ML21125A568

From kanterella
Jump to navigation Jump to search
0 to Updated Final Safety Analysis Report, Chapter 10, Tables
ML21125A568
Person / Time
Site: Cook  
Issue date: 04/19/2021
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21126A238 List: ... further results
References
AEP-NRC-2021-19
Download: ML21125A568 (2)


Text

IINNDDIIAANNAA M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

10.5-1 Page:

1 of 1 AUXILIARY FEEDPUMP DESIGN PARAMETERS TURBINE DRIVEN PUMP MOTOR DRIVEN PUMP Suction Temp. (ºF max.)

120 120 Suction Press (psig) 1 25 25 Design Press (psig) 2 1200 1200 Design Total Dynamic Head (ft) 27143 /27453 2714 Total Shut Off Head (psig)1 15904 1430 Net Discharge flow (gpm) 9003/9064 450 Horsepower (HP) 9003 500 Rated Speed (rpm) 4350 3560 High-Speed Stop Setpoint (rpm) 4378 N/A 1 From Condensate Storage Tank 2 Evaluated to be acceptable to 1590 psig for the TDAFP, 1500 psig for the EMDAFP, and 1550 psig for the WMDAFP (Section 10.5.2.5 - References 1 and 2) 3 At Rated Pump Speed 3 At Turbine High-Speed Setpoint UFSAR Revision 30.0

IINNDDIIAANNAA M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.1 Table:

10.6-1 Page:

1 of 1 CIRCULATING WATER PUMP DESIGN PARAMETERS Quantity 7

Type Vertical, wet pit, propeller Rated Capacity (GPM) each 230,000 Rated Head (ft. H2O) 34.9 Rated Speed (RPM) 252 Rated Motor Power (HP) 2,750 UFSAR Revision 30.0