Forwards Addl Info Re Proposed Rev to Tech Specs Re Electrical Power Sys.Justification Consistent W/Guidelines Provided to NRC on 881026
ML20244C885
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 06/09/1989
From: Mroczka E, Sears C
CONNECTICUT YANKEE ATOMIC POWER CO., NORTHEAST UTILITIES
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
B13236, TAC-66797, NUDOCS 8906150190
Download: ML20244C885 (45)


Text

.-.

4

  • - NORTHEAST UTHJTHIS 9

LT"T%%C ::

WDLVDNE WAfta 7041h C0samaan J 0%C1"I.200 June 9, 1989

)

Docket No. 50-213 B13236 U.S. Nuclear Regulatory Commissior.

Attention: Document Control Desk Washington, DC 20555 Gentlemen:

Haddam Neck Plant Additional Information Regarding Proposed Revision to Technical Specifications Electrical Power Systems (TAC No. 66797)

On August 29, 1988,III Connecticut Yankee Atomic Power Company (CYAPCO) submitted a revised license amendment request in the Westinghouse (H) Standard Technical Specification (STS) format for the degraded grid voltage protection requirements.

On March 30, 1989, CYAPC0 met with the NRC Staff to discuss this proposed i

license amendment and to provide justification for where the proposed Techni-cal Specification deviates from the W STS.

Each justification is 26,1988.gnsistent CYAPC0 with the guidelines submitted to the NRC Staff on October 4

has agreed that the W STS should be adopted except when:

1.

Plant-specific design considerations would dictate otherwise, or 2.

Hardware, structural, or organization changes from previously approved conditions would be required to conform to the W STS, or 3.

Based on past operating experience, the existing plant-specific requirement can be shown to provide an equivalent degree of protec-tion to that provided by the W STS.

(1)

E.

J.

Mroczka letter to U.S.

Nuclear Regulatory Commission Document Control Desk, " Proposed Revision to Technical Specifications, Electrical Power Systems (TAC No. 66797)," dated August 29, 1988.

(2)

E. J.

Mroczka letter to U.S.

Nuclear Regulatory Commission Document Control Desk, " Amendment Request for Sections 1.0, 3/4.2, 3/4.9, 3/4.10, 3/4.11, 5.0 and 6.0 of the Revised Technical Specifications," dated October 26, 1988.

d gains! MAN!

P

4 s.

U.S. Nuclear Regulatory Commission 013 00/hg; 2 sr June 9, 1989 The purpose of this submittal is to document these justifications.

Attach-ment 1 provides a comparison between the proposed Technical Specifications as contained in the August 29, 1988 letter and the M STS, and the justification for any deviations.

As discussed with the NRC Staff, CYAPC0 expects to submit the changes that CYAPC0 has proposed herein for the electrical section by July 15, 1989.

A draft of the proposed Technical Specifications is provided in Attachment 2.

.If you have any questions, please contact us.

Very truly yours, CONNECTICUT YANKEE ATOMIC POWER COMPANY b.b.

Act E. J. Mroczka U

Senior Vice President l-Le 4

By:

C. F. Sears i

Vice President cc:

W. T. Russell, Region I Administrator A. B. Wang, NRC Project Manager, Haddam Neck Plant J. T. Shedlosky, Senior Resident Inspector, Haddam Neck Plant 1

STATE OF CONNECTICUT)

) ss. Berlin COUNTY OF HARTFORD )

Then personally appeared before me, C. F. Sears, who being duly sworn, did state that he is Vice President of Connecticut Yankee Atomic Power Company, a Licensee herein, that he is authorized to execute and file the foregoing information in the name and on behalf of the Licensee herein, and that the statements contained in said information are true and correct to the best of his knowledge and belief.

b q w,h W N o.> fo m NotaYy Public i

1 l

Docket No. 50-213 R13736 l

l Haddam Neck Plant Justification for Deviation from the H STS I

l l

June 1989 l

1

w

\\

U.S. Nuclear Regulatory Commission B13236/Page 1 1

1.

Proposed Technical Specification 3.12.1.1.b Two separate and independent diesel generators, each with:

1)

A separate engine-mounted fuel oil day tank containing a minimum volume of _400 gallons of fuel (except during engine operation),

2)

A separate underground fuel oil storage tank containing a minimum volume of 3,250 gallons of fuel, and 3)

A separate fuel transfer pump.

W STS 3.8.1.1.b Two separate and independent diesel generators, each with:

1)

Separate day and engine-mounted fuel tanks containing a minimum volume of gallons of fuel, 2)

A separate Fuel Storage System containing a minimum volume cf gallons of fuel, 3)

A separate fuel transfer pump, 4)

Lubricating oil storage containing a minimum total volume of gallons of lubricating oil, and 5)

Capability to transfer lubricating oil from storage to the diesel generator unit.

Justification for Deviation This proposed Technical Specification has been worded to account for plant-specific design considerations.

At the Haddam Neck Plant, two diesel generator underground fuel oil storage tanks provide independent, safety (Class IE) qualified, fuel oil storage for each of the diesel gen-erators. The diesel generator fuel oil transfer pumps take suction from these tanks and transfer the fuel oil to the diesel generator fuel oil day tanks (which are engine-mounted).

The proposed Technical Specifica-tion provides an exception from the minimum volume of 400 gallons during engine operation because the fuel oil transfer pumps are controlled by a level switch.

Thus, the pump only starts refilling the day tanks once the level drops below 292 gallons.

The proposed Technical Specifications do not include W STS requirements for lubricating oil storage or transfer capability.

The diesel gener-ators do not have an automatic transfer system nor dedicated lubricating

________ _ a

s U.S. Nuclear Regulatory Commission B13236/Page 2 oil storage tanks.

Each engine contains approximately 400 gallons of lubricating oil.

This is normally changed when major preventative maintenance is performed (usually each refueling outage).

Oil level is monitored by plant operators every 30 minutes when operating and once each shift when not operating. Lubricating oil that is stored on-site is added occasionally as necessary.

These requirements have not been included because the operability of the diesel generator includes the availability of lubricating oil and is monitored by the maintenance program.

Also, stored lubricating oil is consumed slowly with diesel generator operation and additional lubricating oil is not required for immediate diesel generator operation. This is consistent with groundrule 3 in that it provides an equivalent degree of protection to that provided by the H STS.

In addition, this is consistent with Diablo Canyon, Callaway and current Commanche Peak Technical Specifications and the present g proach of the Westinghouse Owners Group (WOG)

MERIT 3 Program.

2.

Proposed Technical Specification 3.12.1.1 Action a and b:

a.

With one offsite circuit inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Specification 3.12.1.1.la.

within I hour and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter.

If either diesel generator has not been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demonstrate its OPERABILITY by performing Surveillance Requirement 3.12.1.1.2a.4 separately for each such diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one diesel generator inoperable, demonstrate OPERABILITY of the A.C.

offsite sources by performing Surveillance Requirement 3.12.1.1.la within I hour and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter; i

and if the diesel generator became inoperable due to any cause other than preplanned maintenance or surveillance testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by performing Surveillance Requirement 3.12.1.1.2a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> regardless of when the inoperable diesel generator is restored to OPERABILITY; restore the diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

(3)

R.

A.

Newton letter to U.S.

Nuclear Regulatory Commission, Document Control Desk,

" Westinghouse Owners Group MERITS Program Phase II, Technical Specifications and Bases," dated March 30, 1989.

w s

U.S. Nuclear Regulatory Commission B13236/Page 3 l

W STS 3.8.1.1 Action a a.

With either an offsite circuit or diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Specifica-tions 4.8.1.1.la and 4.8.1.1.2a 4) within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite circuits and two' diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Justification for Deviation The proposed Technical Specification requires less frequent verification of the operability of the remaining A.C. sources than recommended by the W STS.

The 24-hour time period between breaker alignment checks is consistent with the current Administrative Procedures.

CYAPC0 believes that the 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />'s recommended by W STS does not provide enough Iatitude within an 8-hour shift.

In order to avoid a violation of Technical Specifications, breaker alignment checks would have to be performed at exactly the same time interval within each shift or twice per shift.

A 12-hour time limit would provide for latitude within the shift to allow for normal perturbations which could affect the timing of certain activ-ities (i.e. extended shift turnovers or' additional plant activities requiring attention.)

The intent of the W STS 8-hour limit is to have the brppker alignment check performed once per shift.

