CP-202200357, (CPNPP) Unit 2 - Response to Request for Additional Information, Fall 2021 (2RF19) Steam Generator Tube Inspection Report

From kanterella
(Redirected from ML22258A234)
Jump to navigation Jump to search

(CPNPP) Unit 2 - Response to Request for Additional Information, Fall 2021 (2RF19) Steam Generator Tube Inspection Report
ML22258A234
Person / Time
Site: Comanche Peak Luminant icon.png
Issue date: 09/14/2022
From: Hicks J
Luminant, Vistra Operations Company
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
CP-202200357, TXX-22079
Download: ML22258A234 (5)


Text

CP-202200357 TXX-22079 September 14, 2022 U. S. Nuclear Regulatory Commission Ref 10 CFR 50.55a ATTN: Document Control Desk 10 CFR 50.4 Washington, DC 20555-0001

Subject:

Comanche Peak Nuclear Power Plant (CPNPP) Unit 2 Docket No. 50-446 Response to Request for Additional Information, Fall 2021 (2RF19) Steam Generator Tube Inspection Report

References:

1.

NRC email from Dennis Galvin to Jack Hicks, Comanche Peak Unit 2 - Request for Additional Information - 2RF19 Inspection Summary Report for Steam Generator Tubing (EPID: L 2022-LRO-0065), dated August 17, 2022 2.

Letter TXX-22041 from Jack Hicks to the NRC, Unit 2 Refueling Outage 19 (2RF19) Steam Generator 180 Day Report, dated May 5, 2022 [ML22125A267]

Dear Sir or Madam:

Vistra Operations Company LLC (Vistra OpCo) hereby submits a response to the NRC request for additional information (RAI) (Reference 1) regarding the Comanche Peak 2RF19 steam generator report submitted with Reference 2. The attachment to this letter provides Vistra OpCos response to the NRC information request.

This communication contains no new commitments regarding CPNPP Unit 2.

Should you have any questions, please contact Jim Barnette at (254) 897-5866 or James.Barnette@luminant.com.

Sincerely, Jack C. Hicks

Attachment:

Response to Request for Additional Information - 2RF19 Steam Generator 180 Day Report c (email) -

Scott Morris, Region IV [Scott.Morris@nrc.gov]

Dennis Galvin, NRR [Dennis.Galvin@nrc.gov]

John Ellegood, Senior Resident Inspector, CPNPP [John.Ellegood@nrc.gov]

Neil Day, Resident Inspector, CPNPP [Neil.Day@nrc.gov]

Jack C. Hicks Manager, Regulatory Affairs Comanche Peak Nuclear Power Plant (Vistra Operations Company LLC)

P.O. Box 1002 6322 North FM 56 Glen Rose, TX 76043 T 254.897.6725 Sincerely, Jack C. Hicks a

Luminant

Attachment to TXX-22079 Comanche Peak Nuclear Power Plant Response to NRC Request for Additional Information Regarding the CPNPP 2RF19 Steam Generator 180 Day Report [ML22125A267]

(EPID: L 2022-LRO-0065)

(4 pages including this cover page)

Attachment to TXX-22079 Page 2 of 4 The NRC Staffs requests for additional information (RAI) are provided below in bold text and are followed by the Vistra OpCo responses.

RAI 1

The table in Section c.4 shows that the tubes at Row 40 Column 48 (33 percent through wall), and Row 40 Column 49 (18 percent through wall), in SG 3, were stabilized and plugged. The information in Sections c.2 and c.3 indicates both tubes had single volumetric indications caused by foreign object wear.

With respect to foreign object wear projections, Section d, near the top of page 15 states, A total of 16 objects remained in secondary side of the SGs following 2RF19. All of these objects were small parts and demonstrated by bounding calculations through tube wear projections to not adversely affect tube integrity until at least 2RF22. However, Section c.3, near the top of page 12, states, no foreign objects remain within the vicinity of the affected tubes, so no OA [operational assessment] projection is provided.

