MONTHYEARDD-99-01, Notice of Issuance of Director'S Decision DD-99-01,denying CAN Request to Revoke or Suspend HNP Operating License & to Hold Informal Public Hearing in Vicinity of Site & Granting Request to Consider Application of Requirements of 10CFR721999-01-12012 January 1999 Notice of Issuance of Director'S Decision DD-99-01,denying CAN Request to Revoke or Suspend HNP Operating License & to Hold Informal Public Hearing in Vicinity of Site & Granting Request to Consider Application of Requirements of 10CFR72 ML20154J9761998-10-0707 October 1998 Notice Hereby Given That by Petition Dtd 980911,Citizens Awareness Network (Petitioner) Requested That NRC Take Action with Regard to Haddam Neck Plant to Immediately Revoke or Suspend Util Operating License ML20195J4881998-09-16016 September 1998 Notice of EA & Fonsi Re Licensee Request for Reduction in Amount of Insurance Required for Facility ML20217E8981998-04-22022 April 1998 Notice of Receipt of Petition for Director'S Decision from Citizens Awareness Network,Inc Which Requests That NRC Immediately Suspend Operating License for Haddam Neck Plant ML20203E3421998-02-11011 February 1998 Notice of Issuance of Director'S Decision,Per 10CFR2.206 Wrt 970303 Petition Filed by AA Cizek Re Millstone & Haddam Neck Plants.Petitioner Requests Listed ML20217B9091997-09-12012 September 1997 Notice of Issuance of Partial Director'S Decision Under 10CFR2.206 W/Regard to Petitons & 961223 ML20217B2751997-09-0303 September 1997 Notice of Director'S Decision Re 970311 Petition Filed by R Bassilakis Re Actions Against CYAPC ML20198G9281997-08-27027 August 1997 Notice of Receipt of & Availability for Comment of post-shutdown Decommission Activities Rept ML20137Q8861997-04-0808 April 1997 Notice of Receipt of 970303 Petition Submitted by a Cizek, Per 10CFR2.206 Requesting That Licenses of Three Millstone Nuclear Reactors & Haddam Neck Nuclear Reactor Be Modified by Placing Certain Conditions on OLs ML20137P5241997-04-0303 April 1997 Notice of Receipt of 970311 Petition for Director'S Decision Under 10CFR2.206.Petition Requests Mod of License for Plant That Would Prohibit Decommissioning Activity for 6 Months W/O Any Contamination Events Occurring ML20137H4131997-03-31031 March 1997 Correction to Notice of Withdrawal of 970313 Application for Facility Operating License DPR-61,modifying TSs Pertaining to Manipulator Crane ML20147E9221997-03-17017 March 1997 Notice of Withdrawal of Application for Amend to License DPR-61.License Amend No Longer Required Due to Licensee Certifying Permanent Cessation of Operation & Permanent Offload of Fuel from Reactor Vessel ML20147E8071997-03-13013 March 1997 Notice of Withdrawal of Application for Amend to License DPR-61,Haddam Neck Plant ML20134B4251997-01-23023 January 1997 Notice of Receipt of Petition for Director'S Decision Under 10CFR2.206.Petition Requesting Certain Actions Associated W/Haddam Neck Plant Operated by Nu ML20134H6351996-11-0707 November 1996 Notice of Withdrawal of Application for Amends to Licenses DPR-61,DPR-21,DPR-65,NPF-49 & NPF-86 ML20058G5031993-11-23023 November 1993 Notice of Consideration of Issuance of Amend to Facility OL DPR-61 & Opportunity for Hearing ML20056A5691990-08-0606 August 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Would Add Exception from Requirements of Tech Spec 4.0.4 to Surveillance Requirements 4.7.1.2.2a,b & C ML20056A7861990-08-0303 August 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Rewords Tech Specs Section 3.4.6.2.f to Better Define Which Sections of Piping Needed ML20055G5571990-07-19019 July 1990 Notice of Issuance of Amend 129 to License DPR-61.Amend Will Add Footnote to Tech Spec Section 5.3.1, Fuel Assemblies & Correct Table 