On October 26, 1988,P' CYAPC0 submitted an amendment request which proposes to change the definition of once per shift to once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

A 12-hour limit would provide an equivalent degree of protection to meet the. intent of the W STS and could be successfully implemented at the Haddam Neck Plant.

A 12-hour limit, rather than the proposed 24-hour limit, will be incorpo-rated into the revised Technical Specifications for the electrical section which will be submitted by July 15, 1989.

CYAPC0 will adminis-tratively ensure that this surveillance is performed once per shift.

This 12-hour limit is consistent with groundrule 3 in that it provides an equivalent degree of protection to that provided by the W STS.

The proposed Technical Specification does not require that the diesel generator be demonstrated operable if it has been successfully tested (4)

E. J. Mroczka letter to U.S.

Nuclear Regulatory Commission, Document Control Desk, " Amendment Request for Sections 1.0, 3/4.2, 3/4.9, 3/4.10, 3/4.11, 5.0 and 6.0 of the Revised Technical Specifications," dated October 26, 1988.

1

___________-_______-_U

s U.S. Nuclear Regulatory Commission B13236/Page.4 within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

In addition, the proposed Technical Specifica-tion provides 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in which to demonstrate diesel generator opera-bility compared to one hour in the W STS.

This demonstration of opera-bility 1) follows the recommendations in Generic Letter 84-15, 2) is l

consistent with Amendment No.

25, 1985, for the North Anna Power Station, Unit No. 2,g) issued April and 3) is consistent with the present approach of the WOG MERITS Program.

With regard to the similarity of North Anna Power Station, Unit No. 2 to the Haddam Neck Plant, CYAPC0 has reviewed the electrical section of the l

North Anna Final Safety Analysis Re) ort and has determined that each system is sufficiently similar that tie basis for the technical specifi-cations also apply to the Haddam Neck Plant.

3.

ProDosed Technical Specification 3.12.1.1 Action c c.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Specifica-tions 3.12.1.1.la within I hour and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter; and if the diesel generator became inoperable due to any 1

cause other than preplanned maintenance or surveillance testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel gene-rator by performing Surveillance Requirement 3.12.1.1.2a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; restore at least one of the inoperable sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least ' HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

W STS 3.8.1.1 Action b b.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Specifica-tions 4.8.1.1.la and 4.8.1.1.2a.4) within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore at least two offsite circuits and two (5)

L. B. Engle letter to W. L. Steward, dated April 25, 1985.

4 U.S., Nuclear Regulatory Commission B13236/Page 5 diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Justification for Deviation The same discussion on groundrule 3 related to breaker alignment checks from Item 2 applies to this item.

The proposed Technical Specification does not require the operable diesel generator to be challenged if the inoperable diesel generator was ren-dered inoperable due to preplanned maintenance or surveillance testing.

This is consistent with the North Anna amendment and the WOG MERITS Program.

The proposed Technical Specification provides 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to restore at least one inoperable source while W STS provides 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

The 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is consistent with current Administrative Procedures, however CYAPC0 will change this to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> in the revised Technical Specifications for the electrical section which will _be submitted by July 15, 1989.

4.

Proposed Technical Specification 3.12.1.1 Action d d.

With one diesel generator inoperable, in addition to ACTION b. or c.

above, verify that the charging pump, HPSI pump, LPSI pump and RHR pump which depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE.

If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

W STS 3.8.1.1 Action c c.

With one diesel generator inoperable in addition to ACTION a. or b.

above, verify that:

1.

All required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE, and 2.

When in MODE 1, 2, or 3, the steam-driven auxiliary feedwater pump is OPERABLE.

If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

4 y

'a U.S. Nuclear Regulatory Commission l

B13236/Page 6 j

l I

l Justification for Deviation I

The proposed Technical Specification identifies the specific equipment that must be operable rather than the general description provided in the

M STS.

As discussed in the bases section, this requirement is intended l

-to provide assurance that a loss of offsite. power event will not result l

l ~

period that one of the diesel generators is inoperable. This specifica-I in a complete loss of safety function of critical systems during the I

tion is consistent rith groundrule 3 in that it provides an equivalent i

degree of protection to that provided by the W STS.

1 The proposed Technical Specification does not require the steam-driven auxiliary feedwater pump to be operable due to plant-specific design considerations. M STS are designed for the standard W plant that has two electrically driven auxiliary feedwater. pumps and only one steam-driven pump.

Since the Haddam Neck Plant has two steam-driven _ auxiliary feedwater pumps, having one diesel generator inoperable does not affect auxiliary feedwater availability.

5.

Proposed Technical Specification 3.12.1.1 Action e e.

With two of the above required diesel generators inoperable, demon-strate the OPERABILITY of two offsite A.C. circuits by performing Specification 3.12.1.1.la, within I hour and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore both diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

W STS 3.8.1.1 Action e e.

With two of the above required diesel generators inoperable, demon-strate the OPERABILITY of two offsite A.C. circuits by performing the requirements of Specification 4.8.1.1.la. within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore at least two diesel gener-ators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

4-4-

U.S. Nuclear Regulatory Commission B13236/Page 7 Justification for Deviation The same discussion on groundrule 3 related to breaker alignment checks from Item 2 applies to this item.

6.

Proposed Technical Specification 3.12.1.1 Surveillance 2.a.4 4.

- Verifying the diesel starts from ambient condition and accelerates to at least 900 rpm in less than or equal to 10 seconds.

The generator voltage and frequency shall be.4160 420 volts and 60 1.2 Hz within 10 seconds after the start signal,*

W STS 4.8.1.1.2.a.5 5.

Verifying the diesel starts from ambient condition and accelerates to at least [900] rpm in 'less than or equal to [10] seconds.* The generator voltage and frequency shall be [4160]

. [420] volts and

[60]

[1.2] Hz within [10] seconds

  • after the start signal.

The diesel generator shall be started for this test by using one of the following signals:

a)

Manual, or b)

Simulated loss of offsite power by itself, or c)

Simulated loss of offsite power in conjunction with an ESF Actuation test signal, or d)

An ESF Actuation test signal by itself.

Justification for Deviation The proposed Technical Specification does not specify the type of start signal that may be used for this test.

The method for starting the diesel generator is provided in the plant operating procedures and provides an equivalent degree of protection to that of the W STS.

7.

Proposed Technical Specification 3.12.1.1 Surveillance 2.b b.

At least once per 31 days by verifying that the automatic load sequence timers are OPERABLE with the following allowable elapsed times:

E0VIPMENT ALLOWABLE ELAPSED TIME LPSI Pump 5 3 sec.

HPSI Pump s 10 sec. and > 7 sec.

U.S. Nuclear Regulatory Commission B13236/Page 8 Service Water Pump 33 5 sec.

Backup Service Water Pump 38 5 sec.

Containment Recirc. Fan 43 i 5 sec.

Backup Containment Recire. Fan 48 5 sec.

W STS 4.8.1.1.2.f.12

12. Verifying that the automatic load sequence timer is OPERABLE with the interval between each load block within 10% of its design interval; Justification for Deviation Consistent with groundrule 1,

the proposed Technict.1 Specification provides the exact allowable elapsed times as required by the plant design basis.

8.

Proposed Technical Specification 3.12.1.1 Surveillance 2.d d.

By obtaining a sample of new fuel oil upon delivery to the site prior to addition to storage tanks and:

1)

Verifying in accordance with the tests specified in ASTM-D975-81:

a)

An API gravity of greater than or equal to 30 degrees but less than or equal to 40 degrees; and b)

A water and sediment volume percentage of less than or equal to 0.05% (500 mg/L).

2)

Verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-0976-81 are met when tested in accordance with ASTM-D975-81 except that the analysis for sulfur may be performed in accordance with ASTM-D1552-79 or ASTM-D2622-82.

W STS 4.8.1.1.2.d d.

By sampling new fuel oil in accordance with ASTM-D4057 prior to addition to storage tanks and:

1)

By verifying in accordance with the tests specified in ASTM-D975-81 prior to addition to the storage tanks that the sample has:

1 I

U.S. Nuclear Regulatory Commission B13236/Page 9 a)

An API Gravity of within 0.3 degrees at 60*F, or a specific gravity of within 0.0016 at 60/60*F, when compared to the supplier's certificate, or an absolute specific gravity at 60/60*F of greater than or equal to 0.83 but less than or equal l

to 0.89, or an API gravity of greater than or equal to 27 degrees but less than or equal to 39 degrees; b)

A kinematic viscosity at 40*C of greater than or equal to 1.9 centistokes, but less than or equal to 4.1 centistokes (alternatively, Saybolt viscosity, SUS at 100*F of greater than or equal to 32.6, but not less than or equal to 40.1), if gravity was not determined by comparison with the supplier's certification; c)

A flash point equal to or greater than 125'F; and d)

A clear and bright appearance with proper color when tested in accordance with ASTM-D4176-82.