These two statements about foreign object wear projections appear to be inconsistent.

Therefore, please clarify the basis for stabilizing and plugging these tubes, the location of foreign objects with respect to these tubes, and whether these objects were included in the operational assessment.

Response

The tubes at Row 40 Column 48 (33 percent through wall), and Row 40 Column 49 (18 percent through wall), in SG 3, were stabilized and plugged. Both tubes had single volumetric indications caused by foreign object wear. For SG3 R40C48/49, the foreign object causing the wear could not be removed as it was fixed in place. Therefore, the tubes were plugged and stabilized to protect against tube severing in the event of continued wear.

A total of 16 objects that were visually verified during foreign object search and retrieval (FOSAR) remained in the secondary side of the SGs following 2RF19. Fifteen (15) of these objects were small parts (mostly sludge and scale), whose dimensions were bound by tube wear projections to not adversely affect tube integrity until at least 2RF22. One (1) object at SG3 R40C48/49 was not considered for operational assessment (OA) because it was found to be fixed in place between two tubes with wear indications, and as such the tubes were plugged and stabilized. None of the remaining 15 objects are associated with any foreign object wear indications.

With respect to tubes with detected foreign object wear, it is true that no foreign objects remain within the vicinity of any of these tubes that were returned to service. This was confirmed through secondary side visual inspections and eddy current examinations. Therefore, there is no mechanism to produce further flaw progression during future operations. With no mechanism present for further flaw growth and all wear flaws satisfying condition monitoring limits, all SG performance criteria for structural and leakage integrity will be satisfied until the next SG inspection (no OA projection is necessary). For the foreign object wear indications in SG3 at R40C48/49, the loose part remains in place, but the tubes have been removed from service.

Attachment to TXX-22079 Page 3 of 4

RAI 2

With respect to the single volumetric indication in the tube at Row 6 Column 79 in SG 3:

In Section c.4, the table of tubes plugged or repaired, please clarify the use of the word Preventative as the Plugging Basis. According to Sections c.2 and c.3, the indication was 43 percent through wall, which would require plugging according to TS 5.5.9.c.

Please clarify how this indication was assessed and determined to be foreign object wear (Section c.3) considering its location in the U-bend region (13.55 inches above tube support plate C11) and the absence of a corresponding foreign object in the summary table in Section f.

Response

The 2RF19 Plugging and Stabilization List in Section c.4 is corrected and provided below. The term Preventative for SG3 R6C79 was referring to the fact that the loose part suspected of causing the single volumetric indication (SVI) could not be visually verified. However, as the depth of the flaw is

> 40% TW, a corrected plugging basis is provided.

2RF19 Plugging and Stabilization List SG Row Col Ind Location Plugging Basis Stabilize

?

1 1

69 SAI H3 Axial ODSCC No 2

1 95 High Stress Tube No 2

1 55 High Stress Tube No 3

6 79 SVI C11 Wear > 40% TW No 3

40 48 SVI C2 Preventative Yes 3

40 49 SVI C2 Preventative Yes The single volumetric indication at SG3 R6C79 was determined to be foreign object wear via eddy current inspections. The bobbin probe detected a Non-Quantifiable Indication (NQI) at H11 +13.60, which required a +Point probe diagnostic test to be performed. The +Point probe examination detected a possible loose part (PLP) and an SVI. The loose part (foreign object) was detectable in the

+Point data but could not be visually verified because of location in the U-Bend which is between two Anti-Vibration Bars (AVB). No loose part was recorded in the summary table in Section f because the location is inaccessible from the secondary side, so no part could be visually confirmed.

Attachment to TXX-22079 Page 4 of 4

RAI 3

Please explain the meaning of Limiting/Total wear indications, shown with a value of 279 in the table of Wear Indication at Support Structures in Section c.2

Response

The first table in Section c.2 has been corrected and provided below.

Wear Indications < 20% TW at Support Structures (AVB, TSP, and PBP)

SG1 SG2 SG3 SG4 Total 135 47 55 42 279