October 27, 1987 t
Mr. P. B. Fiedler j
Oyster Creek ruclear Generating Station y'-
'i
'/ ice President and Director ~
l
?ost Office Box 388 ff Forked River, New Jersey 08731 7
Dear Mr. Fiedler:
)
SUBJECT:
ACCEPTANCE OF THE METHODOLOGY TO DEVELOP NEW SEISMIC FLOOR RESP 00 E SPECTRA FOR OYSTER CREEK NUCLEAR GENERATING STATION
\\
On September 3, 1987, at a meeting in Bethesda, Maryland, GPU Nuclear-Corporation presented the methodology you plan to use to develop new seismic i
floor response spectra for Oyster Creek Nucicar _ Generating Station.
For the l
two horizontal components of the ehrthquake, you proposed to use the 0.165g l
ZPA Ground Response Spectra, which was approved for use by the NRC staff during the implementation of the Oyster. Creek Systematic Evaluation Program (SEP). The original design was based on the use of 0.2?g ZPA Housner Spectra committed in the FSAR.
Based on the following considerations:
(1)theseismicdesignphilosophy incorporated in the SEP, (2) the earlier staff review effort expended in the development of the proposed spectra, and (3) confirmation that for the frequency range of interest the designs resulting from the,use of the proposed spectra in combination with the present day engineering criteria would be at least as conservative as those computed from the use of the-original FSAR spectra and accompanied engineering criteria, we accept your proposed ground i
response spectra provided that:
(a) the detailed soil-structure interaction analysis with the spectra con.patible input time histories will be used in accordance with the l
applicable SRP criteria; 1
(b) the responses to the request for additional information and analyses discussed during the meeting and stated in the Meeting Summary dated September 11, 1987 are satisfactory, and; (c) the results of the audit (to be conducted on November 17 and 18, 1987) of the methodology and sample calculations are acceptable.
Sincerely,
/s/
Q10ggyB71027o5ogg9 Project Directorate I-4 Alexander W. Dromerick, Project Manager p
Division of Reactor Projects I/II t
Office of Nuclear Reactor Regulation cc: See next page PDI P
PS -4 SNo W-4 rick JSt '33 10/47/87 l
/87 104 787' U__.__
.._-____.N-_---_-_____.-__-.---_.
...-_._-...]
- Mr. P. B. Fiedler Oyster Creek Nuclear
. Oyster Creek Nuclear Generating Station Generating Station CC:
Ernest L. Blake, Jr.
Resident Inspector Shaw, Pittman, Potts and Trowbridge e/o U.S. NRC 2300 N Street, NW Post Office Box 445 Washington, D.C.
20037 Forked River, New Jersey 08731 J.B. Liberman, Esquire Commissioner Bishop, Liberman, Cook, et al.
New Jersey Department of Energy 1155 Avenue of the Americas 101 Comerce Street.
New York, New York 10036 Newark, New Jersey 07102 Mr. David M. Scott, Acting. Chief Regional Administrator, Region I Bureau of Nuclear Engineering
)
U.S. Nuclear Regulatory Commission Department of Environmental Protection 631 Park Avenue CN 411 L
King of Prussia, Pennsylvania 19406 Trenton, New Jersey 08625 BWR Licensing Manager GPU Nuclear Corporation 1 Upper Pond Road Parsippany, New Jersey 07054 Deputy Attorney General State of New Jersey Department of Law and Public Safety 36 West State Street - CN 112 Trenton, New Jersey 08625 Mayor j
Lacey Township
_j 818 West Lacey Road
{
Forked River, New Jersey 08731
)
Licensing Manager Oyster Creek Nuclear Generating Station Mail Stop: Site Emergency Bldg.
P. O. Box 388 Forked River, New Jersey 08731
.1
1 s
f DISTRIBUTION Docket Tfi F *
(
NRC~'& Local PDRs P0f4 Peading SNorris ADromerick JStolz OGC-Bethesda ACRS(10)
Edordan JPartlow t----- ---- -----