3.3-1a, Reactor Trip Sys Instrumentation Response Time ML20055G5461990-07-19019 July 1990 Notice of Issuance of Amend to License DPR-61,removing Tech Spec Table 4.4-5, Reactor Vessel Matl Surveillance Program- Withdrawal Schedule ML20055F7271990-07-12012 July 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Would Establish Limit of 160 Failed Fuel Rods During Operation ML20247A1661989-08-31031 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing Re 881026 Application, Upgrading Current Custom Tech Spec Format to Westinghouse STS Format ML20246P5541989-08-31031 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Will Change Tech Specs to Reflect Changes Associated W/Plant Fire Detection/ Suppression Sys Upgrades in Support of New Switchgear Bldg ML20246P5601989-08-29029 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Will Change Tech Specs to Reflect Mods to Upgrade Reactor Protection Sys & Nuclear Instrumentation Sys ML20246M5501989-05-0808 May 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Allows Four Containment Air Recirculation Fan Motor HXs to Be Cleaned or Replaced While at Power ML20246F8441989-05-0404 May 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Changes Tech Specs Re Various Operation Conditions & Survelliance Requirements as Discussed ML20195C7131988-10-24024 October 1988 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Revises Tech Specs Re RCS vents,post-accident Sampling & long-term Auxiliary Feedwater Sys ML20196B3831988-01-15015 January 1988 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Prior Hearing.Amend Would Revise Tech Specs Provisions Re Degraded Grid Voltage Protection Sys (Dgvps) to Be Consistent W/Util Dgvps Procedures ML20237E1151987-11-23023 November 1987 Notice of Issuance of Environ Assessment & Finding of No Significant Impact Re Amend to License DPR-61,changing Expiration Date from 040526 to 070629 ML20235S3511987-10-0505 October 1987 Notice of Environ Assessment & Finding of No Significant Impact Re Util 870710 Request for Exemption from Certain Requirements of 10CFR50,App J ML20141A9181986-03-27027 March 1986 Notice of Environ Assessment & Finding of No Significant Impact Re Issuance of Amend to License DPR-61.Amend Revises Tech Specs to Permit Repair of Degraded Steam Generator Tubes by Installing Metal Sleeves in Tubes ML20126M5111985-06-14014 June 1985 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing Re 850611 Application to Update Pressure/Temp Limit Curves ML20054K9961982-06-25025 June 1982 Notice of Issuance & Availability of Amends 85,50 & 78 to Licenses DPR-21,DPR-61 & DPR-65,respectively ML20062C2601978-10-24024 October 1978 Notice of Issuance of Amend 29 to Facil Oper Lic DPR-61, Deleting Lic Condition C(3) of Amend 26 & Rev Tech Spec Re Main Steam Line Break Reanalysis ML20062B0761978-07-20020 July 1978 Notice of Issuance of Amend 27 to License DPR-61.Amend Incorporates New Requirements Re Operability of Water Level Alarms in Primary Auxiliary Bldg & Screenwell Bldg 1999-01-12
[Table view] Category:TEXT-CODE OF FEDERAL REGULATIONS
MONTHYEARDD-99-01, Notice of Issuance of Director'S Decision DD-99-01,denying CAN Request to Revoke or Suspend HNP Operating License & to Hold Informal Public Hearing in Vicinity of Site & Granting Request to Consider Application of Requirements of 10CFR721999-01-12012 January 1999 Notice of Issuance of Director'S Decision DD-99-01,denying CAN Request to Revoke or Suspend HNP Operating License & to Hold Informal Public Hearing in Vicinity of Site & Granting Request to Consider Application of Requirements of 10CFR72 ML20154J9761998-10-0707 October 1998 Notice Hereby Given That by Petition Dtd 980911,Citizens Awareness Network (Petitioner) Requested That