NRC EXAM MATERIAL Page 1 of 13 Palisades April 2020 PALISADES 2020 INITIAL LICENSE EXAM JOB PERFORMANCE MEASURE JPM: CONDUCT OF OPERATIONS: A.1a TITLE: PERFORM OPERABILITY CHECKS FOR SAFEGUARDS TRANSFORMER 1-1 AND STARTUP TRANSFORMER 1-2.
CANDIDATE:
EXAMINER:
NRC EXAM MATERIAL Page 2 of 13 Palisades April 2020 JOB PERFORMANCE MEASURE DATA PAGE Task: PL-342 225 02 01 / Perform operators Daily/Weekly/Bi-Weekly surveillance items in all modes.
Alternate Path: No.
Facility JPM #: New.
K/A: 2.1.7 Importance: RO: 4.4 K/A Statement: Ability to evaluate plant performance and make operational judgments based on operating characteristics, reactor behavior, and instrument interpretation. (CFR: 41.5 / 43.5 / 45.12 / 45.13)
Task Standard: Determine Startup Transformer 1-2 does not meet Operability requirements.
Preferred Evaluation Location: Classroom _X__
In Plant Preferred Evaluation Method:
Perform
_X___
In Plant
References:
SOP-30, Station Power, revision 091 Validation Time: 10 minutes Time Critical: No Candidate:
Time Start: ________
Time Finish: ________
Performance Time:
________ minutes Performance Rating:
SAT______
UNSAT ______
Comments:
Examiner: _______________________________
Date:
Signature
NRC EXAM MATERIAL Page 3 of 13 Palisades April 2020 EXAMINER COPY ONLY Tools/Equipment/Procedures Needed:
SOP-30, Station Power, revision 091 READ TO CANDIDATE DIRECTION TO CANDIDATE:
I will explain the initial conditions and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS:
The plant is at 100% power.
2400 VAC Buses 1C, 1D, and 1E have been transferred from Safeguards/Station Power to Startup Power per SOP-30, Station Power, Section 7.3.2 for emergent inspection of the 2400 VAC Safeguards Bus.
Safeguards Transformer 1-1 and Startup Transformer 1-2 Load Tap Changers are in AUTO.
INITIATING CUE:
The Control Room Supervisor (CRS) directs you to perform SOP-30, Section 7.3.2 step e.7 to ensure voltage requirements of Section 4.2.1, Safeguards Transformer 1-1, and Startup Transformer 1-2 Operability Requirements, are met.
NRC EXAM MATERIAL Page 4 of 13 Palisades April 2020 Time Start: ________
Proc.Step TASK ELEMENT 1 STANDARD Grade N/A Obtain copy of SOP-30.
Candidate simulates or describes where a copy of SOP-30 can be obtained.
S U Comment:
Evaluator Cue: When Candidate simulates or describes where a copy of SOP-30 can be found, provide a copy of SOP-30 (JPM Attachment 1 and JPM Attachment 2).
Proc.Step TASK ELEMENT 2 STANDARD Grade 4.2.1 a.
(1)
For Safeguards Transformer 1-1 and Startup Transformer 1-2 to be considered operable the following requirements apply:
Safeguards Transformer 1-1 and Startup Transformer 1-2, Load Tap Changers shall be maintained in AUTO Candidate verifies Load Tap Changers are in AUTO per Initial Conditions.
S U Comment:
NRC EXAM MATERIAL Page 5 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 3 STANDARD Grade 4.2.1 a.
(2)
The voltage on EVI-0001, 2400V Bus 1C Volts, and EVI-0002, 2400V Bus 1D Status Voltage respectively, must be greater than or equal to 2367 VAC on at least one phase during the normal configuration (i.e., Bus 1C, 1D, and 1E fed from same transformer, either Safeguards Transformer 1-1 or Startup Transformer 1-2).
If voltage indicates 2372 VAC or lower on Bus 1C or 1D, then initiate investigation into the low voltage indication.
Candidate reviews EVI-0001 data.
AND Identifies that all three phases of Bus 1C Volts are < 2372 VAC and < 2367 VAC.
S U Comment:
Evaluator Cue: Provide Candidate JPM Attachment 3 which contains EVI-0001 (Bus 1C), EVI-0002 (Bus 1D), and EVI-0003 (S/U XFMR) readings.
