Text
3,__,_.
P BAW-1823 Revision 1 flovember 1985
'l
.]
1 i
j ONCE-THROUGH STEAM GENERATOR MECHANICAL SLEEVE QUALIFICATION 1
LY, k:
i i
1 1
I
.I i
i d
aM.
8610030164 860924 PCR ADOCK C5000312 P
PDR -
Babcock &Wilcon l
a McDermott company 1
BAW-1823 Revision 1 November 1985 ONCE-THROUGH STEAM GENERATOR MECHANICAL SLEEVE QUALIFICATI0.N
,J 41
!,G n
l BABC0CK & WILC0X Nuclear Power Division P. O. Box 10935 Lynchburg, Virginia 24506-0935 Babcock &Wilcox a McDermott company
1 r
o.
n CONTENTS Page 1.
INTRODUCTION.......................... 1-1 2-1 2.
PROGRAM DESCRIPTION 2.1.
Sleeve Design..................... 2-1 2.2.
Design Requi rements.................. 2-2 2.3.
Test Plan....................... 2-4 2.4.
Su ppl ement a ry Test s.................. 2-5 2.5.
Analyses........................ 2-7 3.
RESULTS AND CONCLUSIONS.....................
3-1 3.1.
Leakage Tests..................... 3-1 3-5 3.2.
Joint Strength Tests 3.3.
Light Expansion Tests................. 3-8 3.4.
Suppl ementa ry Test s.................. 3-10 3. 4.1.
Corrosion Tests 3-10 3.4.2.
Flow-Induced Vibration Analysis 3-10 3.4.3.
Strain Tests................. 3-12 31 3.4.4.
Adjacent Tube Tests 3-14 hi 3.5.
Analysis 3-15 3. 5.1.
Performance 3-15 3.5.2.
Structural.................. 3-16 3.5.3.
Process Control 3-17 4-1 4.
SLEEVE INSTALLATION 4-1 4.1.
Remote Tooling 4.2.
Verification of Free-Span Expansion.......... 4-3 4.3.
Ex amination for Defects................ 4-4 4.4.
Radiological Safety.................. 4-5 5.
SUMMARY
AND RECOMMENDATIONS 5-1 6.
REFERENCES........................... 6-1 List of Tables Table Page 2-1.
Load Conditions 2-8 2-2.
OTSG Transient Design Requirements............... 2-9 2-10 2-11 i
List of Tables (Cont'd)
Page Table 2-12 2-3.
Steam Generator Design Parameters..........
2-12 2-4.
2-13 2-5.
2-14 3-19 3-1, 3-20 3-2.
3-20 3-3.
3-21 3-4.
3-22 1
3-5.
3-23 J
3-6.
3-23 3-7.
3-24 3-8.
3-25 3-9.
3-26 3-10, 3-26 3-11.
3-27 3-12.
4-2 4-1.
OTSG Sleeve Qualification Criteria 4-3 f
List of Figures Page Figure 2-15 2-1.
2-16 2-2.
2-17
>i 2-3.
2-18
)
2-4.
2-19 2-5.
2-20 2-6.
3-28 3-1.
3-29 3-2.
3-30 3-3~.
3-31 3-4.
3-32 3-5.
3-33 3-6.
3-34 3-7.
3-35 3-8.
3-36 3-9.
3-37 3-10.
3-38 3-10A.
3-39 3-11.
b l>C OCk It M IC O E t
a McDermott company
6 1.
INTRODUCTION Some steam generator tubes have been found to have a varying amount of wall degradation after only a few years' service.
If the degradation is extensive, the ncrmal practice of plugging defective tubes may reduce the effectiveness of tha steam generators and eventually reduce the performance of the nuclear steam supply (NSS) system.
An alternative to tube plugging is tube sleeving.
A sleeve is installed as a new pressure boundary inside the original tube to bridge the degraded area, thus permitting the tube to remain in service.
Babcock & Wilcox (B&W) has developed and qualified a mechanical tube sleeve that can be installed in degraded tubes of once-through steam generators (OTSGs).
This sleeve is more resistant to the expected types of corrosive y
attack than the original tubes.
It 1s strong enough and sufficiently leak-free to be used as a permanent remedy to keep degraded tubes in service.
