IR 05000315/2023011

From kanterella
(Redirected from ML23233A187)
Jump to navigation Jump to search
Functional Engineering Inspection - Commercial Grade Dedication Report 05000315/2023011 and 05000316/2023011
ML23233A187
Person / Time
Site: Cook  
Issue date: 08/31/2023
From: Jamie Benjamin
NRC/RGN-III/DORS/EB1
To: Lies Q
Indiana Michigan Power Co
References
IR 2023011
Download: ML23233A187 (1)


Text

SUBJECT:

DONALD C. COOK NUCLEAR PLANT - FUNCTIONAL ENGINEERING INSPECTION - COMMERCIAL GRADE DEDICATION REPORT 05000315/2023011 AND 05000316/2023011

Dear Q. Shane Lies:

On July 24, 2023, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Donald C. Cook Nuclear Plant and discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Jamie C. Benjamin, Chief Engineering Branch 1 Division of Operating Reactor Safety Docket Nos. 05000315 and 05000316 License Nos. DPR-58 and DPR-74

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000315 and 05000316

License Numbers:

DPR-58 and DPR-74

Report Numbers:

05000315/2023011 and 05000316/2023011

Enterprise Identifier:

I-2023-011-0024

Licensee:

Indiana Michigan Power Company

Facility:

Donald C. Cook Nuclear Plant

Location:

Bridgman, MI

Inspection Dates:

June 12, 2023 to June 30, 2023

Inspectors:

E. Fernandez, Senior Reactor Inspector

D. Melendez-Colon, Reactor Inspector

E. Rosario, Reactor Inspector

Approved By:

Jamie C. Benjamin, Chief

Engineering Branch 1

Division of Operating Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a Functional Engineering Inspection - Commercial Grade Dedication at Donald C. Cook Nuclear Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

Type Issue Number Title Report Section Status URI 05000316,05000315/20 23011-01 Safety-Related Motor Control Center Bus Bar Commercial Grade Dedication 71111.21N.03 Open

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.21N.03 - Commercial Grade Dedication Commercial Grade Dedication (section 03.01)

The inspectors reviewed the implementation of the licensees processes for dedicating commercial-grade items/services as basic components and/or for procuring safety-related structures, systems, and components for the following samples:

(1)00035526, Mobilux EP1 Grease, Vesco Oil Corp

(2) CJ18840-1, Garolite Sheet, G-10, 1/2 Thick, 24 x 36, McMaster-Carr (3)00036194, Oil, DTE Extra Heavy, 55gal drum, Vesco Oil Corp (4)00035998, Gauge, Site Glass, Bearing Pedestal Housing with Drain, 3/8 in - 18 NPT Connection, Curtiss Wright Stream (5)100001351, Bushing, Control Room Ventilation Fan, SK-1 7/16 IN. 2 SK1-5/8 IN, Motion Industries
(6) CGD-77720102-1, Cap, Fill, 4 Inch, Glass-Filled PBT, Paragon (7)100001188, Assembly, Cover & Grid Includes Fasteners-Seals & Gaskets, Debora Smith Energy Partners (8)100001491, Pipe Clamp EDGs, McMaster-Carr (9)00034654, Ste, Brass instrument Quick Connect, 1/4 IN FNPT X 3/8 IN, Lennon Fluid Systems LLC (10)00034780, Vertical Bus Bar, Tin Plated Copper, Storm Power Components
(11) CGD-341713-1, Mechanical Seal, Cartridge Single Seal, Paragon (12)100001170 Pressure Gauge, 2-1/2", 0-100 Psi, Power Process Engineering

INSPECTION RESULTS

Unresolved Item (Open)

Safety-Related Motor Control Center Bus Bar Commercial Grade Dedication URI 05000316,05000315/2023011-01 71111.21 N.03

Description:

The Donald C. Cook Nuclear Plant purchased, dedicated and reversed engineered (under Specification No. ES-BUS-BAR-0001-QCN Rev 0) a non-safety related obsolete Cutler Hammer Control 9800 series Motor Control Centers (MCCs) vertical bus bar for use in safety-related applications. Specification No. ES-BUS-BAR-0001-QCN Rev 0 states under Dedication Instructions, Ensure the bus bars are either plain or tin coated copper. The dedication plan did not verify the new bus bar was tin coated. The original Cutler Hammer bus bars were aluminum with a tin coating. The new bus bars are made of copper with a non-documented unknown coating. The new configuration now consist of the new copper bus bar mated to a tin coated aluminum bus bar, which then come into sliding contact with silver plated copper bus stabs. The design change also uses a non-safety related corrosion inhibiting compound (e.g., Penetrox A-13), to prevent early failure of the tin coated aluminum to copper joint.

The inspectors identified three issues of concern with this commercial grade dedication sample.

1. The new configuration consisting of a new cooper bus bar material mated with an existing

tin coated aluminum bus bar has the potential to create a new or unique failure mechanism due to the dissimilar metals. The licensees evaluation did not address this potential failure mechanism.

2. Low contact resistance between bus bar mating surfaces was a listed critical attribute. The

original configuration used tin coatings between the tin coated aluminum bus bar to tin coated aluminum bus bar to create and maintain this condition. The new configuration uses a non-safety related corrosion inhibiting compound, Pentrox A-13, to create and maintain this condition. The licensee did not have documentation to show how this compound was qualified for use in safety-related applications.

3. Preventive maintenance/testing, instructions and inspection procedure acceptance criteria

did not appear to be modified to address this new or unique configuration.

On July 18, 2023, the licensee provide the inspectors a white paper title "DC Cook Response to Proposed Non-Cited Violation" which will be included in the review and final disposition for this Unresolved Item.

