ML23110A216
Text
APPENDIX K K.I-1 REV. 25, APRIL 2015 EXHIBIT I REACTOR PRESSURE VESSEL PURCHASE SPECIFICATION 21A1111
APPENDIX K K.I-1A REV. 25, APRIL 2015 EXHIBIT I - REACTOR PRESSURE VESSEL PURCHASE SPECIFICATION 21A1111 The power rerate design requirements are unchanged from the original design requirements specified in Exhibit I, Section 5 (i.e., design pressure of 1250 psig at bottom of the reactor vessel, design temperature of 575°F).
The power rerate normal operating pressure is increased from 1005 psig to 1035 psig at top of reactor vessel. The normal operating temperature is increased from 547°F to 551°F.
The operating shroud support pressure differentials provided in Appendix K, Exhibit I, Section 7.5.1 are increased from 34.0 and 21.85 to 35.68 and 26.32 psid for power rerate.
Estimates for reactor vessel irradiation at the end of 60 years have been recalculated based on actual data obtained from the reactor vessel surveillance specimens which were removed and analyzed. The updated information presented in Sections 4.2.4 and 4.2.5 supersede the information contained in Exhibit I Section 5.1.11.
Expected operating cycles for which fatigue has been evaluated are listed in UFSAR.
The Unit 2 and 3 TPO power rerate did not change the normal operating pressure or temperature for the reactor vessel.
The extended power uprate (EPU) did not change the normal operating pressure or temperature for the reactor vessel. The design pressure differentials across the shroud support and shroud provided in Appendix K, Exhibit I, Section 7.5.12 are not exceeded for EPU.
PBAPS ern ERAL0 ELECTR re ATOMIC POWER EQUIPMENT Dr'ARTMENT PURCHASE SPECIFICATION -
t.\T:. SH!ET REACTOR PRESSURE VESSEL SECTtON TITLE 1
SCOPE 2
RESPONSIBILITY 3
GENERAL DESCRIPnON 4
CODES 5
DESICH lEQUItwmHts 6
_ DESIGN ANALYSIS 7
CONST1UCTIOH 8
MAnuALS 9
FABRICATION l~
INSPECTION Ale TEST 11 PJEPARATION FOR SUIPMEHT 12 SUBKITTALS AtTACHMENT A - IHSTRUcrION MANUAL.
DIWlING AND D.\TA REQUIIt.!M!HTS ATtACHMENT B -
TEST SAMPLES SPECIAL l'~JEC1
'~.C.HO. 21Allll, MCV.NO. 9
... 110.
2 CON" 0*'.--ca r 3
~----------~--~---.------~----------
1.
SCOPE 1.1.
This specification d.fines the enlineeriDI requirements of the equipment specified herein.
1.2.
The work dODe by*the Saller in accordance with this specification*.hall include all necessary desi6ft. development, analysis. drav1nss, evalu3tion of mat~ria1s and fabrication methods, fabrication, shop testina. inapection and preparatieD for 8hipment.
K.I-2
PURCHASE SPECIFICATION 2.
RESPONSIBILITY GErJERALtj) ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT
....e. NO. 2WlIl,
...v. No.9 1M NO.
3 CONY ON 'H** y 4 2.1.
Th_ Seller shall accept full responsib~lity for his York and for compliance with this specification.
Review or approVal of drawinss,procedur.es, data or speci-fications by the Buyer with regard to general design and controlling dimensioDs does not constitute acceptance of any designs, materials or equipment
~hich will not fulfill the functional or performance 'requirements established by the purchas.
contract.
3.
GENERAL DESCRIPTION 3.i.
The reactor vessel will be used as a pressure. container s~pport1ns the ste..
senerating core.
3.2.
The equipment to be furnished in accordance with this specification shall be one reactor pressure vessel assembly with a removable head and nozzles and certain internal support structures, arranged as shown on Draying 886D499 complete with:
3.2.1.
Attachments for thermal insulation, vessel and,core supports, brackets or legs for lift:f.ng and h<<ndlins of VI;llAIlIP.l hP.Ild, and mounts for outside surface thermo-couples.
3.2.2.
One set of necessary special tools re,uired to remove and replac~ the reactor vessel head.
The set of tools shall
~nclude:
four hydraulic stud ten-sioners,stud elongation measuring device, stud and nut wrenches, one set of stud thread pr~tectors, three head suide caps, one bushing wrench, one stud slinS.
Stud tensioners shall be in accordance with Specification 21A9821 and shall 1n-~
clude a lifting device that properly spaces
~he tensioners over the 'volt circle.
3.2.3.
One set of necessary special tools required to install and remove the re-actor Ve~8p.~ head seals with manual contact.
This set of tools shall include a protective cover for the reactor vessel 'shell flange seal surface.
3.2.4.
MCt~1 boxes for the hand tools.
Boxes shall be suitable for handling with a crane and/or fork lift truck.
3.2.5.
One lot of reactor vessel material test plate and m3terial test specimens
'in accordance with Attachment B.
3.2.6.
Deleted
'SSUED, AUG 2 61970 K.I-3
PURCHASE SPECIFICATION 4.
CODES GENERAL0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT I~EC. NO. 2lAllll.
REV. No.9 IH NO.
4 CONT ON SHEE r 5 4.1.
~e reactor vessel shall be designed, fabricated, inspected, tested and stamped in accordance with the American Society of Mechanical Engineers (AsHE),.
Boiler and Pressure Vessel Code,Section III, applicable requirements for Class A Vessels as defined therein, interpretations of the AsHE Boiler and Pressure Vessel Code, and all laws, rules and regulations of the state in which the reactor plant will be locatea which are in effect on the date of the contract.
4.2.
Deviations from the applicable codes or regulations shall be avoided.
Where a conflict exists among the codes or regulations', the Seller shall bring this to the Buyer's attention.
It shall be the responsibility of the Seller to obtain resolution and disposition of deviation with the Buyer and other appropriate parties and authorities.
4.3.
The intent of this specification is to supplement the req~irements of the codes specified herein and to encompas& the means whereby the design
~bjective is satisfied.
4.4.
All standards and materials specifications shall be per latest revision in effect on the date of the contract.
5.
DESIGN REQUIREl-mNTS 5.1.
Operating Conditions 5.1.1.
.Internal pressure.
Design pressure: 1250 psig at bottom of the reactor vessel.
Normal Operating Pressure:
1005 psig at top of reactor vessel.
5.1.2.
Temperature.
Design temperature:
575°F Normal Operating Temperature:
547°F 5.1.3.
~eactor core and internal weight.
1be weight of the reactor core and in-ternal structure, centers of gravity and distribution of loadings are shown on Drawing 886D499.
5.1.4.
Water weight.
The weight of water contained in the vessel for various conditions of operation are presented on Drawing 886D499.
5.1.5.
Pipe reactions. The Buyer shall provide the Seller with the pipe reactions which the connecting piping will apply to all nozzles with a nominal size larger than the reactor vessel wall thickness and those nozzles which in addition are sub-jected to significant thermal cycling.
The reactions will be limited by the Buyer such that the combined stress 3S due to pipe reactions and design pressure in the vessel shell.at the nozzle attachment will not exceed the design stress allowed by the AS~m Code,Section III.
These pipe reactions shall be used in the detailed stress analysis require~ by the Code and performed by the Seller.
This analysis shall include the thin section of the nozzle in the vicinity of the weld prepara-tion fpr connecting piping, any bi-metal weld and shall-take into account the nozzle el:adding.
ISIUEDI AUG 2 6 1970 K.I-4
PURCHASE SPECIFICATION GEtJ ERA L() ELEeTRIC ATOMIC POWER EQUIPMENT DEPARTMENT S.ECoNO. 21Allll
~EV.NO. 9 SH NO.
5 CONT ON SHeET 6 5.1.6.
Control rod drive weight and reaction.
- The momentary reactions which are suddenly applied to each control rod driue housing in the vessel, bottom head are presented on Drawing 886D499.
5.1.7.
Steady state thermal conditions.
Steady state metal temperatures will be computed by the Seller for no more than twelve locations on the reactor vessel.
The locations will include the head and,shell closure flanges, the sfiell adjacent to the reactor core, the bottom head and major nozzles including the control rod drive nozzles.
Temperature gradients through the shell wall' adjacent to the por-tion of the reactor core peak flux zone will be co~puted by the Buyer and furnished to the Seller.
Data will be presented on Drawings 729E762 and l35B9990.
S.1.8.
Cyclic loading.
Reactor coolant temperature, pressure and flow changes at the above twelve locations, together with the expected number of cycles, will be furnished to the Seller by the Buyer.
The total number of different cyclic changes whieh must be analyzed at anyone location will be limited to six.
Data will be presented on Drawings 729E762 and l35B9S90.
5.1.9.
Earthquake loads.
Earthquake loads shall be taken into account in accord-ance with the criteria and load presented on Drawing 8860499.
5.l.JO.
Internal Heat Generation.
8Amm.Q hE!l!t~_ng 1.8 S.-S'x 103 BTU/ft3 opposite the active fuel zone
- The maximum internal heat generation due to hr at the inside of the reactor pressure vessel 5.1.11.
Neutr~n Irradiation.
The maxim~
neu~ron irradiation for fast
(~l Mev) neutrons is 3.8 x 1017 nvt for 40 years at the inside of the reactor pressure vessel wall opposite the active fuel zone.
5.2.
Design Considerations 5.2.1.
Design*ob1ective.
The objective shall be to design and fabricate this reactor vessel to have a useful life of forty years under operating conditions sp-ecified by the auyer.
5.2.2.
Reactor vessel supports.
Reactor vessel supports, internal supports, their attachments and adjacent shell shall be designed to take maximum combined loads in-cluding control rod drive reactions, earthquake loads, and jet reaction thr~sts as defined on Drawing
~86D499.
There shall be no gross yielding of the reactor vessel
~upports causing permanent displacement under these conditions.
5.2.3.
Stress concentrations.
Care shall be taken in design and fabrication to minimize stress concentrations at changes in sections or penetrations.
Fillet radii shall be equal to at least half the thickness of the thinner of the two sections being joined.
If reinforcement for openings (except the control rod drive and in-core flux monitor nozzles) requires local vessel shell added thickness, such reinforcement shall extend at least 1-1/2 times the diameter of the opening from the c.enter of the opening.
These requirementR are not to be construed as a waiver for evaluating the stresses for use in the analysis for cyclic operation.
' **UEO:
AUG 2 61970 K.I "EY. No.9 CONT ON SHEET 7 PURCHASE SPECIFICATION GENERAL0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT
,PEC. NO. 2lAllli SH NO.* 6 IAuf2 61970 5.2.4.
Corrosion allowance.
Exterior exposed ferritic surfaces of pressure-con-taining parts including heads, shell, flanges and nozzles shall have a minimum corrosion allowance of 1/16 inch.
The interior surface of. carbon or low alloy steel nozzles exposed to the reactor coalant shall also have a minimum corrosion allowance of 1/16 inch.
If the main closure head is left unclad. its interior.
surface shall also have a minimum corrosion allowance >of 1/16 inch.
5.2.5.
Main closure seal.
The reactor pressure vessel main closure seal shall be a double seal designed to have no detectable leakage thro~gh ~he inner or outer member at all operating conditions.
These conditions inclUde, but are not limited to:
(a) cold hydrostatic pressure test.at*the design pressure. (b) heating to design pressure and temperature at a rate of lOO*F/hr** maximum, (c) operating for extended periods of several months duration at operating conditions. and (d) cooling at a rate of lOO*F/hr., maximum.
5.2.6.
Design stress.
Design stress values used in the calculations shall be as contained in ASME Section III and applicable interpretations of ASHE Boiler and Pressure Vessel Code for materials covered therein.
The design stress values for ASME,Section III calculations for other materials approved by the Buyer in accord-ance with Paragraph 8.1. of this specification. shall be determined per APpendix II.