2)

By verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-D975-81 are met when tested in accordance with ASTM-0975-81 except that the analysis for sulfur may be performed in accordance with ASTM-01552-79 or ASTM-D2622-82.

Justification for Deviation The proposed Technical Specification does not specify that new fuel oil will be sampled in accordance with ASTM-D4057.

CYAPC0 disagrees with referencing specific procedures in the Technical Specifications which may be revised or replaced often.

Since 1976, CYAPC0 has followed the recommendations in Regulatory Guide 1.137 which references all ASTM procedures necessary to meet the standards.

Although not stated in the proposed Technical Specification, CYAPC0 will sample in accordance with ASTM-D4057 and therefore, will provide an equivalent degree of protection to that provided by the H STS.

The proposed Technical Specification specifies only one standard for measuring specific gravity.

CYAPC0 does not need the option of using three different values which all correlate to one another.

In addition, the values used for API gravity differ only a small amount from those in i

l the H STS and are consistent with plant-specific data.

This specifica-tion is consistent with groundrule 3, in that it provides an equivalent l

degree of protection to that provided by the H STS.

I CYAPC0 is in the process of procuring equipment and developing a proce-q dure to perform H STS 4.8.1.1.2.d.l.b and c, kinematic viscosity and

)

i l

~

l U.S. Nuclear Regulatory Commission B13236/Page 10 L

l flash point fuel oil tests.

CYAPC0 will include these requirements in the revised-Technical Specifications for< the electrical section which will be submitted by July 15, 1989.

The proposed Technical Specification does not include appearance require-ments because they are subjective in nature and are contained in proce-dures rather than Technical Specifications.

The inclusion of these requirements in procedures provides an equivalent degree of protection to that provided by the W STS.

9.

Prooosed Technical Specification 3.12.1.1 Surveillance 2.f.1 1.

Simulating a loss-of-offsite power. coincident with a Safety Injec-tion Actuation signal, and:

l a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts from normal standby conditions on the auto-start signal,. energizes the emergency busses with permanently connected loads within 10 seconds, energizes the auto-connected shutdown loads through the load sequence timers and operates for greater than or equal to. 5 minutes while its generator is loaded with the shutdown loads; and c)

Verify that all automatic diesel. generator trips, except engine overspeed, generator differential, and engine oil pressure (2 out of 2) are bypassed.

W STS 4.8.1.1.2.f.2. 4 and 6 2.

Verifying the generator capability to reject a load of greater than or equal to [ largest single emergency load] kW while maintaining voltage at [4160] i [420] volts and frequency at [60] i [1.2].Hz

[less than or equal to 75% of the difference between nominal speed and the Overspeed Trip Setpoint, or 15% above nominal whichever is less];

4.

Simulating a loss-of-offsite powar by itself, and:

a)

Verifying deenergization. of the emergency busses and load shedding from the emergency busses, and b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within

[10]

seconds, energizes the auto-connected shutdown loads through the load sequencer and operates for greater than or

u 4,

U.S. Nuclear Regulatory Commission I

B13236/Page 11 equal to 5 minutes while its generator is loaded with the shutdown loads.

After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at

[4160]

[420] volts and [60]

[1.2] Hz during this test.

6.

Simulating a loss-of-offsite power in conjunction with an ESF Actuation test signal, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within

[10] seconds, energizes the auto-connected emergency (accident) loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads.

After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at

[4160] i [420] volts and [60] i [1.2] Hz during this test; and c)

Verifying that all automatic diesel generator trips, except engine overspeed and generator differential, are automatically bypassed upon loss of voltage on the emergency bus concurrent with a Safety Injection Actuation signal.

Justification for Deviation During the March 30, 1989, meeting with the NRC Staff, CYAPC0 agreed to include a new surveillance which is currently performed and meets the

-intent of M STS 4.8.1.1.2.f.2.

The 18-month test to verify diesel generator load rejection of the largest single emergency load is envel-oped by CYAPC0's present 18-month partial loss of A.C. test. However, in lieu of rejecting the largest single emergency load, CYAPC0 rejects greater than the largest single emergency load by opening the output breaker after all accident loads have sequenced on the diesel generator.

The revised Technical Specifications for the electrical section, which will be submitted by July 15, 1989, will include " Verifying the diesel generator capability to reject a load of greater than the largest single load."

The Haddam Neck Plant does not have a solid state sequencer as does the standard M plant.

The Haddam Neck Plant uses discrete time delay relays for loading safety injection motors onto the electrical system. There is no difference between the diesel start and loading logic, with or without an accident signal, and there is also no difference in loading of the safety injection loads, with or without offsite power. Therefore, due to

i l

~

U.S. Nuclear Regulatory Commission j

B13236/Page 12 l

i l

plant-specific design considerations this proposed test is redundant to that done for H STS 4.8.1.1.2.f.4.

The proposed Technical Specification is equivalent to H STS 4.8.1.1.2.f.4 and 4.8.1.1.2.f.6 except that the frequency and voltage requirements are 1

not included.

The voltage and frequency requirements have not been included due to plant-specific design considerations.

The design of the Haddam Neck Plant on-site power system utilizes two GM/EMD 20 cylinder, turbo charged diesel generators, with maximum dead load pickup capability. This design differs from the standard H plant in that the generator is of lower impedance to allow for easy starting of large motors when operating in the isochronous mode.

Power current transformers are utilized to supply the needed energy to the exciter during motor starts while the voltage is depressed to as low as 50% of rated value.

This design also allows for larger frequency swings during motor starts, for the same reason. A fast start test initiated by a loss of normal power, followed by an accident signal, has been performed during every refueling outage for each of these units since they were installed.

The loading, however, could not simulate the worst case loading as the safety injection pumps were in the recirculation mode and could not easily be set up to simulate their runout condition. A special test was conducted during the 1980 refueling outage, which simulated runout safety injection flow and worst case diesel generator loading. The test successfully demonstrated the on-site power systems capability to start and run the design basis loads at the Haddam Neck Plant, without maintaining the voltage and frequency within the guidelines set forth in the H STS.

Consequently, inclusion of voltage and frequency limits in the Technical Specifications is not required.

Successful closure of the generator breaker and starting of motor loads are adequate indication of the diesel generator's readiness.

10.

Proposed Technical Specification 3.12.1.1 Surveillance 2.f.2 2.

Verifying that on a Safety Injection Actuation test signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 min-utes.

W STS 4.8.1.1.2.f.5 5.

Verifying that on an ESF Actuation test signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes. The generator voltage and frequency shall be [4160]

[420] volts and

[60] i [1.2] Hz within [10] seconds after the auto-start signal; the steady-state generator voltage and frequency shall be maintained within these limits during this test;

U.S. Nuclear Regulatory Commission B13236/Page 13 Justification for Deviation The same discussion on groundrule I related to voltage and frequency requirements from Item 9 applies to this item.

11.

Proposed Technical Specification Table 3.12-1 TABLE 3.12-1 DIESEL GENERATOR TEST SCHEDULE l

NUMBER OF FAILURES IN LAST 20 VALID TESTS

  • TfST FRE0VENCY s1 At least once per 31 days 12 At least once per 7 days **

Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, Revision 1, August 1977, where the number of tests and failures is determined on a per diesel generator basis.

For the purposes of this test schedule, only valid tests conducted after the completion of the preoperational test requirements of Regulatory Guide 1.108, Revision 1, August 1977, shall be included in the computation of the "Last 20 Valid Tests."

This test frequency shall be maintained until seven consecutive failure free demands have been performed and the number of failures in the last 20 valid demands has been reduced to one or less.

W STS Table 4.8-1 TABLE 4.8-1 l

DIESEL GENERATOR TEST SCHEDULE NUMBER OF FAILURES IN LAST 100 VALID TESTS

  • TEST FRE0VENCY s1 At least once per 31 days 2

At least once per 14 days 3

At least once per 7 days 14 At least once per 3 days 1

- _ _ _ _ -_- _ __ 0

4 U.S. Nuclear Regulatory Commission B13236/Page 14 Criteria for determining number -of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, Revision 1, August 1977, where the last 100 tests-are determined on a - per nuclear unit basis.

