ML21118A116
| ML21118A116 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 04/28/2021 |
| From: | Southern Nuclear Operating Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML21118A114 | List: |
| References | |
| ND-21-0342 | |
| Download: ML21118A116 (108) | |
Text
Southern Nuclear Operating Company ND-21-0342 Emergency Response Data System (ERDS) Data Point Library For Vogtle Unit 3 (This Enclosure consists of 107 pages, not including this cover page)
ND-21-0342 Southern Nuclear Operating Company Emergency Response Data System
[ERDS]
Data Point Library For Vogtle Unit 3 April 12, 2021 NOTE:
Changes to the information presented herein may require NRG notification per 10 CFR 50, Appendix E, Section VI.
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 REFERENCES
- 1.
NUREG-1394, Rev. 1, "Emergency Response Data System (ERDS] Implementation"
- 2.
APP-DDS-J4-157, Rev. 2, "Data Display and Processing System Emergency Response Data System Datalink Interface Specification"
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
CORE FLOW Point iD:
DDS-FLC46-F0 Piant Spec Point
Description:
Total RCS Corrected Flow Rate Generic/Cond
Description:
Total Reactor Coolant Flow Analog/Digitai:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
1000000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
8 How Processed:
COMPENSATED BASED ON REACTOR POWER Sensor Locations:
ROOM 11204 (101A/B/C/D) ROOM 11202 (102A/B/C/D)
Alarm/Trip Setpoints:
NONE FOR CORR. FLOW, INSTR LOW (95% OF FLOW)
Nl Detector Power Supply Cut-off Power Levei:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 1 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
RCS PRESSURE Point ID:
PMS-WRPR-RA-P6 Plant Spec Point
Description:
RCS Wide Range Pressure Generic/Cond
Description:
Reactor Coolant System Pressure Analog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
AVERAGE Sensor Locations:
ROOM 11400 (PT140A/C) ROOM 11306 (PT140B/D)
Alarm/Trip Setpoints:
LOW 2 (700 PSIG) LOW 3 (450 PSIG)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 2 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
BDS-RY010 Plant Spec Point
Description:
EDI Product Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-07 Maximum Instr Range:
0.01 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 21380 Alarm/Trip Setpoints:
HIGH (2E-007 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 3 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
BDS-RY011 Plant Spec Point
Description:
EDI Reject Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-07 Maximum Instr Range:
0.01 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 21380 Alarm/Trip Setpoints:
HIGH (2E-007 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 4 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
CVS-FT157A Plant Spec Point
Description:
Makeup Pump Disch Header HR Flow Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
175 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 12255 Aiarm/Trip Setpoints:
NONE Ni Detector Power Suppiy Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 5 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
Ni SOURC RNG Point iD:
DDS-RSA39-N1 Riant Spec Point
Description:
Source Range Detector Generic/Cond
Description:
Nuclear Instruments, Source Range Anaiog/Digitai:
A ENGR Units/Dig States:
cps ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
1000000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
4 How Processed:
N/A Sensor Locations:
ROOM 11105 Alarm/Trip Setpoints:
5X BASE COUNT SETPOINT OR ALL CHANNELS 2X GREATER THAN CPS Nl Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Levei:
N/A instrument Faiiure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 6 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
Nl POWER RNG Point ID:
DDS-RSA3J-J1 Plant Spec Point
Description:
Power Range Power (Compensated)
Generic/Cond
Description:
Nuclear Instruments, Power Range Analog/Digital:
A ENGR Units/Dig States:
power ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
160 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
8 How Processed:
N/A Sensor Locations:
ROOM 11105 Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 7 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-TSAT-T1 Plant Spec Point
Description:
RCS Saturation Temperature Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
212 Maximum Instr Range:
710 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpolnts:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 8 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
TEMP CORE EX Point iD:
PMS-CETC-TH-T6 Plant Spec Point
Description:
Fifth Hottest Core Exit Thermocouple Generic/Cond
Description:
Highest Temperature at the Core Exit Anaiog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
70 Maximum Instr Range:
2300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
38 How Processed:
COMPARISON, 5TH HOTTEST SELECTED Sensor Locations:
ROOM 11105 Aiarm/Trip Setpoints:
NONE Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 9 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-IRSL-RA-L6 Plant Spec Point
Description:
IRWST Water Level Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% =
.24FT Minimum Instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
5.5 FT ABOVE TANK BOTTOM PROG or SENS:
S Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
IRWST TANK Alarm/Trip Setpolnts:
LOW (97%)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
DRY Unique System
Description:
