Amendment 29 to Updated Final Safety Analysis Report, Chapter 8, Table 8.8, Evaluation of the 24-V DC Power Supply
ML21286A431
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 10/04/2021
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21286A574 List: ... further results
References
Download: ML21286A431 (3)


Text

BFN-16 Table 8.8-1 (Deleted by Amendment 9)

BFN-16 Table 8.8-2 (Deleted by Amendment 7)

BFN-17 Table 8.8-3 EVALUATION OF THE 24-V DC POWER SUPPLY Results Consequence of Component Losing 24-V DC Supply Losing 24-V DC Supply

1. Source Range Monitors and (a) Loss of source range indication I. Plant shutdown - (all rods in)

SRM Trip Auxiliaries with annunciation of loss a. startup prevented by rod (alarm) block (b) Rod Block b. startup prevented by technical specifications II. In STARTUP MODE (MODE 2)-

a. rod withdrawal stopped by SRM rod block.
2. Intermediate Range Monitors (a) Loss of intermediate range I. In STARTUP MODE (MODE 2)-

and IRM Trip Auxiliaries indication with annunciation a. IRM Rod Block and of loss (alarm) IRM Scram (b) Rod Block II. In RUN MODE (MODE 1)-

a. None - Protection (c) Scram provided by APRM. SRM's and IRM's withdrawn.
3. Trip auxiliaries for off- (a) Off-gas valve isolation signal I. Off-gas valve closes gas radiation monitor and generated timer control
4. Stack Gas Radiation Monitor (a) Instrument failure alarm I. None - Off-gas line isolated on unit with failed 24-V DC system - log off-gas monitors available on all units.
5. Linear Off-gas Radiation (a) Loss of indication I. None - Backed up by two log Monitor off-gas radiation monitors powered from RPS bus.
6. RHR Service Water Effluent (a) Instrument Failure Alarm I. None - Sampling frequency Radiation Monitors increased if RHR service water system in operation.
7. Liquid Rad Waste Effluent (a) Instrument Failure Alarm I. None - Liquid radwaste Radiation Monitor discharge based on tank sampling. However, discharge would be stopped by operator if in progress.
8. Reactor Building Closed (a) Instrument Failure Alarm I. None - Closed system.

Cooling Water System However, sampling frequency Radiation Monitor could be increased.

9. Raw Cooling Water Effluent (a) Instrument Failure Alarm I. None - Increased sampling Radiation Monitor frequency as necessary.