CRITICAL STEP Proc.Step TASK ELEMENT 4 STANDARD Grade 4.2.1 a.
(2)
The voltage on, EVI-0001, 2400V Bus 1C Volts and EVI-0002, 2400V Bus 1D Status Voltage respectively, must be greater than or equal to 2367 VAC on at least one phase during the normal configuration (i.e., Bus 1C, 1D, and 1E fed from same transformer, either Safeguards Transformer 1-1 or Startup Transformer 1-2).
If voltage indicates 2372 VAC or lower on Bus 1C or 1D, then initiate investigation into the low voltage indication.
Candidate reviews EVI-0002 data.
AND Identifies that all three phases of Bus 1D Volts are < 2372 VAC.
S U Comment:
CRITICAL STEP
NRC EXAM MATERIAL Page 6 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 5 STANDARD Grade 4.2.1 a.
(3) - (5)
Determines that steps (3) - (5) are not applicable for plant configuration.
Candidate determines that steps (3) - (5) are not applicable (N/A).
S U Comment:
Proc.Step TASK ELEMENT 6 STANDARD Grade 4.2.1 b.
If any requirement listed in Step 4.2.1a is not met, then declare applicable offsite power source inoperable.
Candidate informs the CRS that all three phases of Bus 1C Volts are < 2372 VAC and < 2367 VAC.
AND Informs the CRS that all three phases of Bus 1D Volts are < 2372 VAC.
AND Informs CRS that low voltage indication on Bus 1C and 1D need to be investigated.
AND Startup Transformer 1-2 Operability Requirements are NOT met and should be declared inoperable.
S U Comment:
Evaluator Note: The Critical Step is to identify that Startup Transformer 1-2 Operability requirements are not met.
Evaluator Cue: If the Candidate informs CRS that voltage requirements for the Startup Transformer 1-2 are NOT met, acknowledge the report.
CRITICAL STEP Time End: ________
END OF TASK
NRC EXAM MATERIAL Page 7 of 13 Palisades April 2020 CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER TO UPON COMPLETION OF TASK)
Special Note: Assume that all Plant Requirements and Precautions and Limitations have been reviewed and complied with. You are NOT expected, nor are you required to consult the Plant Requirements and Precautions and Limitations section of any procedure for this JPM.
INITIAL CONDITIONS:
The plant is at 100% power.
2400 VAC Buses 1C, 1D, and 1E have been transferred from Safeguards/Station Power to Startup Power per SOP-30, Station Power, Section 7.3.2 for emergent inspection of the 2400 VAC Safeguards Bus.
Safeguards Transformer 1-1 and Startup Transformer 1-2 Load Tap Changers are in AUTO.
INITIATING CUE:
The Control Room Supervisor (CRS) directs you to perform SOP-30, Section 7.3.2 step e.7 to ensure voltage requirements of Section 4.2.1, Safeguards Transformer 1-1, and Startup Transformer 1-2 Operability Requirements, are met.
NRC EXAM MATERIAL Page 8 of 13 Palisades April 2020 JPM ATTACHMENT 1
NRC EXAM MATERIAL Page 9 of 13 Palisades April 2020 JPM ATTACHMENT 1 N/A
NRC EXAM MATERIAL Page 10 of 13 Palisades April 2020 JPM ATTACHMENT 1
NRC EXAM MATERIAL Page 11 of 13 Palisades April 2020 JPM ATTACHMENT 2
NRC EXAM MATERIAL Page 12 of 13 Palisades April 2020 JPM ATTACHMENT 2
NRC EXAM MATERIAL Page 13 of 13 Palisades April 2020 JPM ATTACHMENT 3 EVI-0001, 2400V Bus 1C Voltmeter Phase A 2360.6 VAC Phase B 2360.6 VAC Phase C 2360.6 VAC EVI-0002, 2400V Bus 1D Voltmeter Phase A 2370.4 VAC Phase B 2370.4 VAC Phase C 2370.4 VAC EVI-0003, Startup XFMR 1-2 Voltmeter Phase A 2420.1 VAC Phase B 2421.3 VAC Phase C 2422.4 VAC
NRC EXAM MATERIAL Page 1 of 13 Palisades April 2020 PALISADES 2020 INITIAL LICENSE EXAM JOB PERFORMANCE MEASURE JPM:
CONDUCT OF OPERATIONS: A.1b TITLE:
PERFORM SHO-1 SURVEILLANCE STEPS CANDIDATE:
EXAMINER:
NRC EXAM MATERIAL Page 2 of 13 Palisades April 2020 JOB PERFORMANCE MEASURE DATA PAGE Task: PL-342 233 02 01 / Perform Operators Shift Surveillance Items in All Modes.
