ENCLOSURE 1 l
TO SERIAL NLS-87-191 REVISED TECHNICAL SPECIFICATION PAGES BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 & 2 8709160116 870910 DR ADOCK 0500 4
(5280WRWpp )
n (SSEP-1-105) 5.0 -DESIGN FEATURFS 5.1 SITE L
EXCLUSION AREA 5.1.1 The exclusion area shall be as shown in Figure 5.1.1-1.
LOW POPULATION ZONE 5.1.2 The low population zone shall be as shown in Figure 5.1.2-1, based on the information given in Section 2.2 of the FSAR.
SITE BOUNDARY 5.1.3 The SITE BOUNDARY shall be as a shown in Figure 5.1.3-1.
For the purpose of effluent release calculations, the boundary for atmospheric releases is the SITE BOUNDARY and the boundary for liquid releases is the SITE BOUNDARY prior to dilution. in the Atlantic Ocean.
5.2 CONTAINMENT CONFIGURATION 5.2.1 The PRIMARY CONTAINMENT is a steel-lined reinforced concrete structure I
composed of a series of vertical right cylinders and truncated cones which form a drywell. This drywell is attached to a suppression chamber through a series of vents. The suppression chamber is a concrete steel-lined pressure vessel in the shape of a torus. The primary containment has a minimum free air volume of (288,000) cubic feet.
DESIGN TEMPERATURE AND PRESSURE 5.2.2 The primary containment is designed and shall be maintained for:
a.
Maximum internal pressure 62 psig, b.
Maximum internal temperature:
drywell 300 F.
suppression chamber 200 F.
c.
Maximum external pressure 2 psig.
5.3 REACTOR CORE FUEL ASSEMBLIES 5.3.1 The reactor core shall contain 560 fuel assemblies limited to the following fuel types:
8x8R, P8x8R, BP8x8R, and CE8.
BRUNSWICK - UNIT 1 5-1 Amendment No.
(BSEP-2-106) 5.0 DESICN FEATURES I
5.1 SITE l
EXCLUSION AREA 5.1.1 The exclusion area shall be as shown in Figure 5.1.1-1.
n tu LOW POPULATION ZONE
'O 2+
5.1.2 The low population zone shall be as shown in Figure 5.1.2-1.
SITE BOUNDARY M
5.1.3 The SITE BOUNDARY shall be as shown in Figure 5.1.3-1.
For the purpo,se of effluent release calculations, the boundary for atmospheric releases isithe SITE BOUNDARY and the boundary for liquid releases is the SITE -BOUNDARY prior to dilution in the Atlantic Ocean.
5.2 CONTAINMENT CONFIGURATION 5.2.1 The PRIMARY CONTAINMENT is a steel-lined, reinforced concrete structure composed of a series of vertical right cylinders and truncated cones which form a drywell.
This drywell is attached to a suppression chamber through a series of vents. The suppression chamber is a concrete, steel-lined pressure vessel in the shape of a torus. The primary containment has a minimum free air volume of 288,000 cubic feet.
DESIGN TEMPERATURE AND PRESSURE 5.2.2 The primary containment is designed and shall be maintained for:
a.
Maximum internal pressure 62 psig.
b.
Maximum internal temperature:
drywell 300*F Suppression chamber 200*F Maximum external pressure 2 psig.
c.
5.3 REACTOR CORE FUEL ASSEMBLIES 5.3.1 The reactor core shall contain 560 fuel assemblies limited to the following fuel ^ types:
8x8R, P8x8R, BP8x8R, and CE8.
I I