ASHE Code,Section III.
5.2.7.
Dimensional control.
Seller shall show the method of controlling measuring and maintaining alignment and location
~f control rod drive penet~ation8 wfth the vessel and core supporta.
5.2.8.
The reactor shall be designed to minimize retention pockets and crevices.
5.2.9.
The jurisdiction of Section III of the Code shall include all attachments to pressure boundary parts.
wt,~re weld buildup pads are used to attach inte~a!_
or external brackets. the vessel support skirt, the shroud sppport or the refvel-ing bellows support skirt. the weld buildup pad shall be considered the attachment to the pressure boundary part.
Section III shall be used as a guide in the design.
fabrication and inspec.tion of parts attached to the attachments to pressure boundary parts.
6.
DESIGN ANALYSIS 6.1.
Requirements The Seller shall perform the design. calculations and analyses as required by the
>applicable Standards and Codes indicated in Section 4.
The requirements of Article 4.
ASME Code,Section III, shall be fulfilled.
The analysis required shall be performed in two divisions as follows:
6.1.1.
Stress annlysis.
A stress analysis shall be performed in accordance with Section N-430. ASME Code Section III.
CalculatIons shall be performed in accord-ance with Paragraph N-43l to verify that the minimum wall thickness is provided.
A detailed stress analysis shall be performed in accordance with Paragraph N-432.
This analysis shall take into account all combinations of loads in conjunction with metal temperatures, as indicated in Section 5. above, and Drawings 729E762 and l3SB9990, within the nesign Stress Criteria of As~m Code Section III, Article 4.
K.I-6
PURCHASE SPECIFICATION GEr. ERA L~ ELEeTRIC ATOMIC POWER EQUIPMENT DEPARTMENT 21Allll "EV. No.9 7
CONTONt"EE T8 6.1.2.
Analysis for cXclic oper~.
The Selle~ shall perfor. an analysis in accordance with Section N-4IS'of the ASHE Code,Section III,. to determine that the vessel i. suitable for the cyclic loading conditions of Paragraph 5.1.8. above.
This analysis shall also be performed wiUhin" the desian stress criteria of'Section III, Article 4, to establish whether the design objective in Paragraph 5.2.1. above is reached.
The analysis will be used to determine the adequacy of any required thermal baffling used to control or limit*thermal stresses and to place safe opera-ting limits on the cyclic conditions imposed on the vessel where it is reasonable to control them, as in the startup heating rate and shutdown cooling rate.
6.2.
Calculation of Stresses 6.2.1.
The detailed structural analysis required to meet the requirement. of 6.1. shall be made for the stresses resulting from internal pressure, external and internal loadings, and the effects of steady and fluctuation teaperature8 and loads for regions given in 6.3. which involve changes of shape, structural discontinuities, and points of concentrated loadings.
6.2.2.
Where dimensions and loading conditions permit, the adequacy of struc-tural elements will be verified by comparison with completely analyzed elements.
The calculations shall include a complete analysis of stresses under 8teady state and transient conditions to d~termine suitability of the design with respect to the allowable stress given in AS~ Code, Seetloft III,.ad to detetaiBa
~he 0p.~.
tionai l1mitations with respect to fatigue of the reactor vessel materials over the life of the reactor vessel (Design Objective) using the loading conditions supplied by the Buyer.
6.3.
Parts of the Reactor Vessel Ass~mbly to be Analyzed 6.3.1.
The parts of the reacto~ vessel to be analyzed shall include:
head closure, bottom head, shell adjacent to reactor core, reactor vessel supports and stabilizers, supports for reactor vessel internals, control rod drive penetration, feedwater nozzle, poison, nozzle, emergency core cooling nozzles, drive system return nozzle, and all nozzles 10 inches or larger in size.
6.4.
Closure Head Seal Calculation 6.4.1.
To assure meeting sealing requirements of the main closure seal as speci-fied in Paragraph 5.2.5. above, the relative rotations of the flanges shall be calculated.
These totations shall be used to demonstrate analytically satisfactory seal performance using the following assumptions:
6.4.1.1.
The mating surfaces of the flanges shall be assumed rigid.
6.4.1.2.
The rotation shall be assumed to cause contact over the minimum area which will sustain the loading between the faces when stressed to the yield strength at the metal temperature.
6.4.1.3.
The flange faces shall be assumed to diverge from the contact a~ea, speci-fied in Paragraph 6.4.2.,
throub~ the angle of calculated relative rotation les8 any radial
-~per machined on the ce(s) to accommodate the flange rotations.I'~'tltr'2 61970 I IS. 1-7
PURCHASE SPECIFICATION GENERAL" ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT I"EC. NO.
21 Alill IItE¥. NO. 9 1M NO.
8 co.n ON....EET 9
6.4.1.4.
It may be assumed that the seal will be maintained if, at both O-ring seal locations, the separation between flange8 i8 1e88 than the minimum elastic spring-back of the O-ring.
6.5.
Calculations 6.5.1.
The calculations shall be clear and in sufficient detail to permit in-dep~ndent checking.
Specific references shall be given for all formulas and methods used or the formulas and methods shall be derived independent.1y.
Cal-culation shall be submitted to the Buyer for apprOval.
6.6~
Descriptions of Computer.Programs 6.6.1.
If computer programs are used to obtain solutions to design
~roblems, the Seller shall furnish the Buyer the description of each different computer program used.
These descriptions shall be furnished with the first issue of the design calculations incorporating such programs.
The computer program desc~iption shall include computer type, program capabilities, assump~ions, limitations and statement of availability.
6.1.
Measurement Report9 6.7.1.
Measured values of strain, deflections or stresses resulting from tests on models or actual reactor vessels shall be supplied to the Buyer by the Seller.
These reports
~ha1l include all information necessary to duplicate the conditions required to obtain the results repotted.
6.8.
Summary Report 6.8.1.
After completion of the reactor vessel design, the Seller shall furnish the Buyer addi~ional copies of all calculations plus a summary report of results of all computations.
Each copy shall be bound in a suitable paper binding and indexed.
7.
CONSTRUCTION The reactor vessel body including all components which contain pressure including the she~l, lower and upper heads shall be made of rolled plate and/or forgings welded witft full penetration welds throughout except as noted in 7.3.5.
The shell and head flange and nozzles shall be forged.
7.1.,
Shell and Heads 7.1.1.
Longitudinal and circumferential weld joints in the reactor vessel shall be oriented so as not to intersect openings or penetrations, wherever practical.
Circumferential weld seams should avoid regions of highest neutron flux in the core region, if practical.
The region of highest neutron flux occurs between the mid-plane and top of the *core.
ISSUED:
AUG 2 61970 K.I-a
PURCHASE SPECIFICATION GENERALG ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT
."EC. NO. \lAllll REY. NO. 9
.H NO.
CONT ON.MEIET10 7.1.2.
Bottom head.
The section of the bottom head which encompasses the pene-trations for the control rod drives and in-core flux monitors shall be either a single forging or dished plate, if practical.
If this is not practical and a weldment'is used, the orientation of the weld sections shall as far as practical, minimize the number of intersections of weld seams with penetrations.
7.1.3.
Top tiead.
The top head shall be either a single forging or dished plate or shall be fabricated of sections welded together, with the orientation of the weld seams such that no seams intersect openings or penetrations.
7.1.4.
Weld 10ints.
Weld joints shall be designed to facilitate a maximum of radiographic examination per the ASHE Boiler and Pressure Vessel Code,Section III, Paragraph N-624.
7.2.
Head Closure 7.2.1.
Assembly and disassembly 7.2.1.1.
The head closure shall be designed for removal and reassembly, using 4 or more hydraulic stud tensioners.
7.2.1.2.
- It shall be the desi!R objective to replace and remove the head within 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> elapsed ti.e.
Specifically, the cycle shall include placing the head oyer the studs, tightening the studs to operating bolt-up loads, unbolting and removal of the head over the studs.
It is expected that 120 such cycles will be performed during the life of the reactor vessel.
7.2.2. ~
7.2.2.1.
The head seal shall be a double seal with a vent between the se~18
~hrough which leakage of the inner ring can be detected.
The seal vent shall be designed for full desi~ pressure of the reactor vessel.
7.2.2.2.
The seal shall be metal a-ring type with pressure equalizing vents on I.D.
,7*.2.2.3.
The grooves for the a-rings shall be placed in the reactor head flange.
Suitable fasteners shall be provided to hold the a-rings in the grooves during head removal and assembLy operations.
7.2.2.4.
~rovisions shall be made for installation of a low pressure leak detec-tion system outside of the second seal, and may be outside of the bolt circle.
The provisions shall include a vent through the vessel flange with extended linch nipple and socket weld fitting and either a shallow groove or other suitable back-ing to retain a soft asbestos braided packing.
There shall be no protruding parts of this low pressure seal beyond the O.D. of the head and vessel flange.
ISSUED:
AUG 2 61970 K.1-9
PURCHASE SP ECIFICA nON 7.2.3.
Bolting GENERAL ~~ ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT SPEC. NO. 2lAIIIl "EY. No.9 aH NO.
10 CONTON aHEET 11 7.2.3.1.
Studs shall be used to secure the reactor vessel 'head.
Stud, nut and bushing 'threads shall be in accordance with 'Drawing 885D91l.
7.2.3.2.
The stud bolt holes in the reactor vessel flange shall be bushed with removable bushings.
Keys shall be provided for each bushing to prevent rotation of the bushings when removing studs.
7.2.3.3.
Spherical washers shall be used with the $tuds to minimize bending of the studs.
7"2.3.4.
It shall be possible to remove and replace the head with the studs in-stalled.
To facilitate head removal and replacement, three special guide caps shall be provided to couple onto three studs.
The lengths of the guiding surfaces of the guide caps shall be staggered so that the shorter of the three Guide caps shall ex-tend above the top of the installed studs for a minimum distance of 4 inches.
The length of the three guide caps shall be staggered in 3 inch minimum increments.
The internal threads of the guide caps shall be similar to the stud nuts threads.
The upper end of the guide caps shall be provided with a conical leak-in taper and a horizontal through-hole bored to accommodate a round bar for wrenching.
7.'.1.5.
Flange hole, bushing) and stud d~'signs shall be such that the studs st~d perpendicular to the flange surface when the studs and bushings are bottomed in the holes to facilitate removal and replacement of vessel head over studs as called for in Paragraph 7.2.3.4.
7.2.3.6.
The surface of all threads in the studs, nuts and bushings shall be given a phosphate coating to act as a rust inhibitor and to assist in'retaining lubricant on the surfaces.
An approved lubricant should be applied to the stn~
threads as soon as possible after coating.
7.~.3.7.
A stud sling for the main closure' studs shall be provided.
The stud sling shall include & swivel and counter-weight spring to support the weight of the, stud during turning of stud into vessel flange.
Studs are to be provided with a wrenching surface accessible when suspended on sling.
7.2.3.8.
All main load-carrying threads and spherical washers shall be assembled only after cleaningi gaging, and lubricating.
In no case during fabrication or t.esting shall these parts be assembl,ed without lubricant.
Only thread lubricant approved by the Buyer shall be used.
R.I-IO
PURCHASE SPECIFICATION 7.2.4.
Flanges GEr~ ERAL C) ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT
CC. NO.
21A1lll RCV. NO.
9 1M NO.
11 CONY ON IHECT12 7.2.4.1.
The top head flange surface shall.be machined or the area around each stud hole spot faced.
Spot facings shall be complete and extend beyond washer O.D. to accommodate maximum eccentricity of stud in head flange bolt hQle.
7.3.
Nozzle Ends 7.3.1.
The ends of all nozzles other than flanged nozzles shall be prepared for welding in accordance with Drawing l07CS30S.
Nozzle safe ends are considered to be part of the vessel, not part of the connecting piping but in no case shall the s.fe end wall thickness be less than the wall thickness of the connecting pipe.