For the purpose of this schedule, only valid tests conducted after the completion of the preoperational - test requirements of Regulatory Guide 1.108, Revision 1, August,1977, shall be included in the computation of the "Last 100 Valid Tests."

Justification for Deviation The proposed Technical Specification follows the recommendations in Generic Letter 84-15.

12. Proposed Technical Specification 3.12.1.2 Action With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel, or crane operation with loads over the fuel storage pool.

In addition, when in MODE 5 with less than two (2) steam generators OPERABLE, or in MODE 6 with the water level less than 23 feet above the reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.

W STS 3.8.1.2 Action With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement or irradiated fuel, or crane operation with loads over the fuel storage pool, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />,-

depressurize and vent the Reactor Coolant System through a. greater than or equal to square inch vent.

In addition, when in MODE 5 with the reactor coolant loops not filled, or in MODE 6 with the water level less than 23 feet above the reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.

Justification for Deviation The Haddam Neck Plant relies on a separate, dedicated system, Low Temper-ature Overpressure Protection (LTOP), to prevent this accident scenario from occurring.

The requirement for depressurizing and venting the RCS is currently covered by LCO 3.3.4.2.

Thus, CYAPC0 has not included this requirement in this section.

l f~

F l

U.S. ' Nuclear Regulatory Commission l

B13236/Page 15 l

13. Proposed Technical Specification 3.12.2.1.a and b a.

.125-volt Battery Bank No. IA, and an associated or independent full capacity charger, and b.

125-volt Battery Bank No.18, and an associated or independent full capacity charger.

W STS 3.8.2.1.a and b a.

[250/125]-volt Battery Bank No.1, and its associated full capacity charger, and b.

[250/125]-volt Battery Bank No. 2, and its associated full capacity charger.

Justification for Deviation When CYAPC0 submitted the' proposed Technical Specifications in August 1988, the addition of an independent battery charger was contemplated as-part of the new switchgear building design.

Since this time, the design has been modified to provide a non-Category I battery charger which may only be utilized for maintenance during shutdown. The revised Technical Specification for the electrical section, which will be submitted by July 15, 1989, will strike the words "or independent."

14.

Proposed Technical Specification 3.12.2.1 Surveillance a.2 2.

The total battery terminal voltage is greater than or equal t9 125 volts on float charge, and W STS 4.8.2.1.a.2 2)

The total battery terminal voltage is greater than or equal to

[258/129) volts on float charge.

Justification for Deviation The proposed Technical Specification specifies 125 volts based on current Administrative Procedures, however CYAPC0 will change this to 129 volts in the revised. Technical Specifications for the electrical section which will be submitted by July 15.

j p

w L

j U.S. Nuclear Regulatory Commission B13236/Page 16 1

15. -Proposed Technical Specification 3.12.2.1 Surveillance a.3 and b a.

At.least once per 7 days by verifying that:

3)

The electrolyte temperature of the pilot cell is above 60*F.

b.

At least once per 92 days and within 10 days after a battery dis-charge with battery terminal voltage below 110 volts, or. battery overcharge with battery terminal voltage above 150 volts, by verify-ing that:

1)

The parameters in Table 3.12-2 meet the Quarterly limits, and 2)

There is no visible corrosion at either terminals or connec-tors,orgheconnectionresistanceoftheseitemsislessthan 150 x 10- ohm.

W STS 4.8.2.1.b b.

At least once per 92 days and within 7 days after a battery dis-charge with battery terminal voltage below - [220/110] volts, or battery overcharge with battery terminal voltage above [300/150]

volts, by verifying that:

1)

The parameters in Table 4.8-2 meet the Category B limits, 2)

There is no visible corrosion at either terminals or connec-tors,ortg]econnectionresistanceoftheseitemsislessthan

[150 x 10~

ohm, and 3)

The average electrolyte temperature of

[a representative number] of connected cells is above [60*F].

Justification for Deviation The proposed Technical Specification is more conservative in that it requires a representative cell to be checked weekly rather than quarterly as recommended in the M STS.

The proposed Technical Specification requires that surveillance con-tained in Item b be completed within 10 days as compared to 7 days in the W STS. This is consistent with CYAPCO's current operating procedures and is more restrictive than the 31-day requirement that has been recommended in the WOG MERITS Program.

Procedures written in accordance with the battery manufacturer's instructions state that an equalize charge may require as long as 6% days to complete.

At this point, CYAPC0 usually places the batteries on a float charge for at least 3 days before per-

U.S. Nuclear Regulatory Commission B13236/Page 17 1

forming these surveillance.

Performing the surveillance within 10 days provides an equivalent degree of protection to that provided in M STS while considering the manufacturer's recommendations.

In addition, this practice is in accordance with IEEE 450 recommendations.

16.

Proposed Technical Specification 3.12.2.2 As a minimum, one 125-volt battery bank and an associated or independent full capacity charger shall be OPERABLE.

W STS 3.8.2.2 As a minimum, one [250/125]-volt battery bank and its associated full-capacity charger shall be OPERABLE.

Justification for Deviation The same discussion from Item 13 on the independent charger applies to this' item.

17.

Proposed Technical Specification 3.12.2.2 Action With the required battery bank or full capacity charger inoperable, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel; initiate corrective action to restore the required battery bank and full capacity charger to OPERABLE status as soon as possible.

W STS 3.8.2.2 Action With the required battery bank and/or full-capacity charger inoperable, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel; initiate corrective action to restore the required battery bank and full-capacity charger to OPERABLE status as soon as possible, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressurize and vent the Reactor Coolant System through a square inch vent.

Justification for Deviation The same discussion regarding RCS overpressurization protection from Item 12 applies to this item.

18.

Proposed Technical Specification 3.12.3.1 3.12.3.1 The following electrical busses shall be energized in the specified manner with tie breakers open between redundant busses except for short periods of time while locating shorts or grounds not to exceed

_- ________ _ _ O

U.S. Nuclear Regulatory Commission 1

B13236/Page 18-30 minutes:

a.

Train A-A.C.

Emergency Busses consisting of :

1) 4160-Volt Bus #8, and 2) 480-Volt Busses #4 and #5.

b.

Train B-A.C.

Emergency Busses consisting of:

1) 4160-Volt Bus #9, and 2)-

480-Volt Busses #6'and #7.

c.

120-Volt A.C. Vital Bus #A, d.

120-Volt A.C. Vital Bus #B, e.

120-Volt A.C. Vital Bus #C, f.

120-Volt A.C. Vital Bus #D, g.

125-Volt D.C. Bus #1 energized from Battery Bank 1A, and h.

125-Volt D.C. Bus #2 energized from Battery Bank 18.

W STS 3.8.3.1 3.8.3.1 The following electrical busses shall be energized in the specified manner with tie breakers open [both] between redundant busses within the unit-[and between units at the same station]:

a.

Division #1.A.C. Emergency Busses consistent of:

1)

[4160]-Volt Emergency Bus #

, and 2)

[480]-Volt Emergency Bus #

b.

Division #2.A.C. Emergency Busses consisting of:

1)

[4160]-Volt Emergency Bus #

, and 2)

[480]-Volt Emergency Bus #

c.

[120]-Volt A.C.

Vital Bus #

energized from its associated inverter connected to D.C. Bus #

d.

[120]-volt A.C.

Vital Bus #

energized from its associated inverter connected to D.C. Bus #

6 U.S. Nuclear Regulatory Commission B13236/Page 19 e.

[120]-Volt A.C.

Vital Bus #

energized from its associated inverter connected to D.C. Bus #

f.

[120]-Volt A.C.

Vital Bus #

energized from its associated inverter connected to D.C. Bus #

g.

[250/125]-Volt D.C. Bus #1 energized from Battery Bank #1, and h.

[250/125]-Volt D.C. Bus #2 energized from Battery Bank #2.

Justification for Deviation Due to plant-specific design considerations, the proposed Technical Specifications allow the electrical busses to be energized in the speci-fied manner with tie breakers closed between redundant busses for short periods of time not to exceed 30 minutes while locating shorts or grounds.

It is highly desirable to isolate, identify, and remove grounds or shorts while maintaining the facility in a steady state.

Bus tie breakers continue to provide adequate overcurrent protection should a fault occur while trouble shooting.

This design capability in conjunc-tion with the short time limit for tie breakers to remain closed, l

provides assurance that train related design features are not compro-mised. The single line diagrams for the Haddam Neck Plant are provided here for reference.

