 TEH TEC 0.61 CBAY2 240 C
32 32 113 166 0.3 36 PCT 10 P2 VS2
-0.87 TEH TEC 0.61 CBAY2 240 C
32 32 113 168 0.29 135 PCT 11 P2 VS3
-1.09 TEH TEC 0.61 CBAY2 234 C
291 32 113 178 2.18 109 WAR 27 0.26 P21 VS3
-1.11 VS3 TEH 0.61 NYAX2 53 H
10 32 113 178 0.34 139 PCT 11 P2 10H 0.68 TEH TEC 0.61 CBAY2 234 C
240 32 113 178 0.93 122 PCT 24 P2 VS3
-1.19 TEH TEC 0.61 CBAY2 234 C
240 32 114 27 0.56 51 PCT 15 P2 VS3
-1.11 TEC TEH 0.61 CBAY2 45 H
28 32 114 31 0.2 121 PCT 8
P2 VS3 0.88 TEH TEC 0.61 CBAY2 34 C
183 32 114 33 0.18 138 PCT 7
P2 10H
-0.3 TEH TEC 0.61 CBAY2 34 C
191 32 114 51 0.19 113 PCT 7
P2 VS4
-0.71 TEH TEC 0.61 CBAY2 48 C
45
U3R24 PVGS SG32 All Data Page 34 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 114 65 0.31 86 PCT 10 P2 05H 0.73 TEC TEH 0.61 CBAY2 41 H
201 32 114 71 0.28 101 PCT 9
P2 VS2
-0.96 TEC TEH 0.61 CBAY2 41 H
81 32 114 83 0.47 134 PCT 14 P2 VS4 0.64 TEC TEH 0.61 CBAY2 33 H
64 32 114 85 0.46 141 PCT 13 P2 VS3 0.84 TEC TEH 0.61 CBAY2 35 H
38 32 114 89 0.27 75 PCT 9
P2 VS2 0.71 TEC TEH 0.61 CBAY2 31 H
141 32 114 95 0.29 135 PCT 9
P2 VS4
-0.71 TEC TEH 0.61 CBAY2 29 H
33 32 114 99 0.43 124 PCT 13 P2 VS4
-0.76 TEC TEH 0.61 CBAY2 27 H
107 32 114 113 0.43 124 PCT 12 P2 VS2 0.69 TEC TEH 0.61 CBAY2 17 H
280 32 114 133 0.25 70 PCT 10 P2 VS2 0.78 TEH TEC 0.61 CBAY2 238 C
285 32 114 139 0.29 43 PCT 10 P2 VS2 0.76 TEH TEC 0.61 CBAY2 240 C
192 32 114 165 0.29 68 PCT 10 P2 BW1
-0.88 TEH TEC 0.61 CBAY2 240 C
59 32 114 175 1.49 102 PCT 28 P2 VS4
-0.72 TEH TEC 0.61 CBAY2 236 C
288 32 114 175 2.78 110 WAR 30 0.37 P11 VS4
-0.82 VS3 TEC 0.61 NYAX2 258 C
33 32 114 177 0.37 131 PCT 12 P2 10H
-0.3 TEH TEC 0.61 CBAY2 234 C
241 32 114 177 0.31 106 PCT 12 P2 10H 0.72 TEH TEC 0.61 CBAY2 234 C
241 32 114 177 0.3 143 PCT 11 P2 VS3
-0.79 TEH TEC 0.61 CBAY2 234 C
241 32 115 30 0.36 138 PCT 13 P2 VS3 0.79 TEH TEC 0.61 CBAY2 34 C
185 32 115 88 0.17 36 PCT 7
P2 VS1
-0.91 TEC TEH 0.61 CBAY2 31 H
144 32 115 126 0.67 123 PCT 17 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 17 H
59 32 115 128 0.32 134 PCT 10 P2 VS2 0.77 TEC TEH 0.61 CBAY2 19 H
7 32 115 130 0.31 120 PCT 9
P2 VS2 0.75 TEC TEH 0.61 CBAY2 17 H
6 32 115 134 0.27 102 PCT 10 P2 VS4
-0.8 TEH TEC 0.61 CBAY2 238 C
264 32 115 140 0.43 35 PCT 13 P2 BW1 0.99 TEH TEC 0.61 CBAY2 240 C
173 32 115 148 0.22 25 PCT 9
P2 BW1 0.57 TEH TEC 0.61 CBAY2 238 C
163 32 116 35 0.34 84 PCT 11 P2 BW1 0.93 TEH TEC 0.61 CBAY2 40 C
105 32 116 41 0.27 118 PCT 10 P2 VS2 0.83 TEH TEC 0.61 CBAY2 44 C
39 32 116 43 0.23 45 PCT 8
P2 VS2 0.98 TEH TEC 0.61 CBAY2 48 C
118 32 116 45 0.37 114 PCT 13 P2 VS1
-0.84 TEH TEC 0.61 CBAY2 42 C
70 32 116 77 0.38 73 PCT 11 P2 VS2 0.84 TEC TEH 0.61 CBAY2 35 H
149 32 116 81 0.49 128 PCT 13 P2 VS2 0.84 TEC TEH 0.61 CBAY2 35 H
95 32 116 81 0.54 132 PCT 14 P2 VS3 0.82 TEC TEH 0.61 CBAY2 35 H
95 32 116 83 0.42 71 PCT 13 P2 VS3 0.72 TEC TEH 0.61 CBAY2 33 H
63 32 116 83 0.44 122 PCT 13 P2 VS4 0.71 TEC TEH 0.61 CBAY2 33 H
63 32 116 89 0.22 75 PCT 8
P2 VS4 0.83 TEC TEH 0.61 CBAY2 31 H
140 32 116 95 0.41 118 PCT 12 P2 VS2 0.68 TEC TEH 0.61 CBAY2 29 H
32 32 116 103 0.22 86 PCT 8
P2 VS4
-0.92 TEC TEH 0.61 CBAY2 23 H
101 32 116 107 0.16 147 PCT 6
P2 VS2 0.68 TEC TEH 0.61 CBAY2 23 H
39 32 116 113 0.39 107 PCT 11 P2 VS2 0.72 TEC TEH 0.61 CBAY2 17 H
279 32 116 117 0.8 97 PCT 18 P2 VS2 0.8 TEC TEH 0.61 CBAY2 17 H
221 32 116 117 1.81 105 WAR 25 0.6 P15 VS2 0.86 VS3 TEH 0.61 NYAX2 55 H
22 32 116 133 0.2 89 PCT 8
P2 VS2 0.92 TEH TEC 0.61 CBAY2 238 C
286 32 116 141 0.34 94 PCT 12 P2 VS2 0.9 TEH TEC 0.61 CBAY2 238 C
218
U3R24 PVGS SG32 All Data Page 35 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 116 151 0.31 94 PCT 11 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 240 C
116 32 116 165 0.25 52 PCT 10 P2 VS2 0.83 TEH TEC 0.61 CBAY2 238 C
37 32 116 165 0.41 110 PCT 14 P2 VS4
-0.76 TEH TEC 0.61 CBAY2 238 C
37 32 117 32 0.47 116 PCT 14 P2 VS3
-1.28 TEH TEC 0.61 CBAY2 40 C
101 32 117 34 0.29 94 PCT 10 P2 VS3
-1.2 TEH TEC 0.61 CBAY2 40 C
104 32 117 40 0.21 127 PCT 8
P2 VS3
-1.04 TEH TEC 0.61 CBAY2 44 C
40 32 117 42 0.33 93 PCT 12 P2 VS3
-1.24 TEH TEC 0.61 CBAY2 46 C
161 32 117 56 1.19 109 PCT 27 P2 VS2
-0.85 TEH TEC 0.61 CBAY2 46 C
175 32 117 56 0.34 102 PCT 12 P2 VS3
-1.08 TEH TEC 0.61 CBAY2 46 C
175 32 117 56 2.7 105 WAR 30 0.27 P32 VS2
-0.85 VS3 TEH 0.61 NYAX2 51 H
5 32 117 56 0.9 144 WAR 18 P21 VS3
-1.08 VS3 TEH 0.61 NYAX2 51 H
5 32 117 62 0.44 100 PCT 12 P2 VS3
-1.18 TEC TEH 0.61 CBAY2 41 H
204 32 117 66 0.28 132 PCT 9
P2 VS2
-1.18 TEC TEH 0.61 CBAY2 41 H
37 32 117 68 0.38 138 PCT 11 P2 VS2
-1.1 TEC TEH 0.61 CBAY2 41 H
84 32 117 76 1.25 120 PCT 24 P2 VS3
-1.15 TEC TEH 0.61 CBAY2 35 H
153 32 117 76 3.11 100 WAR 32 0.26 P21 VS3
-1.15 VS3 TEH 0.61 NYAX2 51 H
12 32 117 78 0.29 85 PCT 10 P2 VS1
-0.94 TEC TEH 0.61 CBAY2 33 H
123 32 117 78 0.34 151 PCT 11 P2 VS4
-0.8 TEC TEH 0.61 CBAY2 33 H
123 32 117 84 0.28 125 PCT 9
P2 BW1 0.77 TEC TEH 0.61 CBAY2 35 H
42 32 117 84 0.37 119 PCT 11 P2 VS3
-1.22 TEC TEH 0.61 CBAY2 35 H
42 32 117 90 0.86 114 PCT 20 P2 VS3
-1.14 TEC TEH 0.61 CBAY2 29 H
97 32 117 90 2.1 101 WAR 27 0.26 P21 VS3
-1.14 VS3 TEH 0.61 NYAX2 51 H
19 32 117 92 0.27 39 PCT 9
P2 VS1
-0.87 TEC TEH 0.61 CBAY2 31 H
86 32 117 106 0.33 114 PCT 10 P2 VS2
-1.13 TEC TEH 0.61 CBAY2 21 H
42 32 117 108 0.36 104 PCT 11 P2 VS4
-1.09 TEC TEH 0.61 CBAY2 19 H
298 32 117 118 0.24 121 PCT 8
P2 VS4
-0.98 TEC TEH 0.61 CBAY2 17 H
170 32 117 128 0.31 138 PCT 10 P2 BW2 0.92 TEC TEH 0.61 CBAY2 19 H
8 32 117 136 0.57 110 PCT 16 P2 VS2
-0.7 TEH TEC 0.61 CBAY2 240 C
202 32 117 140 0.41 25 PCT 13 P2 BW1 0.85 TEH TEC 0.61 CBAY2 240 C
172 32 117 148 0.39 66 PCT 14 P2 BW1 0.55 TEH TEC 0.61 CBAY2 238 C
164 32 117 158 0.58 43 PCT 16 P2 BW1 0.88 TEH TEC 0.61 CBAY2 240 C
89 32 117 158 0.59 92 PCT 17 P2 VS3
-0.85 TEH TEC 0.61 CBAY2 240 C
89 32 117 160 1.57 117 WAR 24 0.23 P13 VS3
-0.74 VS3 TEH 0.61 NYAX2 53 H
16 32 117 160 0.72 115 PCT 20 P2 VS3
-0.74 TEH TEC 0.61 CBAY2 238 C
100 32 118 31 0.55 106 PCT 16 P2 VS3
-0.84 TEH TEC 0.61 CBAY2 40 C
102 32 118 35 0.32 116 PCT 12 P2 BW1 0.87 TEH TEC 0.61 CBAY2 38 C
64 32 118 35 0.37 110 PCT 13 P2 VS3 0.88 TEH TEC 0.61 CBAY2 38 C
64 32 118 53 0.27 99 PCT 9
P2 VS2
-0.77 TEH TEC 0.61 CBAY2 48 C
125 32 118 55 0.53 120 PCT 15 P2 VS2
-0.75 TEH TEC 0.61 CBAY2 48 C
127 32 118 55 0.45 101 PCT 14 P2 VS3 1
TEH TEC 0.61 CBAY2 48 C
127 32 118 59 0.35 125 PCT 12 P2 VS3
-0.59 TEH TEC 0.61 CBAY2 46 C
178 32 118 61 0.73 87 PCT 18 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 41 H
205