7.3.2.
Where thermal sleeve nozzles are specified to a nominal size, the size of the pipe through the nozzle as well as the nozzle external end shall be the nominal size specified for the nozzle.
Thermal sleeves shall be supplied by the Seller.
7.3.3.
The Buyer will furnish information on the wall thickness. t p* of all piping connections and will set the inner bore diameter including tolerances and allow-ances of the connecting piping will follow ASA Standards.
The Buyer will use the formulas and allowable stresses of B3l.l for establishing the required piping wall
~hi~~nPRRp.R.
~ozzle safe end wall th1c~ness shall be governed by Drawingl07CS305 and will in general be
&r~ater than required by Sectiun.III.
7.3.4.
Details of the transition weld preparation shall be submitted to the Buyer for approval.
7.3.S.
Nozzles of 3 inches nominal size or larger shall be full penetration welded to the ve~sel.
Nozzles less than 3 inches nom1nal size may be.partial penetratio~
welded if permitted by ASHE Code,Section III.
7.4.
The vessel top head nozzles shall be.provided with flanges with small groove facing.
Match marked mating flanges with small tongue facing gaskets and a com-plete set o£ studs
&~d nuts shall also be provided.
The loose flanges for the 6 inch instrument nozzles shall be blind. the Temainder shall be weld neck.
The flanges and gaskets shall be in accordance with ABA Standards 816.5.
The threads on studs and nuts shall be 8-pitch series in accordance with ASA Standard Bl.l.
7.5.
Reactor Vess&l Support~
7.5.1.
External and internal supports shall be provided as an integral part of the reactor vessel.
The location and design of the supports shall be such that stresses in the reactor vessel and supports will be within ASHE Code limits due to reactions at these supports.
The pressure differentials across the shroud support and shroud shall be as tabulated below (higher pressure under the support).
The design of the core shroud support shall take into account the restraining effect of the components attached to the supports and the weight and earthquake and jet loadings as shown on Drawing 886D499, Sheet 7.
The design parameters given in Notes 1-8 of the above Drawing apply to components other than the shroud support. legs.
The design parameters tabulated below shall be applied to the shroud support legs only.
K.I-II
GEr~ ERJ~ J.,r:~) ELEeTnIC
......;.J ATOMIC POWER EQUIP"~ENT OEPARTMENT PURCHASE SPECI FICA TlON 7.5.1.
(Continued)
SHROUD SUPPORT DIFFERENTIAL PRESSURE SPf:C. NO. 2lAllll 12 MEv. NO.
9 Pressure (psid)
Pressur-e Area Design 57.0 39.0 Operating 34.0 21.85
> 98.375"R
=
< 98.375"R SHROUD SUPPORT LEG DESIGN PARA~TERS a.
S max <
Sm for tensile stresses at design pressure and temperature without seismic loads.
b.
S max <
Sm for tensile stresses at operating pressure and temperature with s~ismic loads.
c.
S max <
1.5 Sm for tensile stresses at o~erating pressure and temperature with m~. seismic + jet loads.
u.
S max, 2.0 s~ for tensile stresses at design pressure anrl temperature with ma.". sei.smic + jet loads.
e.
S max
~
0.4 Sy for compressive stresses at zero pressure and room temperature with seismic loads.
f.
S max
~
0.6 Sy for compressive stresses at operating pressure and temperature with m~~. seismic + jet loads.
g.
S max
~
0.8 Sy for compressive atresses at zero pressure and room tecp~rature with max. seismic + jet loads.
K.I-12
GENERAL ~ ELECTRIC SPEC. NO. 2lAlll1 PURCHASE SPECIFICAnON ATOMIC POWER EQUIPMENT OEPARTMENT SH NO.
13 REV. No.9 CONT ON S"F.F.:~ll.
7.5.2.
The anchor bolts and the sole plate on which the reactor vessel rests will be furnished by the Buyer.
7.5.3.
The drain nozzle shall extend 16 inches vertically below the bottom out-side surface of the reactor vessel and shall be of the full penetration design.
7.6.
External Attachments 7.6.1.
Brackets to support insulation shall be provided on the exterior of the reactor vessel in accordance with Drawing 886D499.
7.6.2.
Provisions shall be made for the attachment of at least 36 thermocouples in mounts on the reactor vessel exterior as specified on Drawing 886D499.
Exact location and number will be specified by the Buyer.
The thermocouples shall not be furnished by the Seller.
8.
MATERIALS 8.1.
All materials to be used shall be indicated on the Seller's drawings.
The Seller 9hal1 9ubmit for the Buyer's approval, all material selections
~nd mzterial purchatsing tsp~cification8.
8.2.
Records 8.2.1.
The Seller shall maintain complete records showing use o£ all materials so that it will be possible to relate every component of the finished reactor vessel to the original certification of the material and the fabrication history of the component.
The Seller shall prepare a summary of the heat number, chc~ical composition and mechanical properties for each reactor vessel component.
8.3.
Forgings 8.3.1.
Low alloy steel forgings for pressur~ parts shall be made in accordance with ASTM A-508, in accordance with ASME Code Case 1332-2, Paragraph 5.
Nozzles which are partial penetration welded as specified in 7.3.5. may be nickel-chroc-ium-iron forgings made in accordance with ASHE SB-166 modified in accordance with Code Case 1336 or &A-182, Grade F304.
Forging ingots shall be produced by vacuum degassed pouring.
8.4.
Plate 8.4.1.
Plate for pressure parts shall be in accordance with AS}ffi SA-302, Grade B, Firebox Quality, or as modified in accordance with ASME Code Case 1339, Para. 1.
K.I-13
PURCHASE SPECIFICATION 8.5.
Castings GENERAL~ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO. 2lAllll REV. NO. 9 SH NO.
14 CONT ON SHEE T 15 8.5.1.
The use of castings will be considered by the Buyer but specific Buyer approval shall be required.
Castings for pressure parts shall be made in accord-ance with ASME SA-356. Grade 10. Code Case 1333. Paragraph 1.
8.6.
Material for pressure parts shall be selected and worked to produce as fine a grain size as practical.
It shall be an objective of the fabrication technique to retain a grain size of 5 or finer in all material.
Grain size shall be deter-mined by the method in ASME El12.
8.7.
Heat Treatment 8.7.1.
Heat treatment of carbon and low alloy steel pressure parts shall consist of normalizing and then tempering at not less than l200°F.
For section thickness over 3 inches nominal. heat treatment shall consist of accelerated cooling from the austenitizing temperature to below the martensite finish temperature followed by tempering at not less than 1200°F to obtain tensile and impact properties com-parable to those developed by normalizing and temp~ring section thickness of less than 3 inches nominal.
~.~.
~echanical Properties 8.8.1.
The low alloy steel forging, plate and castings for pressure parts shall be tested in accordance with Paragraph 10.3. and shall have the mechanieal pro-perties requi~ed therein in addition to thos~ required by the applicable ASME Specification.
8.9.
Studs, Nuts, Bushings, aud Washers for Main Vessel Closure 8.9.1.
Studs shall conform to ASTM A540. Grade B23 or B24 and ASME Code Case l335-2~ Paragraph 4, Class. 3. 4 or 5.
8.9.2.
NutS. bushings and washers shall conform to AST~l A540. Grade B23 or B24 and Code Case 1335-2. Paragraph 4. Class 3. 4 or 5 but to suit the stud material used and to have a minimum difference in hardness of Rockwell C points from the stud material.
8.9.3.
Hardness and impact properties shall meet the requirements of Paragraph
'10.3.2.5.
"AUG: 2 6 1970 K.I-14
GENERAL Q ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT PURCHASE SPECI FICA TION 8.10.
Cladding Material SPEC. NO.
S.. NO.
2lAllll REV. NO. 9 15 CON T 0"4 'HEE T 16 8.10.1.
All internal carbon and low alloy steel surfaces of the reactor vessel, including the shell, bottom head, vessel flange (but not including top head and flange), nozzles for connecting stainless steel piping, and internal attachments, shall be clad with weld overlay meeting the following requirements:
8.10.1.1.
Weld overlay cladding shall be a minimum of 0.125 inches total thick-ness.
The finished surface shall have a composition equivalent to ASTM A371, Type ER308 or A240 - Type 304 except the carbon content shall not exceed 0.08 per-cent.
(Exception - the lower head may be clad with Inconel 82 or 182).
8.10.1.2.
Cladding in the "as-clad" condition is acceptable, provided the result-ing surface finish does not interfere with the ultrasonic and liquid penetrant test. requirements.
8.10.1.3.
The sealing surfaces of the reactor vessel head and shell flanges shall be weld overlay clad with austenitic stainless steel which consists of a minimum of two layers and a minimum of 0.25 inch total thickness.
The first layer shall be deposited with an analysis equivalent to ASTM A371, Type ER309.
The second and subsequent layers shall have a composition equivalent to ASTM A37l, Type ER308, except the carbon content shall not exceed 0.08 percent.
~~nimum thickness of 1/4 lnch shall apply after all machining including area under groove.
8.10.1.4.
Six cladding examination patches shall be prepared to meet the examination requirements of Paragraph I-I of t~e ASME Code for Inservice Inspection of Nuclear Reactor Coolant Systems.
8.10.2.
Nozzles for con~ecting carbon steel piping (except for the top head nozzles which shall be unclad) shall be clad through at least the thickness of the vessel wall or' one-half the diameter of the nozzle bore, whichever is less.
8.11.
Attachments 8.11.1.
Internal attachments other than the weld clad ferritic attachments (and the steam dryer hold-down brackets which may be carbon steel) shall be annealed stainless steel, Tyge 304 per ASTM A240 or ASTM A276, or Type F304 per ASTM AI82.
The core support structure shall be stainless steel clad low alloy or carbon steel or solid nickel-chromium-iron alloy per ASHE SB166, SB161 or SB168.
8.11.2.
External attachments to the reactor vessel shall be of the same material as the reactor vessel base material, or shall be of a material which has mechanical and impact properties compatible with the base material.
Where welds must be made to the attachments in the field, the material selected shall not require preheat or post-weld heat treatment.
K.I-1S
GEUERA L ~C) ELEeTAIC ATOMIC POWER EQUIPMENT DEPARTMENT PURCHASE SPECIFICATION 8.12.
Nozzle Safe Ends and Flanges SPEC. NO.
SH NO.
21Al11l REV. NO.
9 16 CONT ON SHEET 17 8.12.1.
Nozzle ends for austenitic pipe shall be ASTM A336, Class F8 or F8M; A240, Type 304, or Type 316; or A376, Type 304 or Type 316 solution heat treated stain-less steel, depending upon the mating pipe material selected by the Buyer.
Nozzle ends for carbon steel pipe shall be ASTM AlOS, Grade II, forgings except phosphorous content shall be 0.03S percent maximum and sulphur 0.040 percent maximum.
Propor-tions shall be as shown on Drawing l07CS30S.
8.12.2.
Standard flanges for flanged nozzles shall be ASTM AIOS, Grade II, except 0.035 percent maximum phosphorus and 0.040 percent maximum sulphur.
8.12.3.
Studs for standard flanges shall be SAl93, Grade B7.
Nuts for standard flanges shall be SAl94, Grade
~H.
8.13.
Pipes and tubes shall be ASTM A213, A249, A312, A376, solution heat treated, Grade TP304 or TP3l6; or A240, Type 304 plate welded and radiographed in accordance with ASME Code,Section III, Paragraph N624.
8.14.
Miscellaneous bolting material shall be subject to the Buyer's approval.
8.15.
W~ld Electrodes and Rods 8.15.1~
Material for weld electrot!es and rods shall be selected from ASTl1 A2"33, A298, A316, A371 or equivalent for other processes and reported to the Buyer for approval.
8.15.2.
All austenitic stainless steel welds and weld cladding shall contain con-trolled amounts of ferrite, confi~ed by quantitative tests.