Alternate Path: No Facility JPM #: New.
K/A: 2.1.19 Importance: RO: 3.9 K/A Statement: Ability to use plant computers to evaluate systems or component status.
(CFR: 41.10 / 45.12 / 45.13)
Task Standard: Identify the four out-of-specification items that do not meet the commitments or requirements of SHO-1.
Preferred Evaluation Location: Simulator
__X__
In Plant Preferred Evaluation Method:
Perform
_X___
In Plant
References:
SHO-1, Operators Shift Items Modes 1, 2, 3, and 4, revision 075 Validation Time: 12 minutes Time Critical: No Candidate:
Time Start: ________
Time Finish: ________
Performance Time:
________ minutes Performance Rating:
SAT______
UNSAT ______
Comments:
Examiner: _______________________________
Date:
Signature
NRC EXAM MATERIAL Page 3 of 13 Palisades April 2020 EXAMINER COPY ONLY Tools/Equipment/Procedures Needed:
SHO-1, Operators Shift Items Modes 1, 2, 3, and 4, Attachment 1 paper copy.
Complete copy of SHO-1.
Red pen Normal Control Room references Also see Simulator Operator Instructions (last page of this document).
READ TO CANDIDATE DIRECTION TO CANDIDATE:
I will explain the initial conditions and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS:
Plant is in MODE 1.
Reactor power is 100%.
It is Wednesday dayshift.
INITIATING CUE:
The Control Room Supervisor (CRS) has given you a paper copy of SHO-1, Operators Shift Items Modes 1, 2, 3, and 4, Attachment 1, Shift Surveillance Data Sheet.
The CRS directs you to complete the following items on Attachment 1 per step 5.1.b of SHO-1:
5.1.15, SIRW Tank Temperature 5.1.32, Main Feedwater Temperature 5.1.33, Main Feedwater Flow 5.1.34, Auxiliary Feedwater Flow
NRC EXAM MATERIAL Page 4 of 13 Palisades April 2020 Time Start: ________
Proc.Step TASK ELEMENT 1 STANDARD Grade 5.1.15 On Panel C-13 CHECK each tank temperature is greater than or equal to 80°F AND Less than or equal to 100°F AND Both channels agree within 5°F.
Candidate records TIA-0328, SIRW Tank Temperature value (range of 74 - 76°F).
AND Records TIA-0332, SIRW Tank Temperature value (range of 86 - 88°F).
AND Initials the Recorded By column.
AND Identifies that the NRC commitment of at least 80 °F is not met for TIA-0328. (OOS #1)
AND Red circles TIA-0328 reading.
AND Identifies that the 5°F allowable difference between channels has been exceeded and may circle TIA-0332 reading. (OOS #2)
AND Provides detailed explanation of issue on Comments section of Attachment 1.
S U Comment:
Evaluator Note: Steps for the review of SHO-1 may be performed in an order different than listed here and throughout JPM.
CRITICAL STEP is to identify TIA-0328 is < 80 °F AND channels do not agree within 5 °F.
Evaluator Cue: If informed of out-of-spec readings, repeat back information to Candidate.
If asked by Candidate whether to proceed, provide cue to continue with SHO-1.
CRITICAL STEP
NRC EXAM MATERIAL Page 5 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 2 STANDARD Grade 5.1.32 CHECK unfiltered Main Feed temperatures on PPC Page 521 are within 10°F of associated readings on REC-C11-03.
Candidate records S/G A Main Feed Temperature, TT_0708A, from PPC Page 521 (range of 436 - 437 °F).
AND Records E6B Outlet on REC-C-11-03 CH 04 as 451.9 °F.
AND Records S/G B Main Feed Temperature, TT_0706A, from PPC Page 521 (range of 437 - 438 °F).
AND Records E6A Outlet on REC-C-11-03 CH 03 as 437.7 °F.
AND Initials the Recorded By column.
AND Determines that TT_0708A is NOT within 10°F of the associated reading on REC-C11-03 CH 04. (OOS #3)
AND Red circles TT_0708A reading and may circle REC-C11-03 CH 4 reading.