U3R24 PVGS SG32 All Data Page 36 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 118 63 0.37 92 PCT 11 P2 BW1 0.85 TEC TEH 0.61 CBAY2 41 H
67 32 118 79 0.4 105 PCT 12 P2 VS3
-0.34 TEC TEH 0.61 CBAY2 33 H
118 32 118 81 0.4 140 PCT 11 P2 VS3
-0.75 TEC TEH 0.61 CBAY2 35 H
94 32 118 83 0.29 106 PCT 10 P2 VS3 0.83 TEC TEH 0.61 CBAY2 33 H
62 32 118 85 0.52 120 PCT 14 P2 VS2
-0.32 TEC TEH 0.61 CBAY2 35 H
36 32 118 89 0.35 80 PCT 11 P2 VS2
-0.31 TEC TEH 0.61 CBAY2 31 H
139 32 118 91 0.34 139 PCT 10 P2 VS3 0.7 TEC TEH 0.61 CBAY2 29 H
91 32 118 91 0.22 61 PCT 7
P2 VS4
-0.79 TEC TEH 0.61 CBAY2 29 H
91 32 118 93 0.55 86 PCT 16 P2 VS2 0.89 TEC TEH 0.61 CBAY2 31 H
80 32 118 93 0.41 127 PCT 13 P2 VS3 0.61 TEC TEH 0.61 CBAY2 31 H
80 32 118 93 0.7 106 PCT 18 P2 VS3 0.91 TEC TEH 0.61 CBAY2 31 H
80 32 118 95 1.6 115 PCT 28 P2 VS3
-1.08 TEC TEH 0.61 CBAY2 29 H
31 32 118 95 0.42 117 PCT 12 P2 VS3 0.62 TEC TEH 0.61 CBAY2 29 H
31 32 118 95 0.45 127 PCT 13 P2 VS4
-0.84 TEC TEH 0.61 CBAY2 29 H
31 32 118 95 2.25 107 WAR 28 0.26 P12 VS3
-0.49 VS3 TEH 0.61 NYAX2 55 H
30 32 118 99 0.27 145 PCT 9
P2 VS2 0.79 TEC TEH 0.61 CBAY2 27 H
105 32 118 123 0.77 126 PCT 19 P2 VS1 0.82 TEC TEH 0.61 CBAY2 19 H
112 32 118 123 0.16 46 PCT 6
P2 VS2 0.72 TEC TEH 0.61 CBAY2 19 H
112 32 118 123 1.39 108 WAR 22 0.23 P15 VS1 1.05 VS3 TEH 0.61 NYAX2 55 H
23 32 118 123 0.59 114 WAR 15 P14 VS2 0.94 VS3 TEH 0.61 NYAX2 55 H
23 32 118 141 0.49 114 PCT 16 P2 VS3
-0.86 TEH TEC 0.61 CBAY2 238 C
219 32 118 145 0.24 52 PCT 10 P2 VS3
-0.75 TEH TEC 0.61 CBAY2 238 C
174 32 118 147 0.28 77 PCT 10 P2 VS3
-0.72 TEH TEC 0.61 CBAY2 240 C
135 32 118 151 0.43 147 PCT 13 P2 BW1 0.8 TEH TEC 0.61 CBAY2 240 C
115 32 118 157 0.37 117 PCT 13 P2 VS3
-0.76 TEH TEC 0.61 CBAY2 238 C
111 32 118 163 0.32 141 PCT 11 P2 VS3
-0.9 TEH TEC 0.61 CBAY2 240 C
75 32 118 163 0.37 130 PCT 12 P2 VS3
-0.41 TEH TEC 0.61 CBAY2 240 C
75 32 118 171 0.27 104 PCT 9
P2 10H
-0.83 TEH TEC 0.61 CBAY2 240 C
37 32 118 175 0.24 142 PCT 10 P2 VS4
-0.75 TEH TEC 0.61 CBAY2 234 C
284 32 119 30 0.31 124 PCT 10 P2 10H 0.8 TEH TEC 0.61 CBAY2 38 C
70 32 119 36 0.42 138 PCT 14 P2 BW1 0.47 TEH TEC 0.61 CBAY2 38 C
76 32 119 44 0.38 22 PCT 13 P2 BW1 0.75 TEH TEC 0.61 CBAY2 42 C
95 32 119 86 0.27 57 PCT 9
P2 VS1
-0.88 TEC TEH 0.61 CBAY2 29 H
153 32 119 94 0.38 121 PCT 11 P2 VS4
-0.85 TEC TEH 0.61 CBAY2 29 H
38 32 119 104 0.38 113 PCT 12 P2 VS2 0.81 TEC TEH 0.61 CBAY2 23 H
46 32 119 106 0.32 100 PCT 10 P2 BW1 0.75 TEC TEH 0.61 CBAY2 21 H
43 32 119 106 0.36 143 PCT 11 P2 VS2 0.77 TEC TEH 0.61 CBAY2 21 H
43 32 119 106 0.4 147 PCT 12 P2 VS4
-0.8 TEC TEH 0.61 CBAY2 21 H
43 32 119 112 0.29 133 PCT 10 P2 VS2 0.76 TEC TEH 0.61 CBAY2 19 H
239 32 119 114 0.32 92 PCT 10 P2 VS2 0.87 TEC TEH 0.61 CBAY2 17 H
226 32 119 136 0.28 29 PCT 10 P2 VS3
-0.83 TEH TEC 0.61 CBAY2 240 C
201 32 119 142 0.31 54 PCT 12 P2 VS3
-0.8 TEH TEC 0.61 CBAY2 238 C
196
U3R24 PVGS SG32 All Data Page 37 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 119 156 0.2 119 PCT 8
P2 06H
-0.73 TEH TEC 0.61 CBAY2 238 C
119 32 119 158 0.29 50 PCT 10 P2 BW1 0.88 TEH TEC 0.61 CBAY2 240 C
90 32 119 170 0.4 136 PCT 13 P2 10H 0.75 TEH TEC 0.61 CBAY2 240 C
65 32 119 174 0.41 122 PCT 14 P2 VS3
-1.18 TEH TEC 0.61 CBAY2 234 C
285 32 120 33 0.39 77 PCT 14 P2 VS2 0.91 TEH TEC 0.61 CBAY2 38 C
66 32 120 41 0.33 37 PCT 12 P2 VS3
-0.7 TEH TEC 0.61 CBAY2 42 C
74 32 120 45 1.36 98 PCT 25 P2 VS3 0.78 TEC TEH 0.61 CBAY2 41 H
239 32 120 45 3.21 95 WAR 32 0.45 P21 VS3 0.76 VS3 TEH 0.61 NYAX2 49 H
46 32 120 49 0.3 108 PCT 11 P2 VS3 1.02 TEH TEC 0.61 CBAY2 46 C
68 32 120 53 0.65 104 PCT 19 P2 VS2
-0.76 TEH TEC 0.61 CBAY2 46 C
171 32 120 53 0.44 82 PCT 15 P2 VS3 1.15 TEH TEC 0.61 CBAY2 46 C
171 32 120 55 0.33 107 PCT 11 P2 VS3
-0.7 TEH TEC 0.61 CBAY2 48 C
123 32 120 57 0.66 110 PCT 18 P2 VS2
-0.91 TEH TEC 0.61 CBAY2 48 C
129 32 120 57 0.32 124 PCT 10 P2 VS3 1
TEH TEC 0.61 CBAY2 48 C
129 32 120 59 0.32 54 PCT 10 P2 VS4 0.78 TEC TEH 0.61 CBAY2 41 H
207 32 120 71 0.14 118 PCT 5
P2 VS3 0.88 TEC TEH 0.61 CBAY2 41 H
132 32 120 75 0.89 121 PCT 21 P2 VS2
-0.84 TEC TEH 0.61 CBAY2 33 H
170 32 120 75 1.6 119 WAR 24 0.32 P16 VS2
-0.88 VS3 TEH 0.61 NYAX2 51 H
14 32 120 77 0.36 143 PCT 11 P2 VS2
-0.85 TEC TEH 0.61 CBAY2 35 H
148 32 120 77 0.46 125 PCT 13 P2 VS3 0.78 TEC TEH 0.61 CBAY2 35 H
148 32 120 83 0.3 120 PCT 10 P2 BW1
-0.92 TEC TEH 0.61 CBAY2 33 H
61 32 120 85 0.99 130 PCT 21 P2 VS2 0.76 TEC TEH 0.61 CBAY2 35 H
35 32 120 85 0.44 119 PCT 12 P2 VS4
-0.87 TEC TEH 0.61 CBAY2 35 H
35 32 120 85 0.75 120 PCT 18 P2 VS4 0.69 TEC TEH 0.61 CBAY2 35 H
35 32 120 85 1.93 114 WAR 26 0.36 P16 VS2 0.71 VS3 TEH 0.61 NYAX2 51 H
16 32 120 87 0.58 106 PCT 15 P2 VS3 0.84 TEC TEH 0.61 CBAY2 29 H
146 32 120 89 0.26 62 PCT 9
P2 VS2 0.79 TEC TEH 0.61 CBAY2 31 H
138 32 120 89 0.73 91 PCT 19 P2 VS3 0.81 TEC TEH 0.61 CBAY2 31 H
138 32 120 95 0.53 160 PCT 14 P2 VS1 0.82 TEC TEH 0.61 CBAY2 35 H
26 32 120 95 0.32 111 PCT 10 P2 VS2 0.82 TEC TEH 0.61 CBAY2 35 H
26 32 120 95 1.85 118 PCT 30 P2 VS3
-0.9 TEC TEH 0.61 CBAY2 35 H
26 32 120 95 1.27 117 PCT 24 P2 VS3 0.89 TEC TEH 0.61 CBAY2 35 H
26 32 120 95 0.45 140 PCT 13 P2 VS4 0.68 TEC TEH 0.61 CBAY2 35 H
26 32 120 95 PID P2 VS3
-0.9 TEH TEC 0.61 CBAY2 54 C
26 32 120 95 3.71 105 WAR 34 0.48 P13 VS3
-0.52 VS3 TEH 0.61 NYAX2 55 H
31 32 120 95 2.06 95 WAR 27 0.26 P20 VS3 0.67 VS3 TEH 0.61 NYAX2 55 H
31 32 120 99 0.2 29 PCT 7
P2 BW1
-0.9 TEC TEH 0.61 CBAY2 27 H
104 32 120 105 0.39 125 PCT 11 P2 VS4
-0.87 TEC TEH 0.61 CBAY2 21 H
96 32 120 115 0.46 118 PCT 13 P2 VS1 0.77 TEC TEH 0.61 CBAY2 19 H
230 32 120 117 0.4 111 PCT 12 P2 VS2 0.85 TEC TEH 0.61 CBAY2 17 H
219 32 120 125 0.5 72 PCT 14 P2 VS2 0.87 TEC TEH 0.61 CBAY2 17 H
108 32 120 127 0.39 117 PCT 12 P2 VS3 0.56 TEC TEH 0.61 CBAY2 19 H
54
U3R24 PVGS SG32 All Data Page 38 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 120 165 0.42 146 PCT 10 P2 10H 0.74 TEH TEC 0.61 CBAY2 238 C
83 32 121 34 0.27 83 PCT 11 P2 VS1 0.84 TEH TEC 0.61 CBAY2 38 C
74 32 121 46 1.15 119 PCT 23 P2 VS2
-0.99 TEC TEH 0.61 CBAY2 45 H
16 32 121 46 2.31 291 WAR 28 0.17 P32 VS2
-0.79 VS3 TEH 0.61 NYAX2 49 H
47 32 121 76 0.45 119 PCT 13 P2 VS2
-0.83 TEC TEH 0.61 CBAY2 35 H
155 32 121 76 0.97 133 PCT 21 P2 VS3
-0.88 TEC TEH 0.61 CBAY2 35 H
155 32 121 76 1
110 WAR 19 P24 VS2
-0.84 VS3 TEH 0.61 NYAX2 51 H
13 32 121 76 2.21 108 WAR 27 0.2 P20 VS3
-0.88 VS3 TEH 0.61 NYAX2 51 H
13 32 121 78 0.35 100 PCT 11 P2 VS3
-1.04 TEC TEH 0.61 CBAY2 33 H
125 32 121 84 0.25 141 PCT 8
P2 VS2
-0.88 TEC TEH 0.61 CBAY2 35 H
44 32 121 94 NDF P13 TSC 0.93 01C TEC 0.61 NYAX2 254 C