This report demonstrates the technical adequacy of the OTSG mechanical sleeve for use in degraded OTSG tubes for both normal and accident load conditions.
The development of the sleeve design requirements and the actual sleeve design are discussed in the program description.
This section continues to describe the qualification program and test specimens designed to evaluate the effect of service conditions on the strength and leakage of the mechanical sleeve.
i The results of the strength and leakage tests are presented and evaluated for both pre-and post-service conditions.
Supplemental tests for corrosion
]
resistance and the effects of tube surface condition and sleeve bending and straightening are also described.
The results of an American Society of Mechanical Engineers (ASME) Code analysis of the sleeve are discussed, as well as the effect of -leeves on plant performance.
The character of flow-induced vibration of a sleeved tube is compared to that of an unsleeved tube.
The i
l 1-1
i remote tooling for installation of sleeves is described, as well as eddy current examination for defects and for verification of proper expansion.
Radiological exposure projections are also included.
The qualification test results are summarized, and conclusions are drawn regarding the use of the sleeve design.
Q i
4
- [
4 Cl l
1 i
(
}
1-2
2.
PROGRAM DESCRIPTION 2.1.
Sleeve Design Tube degradations found in OTSGs have been located most frequently within a few inches above or below the secondary face of the upper tubesheet (UTS).
There is some concentration at the 15th tube support plate (TSP) and in the 16th tube span (i.e., between the 15th TSP and the UTS), and the remainder seem to be ratt.er randomly distributed at elevations below the 15th TSP.
The radial location of degradations tends to be more frequent toward the outer periphery of the tube bundle, and there is some concentration near the open tube lane.
Therefore, a sleeve that extends through the thickness of the UTS and a few inches beyond would serve the most frequent need.
Ex-P:
tending the same sleeve through the 15th tube support plate would be most p-d ef fective.
The sleeve must also be installable in any tube in the steam generator.
The head clearance over the outemost tubes in the OTSG is only about 13 inches, whereas the sleeve length required to extend 6 inches beyond the UTS secondary face is 30 inches.
Thus, installation requires that the sleeves be pre-bent to a gentle radius in order to clear the head and then straightened as they are fed into the tubes.
After the tooling was devel-oped to bend and straighten sleeves as they are installed, it could be modi-fied to bend and straighten longer sleeves.
Therefo re, the qualified de-sign was extended from 30 to 80 inches in order to span the entire 16th tube span and 15th TSP.
This sleeve can be installed in any tube in the generator, and tooli ng modifications could permi t installation from the lower as well as the upper tubesheet.
Thus, the design which has been qualified is a 30- to 80-inch sleeve located in any tube in the OTSG.
The sleeve is made from tubing, according to standards set by ASME SB-163, that has been mill-annealed and heat treated The tube size is 2-1 Babcock &WHcom a McDermott company
j As shown in Fig-
)
ure 2-1, there is expansion in the tube-j sheet, and expansion near the free end of the sleeve.
The length of the sleeve could range between 30 and 80 inches overall.
j t
The installation method quali fied is roller expanding both ends of the sleeve.
This method is quick, gives adequate leak tightness and pullout j
strength, and is easily adapted to remote operation.
Both hydraulic and ex-plosive expansion techniques were considered to obtain a mechanical seal,
f but the rolling technique was preferred due to the speed and sireplicity of the operation and the leak-tight nature of the joint.
Both brazing and wel ding techniques would yield sealed sleeves, but the installation rate was judged to be much too slow and expensive for large installations.
Roller expansion has been used to seal tubes into tubesheets since the D
1930's.
The amount of expansion is easily contolled by limiting the torque q
applied to the expansion tool, sirice there is a rapid increase in torque as 3J the tube is squeezed against the tubesheet and begins to be extruded axial-ly.
Roller expansion of the sleeve in the free-span tube without a tube-f sheet back-up is an innovative application.
f
- various amounts of expansion is evaluited.
k.2.
Design Recairements
)
i The sle' eve design loading requirements have been established to be equiva-1 lent to those of the unsleeved tube on the premise that a sleeved tube could be totally severed without affecting the function of the tube.1 The sleeve is considered to be a structural member that meets all normal, up-
]
set, emergency, and faulted conditions resulting from nonnal operation and accident transients.