AND Provides detailed explanation of issue on Comments section of Attachment 1.
S U Comment:
Evaluator Note: CRITICAL STEP is to identify S/G A MFW Temps do not agree within 10 °F.
Evaluator Cue: If informed of out-of-spec readings, repeat back information to Candidate.
If asked by Candidate whether to proceed, provide cue to continue with SHO-1.
CRITICAL STEP
NRC EXAM MATERIAL Page 6 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 3 STANDARD Grade 5.1.33 CHECK unfiltered Main Feed flow on PPC Page 521 are within 0.5 E6 PPH of readings on FI-0701 and FI-0703 Candidate records FEEDWTR_FLOW_SGA from PPC Page 521 (range of 5.5 - 5.6).
AND FI-0701 at C-01 (CK-FW702) as 5.59.
AND Records FEEDWTR_FLOW_SGB from PPC Page 521 (range of 5.7 - 5.8).
AND FI-0703 at C-01 (CK-FW701) as 5.7 -5.8.
AND Initials the Recorded By column.
AND Identifies that Main Feedwater flows are within requirements for both S/Gs.
S U Comment:
CRITICAL STEP
NRC EXAM MATERIAL Page 7 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 4 STANDARD Grade 5.1.34 CHECK each redundant Auxiliary Feed flow instrument reading is within 30 gpm of its counterpart (45 gpm with no flow to the steam generator).
Records FIC-0749 as 5.
AND Records FI-0749A as 2.
AND Records FIC-0727 as 0.
AND Records FI-0727A as 5.
AND Records FIC-0737A in range of 50 - 60.
AND Records FI-0737 as 0.
AND Records FIC-0736A as 5.
AND Records FI-0736 as 0.
AND Initials the Recorded By column.
AND Identifies that FIC-0737A and FI-0737 do not meet requirements. (OOS #4)
AND Red circles FIC-0737A and FI-0737 readings on Attachment 1.
AND Provides detailed explanation of issue on Comments section of Attachment 1.
S U Comment:
Evaluator Note: CRITICAL STEP is to identify FIC-0737A and FI-0737 do not agree within 45 gpm.
Evaluator Cue: If informed of out-of-spec readings, repeat back information to Candidate.
If asked by Candidate whether to proceed, provide cue to continue with SHO-1.
CRITICAL STEP
NRC EXAM MATERIAL Page 8 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 5 STANDARD Grade N/A Notify CRS that SHO-1 completed as directed.
Candidate notifies CRS that SHO-1 has been completed as directed.
S U Comment:
Evaluator Cue: When informed of completed SHO-1, repeat back information.
Time End: ________
END OF TASK
NRC EXAM MATERIAL Page 9 of 13 Palisades April 2020 SIMULATOR OPERATOR INSTUCTIONS Use IC-120 for LOI2020
NRC EXAM MATERIAL Page 10 of 13 Palisades April 2020 CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER TO UPON COMPLETION OF TASK)
Special Note: Assume that all Plant Requirements and Precautions and Limitations have been reviewed and complied with. You are NOT expected, nor are you required to consult the Plant Requirements and Precautions and Limitations section of any procedure for this JPM.
INITIAL CONDITIONS:
Plant is in MODE 1.
Reactor power is 100%.
It is Wednesday dayshift.
INITIATING CUE:
The Control Room Supervisor (CRS) has given you a paper copy of SHO-1, Operators Shift Items Modes 1, 2, 3, and 4, Attachment 1, Shift Surveillance Data Sheet.
The CRS directs you to complete the following items on Attachment 1 per step 5.1.b of SHO-1:
5.1.15, SIRW Tank Temperature 5.1.32, Main Feedwater Temperature 5.1.33, Main Feedwater Flow 5.1.34, Auxiliary Feedwater Flow
NRC EXAM MATERIAL Page 11 of 13 Palisades April 2020
NRC EXAM MATERIAL Page 12 of 13 Palisades April 2020
NRC EXAM MATERIAL Page 13 of 13 Palisades April 2020
NRC EXAM MATERIAL Page 1 of 10 Palisades April 2020 PALISADES 2020 INITIAL LICENSE EXAM JOB PERFORMANCE MEASURE JPM: EQUIPMENT CONTROL: A.2 TITLE: REVIEW P-7A, SERVICE WATER PUMP, TAGOUT.