48 32 121 106 0.44 121 PCT 12 P2 VS3
-1.02 TEC TEH 0.61 CBAY2 21 H
44 32 121 108 0.35 121 PCT 11 P2 VS2 0.76 TEC TEH 0.61 CBAY2 19 H
300 32 121 108 0.34 94 PCT 11 P2 VS3 0.89 TEC TEH 0.61 CBAY2 19 H
300 32 121 112 0.68 103 PCT 17 P2 VS2 0.71 TEC TEH 0.61 CBAY2 19 H
240 32 121 118 0.42 153 PCT 10 P2 10H
-0.96 TEC TEH 0.61 CBAY2 17 H
172 32 121 122 0.34 120 PCT 10 P2 VS2 0.67 TEC TEH 0.61 CBAY2 17 H
116 32 121 126 0.27 81 PCT 9
P2 VS3
-0.96 TEC TEH 0.61 CBAY2 17 H
62 32 121 132 0.42 41 PCT 13 P2 BW1 0.92 TEH TEC 0.61 CBAY2 240 C
230 32 121 140 0.57 27 PCT 14 P2 06H 0.75 TEH TEC 0.61 CBAY2 240 C
170 32 122 43 0.46 138 PCT 13 P2 VS3 0.68 TEC TEH 0.61 CBAY2 41 H
237 32 122 81 NDF P13 TEH 23.23 01H TEH 0.61 NYAX2 51 H
15 32 122 107 0.17 25 PCT 6
P2 VS1 0.59 TEC TEH 0.61 CBAY2 23 H
36 32 122 173 0.25 123 PCT 10 P2 VS3
-0.72 TEH TEC 0.61 CBAY2 238 C
69 32 123 32 0.43 123 PCT 14 P2 VS3 0.41 TEH TEC 0.61 CBAY2 38 C
72 32 123 38 0.19 143 PCT 8
P2 10H 0.75 TEH TEC 0.61 CBAY2 42 C
77 32 123 40 0.33 28 PCT 12 P2 BW1 0.82 TEH TEC 0.61 CBAY2 42 C
91 32 123 60 0.39 121 PCT 11 P2 VS2 0.61 TEC TEH 0.61 CBAY2 41 H
43 32 123 84 0.75 150 PCT 11 P2 10H 0.84 TEC TEH 0.61 CBAY2 35 H
45 32 123 172 0.3 137 PCT 11 P2 VS3
-1.17 TEH TEC 0.61 CBAY2 238 C
44 32 124 37 0.52 151 PCT 10 P2 10H 0.67 TEH TEC 0.61 CBAY2 42 C
78 32 124 51 0.36 60 PCT 11 P2 VS3 0.89 TEH TEC 0.61 CBAY2 48 C
115 32 124 53 0.53 24 PCT 11 P2 05H 0.88 TEC TEH 0.61 CBAY2 41 H
229 32 124 67 0.26 124 PCT 8
P2 VS1 0.69 TEC TEH 0.61 CBAY2 41 H
128 32 124 71 0.21 146 PCT 7
P2 VS1 1.27 TEC TEH 0.61 CBAY2 41 H
158 32 124 73 0.54 95 PCT 14 P2 VS3 0.81 TEC TEH 0.61 CBAY2 41 H
161 32 124 81 0.3 124 PCT 9
P2 VS1
-0.84 TEC TEH 0.61 CBAY2 35 H
91 32 124 81 0.33 150 PCT 10 P2 VS1 0.77 TEC TEH 0.61 CBAY2 35 H
91 32 124 85 0.38 94 PCT 11 P2 VS3 0.92 TEC TEH 0.61 CBAY2 35 H
33 32 124 87 0.36 47 PCT 11 P2 VS3 0.96 TEC TEH 0.61 CBAY2 29 H
145 32 124 89 0.4 104 PCT 13 P2 VS3 0.89 TEC TEH 0.61 CBAY2 31 H
136 32 124 107 0.19 72 PCT 7
P2 VS2 0.61 TEC TEH 0.61 CBAY2 23 H
35
U3R24 PVGS SG32 All Data Page 39 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 124 123 0.4 66 PCT 12 P2 VS2 0.89 TEC TEH 0.61 CBAY2 19 H
109 32 124 127 0.45 143 PCT 13 P2 VS1 0.71 TEC TEH 0.61 CBAY2 19 H
52 32 125 40 0.57 105 PCT 15 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 41 H
234 32 125 42 0.58 148 PCT 15 P2 VS4 0.76 TEC TEH 0.61 CBAY2 45 H
20 32 125 42 0.62 143 PCT 16 P2 VS5 0.75 TEC TEH 0.61 CBAY2 45 H
20 32 125 52 0.37 84 PCT 11 P2 VS2
-0.92 TEC TEH 0.61 CBAY2 41 H
228 32 125 70 0.33 101 PCT 10 P2 VS3
-0.94 TEC TEH 0.61 CBAY2 41 H
157 32 125 70 0.4 65 PCT 12 P2 VS4
-1 TEC TEH 0.61 CBAY2 41 H
157 32 125 74 0.21 147 PCT 8
P2 VS1
-0.85 TEC TEH 0.61 CBAY2 33 H
180 32 125 74 0.29 119 PCT 10 P2 VS2
-0.91 TEC TEH 0.61 CBAY2 33 H
180 32 125 82 0.41 142 PCT 13 P2 VS3
-0.8 TEC TEH 0.61 CBAY2 33 H
72 32 125 88 0.29 40 PCT 10 P2 VS1 0.82 TEC TEH 0.61 CBAY2 31 H
149 32 125 118 0.36 153 PCT 11 P2 VS1 0.65 TEC TEH 0.61 CBAY2 17 H
174 32 125 126 0.31 147 PCT 10 P2 VS1 0.62 TEC TEH 0.61 CBAY2 17 H
64 32 125 132 0.42 42 PCT 13 P2 VS1 0.8 TEH TEC 0.61 CBAY2 240 C
228 32 125 148 0.31 37 PCT 11 P2 BW1 0.88 TEH TEC 0.61 CBAY2 238 C
168 32 125 150 0.33 27 PCT 11 P2 BW1 1.03 TEH TEC 0.61 CBAY2 240 C
132 32 125 160 0.2 138 PCT 8
P2 06H 0.78 TEH TEC 0.61 CBAY2 238 C
105 32 126 37 0.37 94 PCT 13 P2 VS4
-1.1 TEH TEC 0.61 CBAY2 42 C
88 32 126 41 0.57 134 PCT 15 P2 VS3 0.97 TEC TEH 0.61 CBAY2 41 H
232 32 126 41 0.44 111 PCT 12 P2 VS4
-1.07 TEC TEH 0.61 CBAY2 41 H
232 32 126 43 0.26 126 PCT 8
P2 VS1 0.3 TEC TEH 0.61 CBAY2 41 H
244 32 126 47 0.33 98 PCT 11 P2 VS1 0.36 TEH TEC 0.61 CBAY2 48 C
113 32 126 47 0.32 103 PCT 11 P2 VS3 1.06 TEH TEC 0.61 CBAY2 48 C
113 32 126 47 0.61 108 PCT 17 P2 VS4
-0.93 TEH TEC 0.61 CBAY2 48 C
113 32 126 47 1.67 98 WAR 24 0.46 P11 VS4
-0.92 VS3 TEC 0.61 NYAX2 256 C
11 32 126 51 0.48 115 PCT 13 P2 VS1 0.38 TEC TEH 0.61 CBAY2 41 H
227 32 126 53 0.46 84 PCT 13 P2 VS3 0.95 TEC TEH 0.61 CBAY2 41 H
211 32 126 77 0.69 132 PCT 17 P2 VS3 1.08 TEC TEH 0.61 CBAY2 35 H
145 32 126 85 NDF P4 TEH 24.36 01H TEH 0.61 NYAX2 51 H
17 32 126 105 0.59 135 PCT 15 P2 VS2 0.74 TEC TEH 0.61 CBAY2 21 H
93 32 126 107 0.53 72 PCT 15 P2 VS1
-1.01 TEC TEH 0.61 CBAY2 23 H
34 32 126 109 0.46 60 PCT 13 P2 VS1 0.82 TEC TEH 0.61 CBAY2 21 H
33 32 126 131 0.33 136 PCT 10 P2 VS1 0.77 TEC TEH 0.61 CBAY2 43 H
21 32 126 149 0.21 35 PCT 9
P2 BW1 0.91 TEH TEC 0.61 CBAY2 238 C
145 32 127 38 0.33 155 PCT 10 P2 10H 0.67 TEC TEH 0.61 CBAY2 45 H
23 32 127 38 0.41 50 PCT 12 P2 VS3 0.2 TEC TEH 0.61 CBAY2 45 H
23 32 127 46 0.41 111 PCT 13 P2 VS1
-0.8 TEH TEC 0.61 CBAY2 48 C
109 32 127 48 0.31 111 PCT 10 P2 VS2
-0.99 TEH TEC 0.61 CBAY2 48 C
114 32 127 54 0.41 105 PCT 12 P2 VS3
-1.04 TEC TEH 0.61 CBAY2 41 H
58 32 127 56 0.34 122 PCT 10 P2 VS2 0.94 TEC TEH 0.61 CBAY2 41 H
47 32 127 56 0.38 77 PCT 11 P2 BW2
-0.92 TEC TEH 0.61 CBAY2 41 H
47
U3R24 PVGS SG32 All Data Page 40 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 127 62 0.47 134 PCT 13 P2 VS1 0.31 TEC TEH 0.61 CBAY2 41 H
108 32 127 74 0.31 131 PCT 10 P2 VS3 0.23 TEC TEH 0.61 CBAY2 33 H
181 32 127 110 0.24 123 PCT 8
P2 VS2
-0.88 TEC TEH 0.61 CBAY2 17 H
288 32 127 124 0.43 83 PCT 13 P2 VS1 0.61 TEC TEH 0.61 CBAY2 19 H
67 32 127 132 0.4 73 PCT 12 P2 VS1 0.79 TEH TEC 0.61 CBAY2 250 C
48 32 127 134 0.21 139 PCT 9
P2 06H 0.86 TEH TEC 0.61 CBAY2 238 C
258 32 128 35 0.25 162 PCT 10 P2 VS3
-0.98 TEH TEC 0.61 CBAY2 42 C
86 32 128 43 0.32 113 PCT 12 P2 VS2
-0.86 TEH TEC 0.61 CBAY2 46 C
153 32 128 59 0.77 110 PCT 18 P2 VS3 1.04 TEC TEH 0.61 CBAY2 43 H
37 32 128 59 1.29 92 WAR 22 0.18 P21 VS3 1.04 VS3 TEH 0.61 NYAX2 51 H
8 32 128 61 0.3 119 PCT 9
P2 VS1
-0.88 TEC TEH 0.61 CBAY2 41 H
107 32 128 71 0.33 88 PCT 10 P2 VS1
-0.91 TEC TEH 0.61 CBAY2 41 H
176 32 128 87 0.23 119 DSI P6 FDP 0.34 TEC TEH 0.61 CBAY2 29 H
143 32 128 87 NDF P28 FDP 0.34 01C TEC 0.61 NYAX2 254 C
46 32 128 107 0.2 57 PCT 7
P2 VS5 0.89 TEC TEH 0.61 CBAY2 23 H
33 32 128 137 0.33 55 PCT 12 P2 VS2 0.83 TEH TEC 0.61 CBAY2 248 C
115 32 128 137 0.27 45 PCT 10 P2 VS3
-0.88 TEH TEC 0.61 CBAY2 248 C
115 32 128 149 0.27 42 PCT 9
P2 BW1 0.91 TEH TEC 0.61 CBAY2 250 C
64 32 128 151 0.54 98 PCT 17 P2 VS3
-1.06 TEH TEC 0.61 CBAY2 248 C
79 32 128 167 0.73 147 PCT 12 P2 10H 0.72 TEC TEH 0.61 CBAY2 37 H
133 32 128 167 31.99 185 OXP 2
TSC 0.75 TEC TEH 0.61 CBAY2 37 H
133 32 128 167 NDF P3 TSC 0.75 01C TEC 0.61 NYAX2 252 C
14 32 129 36 0.52 121 PCT 16 P2 VS3
-1.18 TEH TEC 0.61 CBAY2 46 C
139 32 129 64 0.36 102 PCT 11 P2 VS1