The procedures for control of, and testing for the ferrite content of welds and weld cladding sh~ll be submitted to the Buyer for approval.
The acceptance standard for quantitative tests
~hall b~ either % Cr = 1.9 x % Ni, or S percent ferrite minimum.
8.16.
Alternate Materials The Seller shall be free to suggest alternate materials during preparatiou of de-tailed drawings and shall bring such alternates to the attention of the Buyer, but shall not make substitutions without approval of the Buyer.
Request shall include:
-8.16.1.
Reason r substitution 8.16.2.
Identification of the component or parts involved.
ISSUED:
AUG 2 6 1970 K.I-16
SPEC. NO. 2lAllll PURCHASE SPECIFICATION GEN ERAL0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT S~I NO.
17 REV. N0.9 CONT O~' SHEET 18 8.16.3.
Either the complete material specification similar to ASTM for. each type and form of proposed material, or the information as follows:
a.
Type of Service (structural, high/low pressure, temperature, weldable) b.
Manufactured Form (pipe, plate, tube, bar, bolting) c.
Size, thickness limits d.
Alloy Grades (C-steel, Alloy Steel, Stainless Steel Designations) e.
Steel-Making Process (Open hearth, basic electric) f.
Forming Process (Hot forged, hot/cold rolled, drawn, seamless welded, cast) g.
Heat Treatment, Stress Relief Parameters h.
Type, Location and Number of Mechanical Tests (Tensile, Bend Homogeniety, Hydrostatic)
L, l-Iechanical Property Acceptance Limits j.
Chemical Composition Acceptance Llmit~
k.
Inspection Requirements such as:
Radiography, Liquid Pene-tlant, Magnetic Particl~, Ultrasonic including acceptance limits 1.
Surface Finish ac~eptance limits 8.16.4.
.\llowable Stresses (if not an ASME material) 8.16.5.
For major pressure parts, additional information will be required re-garding details of previous applications of the material, impact strength, NDT temperature, micro-structure variations, creep, stress rupture, hardness, radia-tion damage, welding, forming, corrosion and temperature effects as applicable for
~ngineering evaluation of the application and as required for code purposes.
I$5\1EO:
AUG 2 6 1970 K.I-I7
PURCHASE SPECIFICATION GENERALO ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO. 2lAl111 REV. No.9 SMNO.
18 CONT ON SHEET 19 8.17. S:msiti2ationof Stainless steel..
All furnace sensitized wrought stainless steel base metal shall be eliminated by either of the following:
a.
Schedule the manufacturing sequences such that wrought stainless steel is not subjected to furnace heat treat-ment above 800°F after final solution heat treatment.
b.
If any wrought stainless steel base metals have been furnace sensitized after they have been fabricated and installed in the reactor pressure vessel, they shall be removed and replaced per a. above or overlayed with.
308L stainless steel cladding.
9.
FABRICATION 9.1.
Procedures 9.1.1.
The Seller shall submit for the Buyer's apploval, all of the following procedures and procedure specification.
9.1.1.1.
Heat traatmant pro~eaureo foe all thermal pruc~~~~s exceeding 800°F after the mill rolling or forging or foundry casting operation.
9.1.1.2.
Forming and bending procedures for all forming during fabrication sub-sequent to mil: forging or rolling or foundry forming and cladding.
9.1.1.3.
Welding and weld repair procedures including temporary welds as required in accordance with the AS~m Cede,Section IX, Paragraphs Q-lO and 11, and QN-lO and 11,Section III, Paragraph N-540.
9.1.1.4; Method of qualifying welding procedures and performance, if other than ASME Code,Section IX and III.
9.1.1.5.
Repair procedures for major and minor defects as defined in Paragraph 9.4.
9.1.1.6.
Drawings showing location and preparation of test specimens, including specimens required in Attachment B.
~.1.1.1.
Fabrication schedule including the detailed sequence to be followed in fabrication of the vessel.
9.1.2.
All work by the Seller or his sub-suppliers shall be performed in accord-ance'with Buyer approved drawing, and fabrication and test procedures.
9.2.
~.ateri.al Cutting 9.2.1.
Stainless steel and carbon steel shall be cut to size or shaped by machin-ing, shearing or thermal cutting.
K.I-18
PURCHASE SPECIFICATION GENERALG ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT SPEC. NO. 21Allll REV. NO. 9 SH NO.
19 CONT 0'"' SHEET 20 9.2.2.
Thermal cutting of stainless steel shall be followed by the removal of approximately 1/32 inch depth.from the cut surface.
Thermal cutting of,carbon steel shall be followed by the removal of oxides.
9.3.
Welding 9.3.1.
The reactor vessel base material pre-heat and interpass temperature shall be as specified in the welding procedures, but in no case less than 300°F, except weld overlay pre-heat which shall be no less than 20QoF.
Pre-heat temperature shall be maintained after welding until start of post-weld heat treatment.
Pre-heating techniques shall be such as to ensure that the full thickness :of the weld joint preparation and adjacent base material is at the specified te~perature for the distance of "T" or two inches, whichever is greater, where liT" is the material thickness.
9.3.2.
When stainl~ss steel or nickel-chromium-iron alloy is welded to itself or to each other, no pre-heat is required, except when the heat-affected zone reaches ferritic base material as in the cases of welding to buttered nozzle ends or cladding.
When the buttering or cladding is less than 1/4 inch thick, pre-heat to at least 200°F is required, followed by post-weld heat treatment ex-cept that subsequent welding to cladding greater than 1/8 inch thick may be done without pre-heat if the specific welding procedure is qualified to show that the heat affected zone does not reach the base metal.
9.3.3.
All surfaces (to be welded) shall be free of cavities or protrusions which may interfere with the welding procedure.
9.3.4.
Pre-heat, welding and post-weld treat~ent shall be planned and conducted to minimize undue distortion or warpi~g of the parts and preclude cracking.
9.3.5.
Machined surfaces and tnreads shall be protected against weld splatter.
9.3.6.
Stainless steel welds shall be cleaned with stainless steel wool or stain-let9s steel brushes before'adding the next bead and following the final bC:ld to facilitate inspection.
The light oxide discoloration which forms on the weld sur-face need not be removed.
9.3.7.
Welds shall be cleaned of slag and flux between passes and following the final deposit.
9.3.8.
Any cracks, blow holes, or other defects which appear on the surface of weld beads shall be removed by machining, chipping, grinding, or arc gouging.
Austenitic~weld repairs, if arc gouged shall be followed by grinding.
Austenitic welds shall not be peened; ferritic welds may be peened under controlled condi-tions with the approval of the Buyer.
9.3.9.
Wide welds to overcome poor fj.t are not permissible.
Poor fits shall be remedied by. suitable meatis such as regrooving, and approved by the Buyer.
Except for small cavities, the Seller shall not correct a plate edge deficiency unless approved by the Buyer.
The Buyer may require radiography or other methods of ex-amination of welds used to correct* plate edge deficiencies.
ISSUEO:
AUG 2.6 1970 K.I-19
PURCHASE SPECI FICA nON GENERAL () ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO.
SH NO.
2lAIIII REV. No.9 20 CONT ON SHEET 21 9.3.10.
Post-weld heat treatment temperature shall be 1100°F-1150°F. Interstage post-weld heat treatment holding time. shall be 15 minutes minimum.
Final post-weld heat treatment holding time shall be one hour per inch of thickness, minimum.
9.4.
Repair of Defects 9.4.1.
Repair procedures shall be prepared for the repair of all defects.
Major defects shall require prior approval by the Buyer and may require witnessing by the Buyer's representative.
Major repair is defined as (1) a repair to material other than weld metal which requires an excavatiDn greater than 3/8 inch deep or 10 percent of the wall thickness, whichever is less; (2) the repair of any cracks, other than crater cracks, in any material or weld metal; and (3) the repair of any defect which is indicative of either a fundamental material problem or a process out of control.
A minor repair is defined as all other repairs.
10.
INSPECTION AND TEST 10.1.
General
'The Seller shall submit for the Buyer's approval, the following inspection and test proce'.iures:
10.1.1.
Ultrasonic Examination Procedure for the following:
a.
Forginlts b.
Plate c.
Welds d.
Weld build-ups e.
Cladding f.
Tubular Products 10.1.2.
Magnetic Particle Examination Procedures for the following:
10.1.2.1.
Carbon steel and low alloy steel forgings 10.1.2.2.
Carbon steel and low alloy steel welds 10.1.2.3.
Weld Build-ups 10.1.2.4.
Bolting 10.1.2.5.
Carbon steel and low alloy steel tubular products 10.1.2.6.
Carbon steel and low alloy steel castings 10.1.2.7.
Edge preparations of carbon steel and low alloy steel materials 10.1.*3.
Liquid Penetrant Examination Procedures for the following:
10.1.3.1.
Austenitic Forgings ISSUED:
AUG 2 6 1970 K.I-20
REV. NO. ?
CONT ON SHEF:' 22 GENERAL Q ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT PURCHASE SPECIFICATION 10.1.3.2.
Austenitic Welds 10.1.3.3.
Austenitic Weld Buildup 10.1.3.4.
Cladding 10.1.3.5.
Austenitic Tubular Products 10.1.3.6.
Austenitic Castings 10.1.3.7.
Edge Preparations of Austenitic Materials SPEC. NO. 21A111l SH NO.
21 10.1.4.
Radiographic examination procedures for welds, castings, for each type of radiographic source above and below 2 MEV.
10.1.5.
Hydrostatic Examination Procedures 10.1.6.
Leak Check Procedures 10.1.7.
Methods, processes and equipment to be used in establishing "as-built" dimensions and alignment checks which are not normally used in the shop.
10.2.
Definitions 10.2.1.
"As-Fabricated" Specimens.
"As-fabricated" specimens are mechanical test specimens taken from carbon and low alloi st~~l forgings and plates llsed in the vessel fabrication from each heat and heat treatment lot and from welds between base material made by each welding procedure used and in a thickness equal to or greater than the thickest weld made with each procedure.
Coupons for "as-fabri-cated" specimens shall be taken from the forgings or plates following all hot work-ing or forming and all heat treatment except post-weld heat treatment.
These coupons shall then be subj~cted to a post-weld heat treatment equivalent to the treatments which the parts it represents will receive in the completed vessel.
Thi-shall consist cf holding the coupon at the post-weld heat treatment tempera-ture for a time equal to or greater than the longest accumulated time any part it represents shall be at the post-weld heat Creatment temperature.
10.2.2.
"1/4T x T" Locati.on.
The "1/4T x T" location of specimens is defined as a location within the material no closer than "1/4T" from one quenched surface, and jro closer than "T" from any other quenched edge, where "T" is the nominal thickness of the material.
ISSUED:
AUG 2 6 1970 K.I-21
PURCHASE SPECIFICATION GEt~ERAL() ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT SPEC. NO. 21Allll REV. NO.
9 SH NO.
22 CONT ON SHEET23 10.2.3.
NIL-ductility transition (NDT) temperature.
The nil-ductility;transi-tion (NDT) temperature is defined as the temperature at which a specimen is broken in a series of tests in which duplicate no-break performance occurs at a temperature 10°F higher, when tested in accordance with ASTM E208.
10.2.4.
Impact transition curve.
A curve representing breaking energy vs tem-perature from at least twelve Type A Charpy-V specimens, tested in accordance with ASTM A370, except each specimen tested at a different temperature.
The temperature ranSe of testing shall establish the upper plateau, the transition region, and the lower plateau.
~ach plateau shall' be determined by at least one, but not more than two points.
The remaining specimens shall be used to develop the transition region.
The lower plateau need not be developed if it occurs below -BO°F.
10.2.5.
A "lot of Material" consists of all material from one heat (one melt) in one heat treatment furnace charge.
10.3.
Material Mechanical Tests 10.3.1.
Mechanical properties 10.3.1.1.
