Revised Tech Spec Page 3/4-17Ba Re Control Bldg HVAC Sys
ML20247J086
Person / Time
Site: Seabrook NextEra Energy icon.png
Issue date: 05/24/1989
From:
PUBLIC SERVICE CO. OF NEW HAMPSHIRE
To:
Shared Package
ML20247J079 List:
References
NUDOCS 8906010034
Download: ML20247J086 (1)


Text

_ _ _

?

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) b.

The control room exhaust subsystem isolation damper (s) close, and.the exhaust fan trips off; c.

The control room emergency makeup air and filtration subsystem actuates with flows through the HEPA filters and charcoal adsorber banks; 3)

Verifying that upon generation of Remote Intake High Radiation test signal, the following automatic system functions occur:

a.

The normal makeup air fan (s) trip off and the normal makeup air isolation damper (s) close; b.

The control room exhaust subsystem isolation damper (s) close, and the exhaust fan trips off; c.

The control room emergency makeup air and filtration subsystem actuates with flows through the HEPA filters and charcoal adsorber banks; 4)

Verifying that-the Control Room Emergency Makeup Air and Filtration Subsystem maintains the control room at a positive pressure of greater than or equal to 1/8 inch Water Gauge at less than or equal to a pressurization flow of 600 cfm relative -

toadjacentareasduringsystemoperation;and 5)

Verifying that the heaters dissipate 3.6 i 0.36 kW when tested in accordance with ANSI N510-1980 g f.

After each complete.or partial replacement of a HEPA filter bank, by verifying that the filtration system satisfies the in place penetration and bypass leakage testing acceptance criteria of less than.05% in accordance with ANSI N510-1980 for a 00P test aerosol while operating the system at a flow rate of 1100 cfm 10%; and g.

After each complete or partial replacement of a charcoal adsorber bank, by verifying that the filtration system satisfies the in place penetration and bypass leakage testing acceptance criteria of less than.05% in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating the system at a flow rate of 1100 cfm i 10%.

l 8906010034 890524 4