-0.97 TEC TEH 0.61 CBAY2 41 H
144 32 129 64 0.55 108 PCT 14 P2 VS2
-0.89 TEC TEH 0.61 CBAY2 41 H
144 32 129 64 0.83 100 PCT 19 P2 VS3 0.5 TEC TEH 0.61 CBAY2 41 H
144 32 129 64 1.43 103 PCT 26 P2 VS4
-0.82 TEC TEH 0.61 CBAY2 41 H
144 32 129 64 2.13 107 WAR 27 0.4 P27 VS4
-0.67 VS3 TEC 0.61 NYAX2 254 C
45 32 129 66 0.32 92 PCT 10 P2 VS2
-0.9 TEC TEH 0.61 CBAY2 41 H
153 32 129 74 0.36 126 PCT 11 P2 VS1
-0.87 TEC TEH 0.61 CBAY2 33 H
182 32 129 74 0.18 119 PCT 7
P2 VS3 0.7 TEC TEH 0.61 CBAY2 33 H
182 32 129 78 0.32 140 PCT 11 P2 VS2 0.63 TEC TEH 0.61 CBAY2 33 H
129 32 129 84 0.15 138 PCT 5
P2 VS2 0.76 TEC TEH 0.61 CBAY2 35 H
48 32 129 106 0.34 113 PCT 10 P2 VS2 0.79 TEC TEH 0.61 CBAY2 21 H
48 32 129 110 0.73 134 PCT 18 P2 VS1 0.56 TEC TEH 0.61 CBAY2 17 H
289 32 129 110 2.14 113 WAR 27 0.29 P8 VS1 0.63 VS3 TEH 0.61 NYAX2 55 H
19 32 129 118 0.48 137 PCT 13 P2 VS1 0.67 TEC TEH 0.61 CBAY2 17 H
176 32 129 124 0.39 143 PCT 12 P2 VS1 0.69 TEC TEH 0.61 CBAY2 19 H
68 32 129 128 0.37 153 PCT 11 P2 VS1 0.74 TEC TEH 0.61 CBAY2 19 H
14 32 129 130 0.22 149 PCT 7
P2 VS2 0.67 TEC TEH 0.61 CBAY2 17 H
13 32 129 150 0.25 104 PCT 10 P2 VS5
-0.69 TEH TEC 0.61 CBAY2 248 C
80 32 129 152 0.27 117 PCT 10 P2 VS3
-0.78 TEH TEC 0.61 CBAY2 248 C
75
U3R24 PVGS SG32 All Data Page 41 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 129 152 0.25 73 PCT 10 P2 VS4
-0.75 TEH TEC 0.61 CBAY2 248 C
75 32 130 39 0.38 103 PCT 13 P2 05H 0.92 TEH TEC 0.61 CBAY2 46 C
147 32 130 65 0.32 109 PCT 10 P2 VS3 0.93 TEC TEH 0.61 CBAY2 41 H
152 32 130 71 0.39 136 PCT 11 P2 VS1 0.66 TEC TEH 0.61 CBAY2 41 H
181 32 130 77 0.36 142 PCT 11 P2 VS4
-0.81 TEC TEH 0.61 CBAY2 35 H
143 32 130 89 0.29 42 PCT 10 P2 VS1 0.71 TEC TEH 0.61 CBAY2 31 H
133 32 130 93 0.13 125 PCT 5
P2 VS2 1.04 TEC TEH 0.61 CBAY2 31 H
74 32 130 99 0.16 107 PCT 6
P2 VS3 0.76 TEC TEH 0.61 CBAY2 27 H
99 32 130 99 0.21 323 PCT 7
P2 VS5 0.86 TEC TEH 0.61 CBAY2 27 H
99 32 130 109 0.67 139 PCT 16 P2 VS1
-0.66 TEC TEH 0.61 CBAY2 21 H
31 32 130 161 0.17 97 PCT 6
P2 BW1
-0.85 TEC TEH 0.61 CBAY2 39 H
123 32 131 40 0.26 41 PCT 10 P2 BW1 1
TEH TEC 0.61 CBAY2 46 C
146 32 131 48 0.38 93 PCT 11 P2 VS3
-0.93 TEC TEH 0.61 CBAY2 41 H
217 32 131 56 0.41 141 PCT 12 P2 VS1 0.69 TEC TEH 0.61 CBAY2 41 H
101 32 131 70 0.23 92 PCT 7
P2 VS2
-0.9 TEC TEH 0.61 CBAY2 41 H
182 32 131 102 0.61 121 PCT 14 P2 06H 0.76 TEC TEH 0.61 CBAY2 21 H
109 32 131 130 0.16 160 PCT 6
P2 VS4 0.74 TEC TEH 0.61 CBAY2 17 H
14 32 131 156 0.26 143 PCT 10 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 248 C
61 32 132 41 0.26 139 PCT 10 P2 05H 0.83 TEH TEC 0.61 CBAY2 46 C
145 32 132 45 0.36 102 PCT 11 P2 VS3 0.78 TEC TEH 0.61 CBAY2 41 H
221 32 132 65 0.33 95 PCT 10 P2 VS1 0.82 TEC TEH 0.61 CBAY2 41 H
169 32 132 65 0.35 106 PCT 10 P2 VS5 0.67 TEC TEH 0.61 CBAY2 41 H
169 32 132 69 0.2 47 PCT 7
P2 VS1
-0.57 TEC TEH 0.61 CBAY2 41 H
183 32 132 69 0.29 132 PCT 9
P2 VS5 0.54 TEC TEH 0.61 CBAY2 41 H
183 32 132 89 0.32 116 PCT 11 P2 VS1
-0.69 TEC TEH 0.61 CBAY2 31 H
132 32 132 89 0.26 124 PCT 9
P2 VS1 0.76 TEC TEH 0.61 CBAY2 31 H
132 32 132 93 0.11 162 PCT 4
P2 VS5 0.42 TEC TEH 0.61 CBAY2 31 H
73 32 132 123 0.19 46 PCT 7
P2 VS3 0.73 TEC TEH 0.61 CBAY2 19 H
105 32 132 143 3.52 178 DNT P1 VS5
-0.15 TEH TEC 0.61 CBAY2 250 C
71 32 132 143 2.6 177 DNT P1 VS5 0.46 TEH TEC 0.61 CBAY2 250 C
71 32 132 143 NDF P3 VS5
-0.23 VS3 TEC 0.61 NYAX2 252 C
13 32 132 143 NDF P5 VS5 0.41 VS3 TEC 0.61 NYAX2 252 C
13 32 132 145 0.5 87 PCT 15 P2 VS2 0.81 TEH TEC 0.61 CBAY2 250 C
60 32 133 48 0.25 33 PCT 8
P2 BW1
-0.98 TEC TEH 0.61 CBAY2 41 H
53 32 133 80 0.22 27 PCT 7
P2 11C
-0.84 TEC TEH 0.61 CBAY2 35 H
107 32 133 106 0.2 33 PCT 7
P2 BW1 0.84 TEC TEH 0.61 CBAY2 21 H
50 32 133 110 0.2 42 PCT 7
P2 VS5 0.71 TEC TEH 0.61 CBAY2 17 H
291 32 133 112 0.4 93 PCT 12 P2 VS1 0.61 TEC TEH 0.61 CBAY2 19 H
246 32 133 124 0.34 112 PCT 11 P2 BW2
-0.85 TEC TEH 0.61 CBAY2 19 H
70 32 133 136 2.13 177 DNT P1 11C 0.43 TEH TEC 0.61 CBAY2 250 C
75 32 133 136 NDF P15 11C 0.4 11C TEC 0.61 NYAX2 252 C
20 32 133 138 2.47 180 DNT P1 11C 0.62 TEH TEC 0.61 CBAY2 248 C
107
U3R24 PVGS SG32 All Data Page 42 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 133 138 NDF P11 11C 0.73 11C TEC 0.61 NYAX2 252 C
19 32 133 140 2.39 181 DNT P1 11C 1.66 TEH TEC 0.61 CBAY2 248 C
93 32 133 140 NDF P16 11C 1.65 11C TEC 0.61 NYAX2 252 C
18 32 133 142 2.72 179 DNT P1 11C 1.38 TEH TEC 0.61 CBAY2 250 C
72 32 133 142 NDF P15 11C 1.32 11C TEC 0.61 NYAX2 252 C
17 32 133 150 0.32 51 PCT 11 P2 BW1 0.79 TEH TEC 0.61 CBAY2 250 C
56 32 133 152 0.23 138 PCT 8
P2 BW1
-0.91 TEH TEC 0.61 CBAY2 250 C
14 32 133 164 0.19 123 PCT 7
P2 VS5
-0.76 TEC TEH 0.61 CBAY2 37 H
139 32 134 39 0.42 91 PCT 13 P2 03C
-0.77 TEC TEH 0.61 CBAY2 33 H
230 32 134 73 0.37 41 PCT 11 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 37 H
98 32 134 75 0.41 116 PCT 12 P2 VS1
-0.87 TEC TEH 0.61 CBAY2 33 H
163 32 134 91 0.84 116 PCT 18 P2 11H 1.49 TEC TEH 0.61 CBAY2 29 H
83 32 134 93 0.13 132 PCT 5
P2 VS5 0.77 TEC TEH 0.61 CBAY2 31 H
72 32 134 95 1.68 132 PCT 25 P2 11H 1.46 TEC TEH 0.61 CBAY2 33 H
32 32 134 95 1.67 114 WAR 24 0.2 P4 11H 1.48 11H TEH 0.61 NYAX2 55 H
33 32 134 99 0.19 29 PCT 7
P2 BW2
-0.97 TEC TEH 0.61 CBAY2 27 H
97 32 134 103 0.16 58 PCT 6
P2 VS1 0.56 TEC TEH 0.61 CBAY2 23 H
92 32 134 107 0.31 75 PCT 10 P2 VS1
-0.95 TEC TEH 0.61 CBAY2 23 H
30 32 134 145 0.33 146 PCT 12 P2 BW1
-0.73 TEH TEC 0.61 CBAY2 248 C
85 32 134 149 0.27 61 PCT 9
P2 BW1
-0.74 TEH TEC 0.61 CBAY2 250 C
57 32 134 157 0.2 142 PCT 7
P2 BW1
-0.82 TEC TEH 0.61 CBAY2 39 H
119 32 135 44 0.2 70 PCT 7
P2 VS1
-0.79 TEC TEH 0.61 CBAY2 35 H
208 32 135 52 0.69 126 PCT 17 P2 VS3 0.84 TEC TEH 0.61 CBAY2 39 H
50 32 135 58 0.3 61 PCT 10 P2 11H 0.82 TEC TEH 0.61 CBAY2 37 H
59 32 135 58 0.36 143 PCT 11 P2 VS1 0.76 TEC TEH 0.61 CBAY2 37 H
59 32 135 64 0.32 103 PCT 10 P2 VS1
-0.78 TEC TEH 0.61 CBAY2 37 H
84 32 135 76 0.26 144 PCT 8
P2 VS1
-0.88 TEC TEH 0.61 CBAY2 35 H
162 32 135 102 0.54 143 PCT 12 P2 06H 0.75 TEC TEH 0.61 CBAY2 21 H
111 32 135 102 0.42 119 PCT 12 P2 VS1 0.64 TEC TEH 0.61 CBAY2 21 H
111 32 135 104 0.31 145 PCT 10 P2 VS1 0.71 TEC TEH 0.61 CBAY2 23 H
54 32 135 120 0.38 147 PCT 12 P2 VS1 0.64 TEC TEH 0.61 CBAY2 19 H
128 32 135 124 0.27 106 PCT 9
P2 11H 0.72 TEC TEH 0.61 CBAY2 19 H
71 32 135 130 0.31 95 PCT 10 P2 VS2 0.81 TEC TEH 0.61 CBAY2 17 H
16 32 135 164 8.32 177 DNT P1 VS5
-1.14 TEC TEH 0.61 CBAY2 37 H
194 32 135 164 NDF P27 VS5
-1 VS3 TEC 0.61 NYAX2 258 C
35 32 136 41 0.54 133 PCT 12 P2 05H 0.81 TEC TEH 0.61 CBAY2 33 H