CANDIDATE:
EXAMINER:
NRC EXAM MATERIAL Page 2 of 10 Palisades April 2020 JOB PERFORMANCE MEASURE DATA PAGE Task: PL-119 012 03 01 / Conduct Switching & Tagging Orders Alternate Path: No.
Facility JPM #: PLPJPM-LOR-RO Admin 5, revision 00 K/A: 2.2.13 Importance:
RO: 4.1 K/A Statement: Knowledge of tagging and clearance procedures. (CFR: 41.10 / 45.13)
Task Standard: Three (3) preparation errors are identified for P-7A equipment tagout.
Preferred Evaluation Location: Simulator
__X__
In Plant Preferred Evaluation Method:
Perform
_X___
In Plant
References:
EN-OP-102, Protective and Caution Tagging, revision 024 EN-OP-102-01, Protective and Caution Tagging Forms and Checklist, revision 014 SOP-15, Service Water System, revision 069 Palisades P&ID drawings Palisades Electrical drawings Validation Time: 12 minutes Time Critical: No Candidate:
Time Start: ________
Time Finish: ________
Performance Time:
________ minutes Performance Rating:
SAT______
UNSAT ______
Comments:
Examiner: _______________________________
Date:
Signature
NRC EXAM MATERIAL Page 3 of 10 Palisades April 2020 EXAMINER COPY ONLY Tools/Equipment/Procedures Needed:
EN-OP-102, Protective and Caution Tagging, revision 024 EN-OP-102-01, Protective and Caution Tagging Forms and Checklist, revision 014 SOP-15, Service Water System, revision 069 Palisades P&ID drawings Palisades Electrical drawings READ TO CANDIDATE DIRECTION TO CANDIDATE:
I will explain the initial conditions and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS:
- P-7A, Service Water Pump, discharge basket strainer needs cleaning due to high DP.
- A Nuclear Controls Operator (NCO) has developed a new tagout for removing P-7A from service per SOP-15 Section 8.1.1.
- The NCO who developed the tagout has signed as Preparer.
- The eSOMS Clearance module is not available.
INITIATING CUE:
State the following:
Review the tagout for P-7A and either sign as the Reviewer or identify any / all error(s) that need to be addressed prior to signing as Reviewer.
NRC EXAM MATERIAL Page 4 of 10 Palisades April 2020 Time Start: ________
Proc.Step TASK ELEMENT 1 STANDARD Grade N/A Obtain a copy of EN-OP-102.
Candidate simulates or describes where a copy of EN-OP-102 can be obtained.
S U Comment:
Evaluator Cue: When Candidate simulates or describes where a copy of EN-OP-102 can be obtained, provide Candidate a copy of the prepared and EN-OP-102, including EN-OP-102-01 Checklist.
Evaluator Note: EN-OP-102 is to be provided to applicant at the start of the JPM along with the prepared copy of the tagout. Do not provide additional reference material unless the Candidate requests it.
Proc.Step TASK ELEMENT 2 STANDARD Grade EN-OP-102 Sect.
5.6 PERFORM the Review independent of the Tagout Preparation.
Candidate performs review of Tagout using the same tools and techniques used by the Tagout Preparer in Section 5.3.
S U Comment:
Evaluator Note: Candidate may perform steps in an order than listed here during their review of the tagout.
Proc.Step TASK ELEMENT 3 STANDARD Grade N/A Refer to procedures (EN-OP-102 and/or SOP-15) to ensure the proper equipment tagout sequence.
Candidate uses either of the following procedures to determine the tagout sequence:
Tagout Cover Sheet combined with station electrical and mechanical drawings.
OR SOP-15 Section 8.1.1 to remove Service Water Pumps from service.
S U Comment:
Evaluator Cue: If Candidate requests SOP-15 or plant drawings, provide the requested reference materials.
Evaluator Note: Guidance to remove pump P-7A from service is detailed in SOP-15 Section 8.1.1.
NRC EXAM MATERIAL Page 5 of 10 Palisades April 2020 Proc.Step TASK ELEMENT 4 STANDARD Grade SOP-15 step 8.1.1b ENSURE OFF the applicable Service Water Pump and NOT in STANDBY.
Candidate verifies tagging order sequence Step 1 is correct:
NO TAG step for 1-CSW-Pump-P-7A.