N/A Page 10 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
Nl INTER RNG Point ID:
PMS-NFLX-RA-N6 Plant Spec Point
Description:
Intermediate Range Neutron Flux Generic/Cond
Description:
Nuclear Instruments, Intermediate Range Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
N/A Minimum Instr Range:
1e-06 Maximum Instr Range:
200 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
4 How Processed:
N/A Sensor Locations:
ROOM 11105 Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 11 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-PRHF-RA-F6 Plant Spec Point
Description:
PRHR Heat Exchanger Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum Instr Range:
700 Maximum Instr Range:
3000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11300 Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 12 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
PRZR LEVEL Point ID:
PMS-PWLC-RA-L6 Plant Spec Point
Description:
Pressurizer Level Generic/Cond
Description:
Primary System Pressurizer Level Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% = 4.2293 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 (LT195A/C) ROOM 11306 (LT195B/D)
Alarm/Trip Setpoints:
COMPLICATED. BASED ON PLS/PMS LOGIC Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 13 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
SUB MARGIN Point ID:
PMS-SCMG-T5 Plant Spec Point
Description:
RCS Subcooiing Margin Generic/Cond
Description:
Saturation Temperature Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
250 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 14 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
CVS-FT157B Riant Spec Point
Description:
Makeup Pump Disch Header LR Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
60 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 12255 Aiarm/Trip Setpoints:
NONE Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 15 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
BWST LEVEL Point ID:
CVS-LT109 Plant Spec Point
Description:
Boric Acid Storage Tank Level Generic/Cond
Description:
Borated Water Storage Tank Level Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% = 1.8 IN Minimum instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
BOTTOM OF TANK PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
BAST TANK, OUTSIDE OF SV3 TRUCK BAY Alarm/Trip Setpoints:
EMPTY (5%) LOW (93%) HIGH (97%)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
DRY Unique System
Description:
N/A Page 16 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PCS-LT040 Plant Spec Point
Description:
PCS Leak Chase Collection Pot Levei Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% = 0.28 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
0% = 2 IN, 100% = 30 IN PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
POT IN AUX BUILDING STAIRWELL S03 Aiarm/Trip Setpoints:
HIGH (50%)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 17 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PCS-TE024-SEL Plant Spec Point
Description:
PCS Air Flow Discharge Temp Select Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
-40 Maximum Instr Range:
300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ABOVE CNTMT IN AIR DISCH PATH ROOM 12541 Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 18 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PCS-TE036 Plant Spec Point
Description:
PCS Reclrculatlon Heater Inlet Temp Generlc/Cond
Description:
NL Analog/Digital:
A ENGR Unlts/DIg States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
25 Maximum Instr Range:
150 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
UPSTREAM OF THE PCS RECIRC HEATER IN ROOM 12306 Alarm/Trip Setpolnts:
LOW (47.25 DEGF)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 19 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PXS-TE064 Plant Spec Point
Description:
PRHR MX inlet High Point Temperature Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum Instr Range:
650 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
TOP OF PRHR HX INLET LINE DOWNSTREAM OF V101 ROOM 11500 Alarm/Trip Setpoints:
LOW (428 DEGF) HIGH (563 DEGF)
Nl Detector Power Supply Gut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 20 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
ML LEVEL 1/A Point ID:
RCS-LT160A Plant Spec Point
Description:
RCS Hot Leg 1 Level Sensor Generic/Cond
Description:
Hot Leg 1 (or A) Water Level Analog/Digital:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
0.31 IN Minimum Instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
BOTTOM OF HL PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 11204, Alarm/Trip Setpoints:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 21 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
ML LEVEL 2/B Point ID:
RCS-LT160B Plant Spec Point
Description:
RCS Hot Leg 2 Level Sensor Generic/Cond
Description:
Hot Leg 2 (or B) Water Level Analog/Digital:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
0.31 IN Minimum Instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
BOTTOM OF HL PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 11202, UPSTREAM OF RNS CONNECTION Alarm/Trip Setpoints:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 22 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
CL TEMP 1/A Point iD:
RCS-TE125A2 Piant Spec Point
Description:
RCS Wide Range Coid Leg 1A Temperature Generic/Cond
Description:
Stm Gen 1 (or A) Outiet Temperature Analog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 11201, INSIDE COLD LEG 1A Aiarm/Trip Setpoints:
NONE Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Supply Turn-on Power Levei:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 23 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
CL TEMP 2/B Point iD:
RCS-TE125B2 Piant Spec Point
Description:
RCS Wide Range Cold Leg 2A Temperature Generic/Cond
Description:
Stm Gen 2 (or B) Outlet Temperature Analog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
ROOM 11202, INSIDE COLD LEG 2A Alarm/Trip Setpoints:
NONE Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 24 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
PMS-ADS1-AC Piant Spec Point
Description:
ADS Stage 1 Actuation Generic/Cond
Description:
NL Anaiog/Digital:
D ENGR Units/Dig States:
Digital ENGR Units Conversion:
N/A Minimum instr Range:
0=NORMAL Maximum instr Range:
1=ACT Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
2 OUT OF 4 VOTING LOGIC Sensor Locations:
ROOM 11703 185 ELV (V001A) ROOM 11603 160.5 ELV (V001B)
Aiarm/Trip Setpoints:
NONE Ni Detector Power Suppiy Cut-off Power Level:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 25 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-ADS2-AC Plant Spec Point
Description:
ADS Stage 2 Actuation Generic/Cond
Description:
NL Analog/Digital:
D ENGR Units/Dig States:
Digital ENGR Units Conversion:
N/A Minimum Instr Range:
0=NORMAL Maximum Instr Range:
1=ACT Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
2 OUT OF 4 VOTING LOGIC Sensor Locations:
ROOM 11703 185 ELV (V002A) ROOM 11603 160.5 ELV (V002B)
Alarm/Trip Setpoints:
NONE Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 26 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-ADS3-AC Plant Spec Point
Description:
ADS Stage 3 Actuation Generlc/Cond
Description:
NL Analog/Digital:
D ENGR Unlts/DIg States:
Digital ENGR Units Conversion:
N/A Minimum Instr Range:
0=NORMAL Maximum Instr Range:
1=ACT Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
2 OUT OF 4 VOTING LOGIC Sensor Locations:
ROOM 11703 185 ELV (V003A) ROOM 11603 160.5 ELV (V003B)
Alarm/Trip Setpolnts:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 27 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-ADS4-AC Plant Spec Point
Description:
ADS Stage 4 Actuation Generic/Cond
Description:
NL Analog/Digital:
D ENGR Units/Dig States:
Digital ENGR Units Conversion:
N/A Minimum Instr Range:
0=NORMAL Maximum Instr Range:
1=ACT Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
2 OUT OF 4 VOTING LOGIC Sensor Locations:
ROOM 11301 ELV 118.5 (V004A/C) ROOM 11302 ELV 118.5 (V004B/D)
Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 28 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA45-T1 Piant Spec Point
Description:
IRWST Surface Temperature RSA Generic/Cond
Description:
NL Anaiog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum instr Range:
300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11305 Aiarm/Trip Setpoints:
HIGH (110 DEGF)
Ni Detector Power Suppiy Cut-off Power Level:
N/A NI Detector Power Suppiy Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 29 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA47-T1 Riant Spec Point
Description:
IRWST Bottom Temperature RSA Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum Instr Range:
300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11305 Alarm/Trip Setpoints:
HIGH (110 DEGF)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 30 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA59-P1 Plant Spec Point
Description:
Accumulator Tank A Pressure RSA Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
100 Maximum Instr Range:
800 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11206 Alarm/Trip Setpolnts:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System
Description:
N/A Page 31 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA61-P1 Piant Spec Point
Description:
Accumulator Tank B Pressure RSA Generic/Cond
Description:
NL Anaiog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum instr Range:
100 Maximum Instr Range:
800 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11207 Aiarm/Trip Setpoints:
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System
Description:
N/A Page 32 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA67-L1 Piant Spec Point
Description:
CMT A Narrow Range Upper Levei RSA Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% = 0.2 IN Minimum Instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 Aiarm/Trip Setpoints:
LOW (DEP) LOW 2 (69.4%) LOW 3 (DEP)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A NI Detector Power Suppiy Turn-on Power Levei:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 33 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA71-L1 Piant Spec Point
Description:
CMT B Narrow Range Upper Levei RSA Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% = 0.2 iN Minimum instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAiLABLE PARAMETER Sensor Locations:
ROOM 11400 Aiarm/Trip Setpoints:
LOW (DEP) LOW 2 (69.4%) LOW 3 (DEP)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Levei:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 34 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA69-L1 Piant Spec Point
Description:
CMT A Narrow Range Lower Level RSA Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% = 0.379 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 Alarm/Trip Setpoints:
LOW 4 (91%) LOW 5 (73.5%) LOW 6 (DEP)