Impact properties of all as-fabricated carbon and low alloy steel used in the main c:loeu'[e flatlcee and the shell and h~ad materials connecting to these rlCi1i~t:~ $hall Wet:L the reliulreU1t:uL~ UL the ASi*lF; Code, Sect Lon III, Pat..agraph N-J,JO at a temperature no higher than 10°f.
In addition, this material shall have an NDT temperature no higher 10°F as determined per ASTM E208.
10.3.1.2.
Impact properties of all other "as-fa~ricatedn carbon and low alloy steel pressure containing material and the vessel support skirt material shall meet the requirements of the ASME Code,Section III, N-330 at a temperature no higher than 40°F.
In addition, this material shall have an NDT temperature no higher than 40°F as determined per ASTM E203.
The actual NDT temperature of all material opposite the center of
~he active fuel of the core as indicated on Drawing 886D499 shall be determined.
10.3.1.3.
Tensile te~t properties of all ma~erials shall be inspected and tested to meet the requirement of the applicable A~~m Code or ASTM specification.
10.3.1.4.
Test data shall be reported to the Buyer.
10.3.2.
Required number and specimen location.
The number and location of tensile and impact'test specimens required shall be per ASME Code,Section III, N-3l3.2 and the following depending on the form of the material.
The following tests may be integrated with the tests required by the ASME Code and ASTM Specification wherever possible.
ISSUED:
AUG 2 6 1970 K.I-22
PURCHASE SPECIFICATION GEt~ERAL,? ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT SPEC. NO. 2lAllll REV. No.9 SH NO.
23 CONT ON SHEET24 10.3.2.1.
Vessel flange and head flange forgings.
Tangential specimens, as-fabri-cated, shall be taken from locations per ASME Code,Section III, N-313.2 (d) (2).
A total of at least 2 tensile, 6 Charpy-V impact and 4 drop weight specimens shall be tested for each flange from which 1 tensile, 3 Charpy-V impact and 2 drop weight specimens shall De located approximately 180 0 from the other specimens.
The material shall meet the requirements of Paragraph 10.3.1.
10.3.2.2.
Low-alloy steel nozzle forgings.
Specimens, as-fabricated, shall be taken from locations per ASME Code,Section III, N-3l3.2 (d) for forged nozzles.
At least 2 tensile, 3 Charpy-V and 2 drop weight specimens shall be tested for each heat and heat treatment charge.
The material shall meet the r~quirements of Paragraph 10.3.1.
10.3.2.3.
In addition to the tests required by the ASME Boiler and Pressure Vessel Code, longitudinal specimens (parallel to the primary rolling direction), as-fabri-cated, shall be taken from the 1/4T x T location.
At least 2 drop weight specimens shall be tested from the top end (top as determined by ingot pouring) of each mill rolled plate and each heat treatment charge.
The material shall meet the require-ments of Paragraph 10.3.1.
Additional drop weight specimens shall be required for NDT temperature determination per Paragraph 10.3.1.2. for plates located opposite the center of the core.
10.3.2.4.
Castings.
Tangential specimens, as-fabricated, shall be taken from lo-cations per f~~m Code, Section lIt, N-3l3.2 (d).
Castings 1000 1b w~ight and under 3hall have a total of 1 tensile specimen, I metallographic specimen, and 3 Charpy-V and 2 drop weight specimens, te~ted :f5or each heat and heat treatment charge.
Castings over 1000 lb weight shall have a tot~l of 2 tensile specimens, 2 metallo-graphic specimens, 6 Charpy-V and 4 drop weight specimens tested from which 1 tensile specimen, 1 meta1lographic specimen, 3 Charpy-V and 2 drop weight speci-mens shall be taken 180 0 apart and/or diagonally opposite.
The metallographic speci-mens shall be for reference only.
Additional drop weight specimens shall be required in accordance with Paragraph 10.3.1.1. if the casting is located in the core area.
The material shall meet the requirements of Paragraph 10.3.1.
10.3.2.5.
Studs, nuts, bushings and washers for main vessel closure.
Hardness tests shall be made on all main vessel closure bolting to demonstrate that heat treatment has been performed.
Studs, nuts and bHshings shall be hardness tested individually.
One sample from each lot of washers shall be hardness tested.
Im-pact tests required. by ASrlli Code,Section III, Paragraph N-330 shall meet the Code
~equirements at a temperature no higher than 10°F.
In addition the the magnetic particle aT liquid penetrant acceptance standards specified in AS}ffi Code,Section III, Paragraph N-325, axial defects of less than thread depth shall be investigated to determine their nature.
Any cracks or sharply defined linear indications are unacceptable.
ISSUCO:
~*.L;Li 2 6 1970 K.I-23
GEt' ERAL (0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT PURCHASE SPECI FICA TlON 10.4.
Welded Base Material - Mechanical Tests SPH. NO. 2lAIli1 REV. NO.
9
$H NO.
24 CONT ON ''loE?)
10.4.1.
AS}m code weld test plates.
The Seller shall prepare and test weld coupons of Category A and B joints in accordance with ASME Code,Section III N-7l3.
The impact test temperatures shall be determined in accordance
,~ith Paragraph 10.3.1. of this specification.
In addition to the tests required by the Code, 6 drop weight specimens shall be taken from the 1/4T x T location from these plates and, if different welding procedures are used, from plates for base material to base material welds of Category D joints as defined in ASME Code,Section III, N-46l.
Two each of the drop weight specimens shall represent the base metal, heat affected zone and weld metal.
The specimens shall meet the re-quirements of Paragraph 10.3.1.2.
Additional drop weight specimens shall be required in accordance with Paragraph 10.3.1.2. if the welding procedure is to be applied in the area opposite the core.
10.4.2.
One of the test plates of Category A or B required in 10.4.1. above shall be selected by the Buyer for the fabrication tests required in Attachment B, Para-graph 2.
The Seller shall perform all required tests and reports.
These tests are for information only, but time is of the essence and the tests should be per-formed and the results reported as early as practical.
10.4.3.
The Seller shall pr~p~re and ship) but not test, Surveillance Test Pro-gram material and specimens in accordance with Attachment H, Paragraph 3.
10.4.4.
[lange forging weld test plate.
In the event the vessel and head flanges are made by weJding two or more forged segments, the Seller shall prepare a weld test plate from the forging material.
Impact anc tensile specimens shall be pre-pared and tested.
The specimens shall be prepared from material in the weld-heat-affected zone and from the weld metal.
Test results shall meet the requirements of Paragraph 10.3.1.
10.5.
Ult~nic Inspection 10.5.1.
Ultrasonic inspection of plate and forged material shall be performed in accordance with ASHE Code,Section III, except that ASME Case Interpretation 1338-2, Alternate 2 shall not be acceptable, and the plate material testing shall Le a 100 percent volumetric inspection and shall be perforrr.ed after forming and heat treat-ment.
The following acceptance criteria shall apply in addition to Code require-ments.
A defect which causes any echo indication that exceeds 50 percent of the ipdication from the calibration standard and that is continuous during movement of the transducer more than 3 inches in any direction shall be unacceptable, A chart shall be maintained of defects with 50 percent or greater loss of back reflection.
K.I-24
REV. NO. 9 CONT ON S'H:ET26 PURCHASE SPECI FICA TION GEN ERAL Q ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO. 2L\llll Sit
~IO.
2S 10.5.2.
Prior to connecting any attachment, support or bracket, except insulation and thermocouple brackets, to the interior or exterior of plate portions of the vessel by means other than groove welds below the plate, the plate shall be ultra-sonically inspected.
The plate shall be inspected to a depth at least equal to the thickness of the part being joined, and over the entire area of the subsequent connection plus a band all around this area of width equal to half the thickness of the part being joined.
The inspection shall be in accordance vrLth ASNE Code,Section III, Paragraph N-32l, using longitudinal wave technique.
The surface shall be 100 percent inspected with the transverse interval being no greater than 90 per-cent of the crystal diameter.
10.5.2.1.
Reference standard.
The Seller shall prepare a reference standard which consists of a flat bottom hole having a diameter equal to one-quarter of the thick-ness of the part befng joined or 1/4 inch diameter whichever is greater.
The bottom of the hole shall be one thickness of the part being joined below the plate surface.
This reference stacdard shall be used for calibration purposes.
10.5.2.2.
Acceptance standards.
Any defect which produces a trace line pattern equal to or in excess of the appropriate reference 5tandard shall be unacceptable.
10.5.3.
The main closure stud, nut, bushing and washer material shall be ultra-sonically tested follQ,-ring heat treatment and rough machfrrtng to 250 rms 0'[ be r t er r Luisi! using both LcugLtudLnaL awl
~l1t~a(
WdV~ t echnLques.
Loug.I tuJ1nal wave exam-ination shall be performed on 100 percent of the cylindrical surface, and in addi-tion on stud material from both ends of each stnd.
The longitudinal/wave trans-ducer shall ha~Je a maximum diameter of 1/2 inc~.
Shear wave examination shall be performed on 100 percent of the outer cy1indrica~ surface in both axial and cir-cumferential directions.
10.5.3.1.
Reference standards.
The Seller shall prepare a reference standard of the same material thickness and curvature as the part being examined.
The refer-ence standard shall contain calibration features as follows:
a.
L~ngitudinal Wave-Radial Scan:
1/2 inch diameter flat-bottom hole*
having a depth equal to 10 percent of the material thickness.
b.
Longitudinal Wave-End Scan:
Flat-bottom hole uith area equal to 1 percent of stud cross-section or 1/4 inch diameter,
~i\ichever is smaller, ha7ing a depth of 1/2 inch.
c.
Sh~ar Wave:
Square bottomed notches 1 inch long anrl 1 percent of the part thickness in depth, both axial and circumfere.ntial.
ISSUED:
AUG 2 6 1970 K.I-25
PURCHASE SPECIFICATION GEN ERALG ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO. 2lAllll "EV. NO.
9 SM NO.
26 CONT ON UiEET27 10.5.3.2.
Acceptance standards.
Any defect which produces a trace line pattern (echo indication) greater than the indication from the applicable calibration feature shall be unacceptable.
A ~istance-amplitude curve may be used for the longitudinal wave examination.
The curve may be a line established by plugging the hole and examining it from both sides of the material.
For end examination of studs the curve may be established for half the stud length and applied to an examination from each end to the center.
10.6.
Cladding 10.6.1.
Ultrasonic inspection - cladding general.
10.6.1.1.
The cladding bond shall be tested with the transducer on the clad side using a suitable covplant.
The entire clad surface shall be inspected at inter-vals 1.4 times the base material thickness, but not greater than 12 inches, trans-verse to the direction of welding.
10.6.1.2.
Reference standard.
The Seller shall prepare a reference standard which consists of a flat bottom groove in typical clad pl~te.
The groove shall be 0.35 inch maximum width by at least one crystal diameter long, parallel to the direction of welding.
The groove shall be formed by machining the base metal within 1/32 inch
~f th~
~l?~~~~e in~~~f~~~
~n~
~~chpo wi.~h ni~ri~
A~irl to TP-movp-excess ferritic material from the Interfac~.
Thl~
c~[~r~nce staildard shall be used for calibration pur1>,",ses.
10.6.1.3.
Acceptance standards.
Cladding whi:h produces a trace line pattern equal to or in excess of the appropriate Reference Standard shall be unacceptable if a continuous pattern occurs during movement of the transducer more than three inches in any direction or if oce cr more patterns occur during movement of the transducer less than one inch in anyone pattern.
10.6.2.
Liquid penetrant 'inspection - cladding general.
10.6.2.1.
All clad areas and clad repairs shall be liquid penetrant inspected per ASME Code,Section III, N-627.
The followinp, indications shall constitute unaccept-able defects and shall be repaired.
10.6.2.2.
Any crack-like indications or incomplete fusion.
10.6.2.3.
Linearly-disposed spot indications of 4 or more spots spaced 1/4 inch or less from edge to edge of the indications.
10.6.2.4.