S U Comment:
Proc.Step TASK ELEMENT 5 STANDARD Grade SOP-15 step 8.1.1b.
Control Room control switch to TRIP and CAUTION TAG placed.
Candidate verifies tagging order sequence Step 2 is correct:
1-CSW-CKTBRK-152-204CS control room control switch with CAUTION TAG P-7A Tagged Out.
S U Comment:
Proc.Step TASK ELEMENT 6 STANDARD Grade SOP-15 step 8.1.1c.
RACK the applicable Service Water Pump breaker to DISCONNECT.
P-7A / Breaker 152-204 Candidate identifies that breaker 152-204 for P-7A should be IN DISCONNECT with DANGER tag.
AND Identifies that the incorrect breaker (152-205 for P-7C) has been tagged IN DISCONNECT with DANGER tag. (Error #1)
S U Comment:
Evaluator Cue: If the Candidate asks whether the tagout should be corrected by the Preparer, provide cue to continue with review and tell Preparer at completion.
Evaluator Note: Candidate may circle the incorrect item.
CRITICAL STEP
NRC EXAM MATERIAL Page 6 of 10 Palisades April 2020 Proc.Step TASK ELEMENT 7 STANDARD Grade SOP-15 step 8.1.1d.
UNLOCK AND CLOSE the associated Service Water Pump Discharge Valve:
P-7A / MV-SW102 Candidate identifies that the correct position for MV-SW102 should be UNLOCKED and CLOSED with DANGER TAG.
AND Identifies MV-SW102 is incorrectly tagged in the LOCKED OPEN position with DANGER tag. (Error #2).
S U Comment:
Evaluator Cue: If the Candidate asks whether the tagout should be corrected by the Preparer, provide cue to continue with review and tell Preparer at completion.
Evaluator Note: Candidate may circle the incorrect item.
CRITICAL STEP Proc.Step TASK ELEMENT 8 STANDARD Grade SOP-15 step 8.1.1d.
ENSURE CLOSED the associated Service Water Pump Recirculation Valve:
P-7A / MV-SW342 Identifies that MV-SW342 should be tagged as LOCKED CLOSED or CLOSED.
AND Identifies that MV-SW342 should be DANGER tagged.
AND Identifies MV-SW342 is incorrectly identified as being a NO TAG step. (Error #3)
S U Comment:
Evaluator Cue: If the Candidate asks whether the tagout should be corrected by the Preparer, provide cue to continue with review and tell Preparer at completion.
Evaluator Note: Candidate may circle the incorrect items.
CRITICAL STEP
NRC EXAM MATERIAL Page 7 of 10 Palisades April 2020 Proc.Step TASK ELEMENT 9 STANDARD Grade N/A Completes review of Tagout with no additional errors found.
Operator identifies no additional errors.
S U Comment:
Evaluator Cue: When Candidate finishes the review of the tagout, inform the Candidate that another Operator will address the errors identified.
Proc.Step TASK ELEMENT 10 STANDARD Grade N/A Notification that Tagout review has been completed.
Operator notifies that CRS that the Tagout review has been complete and errors will need to be corrected.
S U Comment:
Evaluator Cue: As CRS, provide acknowledgement and reply that another Operator will correct the errors identified.
Time End: ________
END OF TASK
NRC EXAM MATERIAL Page 8 of 10 Palisades April 2020 CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER TO UPON COMPLETION OF TASK)
Special Note: Assume that all Plant Requirements and Precautions and Limitations have been reviewed and complied with. You are NOT expected, nor are you required to consult the Plant Requirements and Precautions and Limitations section of any procedure for this JPM.
INITIAL CONDITIONS:
- P-7A, Service Water Pump, discharge basket strainer needs cleaning due to high DP.
- A Nuclear Controls Operator (NCO) has developed a new tagout for removing P-7A from service per SOP-15 Section 8.1.1.
- The NCO who developed the tagout has signed as Preparer.
- The eSOMS Clearance module is not available.
INITIATING CUE:
State the following:
Review the tagout for P-7A and either sign as the Reviewer or identify any / all error(s) that need to be addressed prior to signing as Reviewer.