The ASME loading condi-tions are tabulated in Table 2-1, and the design transients are tabulated in Table 2-2.
l Babcock &WHcox l
2-2 a McDermott company j
The maximum required pullout strength of the roller-expanded joint Figure 2-2 plots acceptable combinations of axial load and joint slippage, which are dependent upon the yield strength of the parent tube material.
If there were no slip (e.g., an unsleeved tube), the required axial load capability would be the combined thennal and mechanical load (3149 lb) of the worst accident condition, a main steam line break.
If there were no axial load (e.g., a severed tube), the sleeve joint must be able to slip at least 1.09 inches, the maximum relative displacement between the severed ends of the tube without separation of the joint.
A sleeve leakage objective was established based on plant operating limits for primary-to-secondary leakage and an assumed quantity of sleeves which could be ins talled.
Plant Technical Specifications nonnally require that plant shutdown be initiated if steam generator primary-to-secondary leakage exceeds 1.0 gpm.
B The corrosion resistance of the installed sleeve must be equal to or better than the original Inconel 600 tubes as heat treated and stress-relieved for the OTSG.
This is interpreted to include resistances to the following types of corrosion and mechanical damage:
1.
Pitting in the presence of acid chlorides or caustic.
2.
Sulfur-or caustic-induced intergranular attack.
t 3.
Caustic stress corrosion cracking.
4.
Erosion from micron-sized particle impingement.
5.
Abrasive wear from platel ets of debris composed of magneti te (iron oxide).
6.
Corrosion with or followed by low-stress high-cycle fatigue.
The sleeve design must comply with the structural requirements of the ASME Code for the 40-year design life of the OTSG.
This requires that the tube Babcock & WHcom a McDermott company
fatigue analysis be reeval ua ted for the effect of sleeves on the fl ow-induced vibration of the tubes.
This analysis must consider both severed and unsevered tubes due to the worst-case assumption that the degraded area of the tube bridged by the sleeve may not be structurally sound.
The sleeve must be shown to have an adequate pressure boundary thickness 0
according to methods outlined in the ASME Code, for installation in a severed or unsevered tube.
The OTSG design conditions are listed in Table 2-3.
An ASME stress analysis report is required to certify adequacy of the
}
2.3.
Test Plan j
qualification specimens were conditioned and tested to demon-j strate the strength and leakage adequacy of the sleeve design in any OTSG, j
both before and af ter service conditioning to represent 40 years of ser-l vice.
In order to simulate the 40-year service life, the functional specif-ications for all 177-fuel assembly (FA) NSS systems were evaluated with
~
regard to the quantity and severity of design transients.
The conditions that a tube sleeve joint would experience were then arranged as themal
{-
cycles, axial load cycles, pressure cycles, and vibration cycles.
The ex-pected axial loads and service cycles were factored to establish test axial
.3 loads and cycles as required by ASME Code Section III, Appendix II, "Experi-mental Stress Analysis," in order to account for the effects of statistical variations, cycle
- rate, and test temperature.
The resulting service conditions which were applied to the specimens are presented in Table 2-4.
In actual service, the sleeved tubes would simultaneously incur thermal,
[
axial load, pressure, and vibration cycles, but the specimens were indepen-dently subjected to pressure and vibration cycles in order to assess their individual ef fects.
Control specimens were also processed separately with no conditioning to represent as-install ed pre-service sleeve perfomance.
The largest set of samples was subjected to both thermal and axial load J
cycles as an expedient because the effect of the themal cycles was expected to be minor.
The specimens are identified in Table 2-5, and the processing is diagrammed in Figure 2-3.3,4 2-4 Babcock & Wilcox a McDermott company
1 1
l 4
'o 1
'l,
I 2.4.
Supplementary Tests Corrosion resistance was demonstrated by col d-worked samples and control samples which were maintained in a 10% sodium hydroxide solution at 550F in an autoclave with a 190 mV potential Each 24-hour day at these accelerated test conditions represents approximately 1
2-5 Babcock &Wilcox
{-
a ucoermott company
one year of service in an OTSG.,
j
- A met-samples after the autdelave exposure per-allurgical examination of the
)
mitted the comparison of stress corrosion cracking found in the various 1
cold-worked samples with the unworked samples.