Spot indications which are indicative of defects greater than 1/32 inch deep as rev~aled by bleed-out.
K.I-26
GENERAL Q ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT PURCHASE SPECIFICA TlON 10.6.3.
Ultrasonic inspection - cladding special areas.
SPEC. NO. 2lAllll REV. No.9 SH NO.
27 CONT ON 5HEET28 10.6.3.1.
The flange seal surfac~s shall be inspected for bond to the flanges as per 10.6.1. except that the inspection shall be over 100 percent of the area.
Prior to final machining the volume 1/8 inch above and below the surfaces on which the double seals will seat shall be 100 percent inspected for defect using longi-tudinal wave technique.
The acceptance criteria shall be that any defect which produces a trace line pattern equal to or in excess of a 1/16 inch flat bottom hole may be unacceptable.
10.6.3.2.
The final machined surfaces on which the double seals seat shall be inspected by surface wave technique.
Any defect producing a signal greater than the signal produced by the 0.002 inch deep by 1/8 inch long spark machined groove in a reference standard which the Seller shall furnish may be cause for rejection.
10.6.4.
Liquid penetrant inspection - cladding special areas.
10.6.4.1.
The area of the flange seal surfaces on which the double seals seat shall be liquid penetrant inspected per As~m Code,Section III, N-627, except that any indication of any type shall be unacceptable.
10.6.5.
10.6.5.1.
Both internal and external surfaces of all low alloy steel plate material shall be magnetic particle inspected per ASME Code,Section III, Paragraph N-626 following for~ing and heat treatment.
TIle ac~eptance standard of AS~ffi Code,Section III, Paragraph' N-62S.5 shall apply.
10.6.6.
Openings in pressurp. parts.
10.6.6.1.
The entire surface of all openings for partial penetration nozzles, re-gardle~s of size, except for the seal leak detection connection, shall be examined 1n accordance with AS}ffi Code,Section III, N-S13.
10.6.6.2.
The entire surface of the finish~d stud holes in the head flange and the holes in the vessel flange prior to tapping shall be examined by the
~ethods of AS}m Code,Section III, N-S13.
Any indication of cracks or linear indications shall be reported to the Buyer for information.
Any crack or linear indication may be subject to ?emoval and repair if required.
10.7.
Welds 10.7.1.
Radiographs.
10.7.1.1.
Gamma rays shall
~ot be used unless approved by the Buyer.
"'AUG 2 6 1970 J
K.I-27
GE~JERAL ~ ELECTRIC PURCHASE SPEel FICA TlON A TOMle POWER EOUIPMENT DE PARTM(t~ r
!r r r,
~':"
21Allll REV. NO.
9 s ** '.;
2R CO"".,.
ON SHEET29 10.7.1.2.
Films shall be suitably marked to identify the weld.
Film identifica-tion markings shall coincide with the detail drawing markings for each weld.
10.7.2.
Ultrasonic Testing.
All full-penetration pressure carrying welds shall be 100 percent ultrasonically tested as described in Paragraph N-625 of Section III of the Code.
Both shear wave and longitudinal wave techniques shall be used.
10.7.2.1.
Indications with 50 percent or greater loss of back reflection or 50 percent of indication from the calibration standard shall be recorded on charts "to scale" so that they can be used as a basis for comparison with subsequent "in-service" ultrasonic tests.
10.7.2.2.
Any work (additional investigation and testing or repair of welds) which is requested by the Buyer as a result of the ultrasoni~ testing shall be subject to mutual Buyer-Seller agreement.
10.8.
Hydrostatic Tests 10.8.1.
After completion of fabrication but prior to shipment, while the vessel is supported on its normal supports, the reactor
~ssel shall be pressure tested in accordance with the AS~m Boiler and Pressure Vessel Code,Section III, Para-graph N-7l2.
(Paragraph numbering as per Winter 1966 Addenda.)
Reactor vessel material temperature shail be at least lUU~F.
In no caGe, however: shall the water temperature be higher than 180°F.
Suitable gasket material instead of metal O-rings may be used for this test.
Hydrotest water shall be d ther potable tap water "lith addition of TSP, or demineralized wat er,
Hater may be heated with steam provided that the source of feedwater i~ potable or deminer~lized water.
10.8.2.
Following the Code test, the vessel shall be hydrostatically tested at design pressure with new O-rings.
This test shall demonstrcte that the head seal meets the sealing requirements.
10.8.3.
Altetnative Procedures.
As an alternative to 10.8.1 and 10.8.2, the second hy~atic test may be combined 't"ith the Code test if metal O-rings are used and the'stud tension-used, is normal operating bolt-up tennion.
A perQiss-ible variation on the above would be to perform the Code hydrostatic test of 10.8.1 using metal O-rings and hydrostatic test bolt-up tension.
After this test has been completed, the pressure is to be dropped to zero psi and stud tension. decreased
~o normal bolt-up tension.
The leak testing of 10.8.2 is
.then to be performed.
10.9.
The placing of the head, tightening the studs to operating bolt-up loads, unbolting and removal of the head over the studs shall be demonstrated.
The elapsed times for each step shall be recorded.
10.10.
Final inspection after hydrostatic test per ASME Code,Section III, N-6l8 shall include seal surfaces and the nozzle weld preps.
ISS~ot 2 6 1970 K.1-28
S~EC..... 0. 22All11 SH NO.
29 PURCHASE SPECIFICATION GENERAL fD ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT REV. NO. 9 CONT 0... SHEET 30 10.11.
Immediately prior to hydrostatic testing of the reactor vessel, all in-terior surfaces that will contact w~ter during the hydrostatic test, all nozzle fixtures, all piping which will be wed to fill the reactor vessel, and all surfaces of stainless steel and Ni-Cr-Fe components shall be cleaned to remove all halide-bearing soils, grease, oil, penetrant materials, inks, chalk or crayon marks, and all dirt and debris.
All loose dirt and other foreign materials shall be removed by sweeping or vacuuming.
Deposits of grease and oil shall be removed with an appropriate solvent.
Tightly adhering soils may be removed with the aid of stainless steel brushes which have not been previously used on carbon steel, or by grinding.
The vessel shall then be cleaned with high-pressure water con-taining a minimum of 500 ppm of phosphate added as TSP.
The vessel and water temperature shall be less than 180°F during the TSP cleaning step.
The water pressure shall be a minimum of 5,000 psi.
The trisodium phosphate shall be reagent grade per American Chemical Society standards.
Water shall be potable water con-taining less than 50 ppm chlorides, 10 ppm fluorides, and 1 ppm sulfides, or de-mineralized water containing not more than I ppm chlorides, 1 ppm fluorides and 1 ppm sulfides.
The TSP solution may be left on the surface of the vessel.
- However, the vessel must be completely drained so that no puddles of TSP solution remain.
The cleanliness of the vessel shall be checked visually and with the aid of an ultraviolet light to assure that the vessel is clean.
The ultraviolet examination shall be conducted under darkened conditions with a lamp having a minimum brilliance of lOO~foot c~ndJp.~.
A ~ermissible var~ation on the abo~e ulLraviol~L lIght cl~un*
liness e~amination will be to wipe the vessel with clean rags as an tnspp-ction method for determining cleanliness.
10.11.1.
It is intended that hydrostatic tectin~ follow immediately after clean-ing and that all plumbing, welding, or testing work be performed orior ro clean-ing.
During any entry of personnel into the vessel after cleaning has been com-pleted shoe covers shall be worn and clean-room conditions maintained in the re-actor vessel.
10.12.
The water used to fill the vessels for the hydrostatic test may be either tap water or demineralized water.
For vessels filled with tap
,~ater plus a mini-mum phosphate addition of five times the crloride content of the test water in the vessel (but not less than 100 ppm phosphate),
TSP shall be added as reagent-grade
'trisodium phosphate (TSP).
The water used to fill the vessel shall meet the following requirements:
)
pH
=
Cl Fl
=
S
=
5.8 to 8.0 less than 50 ppm less than 10 ppm less than I ppm K.I-29
GENERAL G ELECTRIC PUQCHASE SPECIFICA TlON ATOMIC POWER EQUIPMENT DEPARTMENT
~~*(c. t.o. 21Alill REV. No.9 SH "'0.
30 CONT 0... 'HEEl 31 10.12.1.
For vessels filled with demineralized water, the water in the vessel shall meet the following requirements:
pH Cl
=
F1
=
S
=
5.8 to 8.0 not more than 1 ppm not more than 1 ppm not more than 1 ppm 10.2.2.
The conductivity of the fill water shall be 3 micro mho/cm maximum.
TIle vessel shall be dried as soon as practical after hydro.
TSP shall
~e washed, using demineralized water, from any surface which is heated to above 500°F.
11.
PREPARATION FOR SHIPMENT 11.1.
~ning Procedures 11.1.1.
The Seller shall submit for the Buyer's approval, all cleaning procedures, preserving procedures and a list of cleaning agenta and preservatives together with their chemical content which shall be used during fabrication and in prepar~tion for shipment.
In lieu of a complete chemical analysis, the Buyer shall accept a repor~ whicil
~lalt:~ Un: \;1.1vLi~es, fluvi"i~;::~
.:l~~
~~lf~:-
c~~t~~t::.
0th Q!,
htt1'"Tl'lfl11 elements should also be reported.
11.2.
lnlerior Surfaces 11.2.1.
Interior surfaces of the re~ctor vessel shall be thoroughly cleaned to be visibly free of lubricant, weld spatter, chips, imbedded iron particles and other foreign materials.
The vess~l shall then be cleaned in accordance with Paragraph 10.11 except that demineralized water with 500 ppm phosphate shall be us~d.
After the vessel and head interior surfaces are cleaned, they shall be dried with hot a~r or other suitable means and the vessel and head sealed to prevent entry of moisture, dirt, and other harmful materials.
The coating of TSP from the final wash may be left on the surface.
11.3.
Exterior Surfaces 11.3.1.
Where vessels are to be shipped over salt water (i.e., Peachbottom 2 & 3 and Browns Ferry 2 & 3)the fo l l.cwf.ng requirements apply:
Exterior carbon steel surfaces sh be clean~d of oil and grease after which mill scale, rust, rust scale, paint and other foreig'l matter shall be thoroughly removed by such means as sandblasting.
All surfaces shall be brushed or air cleaned to r~move all traces of sand or grit and shall then be dried and painted.
Sufficient coats of an approved paint (ap-proved by the Buyer - Superior Primary Lead 01746 is not approved) shall be applied to all exterior carbon steel surfaces (stainless steel and Ni~Cr-Fe sur-faces shall ~ot be painted) to assure complete coverage and sufficient protection f~om the we~ther.
Exterior stainless steel and Ni-Cr-Fe surf~ces shall be coated witl\
a juitable'm~terial to prev~nt moisture contact with the surfaces.
The vessel and
.~ :
R.I-30
PURCHASE SPECIFICATION 11.3.1.
(Continuted)
GErJERAL0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT S~CC. NO. 2lAlll1 1M NO.
31 "lEV. No.9 COHT ON 'H,nT 32 closure head shall be purged with dry nitrogen until the gas within the vessel and closure head has attained a dew point of 32°F.
The vessel and closure head shall be fitted with a suitable nitrogen pressure system to maintain a positive pressure of nitrogen within the vessel and closure head.
In lieu of the nitrogen purge re-quirements for the vessel and closure head, it will be acceptable to coat the in-terior surfaces with tectyl (or other Buyer approved preservatives) provided the Seller assumes this additional cleanup responsibility once the vessel and closure head are received at the site.
Where vessels are to be shipped over inland routes (i.e *., Brown Ferry 1) no painting, nitrogen purge or nitrogen pressure system will be required.
Protection of exterior stainless steel surfaces will be required, as above.
11.4.
Small Parts 11.4.1.
Small, loose pieces, including bolting, tools, gaskets, etc., shall be adequately crated or boxed for protection during shipment.