The Haddam Neck Plant design differs from the standard W plant in that it has the capability to cross tie distribution panels, given failure of batteries, battery chargers or inverters.

Specifically, each D.C. bus at the Haddam Neck Plant can obtain power from either battery.

Therefore, should a battery fail while the unit is at power, the tie breaker is available to assist in maintaining the plant in a stable condition, while repairs are made.

In addition, to provide an added assurance against a single failure of instrumentation, an RPS channel trip condition for the affected bus has been included in Action b.2.a of the proposed Technical Specifications as I

compensatory measures.

The proposed Technical Specification does not specify (as recommended in the W STS) that the 120-Volt A.C. vital bus be energized from its asso-i ciated inverter connected to a certain D.C. bus. CYAPC0 did not propose l

to designate each of the 4 RPS power supply channels in order to provide l

latitude for inclusion of tha new switchgear building into the Technical l

Specifications without need for further revisions.

With the addition of the new switchgear building, several dedicated spare inverters will be made available. A design featuta which is under consideration is to have installed spares for the RPS inverters.

The confusion which would be caused by inclusion of all possible combinations of battery, inverter and l

j panel in the Technical Specifications would be counterproductive.

l

_ _ _ _ ____A

4 j

U.S. Nuclear Regulatory Commission B13236/Page 20 i

l Consequently, CYAPC0 did not specify which inverter would normally power which bus.

The revised Technical Specifications for the electrical section, which will be submitted by July 15, 1989, will include the i

following normal lineup of battery, inverter and vital panel:

c.

120-Volt A.C. Vital Bus A energized from its associated inverter connected to D.C. Bus #1, d.

120-Volt A.C. Vital Bus B energized from its associated inverter connected to D.C. Bus #1, e.

120-Yolt A.C. Vital Bus C energized from its associated inverter connected to D.C. Bus #2, f.

120-Volt A.C. Vital Bus D energized from its associated inverter connected to D.C. Bus #2.

19.

Proposed Technical Specification 3.12.3 Action b b.

With one A.C. vital bus not energized from its associatad inverter; (1) return all vital busses to their normal power supply configura-tion within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, or (2)(a) energize the vital bus from its alternate inverter and place the reactor protection trip signal (s) associated with the inoperable bus (in abnormal configuration) in the trip condition (to meet the intent of Table 3.9-1) within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, and (b) return all vital busses to their normal power supply configuration within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

W STS 4.8.3.1 Action b b.

With one A.C. vital bus either not energized from its associated inverter, or with the inverter not connected to its associated D.C.

bus: (1) reenergize the AC vital bus within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; and (2) reenergize the A.C. vital bus from its associated inverter connected to its associated D.C. bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

l

U.S. Nuclear Regulatory Commission B13236/Page 21 Justification for Deviation The Haddam Neck Plant has A.C.

independent backups for the RPS power supplies.

Because of the tie breakers on the vital panels in the control room, the vital bus will be reenergized well within the 2-hour time frame in the M STS.

The 8-hour requirement for each vital bus is consistent with that for the A.C. Emergency Busses (proposed Technical Specification 3.12.3.1 Action a) both at the Haddam Neck Plant and in the W STS.

20.

Proposed Technical Specification 3.12.3 Action c c.

With one D.C. bus not energized fron, its associated battery bank, reenergize the D.C.

bus from its associated battery bank within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

W STS 4.8.3.1 Action c c.

With one D.C. bus not energized from its associated battery bank, reenergize the D.C. bus from its associated battery bank - within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Justification for Deviation The basis for the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> limiting condition for operation (LCO) for battery problems is derived from the Administrative Procedures which allows time for replacement of a failed cell or cells of the battery.

The provision to cross tie the D.C. panels allows the Haddam Neck Plant to provide power to both trains of D.C. while in this LCO. This capabil-ity is part of the Haddam Neck Plant original design and differs from the W standard design.

This time allows for repairs to be made from spare cells in stock, or from other qualified suppliers.

The provision to cross tie the D.C. systems, allows control power to be maintained for all D.C. loads.

If the normal power supply cannot be returned to service within this LC0 time period, an orderly shutdown will commence.

The Haddam Neck Plant's cross tie capability provides justification for an LC0 of greater than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, however, the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> contained in current Administrative Technical Specifications cannot be quantitatively justified at this time.

Therefore, this 72-hour LC0 will be revised to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in the revised Technical Specification for the electrical section which will be submit-ted by July 15, 1989.

U.S. Nuclear Reguutc*y Commission B13236/Page.22 21.

Proposed Technical Specification 3.12.3.2 3.12.3.2 As a minimum, the following electrical busses shall be ener-gized in the specified manner:

a.

4160-Volt Emergency Bus #8 or #9, b.

480-Volt Emergency ' Busses #4 and #5, if Emergency Bus #8 above is energized, or Emergency Busses #6 and #7, if Emergency Bus #9 above is energized,*

c.

120-Volt A.C Vital Busses #A and #B or Vital Busses #C and #D energized from their associated inverters connected to their respec-tive D.C. busses, and d.

125-Volt D.C. Bus #1 energized from its associated battery bank if Emergency Bus #8 above is energized, or 125-Volt D.C. Bus #2 ener-gized from its associated battery bank if Emergency Bus #9 above is energized.

W STS 3.8.3.2 3.8.3.2 As a minimum, the following electrical busses shall be energized in the specified manner:

a.

One division of A.C. emergency busses consisting of one [4160]-volt and one [480]-volt A.C. emergency bus, b.

Two [120]-volt A.C. vital busses energized from their associated inverters connected to their respective D.C. busses, and c.

One [250/125]-volt D.C. bus energized from its associated battery -

bank.

l Justification for Deviation The proposed Technical Specification specifies which busses must be energized. This change fully meets the intent of the H STS and makes the Technical Specification more plant-specific.

22.

Proposed Technical Specification 3.12.3.2 Action With any of the above required electrical busses not energized in the required manner, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel, and initiate corrective action to energize the required electrical busses in the specified manner as soon as possible.

e U.S. Nuclear Regulatory Commission p

B23236/Pe.ge 23 o

i W STS 3.8.3.2 Action With any of the above required electrical busses not energized in the i

l'-

required manner, immediately suspend all operations involving CORE-ALTERATIONS, positive reactivity changes. or movement of irradiated fuel, initiate corrective action to energize the required electrical busses in the specified manner as soon as possible, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressur-ize and vent the RCS through at least a square inch vent.

Justification for Deviation The same discussion regarding RCS overpressurization protection from Item 12 applies to this item.

l l

l l

l

l i!ll

i

+

I N

v g

)

t a n/

..h::hp!!I g

I[II >

}

l).il

_ J

. JJJ.,.. iI i

1 3e jli.

stiit(Udd.p f*

u a

i

),[ [ J!t.Ilh Nil a i i;j, 3

ll d

'. i I.m a

r4

$;;hld'st 3

fid

. >h

. 4 8

d il I

<#ic B

r--------.

.r-------

ii1 i I

~. '.

11

)

c,

\\!*

=

[.

...o._.

c,,,

)

.c r

1 1

8 c..,

~'"m M o-1-

./-

gg

> b,,, I

-c

%5~~.

  • s.1 *":,,,

AI*1-.

-c..

,l '.".,

,'j i

sr

- c.!

-.dE l

J="-?? -

. -c.

a e-1 C

.c,,.

.. e S

c,','

".*.",'"**~2.

. _c,,,

  • % ' 'c "'*

r sg i

.s.....,..

- c.

.t

, - c s

,i c,

,,. CJ. 'h.

- -c,.

'"***S

?

a I

s.

- o-

f. ;.

c

'.t'

(- g,,

e 8

{

e-me eu, e.50s.e aus.

s.

g-r g

. men angoe,..

is

'C as D=s 7 - C IIsNo..a

+g:-

a W.,[

.1'."".

.. _8] { - g L

  • S
          • 8

"'(

wr,

ses ass.

on

4.
  • P l

Ea %

.maa

+

I t

i m

--C

    • =e, 33 h - lg.

a=

s.

v- :

P

. c--

l

-c,!

..., v.

1.

P t,

  • *ll* l'YI.

,'..li

.,*,! 's i

--G.

v.

.,.s.

g

.g.

! 1 m.

i

(

8,2,n!! !

- g ype

.J.

dili e.

