Notice of Violation from Insp on 980113-0223.Violations Noted:On 980117,plant Administrative Procedure 330-1,section c.b.c.4,not Implemented & on 970910,licensee Operated Gwps Differently from Ufsar,Section 11.3.2.1
ML20248L816
Person / Time
Site: Byron  
Issue date: 03/16/1998
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20248L812 List:
References
50-454-98-05, 50-454-98-5, 50-455-98-05, 50-455-98-5, NUDOCS 9803240247
Download: ML20248L816 (5)


Text

-_--_-__--

c

(

NOTICE OF VIOLATION Commonwealth Edison Company Docket Nos. 50-454; 50-455 Byron Station, Units 1 and 2.

License Nos. NPF-37; NPF-66 During an NRC inspection conducted on January 13 through February 23,1998, seven violations of NRC requirements were identified. In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions, NUREG-1600, the violations are listed below:

J 1.-

Technical Specification 6.8.1.a requires that written procedures be established, implemented, and maintained for procedures recommended in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978, s.

Appendix A of Regulatory Guide 1.33, Revision 2, February 1978, specifies equipment control, e.g., locking and tagging, as an example of an administrative procedure.

Byron Administrative Procedure 330-1," Station Equipment Out-of-Service Procedure," Revision 28, Section C.6.c.4, requires, in part, that the equipment listed on the out-of-service (OOS) form be retumed to service.

Out-of-Service No. 970006915 required that the Unit 1 seal water retum filter 1CV02F inlet isolation valve,1CV8396A, the Unit 1 seal water retum filter 1CV02F bypass valve,1CV8399, the control switch for the reactor coolant pump seal water return containment isolation valve,1HS-CV057, and the control switch for the reactor coolant pump seal water retum isolation valve,1HS-CV082, be retumed to service.

Contrary to the above, on January 17,199J, Byron Administrative Procedure 330-1, Section c.b.c.4, was not implemented in that OOS No. 97006915 was cleared without returning to service all equipment listed on the OOS. Specifically, Unit 1 seal water retum filter inlet isolation valve and bypass valve, as well as the control switches for two isolation valves for the reactor coolant pump seal water, were not retumed to service before clearing the OOS.

(50-454/98005-01a(DRP); 50-455/98005-01a(DRP)

This is a Severity Level IV violation (Supplement I).

l l

b.

Regulatory Guide 1.33," Quality Assurance Program Requirements," Revision 2, 1

Appendix A, paragraph 9.e., states, in part, that general procedures for the control i

of maintenance, repair, replacement, and modification work should be prepared i

L before reactcr operation is begun.

Byron Administrative Procedure (BAP) 1610-9, Engineering Requests,"

Revision 4, paragraph A, states that the procedure purpose was to explain when Engineering Requests (ERs) were used and describe the process in which ERs were submitted, completed, and administratively controlled.

. BAP 1610-9, " Engineering Requests," Revision 4, paragraph C.2.a, states that examples of requested activities included design changes (modifications, minor plant changes, exempt changes) and that the changes shall be processed as ER type code potential design change requests.

9803240247 980316 ADOCK0500g4 DR i

4 Notice of Violation Contrary to the above, on July 15,1996, an engineering request was not processed to review a potential design change (modification) to the 1B essential service water pump prior to the actual modification. Specifically, a gasket was installed to stop an oilleak that was not an approved modification.

(50-454/98005-01b(DRP); 50-455/98005-01b(DRP))

This is a Severity Level IV violation (Supplement I).

2.

10 CFR Part 50, Appendix B, Criterion V, " Instructions, Procedures, and Drawings,"

requires, in part, that activities affecting quality shall be prescribed by documented instructions of a type appropriate to the circumstances.

NSWP-A-03, " Foreign Material Exclusion, " Revision 0, provides controls for preventing foreign material from entering systems.

Contrary to the above, on June 5,1997, NSWP-A-03, " Foreign Material Exclusion,"

Revision 0, was not of a type appropriate to the circumstances in that it failed to prevent the intrusion of foreign material, in the form of a condenser tube cleaning brush, into the containment spray system. (50-454/98005-02(DRP); 50-455/98005-02(DRP))

This is a Severity Level IV violation (Supplement I).

3.

10 CFR Part 50.59(a)(1) states, in part, that the holder of a license may make changes to the facility as described in the safety analysis report without prior Commission approval unless the proposed change involves an unreviewed safety question.

10 CFR 50.59(b)(1) states, in part, that the licensee shall maintain records of changes in the facility as described in the safety analysis report. These records must include a written safety evaluation which provides the bases for the determination that the change does not involve an unreviewed safety question.

The Byron Updated Final Safety Analysis Report (UFSAR), Section 11.3.2.1, " Gaseous Waste Management System Design," states, in part, that the gaseous waste processing system (GWPS) processes hydrogen stripped from the reactor coolant and nitrogen from the closed cover gas system. The components connected to the GWPS are limited to those which contain no air or aerated liquids in order to prevent the accumulation of oxygen in the system. Further, the GWPS is maintained at a pressure above atmospheric to avoid intrusion of air. Hence, the GWPS will normally not contain oxygen and special design precautions are taken in order to avoid unintentional intrusion of oxygen.