Parts subject to rusting shall be suitably protected.
All boxes, crates and shipments shall be marked with the equipment piece number.
11.5.
Shipping Weight and Dimensions 11.5.1.
Estimated sh1ppiTlg weights and overall clearance dLmensLons bhdii lit: Sa,owl1 on the drawings when submitted to the Buyer for approval
- 11.6.
Shipping Skids 11.6.1.
The reactor vessel body shall be shipped on a skid which supports the reactor vessel in a horizontal position.
The top head shall likewise be shipped on a skid.
The skids shall be designed to support the reactor vessel adequately and securely during shipment to the site and to permit movement on rollers (not supplied by Seller) at the p.rection site.
12.
SUBMITTALS
~2.1.
Tabulation (for Information Only) 12.1.1.
Fabrication, qualification and inspection procedures, reports processes, and calculations are tabulat~d below (all of which require submittal to the Buyer in quanti~ies as shown on Attachment A).
This tabulation shall in no way be con-strued as being complete or limiting the documents necessary to meet the require-ments of this specification.
AUG 2 6 1970 a.
Heat treatment procedure b.
Forming and bending procedure c.
Welding and weld repair procedure specification d.
Repair procedures e.
Cleaning and preserving procedures f.
Ferrite content or Ni/Cr ratio control procedure g.
Ultrasonic exa~ination procedure h.
}fugnetic particle examination procedure
'liVED, K.I-31
GEN ERAL (~) ELECTRIC ATOMIC POWER EQUIPMENT DEPART.vENT PUQCHASE SPECIFICATION 12.1.1.
(continued)
!.~CC. NO.
~... "",0.
21All11 REV. NO. 9 32 CONT 0... ""'CF;T 33 i.
Liquid penetrant examination procedure j.
Radiographic examination procedure k.
Hydrostatic examination procedure 1.
Leak check procedure m.
Measurement reports n.
Summary reports o.
liAs-built" dimensions and alignment checks procedures p.
Design analysis calculations q.
Material purchase specifications r.
Material selections 12.2.
The following shall be submitted in accordance with Attachment A:
12.2.1.
Drawings 12.2.1.1.
Outline Drawings - A drawing depicting the outline of the reactor vessel indicating overall dimensions, location and size of nozzles, location of supports, shipping and operating weights.
1'..'.1.2.
Assembly Draw1"gs - A section drawln~ depict1ng the 3rran8emen~ of the functional parta, parts list and material designations.
12.2.1.3.
Detail Drawings - Drawings for details of construction such as
~~cld preparations, surface finishes, finished dfmet.s Lons, noazLes, lifting attachments, insulation attachments, thermocouple pads, flanges and supports.
12.2.1.4.
Drawings for Approval - Outline, assembly and detail drawings shall be submitted for approval.
TIle detail drawings submitted shall be for design details enumernted in 12.2.1.3. which are required for coordination with piping and struc-ture and design details which are at variance with the code or the requirements of this specification.
12.2.1.5.
Controlling location arrangement drawings.
One or more drawings shall be devoted exclusively to outl:f.ne dimensions such that mating components designed and supplied by others such as piping, anchor bolts, instruments, etc., may be pro-cured fOT an exact jit with the reactor vessel assembly.
These drawings shall show reference to the controlling detail drawings and show overall dimensions and loca-tions on r.eactor vessel.
12.2.1.6.
Drawings to be Certified - Outlines assembly and detail drawings for design coordination shall, upon completion of the design, be certified to be correct with no further changcs required.
No alterations may be madc to the de-sign after certification without the
~pproval of the Buycr.
'SSUEO:
AUG 2 61970 K.I-32
CONT 0.... SHF:ET 34 PuqCHA SE SP ECI FICA TlON GENE RAL~' ELE ern IC ATO~IC POWER EQUIPMENT DEPART..... ENl
'jPf.C. NO.
~II "10.
2lAllll 33 RE\(. NO.
~
12.2.1.7.
As-Built Drawings - Prior to shipment of the reactor vessel, the Seller shall provide an outline drawing with the previously designated actual measured significant dimensions.
The accuracy of as-built measurements shall be at least 25 percent of the tolerance of the dimensions measure.
If the final construction differs from the previously submitted assembly and detail drawings, corrected drawings shall be provided by the Seller.
12.2.2.
Instruction Manuals.
12.2.2.1.
Instruction manuals shall present the following basic categories of in-formation in a practical, complete and comprehensive manner, prepared for use by operating and/or maintenance personnel:
a.
Instructions for making up the head closure seal for:
1.
Normal operation and, 2.
Hydrostatic tests b.
Instructions for opening up the head closure c.
Instructions for operation, maintenance and repair of all tools provided d.
Recommendeci maximum heating and couling rates with
~aximum allowable temperature differences between the various thermo-couple locations.
e.
Reco~ended inspection points and per40d of inspection f.
Ordering instructions for all replaceable parts, gaskets, etc.
12.2.2.2.
The information shall be organized in a logical and orderly sequence.
A general description of the equipment including significant technical character-istics shall be included to familiarize operating and maintenance personnel with the equipment.
12.2.2.3.
Necessary drawings and/or other illustrations shall be included or copies of appropriate certified drawings may be bound into the manual.
Test, adjustment and calibration information, as appropriate, shall be specified and identified to the specific equipment.
Safety and other warning notices and installation, main-tenance and operating cautions shall be emphasized.
~2.2.2.4. ' A parts list shall be included showing part nomenclature, manufacturer's part number and/or other inform2tion necessary for accurate identification and or-dering of replacement parts.
Common hardware items or other parts to be locally procured shall be adequately identified by Technical description.
IS'UEO:
AUG 2 6 1970 K. 1-33
GENERAL0 ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT PURCHASE SPECIFICATION SPEC. NO.
SH NO.
21Allll REV. N0.9 3/.
CONT ON S....EET F
12.2.2.5.
Instructions and parts list shall be clearly legible and prepared on good quality paper; carbon copies and tissue copies of other flimsy material are not acceptable.
}iultiple page instructions shall be securely bound.
12.2.2.6.
In a standard manual is furnished covering more than the specific equip-ment purchased, the applicable model (or other identification) parts and other in-formation for the specific equipment purchased shall he clearly identified.
12.2.3.
Photographs.
The Seller shall provide the Buyer with sets of progress photographs of the vessel at each significant stage of fabrication.
One set shall consist of one negative and three glossy 8" x 10" prints.
12.2.4.
Engineering schedule 12.2.5.
Fabrication schedule 12.3.
Records The Seller shall maintain records of all material qualifications, all w~ld and weldor qualifications and all process qualifications required by this specifica-tion and the material specifications.
In addition, the Seller shall maintain records of all tests and inspections (e.g., ultrasonic, radiography and hydro-static).
A list of the records shall be submitted to the Buyer on completion of the j~b.
The Buver shall be able to obtain certified copies of such records for a five year period.
Wh~rc the Seller considers th~ actual test recorrlR to h~
~ro prietary, he shall submit certified reports containing all pertinent t~st data ex-cerpted from the actual test reports.
Thes~ certified test reports shall
~lso be available for? 5 year period.
At the en~ of the 5 year period, both the vessel user and the Buyer shall be notified at least 120 days prior to disposal of the records, so that a request can be made (if either the vessel user or the Buyer so desires) to have these records 3ent to either the vessel user or the Buyer.
h_
~
"AUG 2 6 19~
K.I-34
GENERAL;tD ELECTRIC ATOMIC POWER EQUIPMENT OEPARTMENT PURCHASE SPECI FICA TlON ATTAClmENT B -
}~TERIAL TESTS AND TEST SPECIMENS SPEC. NO. 2lAllll SH NO I
REV. No.9 CONT 0"1 SHEET2 1.
SCOPE The Seller shall retain selected portions of the material used to fabricate the reactor vessel of this contract.
He shall process some of this material into finished mechanical specimens which shall be in metallurgical conditions repre-sentative of the following as-fabricated reactor vessel material:
Base-plate, welds and heat-affected zone.
The Seller shall test some of these specimens for "Fabrication Tests" to determine the effect of thickness on the mechanical pro-perties of the material.
The remainder of the specimens and the remainder of the selected test material shall be prepared for shipment.
These latter specimens will be used for "Surveillance Tests" to monitor the effect of neutron irradiation on the mechanical properties of the reactor vessel steel.
2.
FABRICATION TEST PROGRAM 3.
SURVEILLANCE TEST PROGRAM 3.1.
Bas~
Met~l - 'Fienre 1 (DELETE) 3.1.1.
The Seller shall furnish two plates, as shm.;n in Figure 1, from the plate used to make the reactor vessel in the reactor core region, or from a similar plate from the same heat.
3.1.2.
Th2 Seller shall heat t't'eat these plates with the reactor vessel, or in similar fashion, to insure that they represent the metallurg~cal condition of the vessel steel, in the core region of the completed reactor vessel including all post weld heat treat cycles seen by that region.
3.1.3.
The
~eller shall furnish documents to the Buyer, showing the location of the test plates and detailing all metallurgical data concerning the test plates.
3,1.4.
The Seller shall make mechanical test specimens, as outlined belo\v, from one of these plates and send the other to the Buyer.
~.2.
Welded Plate - Figure 2 3.2.1.
The Seller shall furnish a welded plate representative of a reactor vessel longitudinal weld, in the base of reactor vess~ls formed from plate or representative of a reactor vessel girth weld in the case of reactor vessels forml~d from forged rings, as shown in Figure 2, from the plate used to make the reactor vessel in the reactor core region, or from a similar plate from the same heat.
ISSUE 0:
!-\UG 2 G1970 K.I-35
GEr~ERAL0 ELECTRIC PURCHASE SPECIFICA TION ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. No.2lAllll h~....o.
2 "KY. No.9 CONT ON IHCCT 3 3.2.2.
TIle Seller shall heat treat the plate with the reactor vessel, or in similar
- fashion, to insure that it an~ the weld represent the metallurgical condition of a vessel weld, in the core region of the completed reactor vessel including all post weld heat treatment cycles seen by that weld.
3.2.3.
The Seller shall furnish documents to the Buyer showing the location of the test plates, detailing all metallurgical data and demonstrating that the weld was made in a manner similar to a reactor vessel weld.
X-rays of the weld ahall be furnished.
3.2.4.
The Seller shall make mechanical test specimens, as outlined below, from half of 'the plate and shall supply the other half to the Buyer.
3.3.
Surveillance Specimen Fabrication 3.3.1.
The Seller
~hall provide a detailed plan of specimen preparation for the Buyer's approval prior to the start of any work required by this attachment.
The Buyer can furnish a plan which the Seller may use as a guide.
He shall be specific in indicating how the notch location of the Heat-Affected Zone Charpy specimens will be determined.
3.3.2.
All specimen cutting shall be done by machi~ing.
3.3.3.
Specimen M2rking 2n~ m,rk orientation are of upmo~t importAnce.
Each speci-
.men shall be marked seria:Lly Vlith Lhe FAil CoJt:: series provided.
3.3.4.
The Seller shall apply rust preventative to all specimens, shall arrange them in serial groups of like materials, and sh a Ll, wrap them to prevent mechanical damage.
3.3.5.
The Seller shall provide drawings showing all specimen locations with respect to the plate.
3.4.
Preparation of Base Metal Charpy Test Specimens (Refer to Figure 3 and Drawing l17B1549)
The Seller shall prepare 53 standard Charpy V-Notch impact specimens (ASTH E23, Type A, G.E. Drawing l17B1549) from the base plate material described in pre-vious paragraphs.
The specimens shall ~e taken from 1/4 thickness positions in the plate and at least IT from any asquenched edge.
The long axes of the specimens shall be parallel to the plate rolling direction, or principal forg-ing direction~
The specimen notches shrtll be perpendicular to the original plate surface and shall be controlled by the orientation of the end marking on the 'Specimen blanks.