NRC Take Action with Regard to Haddam Neck Plant to Immediately Revoke or Suspend Util Operating License ML20195J4881998-09-16016 September 1998 Notice of EA & Fonsi Re Licensee Request for Reduction in Amount of Insurance Required for Facility ML20217E8981998-04-22022 April 1998 Notice of Receipt of Petition for Director'S Decision from Citizens Awareness Network,Inc Which Requests That NRC Immediately Suspend Operating License for Haddam Neck Plant ML20203E3421998-02-11011 February 1998 Notice of Issuance of Director'S Decision,Per 10CFR2.206 Wrt 970303 Petition Filed by AA Cizek Re Millstone & Haddam Neck Plants.Petitioner Requests Listed ML20217B9091997-09-12012 September 1997 Notice of Issuance of Partial Director'S Decision Under 10CFR2.206 W/Regard to Petitons & 961223 ML20217B2751997-09-0303 September 1997 Notice of Director'S Decision Re 970311 Petition Filed by R Bassilakis Re Actions Against CYAPC ML20198G9281997-08-27027 August 1997 Notice of Receipt of & Availability for Comment of post-shutdown Decommission Activities Rept ML20137Q8861997-04-0808 April 1997 Notice of Receipt of 970303 Petition Submitted by a Cizek, Per 10CFR2.206 Requesting That Licenses of Three Millstone Nuclear Reactors & Haddam Neck Nuclear Reactor Be Modified by Placing Certain Conditions on OLs ML20137P5241997-04-0303 April 1997 Notice of Receipt of 970311 Petition for Director'S Decision Under 10CFR2.206.Petition Requests Mod of License for Plant That Would Prohibit Decommissioning Activity for 6 Months W/O Any Contamination Events Occurring ML20137H4131997-03-31031 March 1997 Correction to Notice of Withdrawal of 970313 Application for Facility Operating License DPR-61,modifying TSs Pertaining to Manipulator Crane ML20147E9221997-03-17017 March 1997 Notice of Withdrawal of Application for Amend to License DPR-61.License Amend No Longer Required Due to Licensee Certifying Permanent Cessation of Operation & Permanent Offload of Fuel from Reactor Vessel ML20147E8071997-03-13013 March 1997 Notice of Withdrawal of Application for Amend to License DPR-61,Haddam Neck Plant ML20134B4251997-01-23023 January 1997 Notice of Receipt of Petition for Director'S Decision Under 10CFR2.206.Petition Requesting Certain Actions Associated W/Haddam Neck Plant Operated by Nu ML20134H6351996-11-0707 November 1996 Notice of Withdrawal of Application for Amends to Licenses DPR-61,DPR-21,DPR-65,NPF-49 & NPF-86 ML20058G5031993-11-23023 November 1993 Notice of Consideration of Issuance of Amend to Facility OL DPR-61 & Opportunity for Hearing ML20056A5691990-08-0606 August 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Would Add Exception from Requirements of Tech Spec 4.0.4 to Surveillance Requirements 4.7.1.2.2a,b & C ML20056A7861990-08-0303 August 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Rewords Tech Specs Section 3.4.6.2.f to Better Define Which Sections of Piping Needed ML20055G5571990-07-19019 July 1990 Notice of Issuance of Amend 129 to License DPR-61.Amend Will Add Footnote to Tech Spec Section 5.3.1, Fuel Assemblies & Correct Table 3.3-1a, Reactor Trip Sys Instrumentation Response Time ML20055G5461990-07-19019 July 1990 Notice of Issuance of Amend to License DPR-61,removing Tech Spec Table 4.4-5, Reactor Vessel Matl Surveillance Program- Withdrawal Schedule ML20055F7271990-07-12012 July 1990 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Would Establish Limit of 160 Failed Fuel Rods During Operation ML20247A1661989-08-31031 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing Re 881026 Application, Upgrading Current Custom Tech Spec Format to Westinghouse STS Format ML20246P5541989-08-31031 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Will Change Tech Specs to