Nl Detector Power Suppiy Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 35 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA73-L1 Riant Spec Point
Description:
CMT B Narrow Range Lower Level RSA Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% = 0.379 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 Aiarm/Trip Setpoints:
LOW 4 (91%) LOW 5 (73.5%) LOW 6 (DEP)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 36 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-RSA1F-T1 Riant Spec Point
Description:
CMT A Top Temperature RSA Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum instr Range:
600 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 Aiarm/Trip Setpoints:
Hi (107.5 DEG F)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A NI Detector Power Suppiy Turn-on Power Levei:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 37 of 105
ND-21-0342 ERDS Data Point Library For Vogtie Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA1L-L1 Plant Spec Point
Description:
CMT B Top Temperature RSA Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum instr Range:
600 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11400 Alarm/Trip Setpoints:
Hi (107.5 DEG F)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 38 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
MN FD FL 1/A Point iD:
DDS-RSA17-F1 Piant Spec Point
Description:
Generic/Cond
Description:
Stm Gen 1 (or A) Main Feedwater Fiow Analog/Digitai:
A ENGR Units/Dig States:
ibm/h ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
9000000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAiLABLE PARAMETER Sensor Locations:
ROOM 20400 Aiarm/Trip Setpoints:
COMPLiCATED. BASED ON MULTiPLE CHANNELS Nl Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Levei:
N/A instrument Faiiure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 39 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
MN FD FL 2/B Point ID:
DDS-RSA21-F1 Piant Spec Point
Description:
SG2 Hi Rng MFW Flow RSA (Unc)
Generic/Cond
Description:
Stm Gen 2 (or B) Main Feedwater Flow Anaiog/Digital:
A ENGR Units/Dig States:
Ibm/h ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
9000000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 20400 Aiarm/Trip Setpoints:
COMPLICATED. BASED ON MULTIPLE CHANNELS Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 40 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
SG PRESS 1/A Point ID:
DDS-RSA91-P1 Plant Spec Point
Description:
SGI Steam Line Pressure RSA Generic/Cond
Description:
Steam Generator 1 (or A)
Pressure Analog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
1300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100, ROOM 12405 Alarm/Trip Setpoints:
Ni Detector Power Supply Gut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 41 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
SG PRESS 2/B Point ID:
DDS-RSA93-P1 Plant Spec Point
Description:
SG2 Steam Line Pressure RSA Generlc/Cond
Description:
Steam Generator 2 (or B) Pressure Analog/Digital:
A ENGR Unlts/DIg States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
1300 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100, ROOM 12406 Alarm/Trip Setpolnts:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 42 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
SG LEVEL 1/A Point ID:
PMS-S1NL-RA-L6 Plant Spec Point
Description:
Compensated NR SGI Water Level Generic/Cond
Description:
Steam Generator 1 (or A) Water Level Analog/Digital:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
2.5331 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
TUBSHT Reference Point Notes:
383.64 IN ABOVE TUBE SHEET PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100 Alarm/Trip Setpoints:
LOW (26%) LOW 2 (21%) Hi (72.8%) Hi 2 (77%) Hi 3 (82%)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 43 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
SG LEVEL 2/B Point ID:
PMS-S2NL-RA-L6 Riant Spec Point
Description:
Compensated NR SG2 Water Level Generic/Cond
Description:
Steam Generator 2 (or B) Water Level Anaiog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
2.5331 IN Minimum instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
TUBSHT Reference Point Notes:
383.64 IN ABOVE TUBE SHEET PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100 Alarm/Trip Setpoints:
LOW (26%) LOW 2 (21%) Hi (72.8%) Hi 2 (77%) Hi 3 (82%)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 44 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
SG LEVEL 1/A Point iD:
PMS-S1WL-RA-L6 Plant Spec Point
Description:
Compensated WR SGI Water Level Generic/Cond
Description:
Steam Generator 1 (or A) Water Level Anaiog/Digitai:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
6.2681 IN Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
TUBSHT Reference Point Notes:
10.14 IN ABOVE TUBE SHEET PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100 Alarm/Trip Setpoints:
LOW (40%) LOW 2 (35%) HI (95%)
Nl Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 45 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
SG LEVEL 2/B Point ID:
PMS-S2WL-RA-L6 Plant Spec Point
Description:
Compensated WR SG2 Water Level Generic/Cond
Description:
Steam Generator 2 (or B) Water Level Analog/Digital:
A ENGR Units/Dig States:
span ENGR Units Conversion:
1% =
6.2681 IN Minimum instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
TUBSHT Reference Point Notes:
10.14 IN ABOVE TUBE SHEET PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100 Aiarm/Trip Setpoints:
LOW (40%) LOW 2 (35%) HI (95%)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
WET Unique System
Description:
N/A Page 46 of 105
ND-21-0342 ERDS Data Point Library For Vogtie Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
AX FD FL 1/A Point ID:
PMS-S1SF-RA-F6 Plant Spec Point
Description:
SGI Startup Feedwater Flow Generic/Cond
Description:
Stm Gen 1 (or A) Auxiliary FW Flow Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
600 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
5 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12211 Alarm/Trip Setpoints:
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 47 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
AX FD FL 2/B Point iD:
PMS-S2SF-RA-F6 Piant Spec Point
Description:
SG2 Startup Feedwater Flow Generic/Cond
Description:
Stm Gen 2 (or B) Auxiliary FW Flow Anaiog/Digitai:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
600 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
5 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12211 Aiarm/Trip Setpoints:
Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 48 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-HSilDS004-E1 Riant Spec Point
Description:
Max IDSA voltage IDSA-DV-1 Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 49 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIiDS004-E5 Plant Spec Point
Description:
Min IDSA voltage IDSA-DV-1 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 50 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIIDS008-E1 Plant Spec Point
Description:
Max IDSB voltage IDSB-DV-1 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpolnts:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 51 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIIDS008-E5 Plant Spec Point
Description:
Min IDSB voltage IDSB-DV-1 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Alarm/T rip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 52 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSiiDS012-E1 Plant Spec Point
Description:
Max IDSB voltage IDSB-DV-2 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Gut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 53 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-HSIiDS012-E5 Plant Spec Point
Description:
Min IDSB voltage iDSB-DV-2 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 54 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-HSIiDS016-E1 Piant Spec Point
Description:
Max IDSC voltage iDSC-DV-1 Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 55 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-HSilDS016-E5 Plant Spec Point
Description:
Min iDSC voitage iDSC-DV-1 Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 56 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIIDS020-E1 Plant Spec Point
Description:
Max IDSC voltage IDSC-DV-2 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 57 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIIDS020-E5 Plant Spec Point
Description:
Min IDSC voltage IDSC-DV-2 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 58 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIiDS024-E1 Plant Spec Point
Description:
Max IDSD voltage IDSD-DV-1 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
HIGHEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 59 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-HSIIDS024-E5 Plant Spec Point
Description:
MIn IDSD voltage IDSD-DV-1 Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
Vdc ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
3 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
1 PER CELL How Processed:
LOWEST SELECTED Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 60 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
DDS-BAP23-A1 Piant Spec Point
Description:
Containment Hydrogen Concentration Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
20 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 1100 Aiarm/Trip Setpoints:
HIGH (3%)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 61 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA1R-L1 Plant Spec Point
Description:
Containment Sump Level RSA Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
In ENGR Units Conversion:
N/A Minimum Instr Range:
7 Maximum Instr Range:
38 Zero Point
Reference:
CNTFLR Reference Point Notes:
5 IN ABOVE SUMP BOTTOM PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11104, IN STILLING WELLS Alarm/Trip Setpoints:
HIGH 2 (20.6 IN)
Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 62 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-CNTP-RA-P6 Plant Spec Point
Description:
Narrow Range Ctmt Pressure Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
-5 Maximum Instr Range:
10 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12452 (PT005/7) ROOM 12341 (PT006/8)
Alarm/Trip Setpoints:
(-0.8 PSIG) HI 1 (0.775 PSIG) HI 2 (6.2 PSIG)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 63 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-ERCP-RA-P6 Plant Spec Point
Description:
Extended Range Ctmnt Pressure Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
psig ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
240 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12452 (PT012/014) ROOM 12341 (PT013)
Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 64 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-CNTR-MX-R6 Plant Spec Point
Description:
High Range Containment Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