NRC EXAM MATERIAL Page 9 of 10 Palisades April 2020
NRC EXAM MATERIAL Page 10 of 10 Palisades April 2020
NRC EXAM MATERIAL Page 1 of 13 Palisades April 2020 PALISADES 2020 INITIAL LICENSE EXAM JOB PERFORMANCE MEASURE JPM: RADIATION PROTECTION: A.3 TITLE: RIA-2322, CONTAINMENT GAMMA MONITOR ELECTRONIC CHECK SOURCE TEST CANDIDATE:
EXAMINER:
NRC EXAM MATERIAL Page 2 of 13 Palisades April 2020 JOB PERFORMANCE MEASURE DATA PAGE Task: PL-342 258 02 01 / Perform In-Service Test Procedure(s).
Alternate Path: No Facility JPM #: New.
K/A: 2.3.5 Importance:
RO: 3.2 K/A Statement: Ability to use radiation monitoring systems, such as fixed radiation monitors and l alarms, portable survey instruments, personnel monitoring equipment, etc. (CFR: 41.11 / 41.12 / 43.4 / 45.9).
Task Standard: Perform Electronic Check Source Test without error.
Preferred Evaluation Location: Simulator
__X__
In Plant Preferred Evaluation Method:
Perform
_X___
In Plant
References:
SOP-39, Area Radiation Monitoring System, revision 018 Validation Time: 6 minutes Time Critical: No Candidate:
Time Start: ________
Time Finish: ________
Performance Time:
________ minutes Performance Rating:
SAT______
UNSAT ______
Comments:
Examiner: _______________________________
Date:
Signature
NRC EXAM MATERIAL Page 3 of 13 Palisades April 2020 EXAMINER COPY ONLY Tools/Equipment/Procedures Needed:
Normal Control Room references.
Any full power IC for LOI 2020.
Also see Simulator Operator Instructions (last page of this document)
READ TO CANDIDATE DIRECTION TO CANDIDATE:
I will explain the initial conditions and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS:
RIA-2322, Containment Hi Range Gamma - Right Chnl, was removed from service for I&C Maintenance repairs.
The Control Room Supervisor (CRS) entered LCO 3.3.7, PAM Instrumentation, Condition A.
RIA-2322 is now ready to be restored to service.
SOP-39, Area Radiation Monitoring System, section 8.2.2 has been completed through step c.
INITIATING CUE:
The CRS directs you to complete RIA-2322 return to service by completing SOP-39 section 8.2.2 step d to perform the Electronic Check Source Test in accordance with Step 7.2.3.
NRC EXAM MATERIAL Page 4 of 13 Palisades April 2020 Time Start: ________
Proc.Step TASK ELEMENT 1 STANDARD Grade N/A Obtains a copy of SOP-39.
Candidate simulates or describes where a copy of SOP-39 can be obtained.
S U Comment:
Evaluator Cue: When Candidate simulates or describes where a copy of SOP-39 can be obtained, provide Candidate with JPM Attachment 1 and JPM Attachment 2.
Proc.Step TASK ELEMENT 2 STANDARD Grade N/A Review SOP-39 section 8.2.2 and determines that section 7.2.3 is to be performed.
Candidate reviews SOP-39 section 8.2.2.
AND Determines that section 7.2.3 is to be performed.
S U Comment:
Proc.Step TASK ELEMENT 3 STANDARD Grade 7.2.3 a.1.
PLACE function switch in TEST position.
Candidate positions function switch from OFF to TEST.
S U Comment:
Evaluator Note: Positioning function switch to TEST clears EK-0226 alarm.
CRITICAL STEP
NRC EXAM MATERIAL Page 5 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 4 STANDARD Grade 7.2.3 a.2 Momentarily DEPRESS ECS push button AND VERIFY the following:
(a) Meter indicates approximately 103 R/hr.
(b) Green (Safe-Reset) light stays illuminated.
(c) IF the meter fails to deflect OR the green light extinguishes after approximately four seconds, THEN VERIFY "CONTAINMENT GAMMA RIA-2321/RIA-2322 FAIL" alarm (EK-0225/EK-0226) annunciates indicating a failure.
Candidate depresses ECS push button.
AND Verifies the meter indicates approximately 103 R/hr.
AND Verifies the Green (Safe-Reset) light stays illuminated for at least four seconds.
AND Determines that a failure has NOT occurred.
S U Comment:
Evaluator Note: NOTE preceding step a.2: Expect an approximately 4 second delay between depressing the ECS pushbutton and meter deflection in the following step.