232 32 136 73 0.34 119 PCT 11 P2 VS3 0.79 TEC TEH 0.61 CBAY2 37 H
95 32 136 79 0.39 110 PCT 12 P2 VS2 0.91 TEC TEH 0.61 CBAY2 33 H
109 32 136 89 0.25 132 PCT 9
P2 VS1
-1.03 TEC TEH 0.61 CBAY2 31 H
130 32 136 95 0.36 96 PCT 11 P2 BW1
-0.72 TEC TEH 0.61 CBAY2 33 H
34 32 136 99 0.57 128 PCT 15 P2 VS1
-1.02 TEC TEH 0.61 CBAY2 27 H
96 32 136 125 0.32 107 PCT 10 P2 11H
-0.23 TEC TEH 0.61 CBAY2 17 H
100
U3R24 PVGS SG32 All Data Page 43 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 136 153 0.29 145 PCT 11 P2 BW1 0.83 TEH TEC 0.61 CBAY2 248 C
27 32 137 60 0.33 89 PCT 10 P2 BW2 1.09 TEC TEH 0.61 CBAY2 37 H
61 32 137 118 0.32 38 PCT 10 P2 BW1 0.85 TEC TEH 0.61 CBAY2 17 H
180 32 138 55 0.55 101 PCT 15 P2 VS1 0.91 TEC TEH 0.61 CBAY2 39 H
14 32 138 55 0.29 144 PCT 9
P2 VS5
-0.73 TEC TEH 0.61 CBAY2 39 H
14 32 138 55 1.36 111 WAR 22 0.22 P32 VS1 0.92 VS3 TEH 0.61 NYAX2 51 H
9 32 138 59 0.38 110 PCT 12 P2 VS1 0.84 TEC TEH 0.61 CBAY2 37 H
55 32 138 69 0.16 63 PCT 6
P2 VS1
-0.55 TEC TEH 0.61 CBAY2 37 H
90 32 138 77 0.33 149 PCT 10 P2 VS4
-0.79 TEC TEH 0.61 CBAY2 35 H
139 32 138 105 0.45 153 PCT 13 P2 BW1
-0.85 TEC TEH 0.61 CBAY2 21 H
87 32 138 111 0.26 134 PCT 9
P2 VS1
-0.97 TEC TEH 0.61 CBAY2 19 H
281 32 138 113 0.37 89 PCT 11 P2 VS1
-0.98 TEC TEH 0.61 CBAY2 17 H
268 32 138 119 0.35 112 PCT 11 P2 VS1 0.87 TEC TEH 0.61 CBAY2 19 H
161 32 138 123 0.28 97 PCT 9
P2 VS1 0.64 TEC TEH 0.61 CBAY2 19 H
102 32 138 155 0.23 133 PCT 8
P2 BW1
-0.91 TEC TEH 0.61 CBAY2 39 H
135 32 139 56 0.48 105 PCT 13 P2 VS3 0.83 TEC TEH 0.61 CBAY2 39 H
9 32 139 138 6.63 178 DNT P1 VS5
-1.25 TEH TEC 0.61 CBAY2 248 C
126 32 139 138 NDF P3 VS5
-1.11 VS3 TEC 0.61 NYAX2 252 C
9 32 139 144 0.34 122 PCT 11 P2 VS1 0.7 TEH TEC 0.61 CBAY2 250 C
119 32 140 47 0.29 119 PCT 10 P2 VS4
-0.94 TEC TEH 0.61 CBAY2 33 H
223 32 140 49 0.24 115 PCT 8
P2 11H
-0.32 TEC TEH 0.61 CBAY2 35 H
213 32 140 55 0.66 120 PCT 17 P2 VS1 0.74 TEC TEH 0.61 CBAY2 37 H
28 32 140 55 0.46 115 PCT 13 P2 VS3 0.75 TEC TEH 0.61 CBAY2 37 H
28 32 140 55 1.5 112 WAR 23 0.23 P32 VS1 0.74 VS3 TEH 0.61 NYAX2 51 H
10 32 140 55 1.1 114 WAR 20 P12 VS3 0.78 VS3 TEH 0.61 NYAX2 51 H
10 32 140 93 0.15 119 PCT 6
P2 VS5 1.06 TEC TEH 0.61 CBAY2 31 H
69 32 140 105 0.48 85 PCT 13 P2 VS1
-1 TEC TEH 0.61 CBAY2 21 H
86 32 140 111 0.53 143 PCT 15 P2 VS1
-0.96 TEC TEH 0.61 CBAY2 19 H
280 32 140 117 0.31 112 PCT 10 P2 VS1
-1.01 TEC TEH 0.61 CBAY2 17 H
210 32 140 119 0.28 102 PCT 9
P2 BW1
-0.99 TEC TEH 0.61 CBAY2 19 H
160 32 140 123 0.31 125 PCT 10 P2 06H 0.72 TEC TEH 0.61 CBAY2 19 H
101 32 140 127 0.16 111 PCT 6
P2 VS5 0.76 TEC TEH 0.61 CBAY2 19 H
44 32 140 159 0.52 135 PCT 12 P2 11H 0.7 TEC TEH 0.61 CBAY2 37 H
189 32 141 50 0.68 134 PCT 13 P2 11H 0.76 TEC TEH 0.61 CBAY2 35 H
214 32 141 62 0.32 118 PCT 10 P2 VS1
-0.99 TEC TEH 0.61 CBAY2 37 H
52 32 142 55 0.5 116 PCT 14 P2 VS3 0.76 TEC TEH 0.61 CBAY2 33 H
273 32 142 63 0.26 73 PCT 9
P2 VS3 1.01 TEC TEH 0.61 CBAY2 37 H
51 32 142 71 0.4 126 PCT 12 P2 VS3
-1.01 TEC TEH 0.61 CBAY2 37 H
77 32 142 97 0.32 75 PCT 11 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 31 H
8 32 142 157 0.88 136 PCT 16 P2 11H 0.65 TEC TEH 0.61 CBAY2 37 H
187 32 143 84 0.21 153 PCT 7
P2 VS1 0.58 TEC TEH 0.61 CBAY2 35 H
55 32 144 47 0.38 120 PCT 12 P2 11H
-0.93 TEC TEH 0.61 CBAY2 33 H
282
U3R24 PVGS SG32 All Data Page 44 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 144 47 0.3 65 PCT 10 P2 VS3
-1.08 TEC TEH 0.61 CBAY2 33 H
282 32 144 55 0.49 125 PCT 13 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 35 H
196 32 144 77 0.53 113 PCT 14 P2 VS4
-0.81 TEC TEH 0.61 CBAY2 35 H
136 32 144 99 0.17 42 PCT 6
P2 VS1
-1.03 TEC TEH 0.61 CBAY2 27 H
92 32 144 99 0.18 149 PCT 6
P2 VS5 0.81 TEC TEH 0.61 CBAY2 27 H
92 32 144 101 0.42 103 PCT 12 P2 VS1
-0.9 TEC TEH 0.61 CBAY2 27 H
19 32 144 147 0.27 141 PCT 9
P2 VS3 0.6 TEC TEH 0.61 CBAY2 39 H
110 32 145 50 0.29 116 PCT 10 P2 VS1
-0.96 TEC TEH 0.61 CBAY2 33 H
241 32 145 58 0.34 129 PCT 11 P2 VS1
-0.94 TEC TEH 0.61 CBAY2 33 H
270 32 145 58 0.33 137 PCT 11 P2 VS1
-0.05 TEC TEH 0.61 CBAY2 33 H
270 32 145 64 0.35 125 PCT 11 P2 VS1
-0.92 TEC TEH 0.61 CBAY2 39 H
38 32 145 70 0.17 129 PCT 6
P2 VS1
-0.92 TEC TEH 0.61 CBAY2 39 H
56 32 145 78 0.39 120 PCT 12 P2 VS1
-0.99 TEC TEH 0.61 CBAY2 33 H
137 32 145 106 0.57 121 PCT 15 P2 VS1 0.33 TEC TEH 0.61 CBAY2 21 H
56 32 145 126 0.2 135 PCT 7
P2 VS4 0.74 TEC TEH 0.61 CBAY2 17 H
74 32 145 146 0.32 101 PCT 10 P2 VS3 0.25 TEC TEH 0.61 CBAY2 39 H
108 32 146 67 0.32 116 PCT 10 P2 VS1 0.76 TEC TEH 0.61 CBAY2 37 H
46 32 146 67 0.51 142 PCT 14 P2 VS3
-0.85 TEC TEH 0.61 CBAY2 37 H
46 32 146 71 0.48 128 PCT 11 P2 08H 0.82 TEC TEH 0.61 CBAY2 39 H
55 32 146 71 0.73 106 PCT 18 P2 VS3
-0.96 TEC TEH 0.61 CBAY2 39 H
55 32 146 75 0.31 106 PCT 10 P2 VS5
-0.83 TEC TEH 0.61 CBAY2 33 H
157 32 146 89 0.25 115 PCT 9
P2 VS1 0.68 TEC TEH 0.61 CBAY2 31 H
125 32 146 115 0.41 137 PCT 12 P2 VS1 0.71 TEC TEH 0.61 CBAY2 19 H
217 32 147 74 0.56 100 PCT 15 P2 VS3 0.48 TEC TEH 0.61 CBAY2 33 H
191 32 147 106 0.22 89 PCT 7
P2 VS1 0.79 TEC TEH 0.61 CBAY2 21 H
57 32 147 116 0.55 102 PCT 15 P2 VS1
-0.9 TEC TEH 0.61 CBAY2 19 H
193 32 148 75 0.3 117 PCT 10 P2 VS1
-0.9 TEC TEH 0.61 CBAY2 33 H
156 32 148 101 0.31 122 PCT 10 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 27 H
17 32 149 74 0.49 119 PCT 14 P2 VS3 0.58 TEC TEH 0.61 CBAY2 33 H
192 32 149 78 0.57 108 PCT 16 P2 VS3 0.55 TEC TEH 0.61 CBAY2 33 H
139 32 149 98 NDF 113 TSC 0.64 01C TEC 0.61 NYAX2 254 C
5 32 150 63 0.41 137 PCT 11 P2 06H 0.73 TEC TEH 0.61 CBAY2 33 H
265 32 150 91 0.33 144 PCT 10 P2 VS1
-0.77 TEC TEH 0.61 CBAY2 29 H
75 32 150 131 0.46 129 PCT 13 P2 VS2
-0.75 TEC TEH 0.61 CBAY2 43 H
9 32 151 94 0.33 139 PCT 10 P2 VS1 0.79 TEC TEH 0.61 CBAY2 29 H
54 32 151 110 0.17 120 PCT 6
P2 VS1 0.8 TEC TEH 0.61 CBAY2 17 H
300 32 152 93 0.21 114 PCT 8
P2 VS2 0.68 TEC TEH 0.61 CBAY2 31 H
63 32 152 95 0.48 131 PCT 14 P2 VS1 0.79 TEC TEH 0.61 CBAY2 33 H
42 32 152 107 0.22 124 PCT 8
P2 VS1 0.74 TEC TEH 0.61 CBAY2 23 H
21 32 152 107 0.22 139 PCT 8
P2 VS2 0.68 TEC TEH 0.61 CBAY2 23 H
21 32 152 147 0.54 155 PCT 10 P2 04H 0.69 TEC TEH 0.61 CBAY2 37 H
177 32 152 147 0.34 102 PCT 11 P2 03C 0.05 TEC TEH 0.61 CBAY2 37 H
177
U3R24 PVGS SG32 All Data Page 45 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 152 149 0.11 146 NQI P1 TSC 0.83 TEC TEH 0.61 CBAY2 41 H
13 32 152 149 NDF P7 TSC 0.83 01C TEC 0.61 NYAX2 258 C
45 32 153 70 0.59 148 PCT 10 P2 08H 0.73 TEC TEH 0.61 CBAY2 35 H
242 32 153 82 0.21 131 PCT 8
P2 VS2
-1.18 TEC TEH 0.61 CBAY2 33 H
86 32 153 114 0.31 110 PCT 10 P2 VS1