Reflect Changes Associated W/Plant Fire Detection/ Suppression Sys Upgrades in Support of New Switchgear Bldg ML20246P5601989-08-29029 August 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Hearing.Amend Will Change Tech Specs to Reflect Mods to Upgrade Reactor Protection Sys & Nuclear Instrumentation Sys ML20246M5501989-05-0808 May 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Allows Four Containment Air Recirculation Fan Motor HXs to Be Cleaned or Replaced While at Power ML20246F8441989-05-0404 May 1989 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Changes Tech Specs Re Various Operation Conditions & Survelliance Requirements as Discussed ML20195C7131988-10-24024 October 1988 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing.Amend Revises Tech Specs Re RCS vents,post-accident Sampling & long-term Auxiliary Feedwater Sys ML20196B3831988-01-15015 January 1988 Notice of Consideration of Issuance of Amend to License DPR-61 & Opportunity for Prior Hearing.Amend Would Revise Tech Specs Provisions Re Degraded Grid Voltage Protection Sys (Dgvps) to Be Consistent W/Util Dgvps Procedures ML20237E1151987-11-23023 November 1987 Notice of Issuance of Environ Assessment & Finding of No Significant Impact Re Amend to License DPR-61,changing Expiration Date from 040526 to 070629 ML20235S3511987-10-0505 October 1987 Notice of Environ Assessment & Finding of No Significant Impact Re Util 870710 Request for Exemption from Certain Requirements of 10CFR50,App J ML20141A9181986-03-27027 March 1986 Notice of Environ Assessment & Finding of No Significant Impact Re Issuance of Amend to License DPR-61.Amend Revises Tech Specs to Permit Repair of Degraded Steam Generator Tubes by Installing Metal Sleeves in Tubes ML20126M5111985-06-14014 June 1985 Notice of Consideration of Issuance of Amend to License DPR-61 & Proposed NSHC Determination & Opportunity for Hearing Re 850611 Application to Update Pressure/Temp Limit Curves ML20054K9961982-06-25025 June 1982 Notice of Issuance & Availability of Amends 85,50 & 78 to Licenses DPR-21,DPR-61 & DPR-65,respectively ML20062C2601978-10-24024 October 1978 Notice of Issuance of Amend 29 to Facil Oper Lic DPR-61, Deleting Lic Condition C(3) of Amend 26 & Rev Tech Spec Re Main Steam Line Break Reanalysis ML20062B0761978-07-20020 July 1978 Notice of Issuance of Amend 27 to License DPR-61.Amend Incorporates New Requirements Re Operability of Water Level Alarms in Primary Auxiliary Bldg & Screenwell Bldg 1999-01-12
[Table view] |
Text
, _ _ _ _
V. .
l ': , 7590-01 UNITED STATES NUCtEAR REGULATORY COMMISSION CONNECTICUT YANKEE ATOMIC POWER COMPANY DOCKET NO. 50-213 NOTICE OF CONSIDERATION OF ISSUANCE OF AMENDMENT TO FACILITY OPERATING LICENSE AND OPPORTUNITY FOR HEARING The U.S. Nuclear Regulatory Commission (the Commission) is considering issuance of amendment to Facility Operating License No. DPR-61 and issued to Connecticut Yankee Atomic Power Company (CYAPC0/ licensee) for operation of the Haddam Neck Plant located in Middlesex County, Connecticut.
The proposed amendnient would provide revised Technical Specifications to reflect changes associated with the Haddam Neck Plant fire detection / suppression system upgrades in support of the new switchgear building. These changes consist of the installation of edditional fire detectors, an increase in the minimum number of these detectors required to be operable, relocation of hose stations, and the addition of the new fire detection and suppression systems associated with the new switchgear building.
Prior to issuance of the proposed license amendment, the Commission will have made findings required by the Atomic Energy Act of 1954, as amended (the Act) and the Commission's regulations.