,? hlse]

.s.se fe..

f f"*

' " *g,$

  • M h* J

{

C.j,'

J "h"'ow o.eas es.m

....g

.1 e-I, b

' ',~r. g g

ts i,

,,e i

F#1 iia L-........J gj i..........W

_~

  • 5
  • tA ha 0

eh ee

n 1

I 1

I

=

1 l

1 l

1 I

3 1 i

$1 Hi s.:s

. l

~

m E:

4A

..t ",iln' g1i &,

gj.

I n

e.

i

d. <d. -d,. If.d. !,I er.

se.

E\\ $h

=5

{

l l'M lr '

I a

s.

f.-~-

i

.N j

M:k..n. ' "h.. @y, slt

  • D l b;

j f!. a I

y e

k 4

S-- Af'(.g L ?l

~

,g i it. z).i n i.

J p'

.; 4 I.

ti i

l

.l:

s

,p

% yl e.

j';

i j

It i

a in # n. H E,.':

l

  • -l.e-t!u-
} bg':! i gi a

p[ a kM.1 Jg ; s

'g l

I W 4

!!ill i f e m: e'n o.

i ln

,ic'.tl4a

.o! 1r i _._ci

=

,n g[

(J,i.! h.* $,i. Q E,'iM 7 / jl....'....., I r"" " D l' I!

.,t T

' ' [* j

-ll

!!l 8

-' In in.,

Q'r'. i! -o, kg,!

s-x p

a,.

ti. i t 37 Y+-

I!' i

.a,qhfjih d.aJ *,h d d 1lll!

o m,-

O*I

[

l4l83'l*8 l

l

  • l

}Tf!!j -,;. f g!'

'sil : $

9 4 e, jrW.I.,

g il;lI virv,I lf ?

r....m o;8 a t-F rI!i i

imwim!

c i

-d,

..4

g'%srpI1pd,d!

u f i i W'.8_ L.g.

j;;;;g;; p"n

- ~

f

' ?- -4l f

( ];.,J

s. g f, l.....

r-*-

e r: g.

. u.;;j

, I,g'

' 1.-Q. e ?j

{Mlini; g

1 i

,t.

0,p s. -

g i

ita n l lIfi H'e"L,i

.j g;!,; p; M y! "'ll

@Nj)fpi y sW s:

C.,,.:r, dil!p.jj, 9 L1 I

e a

W q -.

"i..

Ri19@M

.. sm$li.

y, 3,

u.

l yd

' qIpwy in u 9,ni!!

y

. y 9;e, b

.irJ] 1:

~

i e :c r

,i'

__m l Q,i y 'y',i m.

i.;

1 le $

~Q iilli2'57,et.t!

iNWU'M!

h *. 1

[g T

- ~11

  • fi......*/t " { A d

N.fs

!I. -k..i g i yl

~U+

..)

s L l l

8.i -

t.

ug.

lg:., w!!

.* p jf r.

1,.

i l(l[ Mll4;;vf.J,=I m-

.w

.s.ir

' iv.s.

s;--I ]

J.

a Yti f

2-1

~*-,:

e i

3 e

' i 'd.* ~

gig g 3[.-4 ; j

t g,g,

,)

8

. ("

.ulf D w !!.; V*g------,i s

/

p I

1,h r[.1

1

([.F&

,,...~

a-

_a g

j

-ll in I

w li':1,.

1 il

. ;t - - - '

.~i i :

1%,

..13

i-lIg9 l %>f l

l5 f1MME~r

_.- m:

d

'. :l' l'

$ !!in,!!hl

' 7 N) b I :

"I h'..i.;

Pi "l

i

/ ^N f..J.;.I4

[il gill. ll.fil] ij

!S a

/+

Q !/.4i. 4aJ'W l.F'!*-TMM,

$kj;

~

i'... -i

.i ilil f,j ',,e:j ji m.,4 m

  1. i..

g o.,

4 'P hj j l

'.v'.- sv i

  • ~

6 3

's

)

'S 61 t'. h I

+

] o. +,..H........g...... 4...; t-3 3:

e

........ y'. 3.,

[

ggi g

g.,y

  • 4 U,.4' f.. p',....,4 q'".......... s' f..

.8.L

... y 6

d

+

e i

..e 5 ', '*

 ! ll} l'

,.h..el.

.. b M...~. ~..et............ " "/

3 o' -

b g.<;

ee. y,m, n

]

i I

Docket No. 50-213 B13236 Haddam Neck Plant Draft Revised Technical Specification l

June 1989 l

3.12 ELECTRICAL POWER SYSTEMS 4

3.12.1 A.C. SOURCES

' OPERATING LIMITING CONDITION FOR OPERATION 3.12.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a.

Two physically independent circuits between the offsite transmission network and the onsite' Class IE Distribution System, and b.

Two separate and independent diesel generators, each with:

1)

A separate engine-mounted fuel oil day tank containing a minimum volume of 400 gallons of fuel (except during engineoperation),

2)

A separate underground fuel oil storage tank containing a minimum volume of 3,250 gallons of fuel, and 3)

A separate fuel transfer pump.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

a.

With one offsite circuit inoperable, demonstrate the OPERABILITY of the remaining A. C. sources by performing Specifications 3.12.1.1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> l

thereafter.

If either diesel generator has not been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demonstrate its OPERABILITY by performing Surveillance Requirement 3.12.1.1.2a.4 separately for each such diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.

With one diesel generator inoperable, demonstrate the OPERABILITY of the A.C. offsite sources by performing Surveillance Requirement j

3.12.1.1.la within I hour and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> l

thereafter; and if the diesel generator became inoperable due to any cause other than preplanned maintenance or surveillance testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by performing Surveillance Requirement

?

3.12.1.1.2a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> regardless of when the inoperable diesel generator is restored to OPERABILITY; restore the diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

l 3-21 i

1

_ ELECTRICAL POWER SYSTEMS AC SOURCES LIMITING CONDITION FOR OPERATION ACTION (Continued) c.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A. C. sources by performing Specifications 3.12.1.1.la within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter; and if the diesel generator became inoperable I

due to any cause other than preplanned maintenance or surveillance testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by performing Surveillance Requirement 3.12.1.1.2a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at l

least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, d.

With one diesel generator inoperable, in addition to ACTION b. or

c. above, verify that the charging pump, HPSI pump, LPSI pump and RHR pump which depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE.

If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

e.

With two of the above required diesel generators inoperable, demonstrate the OPERABILITY of two offsite A.C. circuits by performing Specification 3.12.1.1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter; rostore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore both diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

3-22

  • i

. ELECTRICAL POWER SYSTEMS' AC., SOURCES SURVEILLANCE RE0VIREMENTS 4

1.

Each of the above required independent circuits between the offsite l

transmission network and the Onsite Class IE Distribution System shall be:

a.

Determined OPERABLE at least once per 7 days by verifying correct breaker alignments and indicated power availability.

2.

Each diesel generator shall be demonstrated OPERABLE:

l a.

In accordance with the frequency specified in Table 3.12-1 on a STAGGERED TEST BASIS, by:

1)

Verifying the fuel volume in the engine-mounted fuel oil day tank to be at least 400 gallons (except during engine operation),

- 2)

Verifying the fuel volume in the underground fuel oil storage tank to be at least 3,250 gallons.

3)

Verifying the fuel transfer pump starts and transfers fuel from the fuel oil storage tank to the engine-mounted fuel oil day tank, 4)

Verifying the diesel starts from ambient condition and accelerates to at.least 900 rpm in less than or equal to 10 seconds. The generator voltage and frequency shall be 4160 420 volts and 60 1.2 Hz within 10 seconds after the start signal,*

5)

Verifying that once the generator is synchronized and connected to the bus, it is manually loaded to between 2750 kW and 2850 kW in less than or equal to 60 seconds ** and operates with a load between 2750kW to 2850kW for at least 60 -

minutes, and These diesel generator starts from ambient conditions shall be performed only once per 184 days in these surveillance tests. All other engine starts for the purpose of this surveillance testing shall allow for gradual acceleration so that mechanical stress and wear on the diesel engine are minimized.

l The diesel generator shall be loaded within the specified time limit only once per 184 days. All other diesel generator loadings shall allow for gradual loading so that mechanical stress and wear are minimized.

3-22a

I ELECTRICAL POWER SYSTEMS 1

1 SURVEILLANCE RE0VIREMENTS (Continued) 6)

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.

b.