-0.89 TEC TEH 0.61 CBAY2 17 H
243 32 153 114 0.39 138 PCT 11 P2 VS1 0.77 TEC TEH 0.61 CBAY2 17 H
243 32 153 120 0.31 105 PCT 10 P2 VS1
-0.87 TEC TEH 0.61 CBAY2 19 H
137 32 154 85 0.25 136 PCT 8
P2 VS1 0.86 TEC TEH 0.61 CBAY2 35 H
16 32 154 95 0.38 123 PCT 12 P2 VS1 0.79 TEC TEH 0.61 CBAY2 33 H
43 32 154 123 0.35 116 PCT 11 P2 BW2 0.89 TEC TEH 0.61 CBAY2 19 H
94 32 154 145 0.6 143 PCT 12 P2 11H 0.52 TEC TEH 0.61 CBAY2 37 H
175 32 155 74 0.47 154 PCT 14 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 33 H
195 32 155 106 0.26 135 PCT 8
P2 VS1 0.64 TEC TEH 0.61 CBAY2 21 H
61 32 155 106 0.21 121 PCT 7
P2 VS2 0.67 TEC TEH 0.61 CBAY2 21 H
61 32 155 116 1.26 109 PCT 25 P2 VS1
-0.84 TEC TEH 0.61 CBAY2 19 H
197 32 155 116 2.95 98 WAR 31 0.54 P16 VS1
-0.81 VS3 TEH 0.61 NYAX2 55 H
20 32 156 65 0.41 138 PCT 10 P2 11H
-0.3 TEC TEH 0.61 CBAY2 35 H
229 32 156 67 0.55 95 PCT 15 P2 VS5
-0.99 TEC TEH 0.61 CBAY2 35 H
184 32 156 67 0.6 134 PCT 15 P2 BW2 0.86 TEC TEH 0.61 CBAY2 35 H
184 32 156 77 0.55 124 PCT 15 P2 BW2 1
TEC TEH 0.61 CBAY2 35 H
130 32 156 89 0.33 109 PCT 11 P2 BW1
-0.91 TEC TEH 0.61 CBAY2 31 H
120 32 156 89 0.43 123 PCT 13 P2 VS1 0.68 TEC TEH 0.61 CBAY2 31 H
120 32 156 111 0.17 113 PCT 6
P2 VS5 0.73 TEC TEH 0.61 CBAY2 19 H
272 32 156 137 0.26 143 PCT 8
P2 08H 0.76 TEC TEH 0.61 CBAY2 39 H
153 32 156 141 0.22 132 PCT 8
P2 BW1
-0.93 TEC TEH 0.61 CBAY2 37 H
162 32 156 143 0.27 133 PCT 9
P2 06H 0.8 TEC TEH 0.61 CBAY2 37 H
173 32 156 143 0.29 100 PCT 9
P2 03C 0.03 TEC TEH 0.61 CBAY2 37 H
173 32 157 62 0.4 111 PCT 12 P2 VS2
-0.96 TEC TEH 0.61 CBAY2 33 H
253 32 157 70 0.62 137 PCT 16 P2 BW2 0.89 TEC TEH 0.61 CBAY2 33 H
258 32 157 72 0.37 109 PCT 11 P2 VS1
-0.82 TEC TEH 0.61 CBAY2 37 H
11 32 157 72 0.31 130 PCT 10 P2 VS4 0.68 TEC TEH 0.61 CBAY2 37 H
11 32 157 74 0.34 135 PCT 11 P2 VS1 0.73 TEC TEH 0.61 CBAY2 33 H
196 32 157 74 0.49 99 PCT 14 P2 VS3 0.53 TEC TEH 0.61 CBAY2 33 H
196 32 157 76 0.4 145 PCT 12 P2 VS1
-0.76 TEC TEH 0.61 CBAY2 35 H
173 32 157 84 0.37 148 PCT 11 P2 VS1 0.78 TEC TEH 0.61 CBAY2 35 H
62 32 157 84 0.45 134 PCT 13 P2 VS4 0.68 TEC TEH 0.61 CBAY2 35 H
62 32 157 88 0.1 156 PCT 4
P2 VS5 0.72 TEC TEH 0.61 CBAY2 31 H
165 32 157 90 PIV TEC TEH 0.61 CBAY2 29 H
117 32 157 90 TBP TEC TEH 0.61 CBAY2 29 H
117 32 157 90 0.53 131 PCT 14 P2 VS1 0.61 TEC TEH 0.61 CBAY2 29 H
117 32 157 90 14.72 93 PLP 12 FDP 0.7 01C TEC 0.61 NYAX2 258 C
19 32 157 92 0.11 150 PCT 4
P2 VS5 1.07 TEC TEH 0.61 CBAY2 31 H
106
U3R24 PVGS SG32 All Data Page 46 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 157 96 0.14 16 PCT 5
P2 BW1 0.91 TEC TEH 0.61 CBAY2 31 H
46 32 157 110 0.11 109 PCT 4
P2 VS2 0.35 TEC TEH 0.61 CBAY2 17 H
303 32 157 114 0.28 135 PCT 9
P2 VS1 0.61 TEC TEH 0.61 CBAY2 17 H
245 32 157 128 0.31 111 PCT 10 P2 BW2 0.86 TEC TEH 0.61 CBAY2 19 H
28 32 157 142 0.54 120 PCT 15 P2 VS1
-0.88 TEC TEH 0.61 CBAY2 37 H
172 32 157 142 0.33 72 PCT 10 P2 VS4
-0.89 TEC TEH 0.61 CBAY2 37 H
172 32 157 142 0.58 123 PCT 16 P2 VS5
-0.92 TEC TEH 0.61 CBAY2 37 H
172 32 157 142 0.45 124 PCT 13 P2 BW2 0.99 TEC TEH 0.61 CBAY2 37 H
172 32 157 142 0.51 153 PCT 10 P2 04C 0.91 TEC TEH 0.61 CBAY2 37 H
172 32 158 63 0.56 137 PCT 12 P2 08H 0.78 TEC TEH 0.61 CBAY2 33 H
254 32 158 73 0.78 114 PCT 19 P2 VS5
-0.86 TEC TEH 0.61 CBAY2 37 H
10 32 158 79 0.35 101 PCT 11 P2 VS1 0.83 TEC TEH 0.61 CBAY2 33 H
98 32 158 85 0.53 135 PCT 14 P2 VS1 0.66 TEC TEH 0.61 CBAY2 35 H
14 32 158 89 PIV TEC TEH 0.61 CBAY2 31 H
119 32 158 89 TBP TEC TEH 0.61 CBAY2 31 H
119 32 158 89 0.24 47 PCT 9
P2 VS1 0.83 TEC TEH 0.61 CBAY2 31 H
119 32 158 89 0.26 109 PCT 9
P2 VS2
-0.9 TEC TEH 0.61 CBAY2 31 H
119 32 158 89 0.8 80 PLP 7
FDP 1.5 TEC TEH 0.61 CBAY2 31 H
119 32 158 89 16.95 120 PLP 108 FDP 1.02 01C TEC 0.61 NYAX2 252 C
23 32 158 99 0.23 146 PCT 8
P2 VS5 0.83 TEC TEH 0.61 CBAY2 27 H
85 32 158 129 0.79 103 PCT 18 P2 BW2 0.9 TEC TEH 0.61 CBAY2 17 H
35 32 159 70 0.22 159 PCT 7
P2 VS1
-0.82 TEC TEH 0.61 CBAY2 35 H
181 32 159 70 0.28 137 PCT 9
P2 VS2
-1.05 TEC TEH 0.61 CBAY2 35 H
181 32 159 70 0.58 137 PCT 15 P2 BW2 0.81 TEC TEH 0.61 CBAY2 35 H
181 32 159 90 TBP TEC TEH 0.61 CBAY2 29 H
118 32 159 90 PIV TEC TEH 0.61 CBAY2 29 H
118 32 159 90 1.1 125 PCT 23 P2 VS3
-0.84 TEC TEH 0.61 CBAY2 29 H
118 32 159 90 0.39 128 PCT 12 P2 VS5 0.9 TEC TEH 0.61 CBAY2 29 H
118 32 159 90 0.27 81 PLP 7
FDP 1.87 TEC TEH 0.61 CBAY2 29 H
118 32 159 90 2.76 110 WAR 30 0.52 P12 VS3
-0.64 VS3 TEH 0.61 NYAX2 55 H
34 32 159 90 NDF P15 FDP 1.87 01C TEC 0.61 NYAX2 252 C
21 32 159 94 0.22 120 DSI P6 FDP 0.35 TEC TEH 0.61 CBAY2 29 H
58 32 159 94 NDF P30 FDP 0.35 01C TEC 0.61 NYAX2 254 C
4 32 159 102 0.43 125 PCT 11 P2 11H 0.56 TEC TEH 0.61 CBAY2 21 H
122 32 159 140 0.4 130 PCT 12 P2 BW2
-0.95 TEC TEH 0.61 CBAY2 37 H
169 32 160 73 0.59 139 PCT 15 P2 VS5 0.89 TEC TEH 0.61 CBAY2 35 H
238 32 160 79 0.49 134 PCT 14 P2 VS4 0.63 TEC TEH 0.61 CBAY2 33 H
97 32 160 89 0.22 45 PCT 8
P2 VS1
-0.94 TEC TEH 0.61 CBAY2 31 H
118 32 160 89 0.19 108 NQI 3
FDP 2.05 TEC TEH 0.61 CBAY2 31 H
118 32 160 89 0.45 125 PLI 13 0.2 P16 FDP 2.06 01C TEC 0.61 NYAX2 252 C
22 32 160 89 3.7 91 PLP 136 FDP 2.14 01C TEC 0.61 NYAX2 252 C
22 32 160 89 0.48 69 PLI 0.19 P3 FDP 2
FDP FDP 0.61 ZPSMR 260 C
6
U3R24 PVGS SG32 All Data Page 47 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 160 89 0.23 45 PCT 36 0.19 P5 FDP 2
FDP FDP 0.61 ZPSMR 260 C
6 32 160 89 9.39 91 PLP 8
FDP 2.14 FDP FDP 0.61 ZPSMR 260 C
6 32 160 89 TBP FDP FDP 0.61 ZPSMR 262 C
5 32 160 89 PID P3 FDP 2
FDP FDP 0.61 ZPSMR 262 C
5 32 160 99 0.18 114 PCT 6
P2 VS5 0.71 TEC TEH 0.61 CBAY2 27 H
84 32 160 113 0.37 119 PCT 11 P2 VS1
-0.89 TEC TEH 0.61 CBAY2 17 H
257 32 160 125 0.64 106 PCT 16 P2 BW2 0.9 TEC TEH 0.61 CBAY2 17 H
88 32 160 129 0.43 119 PCT 12 P2 BW2
-0.9 TEC TEH 0.61 CBAY2 17 H
34 32 161 70 0.54 147 PCT 14 P2 BW2 0.83 TEC TEH 0.61 CBAY2 35 H
234 32 161 72 0.85 120 PCT 19 P2 BW2
-0.81 TEC TEH 0.61 CBAY2 35 H
179 32 161 76 0.44 113 PCT 12 P2 VS3 0.63 TEC TEH 0.61 CBAY2 35 H
175 32 161 76 0.4 134 PCT 11 P2 VS4 0.78 TEC TEH 0.61 CBAY2 35 H
175 32 161 76 0.42 140 PCT 12 P2 VS5 0.64 TEC TEH 0.61 CBAY2 35 H
175 32 161 80 0.38 141 PCT 11 P2 VS4 0.84 TEC TEH 0.61 CBAY2 35 H
121 32 161 94 0.38 112 PCT 11 P2 VS4 0.95 TEC TEH 0.61 CBAY2 29 H
59 32 161 126 0.43 92 PCT 12 P2 BW2 1.1 TEC TEH 0.61 CBAY2 17 H
82 32 161 130 0.78 108 PCT 18 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 17 H
29 32 162 69 0.52 135 PCT 12 P2 10H 0.68 TEC TEH 0.61 CBAY2 33 H
201 32 162 69 0.46 37 PCT 14 P2 BW2 0.94 TEC TEH 0.61 CBAY2 33 H
201 32 162 79 0.31 140 PCT 10 P2 BW1