By October 10, 1989 , the licensee may file a request for a hearing with respect to issuance of the amendment to the subject facility operating license and any person whose interest may be affected by this proceed-ing and who wishes to participate as a party in the proceeding must file a written request for hearing and a petition for leave to intervene. Requests for l
8909110147 890831 DR ADOCK0500gg3
[
(y a hearing and petitions for leave to intervene shall be filed in.accordance with the Comission's." Rules of Practice for Domestic Licensing Proceedings" in 10 CTR Part 2. If a request for a hearing or petition for leave to intervene
,_ is filed by the above date, the Comission or an Atomic Saf ety and Licensing Board, designated by the Comission or by the Chairman of the Atomic Safety and Licensing Board Panel, will rule on the request and/or petition, and the Secretary or the designated Atomic Safety and Licensing Board will issue a notice of hearing or an appropriate order.
As' required by 10 CFR 2.714, a petition for leave to intervene shall set forth with particularity the interest of the petitioner in the proceeding and how that-interest may be affected by the results of the proceeding. The petition should specifically explain the reasons why intervention should be pemitted with particular reference to the following factors: (1) the nature of the petitioner's right under the Act to be made a party to the proceeding; (2) the nature and extent of the petitioner's property, financial, or other interest in the proceeding; and (3) the possible effect of any order which may be entered in the proceeding on the petitioner's interest. The petition should also identify the specific aspect (s) of the subject matter of the proceeding as to which petitioner wishes to intervene. Any person who has filed a petition for leave
_ to intervene or who has been admitted as a party may amend the petition without requesting leave of the Board up to fifteen (15) days prior to the first pre-hearing conference scheduled in the proceeding, but such an amended petition must satisfy the specificity requirements described above.
. . s Not later than fifteer. (15) days prior to the first prehearing conference scheduled in the proceeding, a petitioner shall file a supplement to the petition to intervene, which must include a list of the contentions that are sought to be litigated in the matter, and the bases for each contention set forth with reason-able specificity. Contentions shall be limited to matters within the scope of the amendments under consideration. A petitioner who fails to file such a supple-ment which s:tisfics thest requirements with respe:t to at least one contention willnitbepermittedte participate as a party.
Those permitted to intervene become parties to the proceeding, subject to any. limitations in the order granting leave to intervene, and have the opportunity to participate fully in the conduct of the hearing, including the opportunity to present evidence and cross-examine witnesses.
A request for a hearing or a petition for leave to intervene must be filed with the Secretary of the Commission, U.S. Nuclear Regulatory Commission, Washington, D.C. 20555, Attention: Docketing and Service Branch, or may be delivered to the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW. Washington, DC, by the above date. Where petitions are filed during the last ten (10) days of the notice period, it is requested that the petitioner promptly so inform the Commission by a toll-free telephone call to Western Union at 1-800-325-6000 (in Missouri 1-800-342-6700). The Western Union operator should be given Datagram Identification Number 3737 and the
'following message addressed to John F. Stolz: petitioner's name and I telephone number; date petition was mailed; plant nare; and publication date
'l i
/ ~. . . .
- - ~'
4 and page number of this FEDERAL REGISTER notice. A copy of the petition should also be sent to the Office of the General Counsel, U.S. Nuclear Regulatory Comission, Washington, DC 20555, and to Gerald Garfield, Esquire, Day, Berry
, &.Howard, Counselors at Law, City Place, Hartford, Connecticut 06103-3499 (attorney for the licensee).
Nontimely filings of petitions for leave to intervene, amended petitions, supplemental petitions and/or requests for hearing will not be entertained absent a determination by the Comission, the presiding officer or the presiding Atomic Safety and Licensing Board that the petition and/or request should be granted based upon a balancing of the factors specified in 10 CFR 2.714(a)(1)(1)-(v) and 2.714(d). ,
If a request for hearing is received, the Commission's staff may issue the amendments after it completes its technical review and prior to the completion of any required hearing if it publishes a further notice for public coment of its proposed finding of no significant hazards consideration in accordance with 10 CFR 50.91 and 50.92.
For further details with respect to this action, see the application for amendment dated July 31, 1989, which is available for public inspection at the Comission's- Public Document Room, the Gelman Building, 2120 L Street, NW , Washington, D.C. 20555, and at the Russell Library, 123 Broad Street, Middletown, Connecticut 06457.
Dated at Rockville, Maryland, this31st day of August, 1989.