CRITICAL STEP Proc.Step TASK ELEMENT 5 STANDARD Grade 7.2.3 a.3 PUSH AND HOLD Channel Test push button AND OBSERVE Alert, High, and Channel Test lamps light immediately and annunciator EK-0225 or EK-0226 will alarm.
Candidate pushes and holds Channel Test push button.
AND Observes Alert, High, and Channel Test lamps light immediately.
AND Verifies that annunciator EK-0225 or EK-0226 alarms.
S U Comment:
CRITICAL STEP
NRC EXAM MATERIAL Page 6 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 6 STANDARD Grade 7.2.3 a.4 RELEASE Channel Test push button AND OBSERVE the Alert and High lamps shall go out. The Safe/Reset lamp may go out.
Candidate releases Channel Test push button.
AND Observes the Alert and High lamps shall go out.
AND Observes the Safe/Reset lamp may go out.
S U Comment:
Evaluator Note: Note preceding step a.4: The green (Safe/Reset) lamp operates at all times when a greater than 1 R/hr indication is read on the meter. The Safe/Reset lamp should extinguish during the test, if the meter indication is less than 1R/hr.
CRITICAL STEP Proc.Step TASK ELEMENT 7 STANDARD Grade 7.2.3 a.5 PLACE function switch to ALL position.
Candidate positions function switch to ALL.
S U Comment:
CRITICAL STEP Proc.Step TASK ELEMENT 8 STANDARD Grade 7.2.3 a.6 MOMENTARILY DEPRESS ECS push button AND VERIFY the following:
(a) Meter indicates approximately 103 R/hr.
(b) Green (Safe-Reset) light illuminates.
(c) IF the meter fails to deflect OR the green light extinguishes after approximately four seconds, THEN VERIFY "CONTAINMENT GAMMA RIA-2321/RIA-2322 FAIL" alarm (EK-0225/EK-0226) annunciates indicating a failure.
Candidate depresses ECS push button.
AND Verifies the meter indicates approximately 103 R/hr.
AND Verifies the Green (Safe-Reset) light stays illuminated for at least four seconds.
AND Determines that a failure has NOT occurred.
S U Comment:
CRITICAL STEP
NRC EXAM MATERIAL Page 7 of 13 Palisades April 2020 Proc.Step TASK ELEMENT 9 STANDARD Grade N/A Notifies CRS that RIA-2322 Electronic Check Source Test has been completed.
Candidate notifies CRS that RIA-2322 Electronic Check Source Test has been completed.
S U Comment:
Evaluator Cue: Repeat back and acknowledge report.
Time End: ________
END OF TASK
NRC EXAM MATERIAL Page 8 of 13 Palisades April 2020 SIMULATOR OPERATOR INSTRUCTIONS Use IC-17 for LOI 2020.
RIA-2322 selector switch positioned to OFF.
EK-0226, Cont Gamm RIA-2322 Fail, is in and Acknowledge.
NRC EXAM MATERIAL Page 9 of 13 Palisades April 2020 CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER TO UPON COMPLETION OF TASK)
Special Note: Assume that all Plant Requirements and Precautions and Limitations have been reviewed and complied with. You are NOT expected, nor are you required to consult the Plant Requirements and Precautions and Limitations section of any procedure for this JPM.
INITIAL CONDITIONS:
RIA-2322, Containment Hi Range Gamma - Right Chnl, was removed from service for I&C Maintenance repairs.
The Control Room Supervisor (CRS) entered LCO 3.3.7, PAM Instrumentation, Condition A.
RIA-2322 is now ready to be restored to service.
SOP-39, Area Radiation Monitoring System, section 8.2.2 has been completed through step c.
INITIATING CUE:
The CRS directs you to complete RIA-2322 return to service by completing SOP-39 section 8.2.2 step d to perform the Electronic Check Source Test in accordance with Step 7.2.3.
NRC EXAM MATERIAL Page 10 of 13 Palisades April 2020 JPM ATTACHMENT 1 N/A
NRC EXAM MATERIAL Page 11 of 13 Palisades April 2020 JPM ATTACHMENT 1
NRC EXAM MATERIAL Page 12 of 13 Palisades April 2020 JPM ATTACHMENT 2
NRC EXAM MATERIAL Page 13 of 13 Palisades April 2020 JPM ATTACHMENT 2