-1.03 TEC TEH 0.61 CBAY2 33 H
96 32 162 83 0.33 77 PCT 11 P2 VS2 0.73 TEC TEH 0.61 CBAY2 33 H
11 32 162 103 0.17 115 PCT 6
P2 BW1 0.88 TEC TEH 0.61 CBAY2 23 H
77 32 162 107 0.15 64 PCT 6
P2 VS5 1.24 TEC TEH 0.61 CBAY2 23 H
16 32 162 121 0.56 87 PCT 15 P2 BW2 0.95 TEC TEH 0.61 CBAY2 17 H
143 32 162 125 1.78 112 PCT 29 P2 BW2
-0.93 TEC TEH 0.61 CBAY2 17 H
87 32 162 125 3.29 106 WAR 32 0.4 P21 BW2
-0.95 VS3 TEC 0.61 NYAX2 254 C
57 32 162 129 1.03 113 PCT 22 P2 BW2 0.9 TEC TEH 0.61 CBAY2 17 H
33 32 162 129 2.21 108 WAR 27 0.23 P3 BW2 0.9 VS3 TEC 0.61 NYAX2 252 C
10 32 163 74 0.37 146 PCT 10 P2 10H 0.73 TEC TEH 0.61 CBAY2 33 H
199 32 163 96 0.22 82 PCT 8
P2 VS5 0.77 TEC TEH 0.61 CBAY2 31 H
49 32 163 118 0.38 108 PCT 11 P2 VS5 0.86 TEC TEH 0.61 CBAY2 17 H
193 32 163 124 0.58 105 PCT 16 P2 BW2 0.94 TEC TEH 0.61 CBAY2 19 H
85 32 163 128 1.52 106 PCT 28 P2 BW2 0.94 TEC TEH 0.61 CBAY2 19 H
31 32 163 128 2.43 112 WAR 28 0.31 P6 BW2 0.99 VS3 TEC 0.61 NYAX2 254 C
55 32 163 130 0.69 100 PCT 17 P2 BW2
-0.98 TEC TEH 0.61 CBAY2 17 H
30 32 163 132 NDF P7 11C 26.31 VS3 TEC 0.61 NYAX2 254 C
52 32 164 73 0.23 132 PCT 7
P2 10H 0.7 TEC TEH 0.61 CBAY2 35 H
237 32 164 75 0.83 137 PCT 16 P2 10H 0.68 TEC TEH 0.61 CBAY2 33 H
148 32 164 75 1.08 100 PCT 23 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 33 H
148 32 164 75 1.13 100 PCT 23 P2 BW2 0.86 TEC TEH 0.61 CBAY2 33 H
148 32 164 75 2.13 95 WAR 27 0.26 P19 BW2
-0.8 VS3 TEC 0.61 NYAX2 254 C
44 32 164 75 2.13 120 WAR 27 0.31 P4 BW2 0.94 VS3 TEC 0.61 NYAX2 254 C
44
U3R24 PVGS SG32 All Data Page 48 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 164 79 0.31 106 PCT 10 P2 VS5
-0.96 TEC TEH 0.61 CBAY2 33 H
95 32 164 79 0.47 125 PCT 14 P2 VS5 0.79 TEC TEH 0.61 CBAY2 33 H
95 32 164 83 0.32 108 PCT 10 P2 VS1 0.91 TEC TEH 0.61 CBAY2 33 H
10 32 164 93 0.29 49 PCT 10 P2 VS1
-0.93 TEC TEH 0.61 CBAY2 31 H
57 32 164 103 0.23 63 PCT 8
P2 BW1
-0.97 TEC TEH 0.61 CBAY2 23 H
76 32 164 121 0.75 115 PCT 18 P2 BW2
-0.93 TEC TEH 0.61 CBAY2 17 H
142 32 164 129 0.72 95 PCT 17 P2 BW2 0.99 TEC TEH 0.61 CBAY2 17 H
32 32 165 74 0.29 122 PCT 10 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 33 H
200 32 165 76 0.59 139 PCT 11 P2 10H 0.7 TEC TEH 0.61 CBAY2 35 H
177 32 165 78 0.65 151 PCT 11 P2 10H 0.65 TEC TEH 0.61 CBAY2 33 H
147 32 165 84 0.56 147 PCT 15 P2 VS5 0.68 TEC TEH 0.61 CBAY2 35 H
66 32 165 92 0.12 131 PCT 5
P2 VS4 0.68 TEC TEH 0.61 CBAY2 31 H
110 32 165 92 0.16 148 PCT 6
P2 VS5 0.96 TEC TEH 0.61 CBAY2 31 H
110 32 165 102 0.29 100 PCT 9
P2 VS2
-0.81 TEC TEH 0.61 CBAY2 21 H
125 32 165 102 0.46 123 PCT 13 P2 VS4 0.82 TEC TEH 0.61 CBAY2 21 H
125 32 165 106 0.21 98 PCT 7
P2 VS4 0.73 TEC TEH 0.61 CBAY2 21 H
66 32 165 120 1.08 110 PCT 23 P2 BW2
-0.92 TEC TEH 0.61 CBAY2 19 H
143 32 165 120 2.32 111 WAR 28 0.37 P21 BW2
-0.89 VS3 TEC 0.61 NYAX2 254 C
58 32 165 122 0.38 147 PCT 11 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 17 H
138 32 165 126 0.17 134 PCT 6
P2 VS4 0.79 TEC TEH 0.61 CBAY2 17 H
84 32 165 126 0.17 94 PCT 6
P2 VS5 0.92 TEC TEH 0.61 CBAY2 17 H
84 32 165 130 1.25 122 PCT 24 P2 BW2 0.97 TEC TEH 0.61 CBAY2 17 H
31 32 165 130 2.65 121 WAR 29 0.49 P7 BW2 0.89 VS3 TEC 0.61 NYAX2 254 C
53 32 166 77 0.58 151 PCT 11 P2 10H 0.73 TEC TEH 0.61 CBAY2 35 H
125 32 166 79 0.42 134 PCT 13 P2 VS2 0.83 TEC TEH 0.61 CBAY2 33 H
94 32 166 79 0.46 132 PCT 14 P2 VS4
-0.88 TEC TEH 0.61 CBAY2 33 H
94 32 166 79 0.63 124 PCT 17 P2 VS5 0.81 TEC TEH 0.61 CBAY2 33 H
94 32 166 79 0.5 83 PCT 14 P2 BW2
-0.11 TEC TEH 0.61 CBAY2 33 H
94 32 166 79 0.57 63 PCT 16 P2 BW2 0.96 TEC TEH 0.61 CBAY2 33 H
94 32 166 83 0.79 126 PCT 19 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 33 H
9 32 166 101 0.37 110 PCT 11 P2 VS5 0.85 TEC TEH 0.61 CBAY2 27 H
8 32 166 103 0.37 121 PCT 11 P2 VS5
-0.89 TEC TEH 0.61 CBAY2 23 H
75 32 166 107 0.2 87 PCT 7
P2 VS2 0.7 TEC TEH 0.61 CBAY2 23 H
14 32 166 113 0.38 107 PCT 11 P2 VS5
-0.8 TEC TEH 0.61 CBAY2 17 H
254 32 166 117 1.57 118 PCT 27 P2 BW2
-0.88 TEC TEH 0.61 CBAY2 17 H
198 32 166 117 2.74 104 WAR 30 0.26 P20 BW2
-0.8 VS3 TEC 0.61 NYAX2 254 C
60 32 166 121 0.42 120 PCT 12 P2 BW2 0.95 TEC TEH 0.61 CBAY2 17 H
141 32 166 127 NDF 191 11C 29.87 VS3 TEC 0.61 NYAX2 254 C
54 32 167 80 0.26 138 PCT 8
P2 VS3 0.58 TEC TEH 0.61 CBAY2 35 H
124 32 167 84 0.4 140 PCT 11 P2 VS5 0.77 TEC TEH 0.61 CBAY2 35 H
67 32 167 86 0.29 108 PCT 10 P2 VS3 0.75 TEC TEH 0.61 CBAY2 33 H
6 32 167 86 0.31 129 PCT 10 P2 VS5 0.67 TEC TEH 0.61 CBAY2 33 H
6
U3R24 PVGS SG32 All Data Page 49 of 49 SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx 32 167 92 0.24 301 PCT 9
P2 VS4 0.78 TEC TEH 0.61 CBAY2 31 H
111 32 167 92 0.22 300 PCT 8
P2 VS5 0.91 TEC TEH 0.61 CBAY2 31 H
111 32 167 116 0.97 106 PCT 22 P2 BW2
-0.97 TEC TEH 0.61 CBAY2 19 H
203 32 167 116 1
85 WAR 20 0.4 P20 BW2
-0.96 VS3 TEC 0.61 NYAX2 254 C
59 32 167 120 0.42 137 PCT 13 P2 BW2 0.91 TEC TEH 0.61 CBAY2 19 H
144 32 167 122 0.38 111 PCT 11 P2 BW2 1
TEC TEH 0.61 CBAY2 17 H
139 32 167 124 0.32 134 PCT 10 P2 BW2
-0.87 TEC TEH 0.61 CBAY2 19 H
87 32 167 124 1.3 93 PCT 25 P2 BW2 0.94 TEC TEH 0.61 CBAY2 19 H
87 32 167 124 2.24 111 WAR 28 0.37 P5 BW2 0.94 VS3 TEC 0.61 NYAX2 254 C
56 32 168 81 0.51 121 PCT 14 P2 BW2 0.91 TEC TEH 0.61 CBAY2 35 H
69 32 168 83 0.59 120 PCT 16 P2 VS4 0.58 TEC TEH 0.61 CBAY2 33 H
8 32 168 83 0.52 104 PCT 15 P2 BW2
-0.96 TEC TEH 0.61 CBAY2 33 H
8 32 168 83 0.56 152 PCT 12 P2 02C 0.78 TEC TEH 0.61 CBAY2 33 H
8 32 168 85 0.33 124 PCT 10 P2 BW2
-0.86 TEC TEH 0.61 CBAY2 35 H
9 32 168 93 0.22 36 PCT 8
P2 BW1
-1 TEC TEH 0.61 CBAY2 31 H
55 32 168 95 0.38 112 PCT 12 P2 VS5 0.84 TEC TEH 0.61 CBAY2 33 H
50 32 168 99 1.14 101 PCT 23 P2 01C
-0.15 TEC TEH 0.61 CBAY2 27 H
80 32 168 99 3.16 104 WAR 32 0.61 P19 01C
-0.14 01C TEC 0.61 NYAX2 254 C
6 32 168 101 1.11 82 PCT 23 P2 01C
-0.85 TEC TEH 0.61 CBAY2 27 H
7 32 168 101 2.35 301 WAR 28 0.47 P9 01C
-0.85 01C TEC 0.61 NYAX2 254 C
7 32 168 107 0.17 139 PCT 6
P2 VS2 0.78 TEC TEH 0.61 CBAY2 23 H
13 32 168 113 0.48 107 PCT 13 P2 BW2
-0.95 TEC TEH 0.61 CBAY2 17 H
253 32 168 121 0.67 128 PCT 16 P2 BW2
-0.96 TEC TEH 0.61 CBAY2 17 H
140 32 169 86 0.42 100 PCT 13 P2 BW2
-0.69 TEC TEH 0.61 CBAY2 33 H
7 32 169 92 0.16 115 PCT 6
P2 VS4 0.98 TEC TEH 0.61 CBAY2 31 H
112 32 169 102 0.65 108 PCT 17 P2 01C 0.85 TEC TEH 0.61 CBAY2 27 H
4 32 169 102 1.53 105 WAR 23 0.43 P28 01C 0.83 01C TEC 0.61 NYAX2 254 C
9 32 169 116 0.35 137 PCT 11 P2 VS1
-0.89 TEC TEH 0.61 CBAY2 19 H
204 32 169 116 0.29 113 PCT 10 P2 BW2 0.94 TEC TEH 0.61 CBAY2 19 H
204 32 169 120 0.29 130 PCT 10 P2 BW2 0.94 TEC TEH 0.61 CBAY2 19 H