rad/h ENGR Units Conversion:
N/A Minimum Instr Range:
1 Maximum Instr Range:
10000000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
4 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11500 185 ELV Alarm/Trip Setpoints:
REFERENCE 6 N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 65 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
PMS-WRCL-RA-L6 Plant Spec Point
Description:
Containment WR Water Level Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% =
.393 FT Minimum instr Range:
0 Maximum Instr Range:
100 Zero Point
Reference:
COMPLX Reference Point Notes:
BOTTOM OF REACTOR CAVITY PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 11104,71.5 ELV Alarm/Trip Setpoints:
HI (2%) HI2 (3.3%) HI3 (25.7%) HI4 (67.9%) HI5 (87.3%) HIS (94.4%)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 66 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
CL TEMP 3/C Point ID:
RCS-TE125C2 Plant Spec Point
Description:
RCS WR Cold Leg IB Temperature Generic/Cond
Description:
Stm Gen 3 (or C) Outlet Temperature Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum Instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
NONE Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 67 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
CL TEMP 4/D Point iD:
RCS-TE125D2 Piant Spec Point
Description:
RCS WR Cold Leg 2B Temperature Generic/Cond
Description:
Stm Gen 4 (or D) Outlet Temperature Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
NONE Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 68 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
ML TEMP 1/A Point iD:
RCS-TE135A Riant Spec Point
Description:
RCS WR Hot Leg 1 Temperature Generic/Cond
Description:
Stm Gen 1 (or A) iniet Temperature Analog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum instr Range:
50 Maximum Instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
HiGH (200 DEGF)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Levei:
N/A instrument Faiiure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 69 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
ML TEMP 2/B Point iD:
RCS-TE135B Piant Spec Point
Description:
RCS WR Hot Leg 2 Temperature Generic/Cond
Description:
Stm Gen 2 (or B) inlet Temperature Anaiog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
HIGH (200 DEGF)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A NI Detector Power Suppiy Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 70 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
PMS-PCSL-RA-L6 Plant Spec Point
Description:
PCS Storage Tank Water Level Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
ENGR Units Conversion:
1% =
.28 FT Minimum instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
SEALEV Reference Point Notes:
294.25 FT ABOVE TANK BOTTOM PROG or SENS:
P Number of Sensors:
2 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12701 Aiarm/Trip Setpoints:
EMPTY (8.64%)
Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 71 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
PMS-PCCF-SM-F6 Plant Spec Point
Description:
PCS Water Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
660 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
N/A Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/T rip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 72 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
RCS-TE161 Plant Spec Point
Description:
PRHR Outlet Heat Ex Temperature Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum Instr Range:
700 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
COLD TRAP DOWNSTREAM OF PRHR HX Alarm/Trip Setpoints:
HIGH (220 DEGF)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 73 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
RMS-RY012 Plant Spec Point
Description:
Fuel Handling Area 1 Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
mrad/h ENGR Units Conversion:
N/A Minimum instr Range; 0.1 Maximum Instr Range:
10000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
V Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 74 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
RMS-RY020 Piant Spec Point
Description:
Fuel Handling Area 2 Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
mrad/h ENGR Units Conversion:
N/A Minimum instr Range:
0.1 Maximum Instr Range:
10000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
V Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 75 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SFS-FT013A Plant Spec Point
Description:
SFS Pump A Discharge Flow Generlc/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
1500 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
SFS DISCH LINE UPSTREAM OF SFS MX INLET NOZZLE Alarm/Trip Setpoints:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 76 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SFS-FT013B Plant Spec Point
Description:
SFS Pump B Discharge Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
gpm ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
1500 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
SFS DISCH LINE UPSTREAM OF SFS MX INLET NOZZLE Alarm/Trip Setpoints:
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 77 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
SFS-TE018 Riant Spec Point
Description:
Spent Fuel Pool Temperature Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
50 Maximum instr Range:
250 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
NE CORNER OF SFP Aiarm/Trip Setpoints:
HIGH (140 DEGF)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 78 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SGS-RY026A Plant Spec Point
Description:
SG 1 Main Steam Line Noble Gas Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCI/cc ENGR Units Conversion:
N/A Minimum Instr Range:
0.1 Maximum instr Range:
1000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
MAIN STEAM LINE Alarm/Trip Setpoints:
HIGH (0.2 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 79 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SGS-RY027A Plant Spec Point
Description:
SG 2 Main Steam Line Noble Gas Generlc/Cond
Description:
NL Analog/Digital:
A ENGR Unlts/DIg States:
uCI/cc ENGR Units Conversion:
N/A Minimum Instr Range:
0.1 Maximum Instr Range:
1000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
MAIN STEAM LINE Alarm/Trip Setpolnts:
HIGH (0.2 UCI/CC)
Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 80 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
Site Specific Piant Spec Point
Description:
Atmospheric Stabiiity Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Suppiy Cut-off Power Levei:
N/A NI Detector Power Suppiy Turn-on Power Levei:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 81 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SV3-MES-100-A Plant Spec Point
Description:
60M Wind Speed Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
MPH ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
112 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 82 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SV3-MES-101-A Plant Spec Point
Description:
60M Wind Direction Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEG ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
360 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 83 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SV3-MES-100-B Plant Spec Point
Description:
60M Wind Speed Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
MPH ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
112 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 84 of 105
ND-21-0342 ERDS Data Point Library For Vogtie Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SV3-MES-101-B Plant Spec Point
Description:
60M Wind Direction Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEG ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
360 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 85 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
SV3-MES-103-A Riant Spec Point
Description:
10M Wind Speed Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
MPH ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
112 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Levei:
N/A instrument Faiiure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 86 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
SV3-MES-103-B Plant Spec Point
Description:
10M Wind Speed Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
MPH ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
112 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 87 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
SV3-MES-104-A Plant Spec Point
Description:
10M Wind Direction Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
DEG ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
360 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 88 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
SV3-MES-104-B Riant Spec Point
Description:
10M Wind Direction Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
DEG ENGR Units Conversion:
N/A Minimum instr Range:
0 Maximum instr Range:
360 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
N/A How Processed:
N/A Sensor Locations:
N/A Aiarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 89 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
SWS-RY008 Piant Spec Point
Description:
Service Water BD Radiation Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-07 Maximum instr Range:
0.01 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
SERVICE WATER SLOWDOWN LINE Aiarm/Trip Setpoints:
HIGH (2.0E-007 UCi/CC)
Ni Detector Power Suppiy Cut-off Power Level:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 90 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
TDS-FT002 Plant Spec Point
Description:
Turbine Island Vent Exhaust Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
scfm ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
6500 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 91 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
TDS-RY001 Piant Spec Point
Description:
Turbine Vent Discharge Radiation Generic/Cond
Description:
NL Anaiog/Digitai:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
1e-06 Maximum instr Range:
100000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
HIGH (8.0E-002 UCi/CC)
Ni Detector Power Suppiy Cut-off Power Level:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 92 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
VAS-RY001 Plant Spec Point
Description:
Fuel Handling Area Exhaust Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-06 Maximum Instr Range:
0.03 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
COMMON DUCT ON SUCT SIDE OF FHA EXH FANS 006A/B Alarm/Trip Setpoints:
HIGH (4.0E-006 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 93 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
CTMNT TEMP Point ID:
VCS-TIY061 Plant Spec Point
Description:
Containment Volumetric Average Temperature Generic/Cond