The comparison permits a conclusion regarding the effect on corrosion resistance due to the cold-workir.g by roller expansion or bending and straightening.
A group of free-span joint specimens was leak and pull tested in order to evaluate the effect of the tube surface on the joint strength and leak-age.
?
l Four complete samples were assembled to detennine whether the sequence of roller expansion has any significant effect upon the quality of the rolled f
joints or the strain in the sleeve and tube.
2-6 Babcock & WIIcom a McDermott company 1
L
)
sleeves were bent and straightened to represent the worst-case (i.e.,
most curved) sleeves which would be inserted into tubes.
These sleeves were assembled in tubes with tubesheets and then leak and pull tested to determine whether the bending and straightening affects the quality of the r
t rolled joint.
i.
The effect of rolling sleeves in adjacent tubes was demonstrated by rolling plugs in a sample tubesheet test block.
i i
2.5.
Analyses The effect of sleeve installation on the perfonnance of the steam genera-tors was analyzed for flow restriction and heat transfer capacity.
In or-der to scope the worst case, it was assumed that as many as 10,000 80- inch long sleeves are installed in one OTSG.
Temperature distribution and 9[
effect on steam outlet temperature were also analyzed.
The likelihood of flow-induced vibration of a sleeved tube was evaluated.
It was assumed that an 80-inch or a 30-inch sleeve was installed in any tube in the generator, and that the tube may be severed or unsevered.
The sleeve adds mass which tends to reduce the natural frequency, but it also adds stiffness which tends to increase the damping.
The net effect of the sleeve is not obvious, and all cambinations were considered to assure that the worst case was identified.
A sleeved severed tube was analyzed to confirm compliance with Nuclear Regu-latory Commission (NRC) and ASME Code requirements.
This included the cal-culation of requi red thickness for nonnal operating loads, faulted condi-r tions, and primary plus secondary (thennal) stresses according to ASME Section III Appendix F,
and NRC Regulatory Guide 1.121.
The resul ting minimum sleeve wall requirement establishes a degradation limit which in-dicates when a sleeved tube must be plugged or rcoved from service.
E The potential for a sleeve to collapse from external pressure was evalu-ated.
The bending and straightening operations may leave the sleeve with a slightly oval cross section.
Under some accident conditions, there could l
2-7 Dabcock &WIIcom a McDermott comparty
\\
be a secondary-to-primary pressure difference.
If a sleeved tube is sev-l ered, an oval sleeve could conceivably be subjected to this external pres-l If a leaking tube subsequently self-seals, water trapped between the sure.
sleeve and tube may also tend to collapse an oval sleeve.
The consequences of a collapsed sleeve were also evaluated.
The variables of the roller expansion process were analyzed to assure that adequate roller expansions could be reliably reproduced.
The result was an engineer-ing requirements document which established limi ting conditions for the rolling process which are dependent upon the dimensions of the tube to be sleeved.
Table 2-1.
Load Conditions d
Seismic Loading case Static Transients and LOCA Design DW DP OBE a
Level A/B DW OP, ML, HL (consideration of OBE all specified level A/B ther-mal transient loading cambina-tions)
OP -- Design pressure OP -- Operating pressure DW -- Dead weight SSE -- Safe shutdown earthquake ML -- Mechanical loads OBE -- Operating basis earthquake HL -- Hydraulic loads i
l i
2-8 Babcock &WIIcom a McDermott company L
1
?1 q
w
)
2-11 Babcock &Wilcox n
a McDermott company
1 Table 2-3.
Steam Generator Design Parameters Primary side Secondary side Design pressure, psig 2500 1050 Design temperature, F 650 600 Full-load flow,106 lb/h 65.6 5.6 Full-load operating pressure, psia 2200 925 (OTSG inlet)
(Steam outlet)
Full-load inlet temperature, F 604 460 Full-load outlet temperature, F 554 570 Full-load pressure drop, max. psi 33 50 3
- s 1
1 Babcock &Wilcom 2-12 a McDermott company l
t
I 3.
RESULTS AND CONCLUSIONS 3.1.
