Responds to Telcon Re 870727 Application to Amend License NPF-52,to Allow Moving of Hydraulic Oil Pressure Sensors from Main Turbine Control Valves to Turbine Stop Valves. Relocation Will Alleviate Unnecesssary Reactor Trip
ML20235W277
Person / Time
Site: Catawba 
Issue date: 10/08/1987
From: Tucker H
DUKE POWER CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8710160105
Download: ML20235W277 (2)


Text

P-v

[:. g.*

DUKE POWER GOMPANY P.O. nOX 33180 CHARLOTTE, N,0,28242 HALILTUCKER TELEPHONE (yo4) 3y3 4531 r

y,o,,,,,,,,,,

wuotmampeouonon October 8, 1987 U. S. Nuclear Regulatory Commission

. Attention: Document Control Desk Washington, D C. 20555

Subject:

Catawba Nuclear Station' Units 1 and 2 Docket Nos. 50-413 and 50-414 Technical Specification Amendment Unit 2 Reactor Trip on Turbine Trip

Dear Sir:

This letter is in response to telephone conference calls between Duke Power personnel and members of the NRC Staff concerning the license amendment application dated July 27, 1987. This amendment request was to allow the moving of the hydraulic oil pressure. sensors from the main turbine control valves to the main turbine stop valves.

The placement of the sensors on the stop valves will not result in any adverse affects on any plant systems as a result of any tran::tients analyzed in the Catawba FSAR..The control valves and the stop valves are supplied hydraulic oil from +.he same system and sense the same oil pressures. The sensors will be remounted on the sama elevation that they are currently located on.

The main

' difference this relocation will make will be the alleviation of unnecessary reactor trips from the' pressure sensors when the control valves move in response to a Power Load-Unbalance signal.

In this situation the control valves are normally throttled back but the stop valves will remain open. After this change.

is implementc.d only a true turbine trip (which will. result in the closing of the stop valves) will generate a reactor trip signal.

If there are any further questions, pleasa contact Mr. Roger Que11ette at (704)373-7530.

i As this letter is a supplement to a previous amendment request no application fees are required.

Very truly yours, f

f/t, f

Ital B. Tucker RWO/128/sbn 8710160105 871008

% 'J PDR ADOCK 05000414 j

i

\\\\0 P

PDR L__ _ --

.f d

',pt:N t

LUhS[NuclocrlR!guistoryCommission i,:

Llf/j 10i,tobes 8, 1987;.

:i Page 2 z

x p~ a~.
u. % [:Dr. J.-Nelson Grace,~ Regional Administrator l

i.J.

'U. S. Nuclear-Regulatory Commission N

' Region.II;'

101.Marietta Street, NW, Suite.2900

- Atlanta, Georgia '30323-Mr.:Heyward Shealy, Chief

' Bureau of Radiological. Health-

' South Carolina Department of Health &

Environmental Control 12600 Bull Street.

Columbia, South Carolina 2920!..

N&M Nuclear Consultants-

'1221' Avenue of the: Americas New York, New York 10020' l

.INPO Records Center

. Suite 1500 1100 Circle 75 Parkway Atlanta, Georgia,30339 American Nuclear Insurers c/o Dottie Sherman, ANI Library The-Exchange ~,, Suite 245 270 Farmington Avenue.

Farmington, CT 06032 Mr. P. K. Van Doorn NRC' Resident-Inspector Catawba Nuclear Station.

l

. _ - _. _ - _ -