Contrary to the above, on September 10,1997, the licensee operated the GWPS different from that described in UFSAR, Section 11.3.2.1, in that a system containing air was vented to the GWPS via the chemical and volume control systern. A written safety evaluation had not been performed to determine that the change to the facility as described in the UFSAR did not involve an unreviewed safety question. Specifically, Temporary Change 97-2-156 (Revision 15 dated September 10,1997) to 2BVS 1.2.3.1-2,

" Unit 2 Train B ASME Surveillance Requirements for Centrifugal Charging Pump 2B and

c Notice of Violation Chomical and Volume Control System Valve Stroke Test," allowed portions of the chemical and volume control system piping that had been exposed to air during maintenance activity WR 9700068333, " Seal Injection Lines Need to be Cleaned," be vented to the volume control tank which is vented to the GWPS.

(50-454/98005-04(DRP); 50-455/98005-04(DRP))

l This is a Severity Level IV violation (Supplement I).

1 4.

Technical Specification 6.8.1.g states that written procedures shall be established,

)

implemented, and maintained covering the Fire Protection Program implementation.

j a.

Byron Administrative Procedure (BAP) 110r 9," Control, Use, and Storage of r

Flammable and Combustible Liquids and Aerosols," Revision 4, Step C.6,

" Cleanup of Flammable / Combustible Liquids," paragraph a, requires that flammable or combustible liquids whic.h are leaked or spilled shall be promptly cleaned up and not allowed to accumulate. Materials used to clean up the spill should be removed from the building.

Contrary to the above, on February 4,1998, the licensee did not implement Procedure BAP 1100-9, paragraph C.6.a, in that the inspectors identified a large plastic trash can full of materials that had been used to clean up a spill and not removed from the bu!iding. (50-454/98005-05a(DRP); 50-455/98005-05a(DRP))

This is a Severity Level IV violation (Supplement I).

b.

Byron Administrative Procedure (BAP) 1100-9, " Control, Use, and Storage of Flammabla and Combustible Liquids and Aerosols," Revision 4, paragraph C.2.b.,

states, in part, that flammable / combustible liquid containers that do not require prior authorization are: 1) approved / original containers of five gallons or less being transported and used immediately in the plant while in attendance of plant cersonnel.

Contrary to the above, the licensee did not implement Procedure BAP 1100-9, paragraph C.2.b., as evidenced by the following examples (50-454/98005-05b(DRP); 50-455/98005-05b(DRP)):

On February 4,1998, the inspectors identified two original containers of cleaning solution, less than five gallon containers, marked as combustible, i

not in attendance of plant personnel at the river screen house.

On January 27,1998, the inspectors identified two original containers of anti-seize lubricant, less than five gallon containers, marked as combustible, near the 1B essential service water pump not in attendance 1-of plant personnel.

I

.-__._._-_-___.___.-____._a

l 4

l.*

l Notice of Violation

-4 l

On January 30,1998, the inspectors identified an approximately %-gallon can containing oil in the Spent Fuel Pool (SFP) pump room not in attendance of plant personnel.

This is a Severity Level IV violation (Supplement 1).

c.

Byron Administrative Procedure (BAP) 1100-9, " Control, Use, and Storage of Flammable and Combustible Liquids and Aerosols," Revision 4, paragraph C.2.c.,

states that aerosol containers should be transported and used in quantities not to excero the amount needed for a specific job. These containers should not be left unattor,ded in the plant at any time. Storage in a Fire Marshal approved Flammable Liquids cabinet per paragraph C.5 is acceptable.

Contrary to the above, the licensee did not implement Procedure BAP 1100-9, paragraph C.2.c., as evidenced by the following examples (50-454/98005-05c(DRP); (50-455/98005-05c(DRP)):

On February 4,1998, the inspectors identified three aerosol cans in the river screen house unattended and not in a storage cabinet.

l On January 27,1998, the inspectors identified two unattended cans of aerosol degreaser, not in a storage cabinet, near the 1B essential service i

water pump.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, Commonwealth Edison is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region lil, and a copy to the NRC Resident inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter tran,nitting the Notice of Violation (Notice). This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. If an adequate reply is not received within the time specified in the Notice, an order may be issued to show cause why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response tinie.

If you contest this enforcement action, you should also provide a copy of your response to the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC i

20555-0001.

I 1

1 Under the authority of Section 182 of the Act,42 U.S.C. 2232, this response shall be submitted under oath.or affirmation.

l 1

i 1

l t

i Notice of Violation l Bc suse your response will be placed in the NRC Public Document Room (PDR), to the extent l

possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be placed in the PDR without redaction. If personal privacy or proprietary information is necessary to provide an acceptable response, then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your i

response that deletes such information. If you request withholding of such material, you MMil specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of withholding (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 C.FR 2.790(b) to support a request for withholding confidential commercial or financial information). If safeguards information is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

Dated at Lisle, Illinois this 16th day of March 1998 1

!