Planned Closure Actions: The inspectors planned to review the licensee's white paper to determine if any of the listed issues of concern represent a performance deficiency, and or violation of NRC requirements.

Corrective Action References: AR 2023-4974

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On July 24, 2023, the inspectors presented the Functional Engineering Inspection - Commercial Grade Dedication results to Q. Shane Lies and other members of the licensee staff.

On July 5, 2023, the inspectors presented the Exit for DC Cook Commercial Grade Dedication inspection results to Shane Lies - SVP Chief Nuclear Officer and other members of the licensee staff.

On July 24, 2023, the inspectors presented the Re-Exit inspection results to Steve Mitchell and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

22-6828

Unit 1 Reactor Trip - RCP 13 Trip

08/28/2022

22-6872

U1 RCP 12 Motor Electrical Penetration Corrosion and

Heat

08/29/2022

Corrective Action

Documents

22-9357

OSDD PO C1005443: Motion Industries

11/14/2022

23-4546

Review Current Practices for Oil Storage

06/19/2023

Corrective Action

Documents

Resulting from

Inspection

23-4974

NRC Inspection-Commercial Grade Dedication Violation

for Vertical Bus Bar

07/06/2023

00031489

Commercial Grade Item Dedication Evaluation - Bushing,

S Type QD Sure Grip-QMW

Rev. 0

00034654

Commercial Grade Item Dedication Evaluation - Stem,

Brass Instrument Quick Connect, 1/4 IN FNPT X 3/8 IN

Rev. 0

00034780

Commercial Grade Item Dedication Evaluation for Bus

Bar

00035526

Commercial Grade Item Dedication Evaluation - Grease,

Mobilux EP1, in 12 to 14 oz Tubes

Rev. 0

00035998

Commercial Grade Item Dedication Evaluation - Gauge,

Sight Glass, Bearing Pedestal Housing with Drain,

3/8 IN - 18 NPT Connection

Rev. 0

00036194

Commercial Grade Item Dedication Evaluation - Oil, DTE

Extra Heavy, 0121, 55 Gallon Drum

Rev. 0

100001170

Commercial Grade Item Dedication Evaluation for

Pressure Gauge for EDG

100001188

Commercial Grade Item Dedication

Evaluation - Assembly, Cover & Grid

Rev. 0

100001351

Commercial Grade Item Dedication Evaluation - Bushing,

S Type QD Sure Grip-QMW, SK-1 7/16 IN

Rev. 0

100001491

Commercial Grade Item Dedication Evaluation - Clamp,

Pipe, 2 Mounting Holes, Steel

Rev. 0

CE-NEYS-0010

COMPONENT EVALUATION: Penetrox A and

Penetrox A-13

71111.21N.03

Engineering

Evaluations

CGD-341713-1

Commercial Grade Item Dedication Technical Evaluation,

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Test Plan, and Test Datasheet for Mechanical Seal

CGIEL02

EPRI CGI Joint Utility Task Group Commercial Grade

Item Evaluation for Lugs, Compression, Un-Insulated

CGSR-AVL-1130-

Commercial Grade Survey Report for Paragon

DCCPS-604-QCS

Specification for Cable Terminations and Splices

ES-BUS-BAR-

0001-QCN

Purchase and Design Specification for Vertical Bus Bar

HP-0045

Emergency Diesel Generator (EDG) Fuel Linkage Parts

10/12/2004

237-3-902-2

Oil Sample Analysis Report

06/28/2023

24454

Commercial Grade Survey Report Transmittal - FENOC

Survey 2017-0021

07/05/2017

24974

NUPIC Joint Commercial Grade Survey of Swagelok

Company

03/05/2021

77720102

Test Data Package - Fill Cap

Rev. 1

CJ18840-1

Dedication Plan for Garolite Sheet

Rev. 0

Miscellaneous

EM-C-2130

Bus Operation and Maintenance

08/30/2022

2-EHP-5043-

CGD-001

Commercial Grade Dedication

Rev. 22

2-EHP-5043-

SLE-001

Shelf Life

Revs. 9, 10,

2-MMP-3120-

NETS-001

Receipt Inspection of Safety Related/Safety Interfaced

Material and Equipment

Rev. 23

2-MMP-3120-

NETS-001

Receipt Inspection of Safety Related/Safety Interfaced

Material and Equipment

Rev. 16

Procedures

2-MMP-7090-

NETS-011

Material Testing

Rev. 11

01591934

Receipt Inspection Report - 185731

07/26/2021

01593390

Receipt Inspection Report - 62725200

06/02/2021

01597677

Receipt Inspection Report - 0001374362, 0001374363

10/27/2022

01600299

Receipt Inspection Report - 196836

08/07/2020

01601287

Receipt Inspection Report - 198407

03/11/2021

Shipping Records

197350

Receipt Inspection Report Bus Bar PO# 01599553

09/24/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

C1001629

Receipt Inspection Report Pressure Gauge for EDG

C1004435

Receipt Inspection Report - 1386277

08/31/2022

C1004553

Receipt Inspection Report for Mechanical Seal

C1005296

Receipt Inspection Report - 1388211

2/12/2022

C1005443

Receipt Inspection Report - 1388079, 1388081

11/09/2022

C1005887

Receipt Inspection Report - 1389264

2/13/2023

RTN-23933

Receipt Inspection Report - 1389380

01/26/2023

55522280-01

MTH: 2-HV-ACRA-1; Investigate Abnormal Noise

10/24/2019

55550267-06

MTM, 1-WRV-761-ACT, Remove Air Line TCC/EC-57644

2/18/2021

Work Orders

C10038459001

2-TK-47-CD, Replace Locking Fill Cap

03/01/2023