m.

^

.l

..a REACTOR COOLANT SYSTEM L'

.i

[~.

LIMITING CONDITION FOR OPERATION I

i:

I

' ACTION (Continued)'

' ' MODES 1, 2,' 3, 4, and 5:

With the specific activity of the. reactor coolant greater than 1 micro-l Curie per gram DOSE EQUIVALENT I-131 or greater than 100/E microcuries per gram of gross radioactivity, perform the sampling and analysis requirements of Item 4.a) of Table 4.4-4 until the specific activity of the reactor coolant is restored to within its limits.

i l

J

.j q

l l

]

l l

)

SURVEILLANCE REQUIREMENTS 1

4.4.8 The. specific activity of the reactor coolant shall be determined to be within the limits by performance of the sampling and analysis program of Table 4.4-4.

1 0710260316 871000 PDR ADOCK 05000403

.p PDR 1

CALLAWAY - UNIT 1 3/4 4-26 Amendment No. 27