145 32 170 89 0.28 113 PCT 10 P2 BW1
-0.79 TEC TEH 0.61 CBAY2 31 H
113 32 170 93 0.27 77 PCT 9
P2 11H
-1.05 TEC TEH 0.61 CBAY2 31 H
54 32 170 99 1.02 106 PCT 22 P2 01C
-0.9 TEC TEH 0.61 CBAY2 27 H
79 32 170 99 2.95 118 WAR 31 0.67 P9 01C
-0.86 01C TEC 0.61 NYAX2 254 C
8 32 170 103 0.23 127 PCT 8
P2 11H 0.6 TEC TEH 0.61 CBAY2 23 H
73 32 170 107 0.61 120 PCT 16 P2 VS4 0.65 TEC TEH 0.61 CBAY2 23 H
12 32 170 107 0.68 101 PCT 18 P2 VS5 0.79 TEC TEH 0.61 CBAY2 23 H
12 32 170 109 0.38 90 PCT 11 P2 11H
-0.05 TEC TEH 0.61 CBAY2 21 H
11 32 170 115 0.35 107 PCT 11 P2 BW2
-0.84 TEC TEH 0.61 CBAY2 19 H
205 32 171 100 0.28 143 PCT 9
P2 11H 0.76 TEC TEH 0.61 CBAY2 27 H
78 32 171 102 0.45 114 PCT 13 P2 01C 0.9 TEC TEH 0.61 CBAY2 27 H
5 32 171 108 0.44 100 PCT 13 P2 01C
-0.97 TEC TEH 0.61 CBAY2 23 H
11
APPENDIX D PLI & PLP DATA SHEETS
SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx Comment 31 102 27 1.84 135 PLP 8
TSC 14.15 TEC TEH 0.61 CBAY2 53 H
133 Historical 31 102 27 17.22 109 PLP 44 TSC 14.49 01C TEC 0.61 NYAX2 266 C
33 Historical 31 99 28 3.74 93 PLP 164 TSC 13.46 01C TEC 0.61 NYAX2 266 C
45 New 31 101 28 1.27 70 PLP 7
TSC 14.05 TEH TEC 0.61 CBAY2 66 C
178 New 31 101 28 9.36 105 PLP 160 TSC 14.05 01C TEC 0.61 NYAX2 266 C
39 Historical 31 103 28 12.1 111 PLP 164 FDP
-0.64 01C TEC 0.61 NYAX2 266 C
34 Historical 31 127 38 0.63 146 PLP 187 TSH 1.15 01H TEH 0.61 NYAX2 67 H
20 Historical 31 166 103 2.16 105 PLP 4
TSC 0.7 01C TEC 0.61 NYAX2 264 C
52 New 31 18 131 1.1 88 PLP 7
FDP 1.38 TEH TEC 0.61 CBAY2 226 C
213 New 31 51 144 8.19 76 PLP 144 TSH 0.17 01H TEH 0.61 NYAX2 59 H
53 New 31 53 144 6.69 74 PLP 132 TSH 0.14 01H TEH 0.61 NYAX2 59 H
54 New 31 54 145 10.25 132 PLP 139 TSH 0.2 01H TEH 0.61 NYAX2 59 H
47 Historical 31 55 146 3.84 135 PLP 163 TSH 0.2 01H TEH 0.61 NYAX2 59 H
41 Historical 3R24 SG31 PLP/PLI
SGID Row Col Volts Deg Ind Per CrLen Chn Locn Inch1 Inch2 BegT EndT PDia PType Cal L
Idx Comment 32 3
24 0.69 54 PLP 7
07H 6.96 TEH TEC 0.61 CBAY2 22 C
60 Historical 32 3
24 4.44 119 PLP 24 07H 7.05 08H TEH 0.61 NYAX2 49 H
18 Historical 32 158 89 0.8 80 PLP 7
FDP 1.5 TEC TEH 0.61 CBAY2 31 H
119 New 32 158 89 16.95 120 PLP 108 FDP 1.02 01C TEC 0.61 NYAX2 252 C
23 New 32 160 89 0.45 125 PLI 13 0.2 P16 FDP 2.06 01C TEC 0.61 NYAX2 252 C
22 New 32 160 89 3.7 91 PLP 136 FDP 2.14 01C TEC 0.61 NYAX2 252 C
22 New 32 160 89 0.48 69 PLI 0.19 P3 FDP 2
FDP FDP 0.61 ZPSMR 260 C
6 New 32 160 89 9.39 91 PLP 8
FDP 2.14 FDP FDP 0.61 ZPSMR 260 C
6 New 32 157 90 14.72 93 PLP 12 FDP 0.7 01C TEC 0.61 NYAX2 258 C
19 New 32 159 90 0.27 81 PLP 7
FDP 1.87 TEC TEH 0.61 CBAY2 29 H
118 New U3R24 SG32 PLP/PLI
APPENDIX E PLUG MAPS
- 138 PLUGGED TUBE A
53 STAY ROD A
5 Tube Plugged HL & CL U3R24 SG - 31 Tubes Plugged U3R24 Palo Verde U3R24 PVNGS3 3RSG Westinghouse Electric Company LLC - ST Max 04/22/2024 11:16:10
5 5
10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170 175 175 180 180 185 185 190 190 195 195 200 200 5
5 10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170
53 STAY ROD A
- 140 PLUGGED TUBE A
8 Tube Plugged HL and CL U3R24 SG - 32 Tubes Plugged U3R24 Palo Verde U3R24 PVNGS3 3RSG Westinghouse Electric Company LLC - ST Max 04/22/2024 11:25:04
5 5
10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170 175 175 180 180 185 185 190 190 195 195 200 200 5
5 10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170
APPENDIX F FORM NIS-1
APS NIS - 1 FORM OWNERS DATA REPORT FOR INSERVICE INSPECTIONS
- 2. PLANT PALO VERDE GENERATING STATION 2a. ADDRESS 5801 SOUTH WINTERSBURG ROAD, TONOPAH, ARIZONA 85354
- 3. UNIT NUMBER 3
- 4. OWNERS CERTIFICATE OF AUTHORIZATION NONE
- 5. COMMERCIAL SERVICE DATE 1-8-88
- 6. COMPONENTS INSPECTED:
COMPONENT OR APPURTENANCE MANUFACTURER OR INSTALLER SERIAL NUMBER STATE OR PROVINCE NATIONAL BOARD NO 3MRCEE01A STEAM GENERATOR 31 Ansaldo 242 NA 191 3MRCEE01B STEAM GENERATOR 32 Ansaldo 243 NA 192
APS NIS - 1 BACK OWNERS DATA REPORT FOR INSERVICE INSPECTIONS
- 7. EXAM DATES April 2024
- 8. INSPECTION INTERVAL 4th Interval dates: 06-01-18 to 01-10-28
- 9. ABSTRACT OF EXAMINATIONS. INCLUDE A LIST OF EXAMINATIONS AND A STATEMENT CONCERNING STATUS OF WORK REQUIRED FOR CURRENT INTERVAL.
Table 1 in the report summary section documents the number and type of each examination performed.
A summary of the tubes with indications of degradation is listed in Appendix B and C of this report for SG 31 and 32 respectively. The tubes identified on the attached page 3 were plugged as a result of this examination.
The number of tubes plugged are as follows: SG 31 = 5 tubes SG 32 = 8 tubes WE CERTIFY THAT THE STATEMENTS MADE IN THIS REPORT ARE CORRECT AND THE EXAMINATIONS AND CORRECTIVE MEASURES TAKEN CONFORM TO THE RULES OF THE ASME CODE, SECTION XI.
DATESIGNED: ARIZONA PUBLIC SERVICE COMPANY BY _________________________________
CERTIFICATE OF INSERVICE INSPECTION I, THE UNDERSIGNED, HOLDING A VALID COMMISSION ISSUED BY THE NATIONAL BOARD OF BOILER AND PRESSURE VESSEL INSPECTORS AND THE STATE OF PROVINCE OF ARIZONA EMPLOYED BY THE HARTFORD STEAM BOILER INSPECTION AND INSURANCE COMPANY HAVE INSPECTED THE COMPONENTS DESCRIBED IN THIS OWNERS REPORT DURING THE PERIOD 04/06/24 TO 05/08/24 AND STATE THAT TO THE BEST OF MY KNOWLEDGE AND
- BELIEF, THE OWNER HAS PERFORMED EXAMINATIONS AND TAKEN CORRECTIVE MEASURES DESCRIBED IN THIS OWNERS REPORT IN ACCORDANCE WITH THE REQUIREMENTS OF THE ASME CODE, SECTION XI. BY SIGNING THIS CERTIFICATE NEITHER THE INSPECTOR NOR HIS EMPLOYER MAKES ANY
- WARRANTY, EXPRESSED OR IMPLIED, CONCERNING THE EXAMINATIONS AND CORRECTIVE MEASURES DESCRIBED IN THIS OWNERS REPORT. FURTHERMORE, NEITHER THE INSPECTOR NOR HIS EMPLOYER SHALL BE LIABLE IN ANY MANNER FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE OR A LOSS OF ANY KIND ARISING FROM OR CONNECTED WITH THIS INSPECTION.
INSPECTOR_______________________________________ COMMISSIONS__N.B 9685 "C, I, N, R"_________
NATL BOARD, STATE, PROVINCE DATE__________10/03/2024__________________
Harley Martin, Rachael J(Z09624)
Digitally signed by Harley Martin, Rachael J(Z09624)
Date: 2024.10.03 08:31:32 -07'00' Hogstrom, Robert (YH2450)
Digitally signed by Hogstrom, Robert (YH2450)
Date: 2024.10.03 08:49:15 -07'00'
APS NIS - 1 Page 3 OWNERS DATA REPORT FOR INSERVICE INSPECTIONS SGID Row Col Ind 31 40 85 TBP 31 47 108 TBP 31 46 115 TBP 31 35 122 TBP 31 41 124 TBP SGID Row Col Ind 32 31 80 TBP 32 41 86 TBP 32 158 89 TBP 32 160 89 TBP 32 157 90 TBP 32 159 90 TBP 32 50 93 TBP 32 50 107 TBP