Description:
Containment Temperature Analog/Digital:
A ENGR Units/Dig States:
DEGF ENGR Units Conversion:
N/A Minimum Instr Range:
32 Maximum Instr Range:
422 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
P Number of Sensors:
8 How Processed:
WEIGHTED AVERAGE Sensor Locations:
N/A Alarm/Trip Setpoints:
HIGH (71.3 DEGF) LOW (48.7 DEGF)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 94 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
VFS-FT105 Plant Spec Point
Description:
Plant Vent Flow Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
cfm ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
110000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
N/A Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 95 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
VFS-RY001 Piant Spec Point
Description:
Containment Exhaust Radiation Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
5e-07 Maximum Instr Range:
0.03 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Aiarm/Trip Setpoints:
HIGH (2.4E-002 UCI/CC)
Ni Detector Power Suppiy Cut-off Power Levei:
N/A Ni Detector Power Suppiy Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Levei Reference Leg:
N/A Unique System
Description:
N/A Page 96 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
VFS-RY101 Plant Spec Point
Description:
Plant Vent Effluent Particle Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
1e-12 Maximum instr Range:
1e-07 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Alarm/Trip Setpoints:
HIGH (8.0E-008 UCI/CC)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 97 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
VFS-RY102 Plant Spec Point
Description:
Plant Vent iodine Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-11 Maximum instr Range:
1e-06 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Alarm/Trip Setpoints:
HIGH (8.0E-007 UCI/CC)
Ni Detector Power Supply Cut-off Power Level:
N/A NI Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 98 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
VFS-RY103 Piant Spec Point
Description:
Plant Vent Gas Normal Range Radiation Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
1e-07 Maximum instr Range:
0.01 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Aiarm/Trip Setpoints:
HIGH (8.0E-003 UCI/CC)
Ni Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 99 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
VFS-RY104A Plant Spec Point
Description:
Plant Vent Gas Mid Range Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
0.0001 Maximum instr Range:
100 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Aiarm/T rip Setpoints:
HIGH (8.0E001 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 100 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
VFS-RY104B Plant Spec Point
Description:
Plant Vent Gas High Range Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
0.1 Maximum Instr Range:
100000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
EXH TO PLANT VENT DUCT Aiarm/Trip Setpoints:
HIGH (8.0E004 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 101 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
DDS-RSA41-L1 Plant Spec Point
Description:
Spent Fuel Pool Level RSA Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
ft ENGR Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
25.75 Zero Point
Reference:
SEALEV Reference Point Notes:
AT ELV 109.5, 0.25 FT BELOW TOP SFP RACKS PROG or SENS:
P Number of Sensors:
3 How Processed:
BEST AVAILABLE PARAMETER Sensor Locations:
ROOM 12365 (019A/C) ROOM 12341 (019B)
Alarm/Trip Setpoints:
LOW 2 (23.5 FT)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 102 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
WGS-RY017 Plant Spec Point
Description:
Gaseous Radwaste Outlet Radiation Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
0.0001 Maximum Instr Range:
100000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
N/A Alarm/Trip Setpoints:
HIGH (2.5 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A Instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 103 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtie 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point ID:
WLS-RY229 Piant Spec Point
Description:
Liquid Radwaste Effluent Radiation Generic/Cond
Description:
NL Analog/Digitai:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum instr Range:
1e-07 Maximum Instr Range:
0.1 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
WLS EFFLUENT DISCHARGE PATH Alarm/Trip Setpoints:
HIGH (5.0E-005 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Ni Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 104 of 105
ND-21-0342 ERDS Data Point Library For Vogtle Unit 3 Date:
04/12/2021 Reactor Unit:
Vogtle 3 Data Feeder:
N/A NRC ERDS Parameter:
NL Point iD:
WWS-RY021 Plant Spec Point
Description:
Waste Water Channel Activity Generic/Cond
Description:
NL Analog/Digital:
A ENGR Units/Dig States:
uCi/cc ENGR Units Conversion:
N/A Minimum Instr Range:
1e-07 Maximum instr Range:
0.1 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROG or SENS:
S Number of Sensors:
1 How Processed:
N/A Sensor Locations:
WLS EFFLUENT DISCHARGE PATH Aiarm/Trip Setpoints:
HIGH (2E-007 UCI/CC)
Nl Detector Power Supply Cut-off Power Level:
N/A Nl Detector Power Supply Turn-on Power Level:
N/A instrument Failure Mode:
N/A Temperature Compensation For DP Transmitters:
N Level Reference Leg:
N/A Unique System
Description:
N/A Page 105 of 105