Leakage Tests The expected leakage per sleeved tube was detemined by measuring the leak-age of each sample over a rangs of axial loads, fitting regres-l sion lines to the observed data, and factoring the control or as-installed l
specimen leakage by the ratio of service cycle leakage to control leakage.
This resul ts in an end-of-life leakage curve that can be compared to the as-installed leakage curve.
The maximum expected leakages for nomal opera-tion and accident conditions are read from these curves at the appropriate axial loads.
They are conservative because the samples were made using low-yield tube material, which is the worst case, and conservative applied T
service cycles.
h l
The mean value of measured leakage for each applied axial load is plotted f'
in scatter diagrams in Figure 3-1.
The control, axial / thermal, pres-sure, and vibration-cycled groups of specimen data are each represented by l
a linear regression line fitted by minimizing the sum of the squares of deviations from the line.
l Leakages for f
zero axial load were not available because internal hydrostatic pressure on h
l the tube end-plugs created an axial load of almost 400 lbs.
The regression lines of Figure 3-1 indicate that leakage is Table 3-1, these relation-ships have been expressed as factors that are ratios of conditioned leakage to control leakage at each test load.
The cumulative effect of all the conditioning could be expressed as the product of these three factors, but 3-1 Babcock & Wilcom a McDermott company
the healing effect of cycling has not been.confimed in conjunc-tion with vibration cycling.
Rather than underestimate the predicted leak-q age, all ratios of less than 1.0 were arbitrarily increased to 1.0 in order to assure conservatism.
The resulting overall service factors and cumula-tive leakage after 40 years' simulated service are presented in Table 3-1 f
and plotted in Figure 3-2.
Within the range of normal operation the maximum leakage is well within
]
the 2.5 ml/h average leakage objective.
The tightness of a rolled joint is highly dependent upon the yield strengths of the materials used.
In this qualification, both tubes and sleeves were type 600 Inconel per ASME Specification SB-163, which pennits
]
a minimum yield strength of 35,000 psi.
All sleeves were made from a single heat of material which had a yield strength of Figure 3-3 includes a scatter dia-m gram of the mean measured leakage of these high-yield suples at various h
axial loads and a linear regression line fit to these points.
A comparison with the regression line for the low-yield tubes, also plotted in Figure 3-3, confinns that the stronger tubes are also much tighter.
Table 3-2 tab-9 ulates specific values from these two curves and the ratios of these leak-ages are used as factors to predict the leakage of high-yield service-condi-tioned sleeve joints at various axial loads.
i Two samples were tested to assess the effects of test temperature on tube l eakage.
When the specimens were maintained at 388F, the mean leakage with no axial load was At the ambient temperature of 67F, the corre-sponding mean leakage was Although it was not practical to leak test at the full design temperature, the hot test results show y
Since both sleeve and d
i In service, the annulus between sleeve and tube may tend to i
insulate the tube so that the sleeve is hotter 3-2 Babcock &WHcom a McDermott company i
I Samples were tested to evaluate the effect of tube surface condition on the quality of the joint.
1 The measured leakage of these specimens is tabulated in Table 3-3.
The tube samples all show very little leakage with no significant differences The mean leakage Space limitations require that the sleeves be bent into a gentle arc out-9y side the OTSG and straightened as they are fed into the tubes.
Two sample sleeves which had been bent and straightened were expanded into tubes and leak tested to verify that the insertion process does not degrade the quality of the expansion joint.
The measured leakage is tabulated in Table 3-4.
As these expansions were made in high-yiel d tubes, the leakage in similar high-yield samples which had not been bent and straightened is also listed for comparison.
The measured leakages are quite low at all axial
- loads, The axial load on a tube during operation is a function of the pressures, the position of the tube in the OTSG, and the tube and shell temperature di f ference, which in turn is a function of the service transient.
For nonnal operation, the transient that results in the greatest total tube load is a cooldown from 157, power.
During this transient, the load on a Babcock &Wilcou 3-3 a McDermott company
center tube reaches 649 lb while the load on a peripheral tube reaches 1107 lb.12 The worst accident condition is a main steam line break (MSLB),
which results in a 3140-1b total load on a peripheral tube of high-yield strength,12 or 2620 lb if the tube has a low-yield strength, according to Figure 2-2.