At least once per 31 days by verifying that the automatic load sequence timers are OPERABLE with the following allowable elapsed times:

E0VIPMENT ALLOWABLE ELAPSED TIME LPSI Pump 5 3 sec.

HPSI Pump s 10 sec. and 2 7 sec.

Service Water Pump 33 5 sec.

Backup Service Water Pump 38 5 sec.

Containment Recirc. Fan 43 5 sec.

Backup Containment Recire. Fan 48 5 sec.

c.

At least quarterly by checking for and removing accumulated water from the underground fuel oil storage tanks.

d.

By obtaining a sample of new fuel oil upon delivery to the site prior to addition to storage tanks:

1)

Verifying in accordance with the tests specified in ASTM-0975-81; a)

An API gravity of greater than or equal to 30 degrees but less than or equal to 40 degrees; and b)

A water and sediment volume percentage of less than or equal to 0.05% (500 mg/L);

c)

A Saybolt viscosity, SUS at 100*F of greater than or equal to 32.6, but not less than or equal to 40.1; and d)

A flash point equal to or greater than 125'F.

2)

Verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-D975-81 are met when tested in accordance with ASTM-D975-81 except that the analysis for sulfur may be performed in accordance with ASTM-D1552-79 or ASTM-D2622-82.

e.

At least once every 31 days by obtaining a sample of fuel oil from the underground fuel oil storage tanks in accordance with ASTM-D-270-75, and verifying that:

(1) API gravity is greater than or equal to 30 degrees but less than or equal to 40 degrees; (2) Water and sediment volume percentage is less than or equal to 0.05% (500 mg/L); and i

3-22b

ELECTRICAL POWER SYSTEMS j

1 SURVEILLANCE RE0VIREMENTS~(Continued)

(3) Kinematic viscosity at 40"C is greater than or' equal to 1.9 centistokes, but less than or equal to 4.1 cegtistokes (alternatively, saybolt viscosity, SUS at 100 F of greater I

than or equal to 32.6, but less than or equal to 40.1).

f.

At least once per 18 months, during shutdown, by:

1)

Simulating a loss-of-offsite power coincident with a Safety-Injection Actuation signal, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts from normal standby conditions on the auto-start signal, energizes the emergency busses with permanently connected loads within 10 seconds, energizes the auto-connected shutdown loads through the load sequence timers and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads; and c)

Verify that all automatic diesel generator trips, except engine overspeed, generator differential, and engine oil pressure (2 out of 2) are bypassed.

d)

Verifying the diesel generator capability to reject a load of greater than the largest single load.

2)

Verifying that on a Safety Injection Actuation test signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes.

3)

Verifying the diesel generator's capability to:

a)

Synchronize with the offsite power source while the generator is loaded with its emergency loads upon a simulated restoration of offsite power, b)

Transfer its 1 gads to the offsite power source, and c)

Be restored to its standby status.

3.

Reports - All diesel generator failures, valid or nonvalid, shall be l

reported to the Commission in a Special Report within 30 days.

Reports of diesel generator failures shall include information recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revision 1, August 1977.

If the number of failures in the last 20 valid tests is greater than 3, the report shall be supplemented to include the additional information recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revision 1, August 1977.

3-22c

_-_____-_________a

r'

~-

- - - ~ ' _ - - -

TABLE 3.12-1 DIESEL GENERATOR TEST SCHEDULE L

NUMBER'0F FAILURES-IN

!i LAST 20 VALID TESTS

  • TEST' FREQUENCY 11 At least once per 31 days l

22 At least once per 7 days **

Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide.l.108, Revision 1, August 1977, where the; number of tests and failures is determined on a per diesel generator basis. For the purposes of this test schedule, only valid tests conducted after the completion of the preoperational test requirements of Regulatory Guide 1.108, Revision 1, August 1977, shall be included in-the computation of the "Last 20 Valid Tests."

This test frequency shall be maintained until seven consecutive failure:

free demands have been performed and the number of failures in the last 20 valid demands has been reduced to one or less.

1

'l l

1 l

l 3-22d l

1 l

. ELECTRICAL POWER SYSTEMS

~

' SHUTDOWN-LIMITING CONDITION FOR OPERATION 3.12.1.2 As a minimum, the following A. C. electrical power sources shall be OPERABLE:

a.

One circuit between the offsite transmission network and the Onsite class IE Distribution System, and b.

One diesel generator, associated with the OPERABLE Onsite Class IE Distribution circuit, with:

1)

An engine-mounted fuel oil day tank containing a minimum volume of 400 gallons of fuel (except during engine operation),

2)>

An underground fuel oil storage tank containing a minimum volume of 3,250 gallons of fuel,and 3)

A-fuel transfer pump.

APPLICABILITY: MODES 5 and 6.

ACTION:

With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel, or crane operation with loads over the fuel storage pool. In addition, when in MODE 5 with less than two (2) steam generators OPERABLE, or in MODE 6 with the water level less than 23 feet above the reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.

SURVEILLANCE RE0VIREMENTS The above required A.C. electrical power sources shall be demonstrated l

OPERABLE by the performance of each of the requirements of Specifications 3.12.1.1.1, 3.12.1.1.2 (except for Specification 3.12.1.1.2a.5, 3.12.1.1.2b, 3.12.1.1.2f), and 3.12.1.1.3.

i l

l l

l 3-22e

. ELECTRICAL POWER SYSTEMS 3.12.2 D.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.12.2.1 As a minimum, the following D.C. electrical sources shall be OPERABLE:

a.

125-volt Battery Bank No. IA, and an associated full capacity j

charger, and b.

125-volt Battery Bank No.18, and an associated full capacity l

charger.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

With one of the required battery banks or full capacity chargers inoperable, restore the inoperable battery bank and full capacity charger to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE0VIREMENTS Each 125-volt battery bank and charger shall be demonstrated OPERABLE:

l a.

At least once per 7 days by verifying that:

1)

The parameters in Table 3.12-2 meet the Weekly limits, 2)

The total battery terminal voltage is greater than or equal to 129 volts on float charge, and l

3)

The electrolyte temperature of the pilot cell is above 60 F.

1 3-22f

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE0VIREMENTS (Continoed) b.

At least once per 92 days and within 10 days after a battery discharge with battery terminal voltage below 110 volts, or battery overcharge with battery terminal voltage above 150 volts, by verifying that:

1)

The parameters in Table 3.12-2 meet the Quarterly limits, and 2)

There is no visible corrosion at either terminals or connectors,orthegonnectionresistanceoftheseitemsis less than 150 x 10- ohm.

c.

At least once per 18 months by verifying that:

1)

The cells, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration, 2)

The cell-to-cell and terminal connections are clean, tight, and coated with anticorrosion material, and 3)

The resistance of each cell-to-celg and terminal connection is less than or equal to 150 x 10- ohm.

d.

At least once per 18 months, during shutdown, by verifying that the battery capacity is adequate to supply and maintain in OPERABLE status all of the actual or simulated emergency loads for the design duty cycle when the battery is subjected to a battery service test; e.

At least once per 60 months, during shutdown, b) verifying that the battery capacity is at least 80% of the manufacturer's rating when subjected to a performance discharge test. Once per 60-month interval this performance discharge test may be performed in lieu of the battery service test required by Specification 3.12.2.1d.;

and f.

At least once per 18 months, during shutdown, by giving performance discharge tests of battery capacity to any battery that shows signs of degradation or has reached 85% of the service life expected for the application. Degradation is indicated when the battery capacity drops more than 10% of rated capacity from its average on previous performance tests, or is below 90% of the manufacturer's rating.

3-229 l

f-TABLE 3.12-2 BATTERY SURVEILLANCE RE0VIREMENTS Weekly (I)

Quarterly (2)

PARAMETER LIMITS FOR EACH LIMITS FOR EACH ALLOWABLEI3)

DESIGNATED PILOT CONNECTED CELL VALUE FOR EACH CELL CONNECTED CELL Electrolyte

> Minimum level

> Minimum level Above top of Level indication mark, indication mark,

plates, and < %" above and < %" above and not maximum level maximum level overflowing indication mark indication mark Float _ Voltage 12.10 volts 12.10 volts 22.07 volts Specifi{4) 21.200(5) 11.190 Not more than Gravity 0.020 below the average of all connected cells average of all Average of all connected cells connec{gf cells

>1.200

>1.195 TABLE NOTATIONS (I)

For any Weekly parameter (s) outside the limit (s) shown, the battery may be considered OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Quarterly measurements.cre taken and found to be within their allowable values, and provided all Weekly and Quarterly parameter (s) are restored to within limits within the next 6 days.