3.5.
Presparation of Base }tetal Tcnsil~eci~ens (Refer to Figure 3 and G.E.
Drawing ll7B1550)
IIIU£OI
,\lJG '2 G 1~~7.,
i
......_~--'...-_,1 TIle Seller shall prepare 14 1/4-inch gage diameter tensile specimens as per G.E. Drawing l17B1550, froQ the base plate material previollsly uescribed.
The specimens shall be taken from 1/4 thickness positions in the plate and at least IT from any as-quenched edge.
The long axes of the specimens shall
~e parallel to the plate rolling direction or principal forging direction.
K.I-36
PURCHASE SP ECIFICATION GErJfnAL0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT S~[C. NO. 2lAllll
KY. NO.
9 JHNO.
3 CONTONIHI:CT 4 3.6.
Preparation of Weld Charpy Specimens (Refer to Figure 4 and G.E. Drawing l17B1549)
The Seller shall prepare 53 Qlarpy impact specimens, per G.E. Drawing l17B1549 and Figure 4, from the weld deposit material of the furnished plate.
The long axes of the specimens shall be perpendicular to the weld direction and parallel to the plate surface, with the middle of the specimen at the mid-plane of the weld, as shown in Figure 4.
The specimen location in the stock material shall be recorded, approximately, by the numbering system.
The notch shall be parallel to the plate sur-face and its orientation shall be controlled by the orientation of the marking symbols.
3.7.
Preparation of Weld Tensile Specimens (Refer to Figure 5 and G.E. Drawing l17B1550)
The Seller shall prepare_ 13 tensi:e specimens, per G.E. Drawing !17B1550 from the weld deposit material of the furnished plate.
The long axes of the specimens ahall be parallel to the length of the we!d and parallel to the top surface of the plate (See Figure 5).
The gage length of the speci-mens shall be of weld-deposit metal only.
The treaded ends of the specimens may include Heat-Affected Zone or base metal.
The approximate location of the Gpecimens in the stock materi~l shRll. he recorded by the marking system.
3.8.
Preparation of Heat-Affected Zone Tensile Speci~
(Refer to Figure 6 and G. E. Draw.Lng l17B1550)
The Seller shall prepare 13 tensile specimens, per G.E.
Drawing l17B1550, f rom the weLded material of the furnished plate.
The long axes of the speci-mens shall be perpendicular to the length of the weld and parallel to the top surface of the plate (See Figure 6).
The center of the specimen shall be in the Heat-Affected Zone adjacent to the edge of the weld metal.
TIle approximate location of* the specimens in the stock material shall be recorded by the, marking system.
3.9.
Preparation of Heat-Affected Zone Charpy Specimens (Refer to Figure 7 and G.E. Drawing ll7B1549)
The Seller shall prepare 53 Charpy specimens, per G.E.
Drawing 117B1549, from the welded material of the furnished plate.
The long axes of the specimens shalL be perpendicular to the length of the Held and parallel to the top sur-face of the plate (See Figure 7).
The radius of the notch of the specimen shall be at one outer edge of the weLd,
The axis of the notch shall be par-allel to the original plate surface.
The notch orientation shall be controlled by the marking orientation.
The location of the speciT:1en in the stock material shal~ be recorded, appioximately, by the marking system.
,....-_._----_... ~..
K.r-37
PURCHASE SPECIFICATION GEN EAAL 0 ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT IPEc.No.2LAllll
~CV. NO.9 llot NO.4 CONT ON IHEe T 5 FLAMECUT OR WELD EDGES 1
~~CHINE CUT EDG~S t."""., PI?ESSf/i'(E Ll.ESScL
~/I'1L.L. T///CI(IV£"SS (CL) -
71//5 OII1ENS/Of\/
1'111 y' BE
- tI~tV/SI/i
.11.5 2. Of? 3 SI1ALLE/
PieCES.
"Al1~ 2 6 1970
~
______ <0:;)
K.I-38
PURCHASE SPEel FICA TlON GENERAL 0 ELECTRIC ATOMIC POWER eQUIPMENT DEPARTMENT SPEC. NO. 2lAllll REV. No.9 SH NO.
5 CONT ON SHEET 6
ORIGINAl-PL-ATE ECJ&,G MUST 8E
,4J1YAY,.t::RC)/'r? /YeLD t -
PRe-SSU.RE.. VESS~~
- W,4I.t. rHICKIV4SS.
~
(I.-
(cr,) -
SEVERAL 'P/ec~s
~AN'&fv'o//ve.o. TtJ N,w$'.7Ii/..1 £)/MAI/.51011 NiJw6yir~) h/ez,O Ma;r es Ctj7lT//(VOVS.
~.MINI~tlH H/N!N~V1 3t 3t
~ W£LD ceNTEP"oLAN£ r/G. 2 TE5T WELD FOR
)'V£~LD;I #EAT AFFECTED t
ZONE 5PEC//y/EN
'Autf2 6 1970 K.I-39
GEtl ERAL ~ ELECTRIC ATOMIC POWER EQUIPMENT DEPARTMENT SPEC. NO.
21All11 REV. NO. 9 HI NO.
6 CONT ON SHEET 7 t
t - \;, P\.J\"~ -r~\CJ~NaS~
(\. \~ Cl4.~RP,(
e.,LAN~ \'\!.!~~"H b.. \~ T~~1r:J\'-~ i~\..A~lK Le.~<!l"H K.I-40 FIG.
3 PL.-ATE. SURFA'c.E.
CHARPY & ENSILE SPECIMEN LOCATION
GENERAl e ELECTRIC ATOMIC POWE R EQUIPME NT DE PART MENT WELD FIGURE 4 WELD CHARP\'
K.I-41
!>p£c. NO. 2V.llll R£V. No.9
!>H NO 7
CONT ON SH[n 8 a -
FJl3fiV; /2".
~-J:eS$ct. WAL.I. TN./'.
~ -C/l~SI $UJNK nq.
~ ~...bItCtfIIIP '?EM fl/lT~~/JL *
['AUG'2 6 1970
GENERAl(jJp ELECTRIC ATOMIC PowER [QUIPI,I.(NT DEPARTMENT sp[e No.21Allll
11:'. "'0. 9 s..
'JO 8
co~r ON SHEEr 9
~ -~UT /2(/(30(111/)
e -l'4SSS. JfI/IU 11(~
q-hlfU; M'/)~.p./.
3f -1)JSCIJe~ 7//.IS N~/I1.L 5
213 IN---':'_;iI fi~~
~./cL{) TEAl4S'/LE ISSuED.
AUG 2 6 1970 K.I-42
GENERAL@ ELECTRIC ATOMIC PowE R EOUIPME NT DE PAR TMEN T SPEe... o, 2lA 1111 REV. No.9 SH NO.
9 CONT ox SHFET 1:'
t
~ -- VESSEL.
f'II1LL T/IICj(NESS
.--- O/SCARD TillS I1/jTc;'(I/!L K.I-43 ISSUED' AUG 2 6 1970
GENERAL (J) ELECTRIC ATOMIC powER EOUIPMENT OEPARTMENT SPEC. NO.
21Allll
~EV. No.9 h.... 0.
10 NOTES:-*
fr.I~1 t,.V&:SS~L WALL THICJ{NES3 Ihl~
~
11"= Ol5CARO 'rHI~ M"Tt:RIAL.
J\~V d J~2" 1'.P;.r-:------
)~£~;..t
.Lt=:======:.::---
~1'cIJ!j1~
T l=========:..::=:::=========~=====:V t*
COST ON SHEEr
"~VEO AUG 2 6 1970 K.I-44
PBAPS 22 October 1970 Project:
Contrac t:
P. 0:
Date:
1V,\ 1 t. 2 C,lO-0127 20S-S5577 10/23/70 Project:
Contract:
P. 0:
TVA 3 610-0145 205-H0397 Proi cc t :
Contrac t :
P. 0:
PB 2 (( 3 610-0139 205-Cl15G 10.6.2 CLr\RIFICATln;~s OF Sr[CIFICATIOi~
211\1111, PE\ITSIOj! 9 8.7.1 Jcmpcri nq at 1175°F meets the intent of tile specification nrovided the post \'/elo heat treatment maximum temperatures do not exceed 1150°F.
9.3.1 The provisions for preheat and maintenance of preheat in
[32'~'1 Spcci t t ca t i on tWS-129, Rev. 4, dated 3/31/69, are acceptable alternate requirements.
10.5.3.1 The V-notch calibration s tandard described in
[3&~'1 Specifioation f!UT-82, Rcv. 0, datcd 4/19/67, is an accep tabl e alternate standard-to the square bottomed notch.
The acccpt.ance standard of 8&\*J Specification {IS-102C, Rev. 5, Paraqraph 8.2.2 - 1\11 rounded indications with dimensions nreater than 3/16 inch, is an acceptable ulternute standurd to srot indicutions which arc indic-ative of defects greater than 1/32 inch deep as r~veu1ed by bleed-out.
10.6.3.2 The O.OOG inch deer cul ibre t ion crcove described in
~&\'1 Spaci f i ca t i nn OUT-GU, Rev. 0, dated
~/19/G7, is un accertab1e ulternute stundilrd when used for testing Nic~el-Chroilliurn-Ironclad flange seu1 surfaces.
iO.6.6.1 The fo l l ow i nr; alternate acceptance s tandard may be appl i ed to the orrcninqs for purtia1 penetration nozzles not requlreu to be examined by Paragraph rl-513 of the Secticn III Code:
Cracks and l i ncar indications wh i ch are non-Lami nar shall be repaired.
K.I-45
PBAPS GENERAL" ELECTRIC COMPANY 175 CURTNER AVE.,
SAN
- JOSE, CALIF.
95125 ***
AREA CODE 408, TEL. 297*3000 TWX NO. 910*338*0116 Au gus t 6 t 1970 TO WHOM IT MAY CONCERN:
NUCLEAR ENERGY DIVISION ATOMIC POWER EQUIPMENT DEPARTMENT This letter of certification lists the specification and draw-ings which comprise the Design Specification for the reactor pressure vessels for Units 2 &3 of the Philadelphia Electric Company's Peach Bottom Atomic Power Station as required by Paragraph N-14l of the ASME Boiler and Pressure Vessel Code t Section lIlt Nuclear Vessels.
The specification and drawings are:
21Al1ll,Rev. 9 - Reactor Pressure Vessel 8860499 - Reactor Vessel Purchased Part Sheet No.
Rev. No.
Sheet No.
Rev. No.
1 11 5
3 2
8 6
4 3
3 7
6 4
6 8
0 729E762, Rev. o - Reactor Thermal Cyc1es 13589990 - Nozzle Thermal Cycles Sheet No.
Rev. No.
Sheet No.
Rev.
No.
1 1
5 0
2 0
6 0
3 0
7 0
4 0
8 0
8850911, Rev. 2 - Vessel Flange Bolting 107C5305, Rev. 2 - Nozzle End Preparation K.I-46
PBAPS GENERAL 0 ELECTRIC Page 2 This certification is issued in order that design and fabrica-tion of the reactor pressure vessels identified by General Electric Company Purchase Orders No. 205-Bl156, No.
205-H4641 and No. 205-H4642, may proceed in accordance with the require-ments of Section III of the ASME B&PV Code.
The certification is issued solely for the purpose of complying with the require-ments of Paragraph N-141 of Section III and is not to be con-strued as involving, modifying, or changing contractual rela-tions or legal liabilities.
The Design Specification is certified to be in compliance with the requirements of Paragraph N-14l of Section III of the ASME B&PV Code and is correct and complete with respect to functions and operating conditions in accordance with Section III, 1965 Edition with addenda to and including Winter 1965 Addenda.
CERTIFIED BY:
~t tP~
DATE: ~~ &70 ReglSered Professional Engineer
~).
California STATE:
BRANCH: Mechanical NO:
13540
--~-------
RLC/jf' K.I-47