(2)

For any Quarterly parameter (s) outside the limit (s) shown, the battery-may be considered OPERABLE provided that the Quarterly parameters are within their allowable values and provided the Quarterly parameter (s) are restored to within limits within 7 days.

(3)

Any Quarterly parameter not within its allowable value indicates an inoperable battery.

(4)

Corrected for electrolyte temperature and level.

(5)

Or battery charging current is less than 2 amps when on charge.

3-22h

M L

. ELECTRICAL POWER SYSTEMS SHUTDOWN-LIMITING CONDITION FOR OPERATION 3.12.2.2 As a minimum, one 125-soi't battery bank and an associated full l

capacity charger shall be OPERABLE.

APPLICABILITY: MODES 5 and 6.

ACTION:

With the required battery bank or full capacity charger inoperable, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel; initiate corrective action to restore the required battery bank and full capacity charger to OPERABLE status as soon as possible.

SURVEILLANCE RE0VIREMENTS The above required 125-volt battery bank and full capacity charger shall be l

demonstrated OPERABLE in accordance with Specification 3.12.2.1.

3-221

I

?

' ELECTRICAL POWER SYSTEMS 3.12.3 ONSITE POWER DISTRIBUT10N OPERATING LIMITING CONDITION FOR OPERATION 3.12.3.1 The following electrical. busses shall be energized in the specified manner with tie breakers open between redundant busses except for short periods of time while locating shorts or grounds not to exceed 30 minutes:

a.

Train A-A.C. Emergency Busses consisting of:-

1) 4160-Volt Bus #8, and 2) 480-Volt Busses #4 and #5.

b.

Train B-A.C. Emergency Busses consisting of:

1) 4160-Volt Bus #9, and 2) 480-Volt Busses #6 and #7.

c.

120-Volt A.C. Vital Bus A, energized from its associated inverter connected to D.C. Bus #1, d.

120-Volt A.C. Vital Bus B, energized from its associated inverter connected to D.C. Bus #1, e.

120-Volt A.C. Vital Bus C, energized from its associated inverter connected to D.C. Bus #2, f.

120-Volt A.C. Vital Bus D energized from its associated inverter connected to D.C. Bus #2, g.

125-Volt D.C. Bus 1 energized from Battery Bank 1A, and h.

125-Volt D.C. Bus 2 energized from Battery Bank 18.

t APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

a.

With one of the required trains of A.C. emergency busses not fully energized, reenergize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, l

3-22j j

. ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION ACTION (Continuedl b.

With one A.C. Vital bus not energized from its associated inverter:

(1) return all vital busses to their normal power supply configuration within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, or (2)(a) energize the vital bus from its alternate inverter and place the reactor protection trip signal (s) associated with the inoperable bus (in abnormal configuration) in the trip condition (to meet the intent of Table 3.9-1) within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, and (b) return all vital busses to their normal power supply configuration within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, c.

With one D.C. bus not energized from its associated battery bank, reenergize the D.C. bus from its associated battery bank within 24 l

hours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS The specified busses shall be determined energized in the required manner at l

1 east once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.

1 l

3-22k

i e

1 E'

ELECTRICAL POWER SYSTEMS

.g t&

SHUTDOWN LIMITJNG CONDITION FOR OPERATION 3.12.3.2 As a minimum, the following electrical busses shall be energized in the specified manner:

..a.

4160-Volt Emergency Bus #8 or #9, b.

480-Volt Emergency Busses #4 and #5, if Emergency Bus #8 above is energized, or Emergency Busses #6 and #7, if Emergency Bus #9 above is energized,*

c.

120-Volt A.C. Vital Busses A and B or Vital Busses C and D l

'I energized from their associated inverters connected to their respective D.C. busses, and d.

125-Volt D.C. Bus #1 energized from its associated battery bank if l

Emergency Bus #8 above is energized, or 125-Volt D.C. Bus #2 energized from its associated battery bank if Emergency Bus #9 above is energized.

APPLICABILITY 1 MODES 5 and 6.

ACTION:

With any of the above required electrical busses not energized in the required manner, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel, and initiate corrective action to energize the required electrical busses in the specified manner as soon as possible.

SURVEILLANCE RE0VIREMENTS The specified busses shall be determined energized in the required manner at l

least once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.

l Tie breakers 4T5 and 6T7 may be closed to meet this requirement.

3-221 L

I

  • v 3.12 ELECTRICAL POWER SYSTEMS BASES j

l 3.12.1. 3'.12.2 AND 3.12.3 A. C. SOURCES. D. C. SOURCES. ONSITE POWER DISTRIBUTION The OPERABILITY of the A. C. and D. C. power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety-related equipment required for: (1) the safe shutdown of the facility, and (2) the mitigation and control of accident I

conditions within the facility. The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix A to 10 CFR Part 50.

The ACTION requirements specified for the levels of degradation of the power sources provide restriction upon continued facility operation commensurate with the level of degradation. The OPERABILITY of the power sources is consistent with the initial condition assumptions of the safety analyses and based upon maintaining at least one redundant set of onsite A.C. and D.C.

power sources and associated distribution systems OPERABLE during accident conditions coincident with an assumed loss-of-offsite power and single failure of the other onsite A.C. source. When one diesel. generator is inoperable, there is an additional ACTION requirement to verify that the charging pump, HPSI pump, LPSI pump and RHR pump that depend on the remaining OPERABLE diesel generator as a source of emergency power, are also OPERABLE. This requirement is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable. The term, verify, as used in this context means to administratively check by examining logs or other. information to determine if certain components are out-of-service for maintenance or other reasons.

It does not mean to perform the Surveillance Requirements needed to demonstrate the OPERABILITY of the component.

The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling condition ensures that:

(1) the facility can be maintained in the refueling or shutdown condition for extended time periods, and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the facility status.

The Surveillance Requirements for demonstrating the OPERABILITY of the diesel generators are based on the recommendations of Regulatory Guides 1.9,

" Selection of Diesel Generator Set Capacity for Standby Power Supplies",

March 10, 1971; 1.108, " Periodic Testing of Diesel Generator Units Used as Onsite Electric Power Systems at Nuclear Power Plants", Revision 1, August 1977; and 1.137, " Fuel-Oil Systems for Standby Diesel Generators", Revision 1, October 1979, and guidance given in Generic Letter 84-15.

3-22m o

.l s

1 E_LECTRIC POWER SYSTEMS BASES

\\

A.C SOURCES. D.C. SOURCES. and ONSITE DISTRIBUTION (Continued)

The Surveillance Requirements for demonstrating the OPERABILITY of the station batteries are based on the recommendations of Regulatory Guide 1.129, " Maintenance Testing and Replacement of Large Lead Storage Batteries for Nuclear Power Plants," February 1978, and IEEE Std 450-1980, "IEEE Recommended Practice for Maintenance, Testing, and Replacement of Large Lead Storage Batteries for Generating Stations and Substations."

Operability of the batteries and the effectiveness of their charging system is demonstrated by: verifying proper electrolyte temperature, total battery terminal voltage on float charge, intercell connection integrity, and performing battery service and performance (capacity) discharge tests.

Table 3.12-2 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level, float voltage and specific gravity. The simits for the designated pilot cells float voltage and specific gravity, greater than 2.10 volts and 0.015 below the manufacturer's full charge specific gravity or a battery charger current that had stabilized at a low value, is characteristic of a charged cell with adequate capacity. The normal limits for each co.nnected cell for float voltage and specific gravity, greater than 2.10 volts and not more than 0.025 below the manufacturer's full charge specific gravity with an average specific gravity of all the connected cells not more than 0.015 below the manufacturer's full charge specific gravity, ensures the OPERABILITY and capability of the battery.

Operation with a battery cell's parameter outside the normal limit but within the allowable value specified in Table 3.12-2 is permitted for up to 7 days. During this 7 day period:

(1) the allowable values for electrolyte level ensure no physicel damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, not more than 0.020 below the manufacturer's recommended full charge specific gravity, ensures that the decrease in rating will be less than the safety margin provided in sizing; (3) the allowable value for specific gravity of an individual cell, not more than 0.040 below the manufacturer's full charge specific gravity, ensures that the overall capability of the battery will be maintained within an acceptable limit; and (4) the allowable value for an individual cell's float voltage, greater than 2.07 volts, ensures the battery's capability to perform its design function.

3-22n

__ __ __ -