For a central tube, the maximum load of 1585 lb is a result of a loss-of-coolant accident (LOCA).
These, loads are plotted in Figure 3-4 against expected leakage curves for high-and low-yield tubes.
This indi-cates that under maximum operating load, the greatest expected leakage for a peripheral tube would range from It also indicates that under maximum accident load, the greatest leakage for a peripheral tube In order to predict the leakage in a sleeved 0TSG, it is necessary to make some assumptions regarding the location and yield strength of the sleeved tub es.
Figure 3-5 shows the radial distribution of upper tubesheet tube ed-dy current indications at a typical plant..
?
f.
n In Figure 3-4, dash lines are shown connecting these mean loads between the high-and low-yield leakage l
lines.
It is reasonable to assume that the yield strengths of all of the tubes in an OTSG are for a typical OTSG in Table 3-5.
Thus, the predicted maximum leakage for under nonnal operating loads If there were 10,000 sleeved tubes in a plant (and all of the tubes leaked), the predicted leakage in nomal opera-tion would be of the usual 1
Technical Specification plant shutdown limit.
For accident conditions, the rate would be These predicted leak rates are conservative for nomal expansions.
It is difficult to quantify the amount of conservatism, but factors that contrib-ute to the overall conservatism are as follows:
3-4 Babcock &Wilcox L
._a McDermott company __ __ _ __
1.
It is assumed that all the sleeved tubes have through-wall defects.
If a degraded tube remains leak-tight, sleeve leakage would not contribute to overall primary-to-secondary leakage.
2.
The maximum operating load is not continuous.
It occurs only during The axial loads during steady stai.o and the lesser transients are much lower.
3.
The leakage at is considerably less than However, all of the leakage predictions are based upon 4
tube surfaces tend to result in tighter rolled joints, but some of the qualification tests used In the event of a complete failure of a rolled joint, such as a full circum-
.ferential tube crack at the lower roll transition, the tube and sleeve have been designed to remain engaged under worst-case accident conditions The maximum leakage which could occur in such R
For comparison, the maximum a failed tube has been calculated as leakage for an unsleeved ruptured tube has been calculated p
3.2.
Joint Strength Tests The expected joint strength was detennined by measuring under' a range of axial loads, fitting regression lines to the observed da ta,
This results in an end-of-life curve which can be compared to the as-installed curve.
The mean value of measured each applied axial load is plotted in scatter diagrams in Figure 3-6.
The
(
groups of specimen data arc each h
represented by a linear regression line fitted by minimizing the sum of the squares of deviations from the line.
The sample dat& are
)
al so plotted in Figure 3-7 3-5 Babcock &Wilcox a McDermott cornpany
.s The regression lines of Figures 3-6 and 3-7 indicate that joint strength is reduced the individual conditioning samples at each axial load is tabulated in Table 3-6 and plotted in Figure 3-7.
This represents the cummulative effect of all the conditioning.
Y.n di
.The strengtn of a rolled joint is dependent upon the yield strength of the n
materials used.
In this qualification, most of the tubes were made from All sleeves were made from material.
Figure 3-8 includes a scatter diagram of the samples at various axial loads and a linear re-gression line to fit these points.
Table 3-7 tabulates specific values from these curves, I
Samples were tested to evaluate the effect of tube surface condition on the strength of the joint.
Table 3-8 reports the various surface samples at several axial loads.
3-6 Babcock &WHcom a McDermott company i
L __.
^
tube joints made with sleeves that had been bent and straightened were measured at various axial tube loads.
The results are presented in Table 3-9 and compared to joints where the sleeve had always been straight.
The expected displacement of the rolled joint after 40 years of service ir compared to the design requirement in Figure 3-9.
The acceptance limits for high-and low-yield tube material from Figure 2-2 have been replotted, and the maximum operating loads for center and peripheral tubes have been added in the manner of Figure 3-5.
It is evident that the expected joint is well within the acceptance limits for both maximum operating and accident loads.
The are based upon low-yield tubes on the outer periphery of the OTSG undergoing the maximum cooldown rate or maximum hypo-thetical accident conditions.
They also presume that the sleeved tube is totally severed so that the rolled sleeve joint must carry the entire axial 1oad on the tube.
In actual practice, the tube would nonnally share the load with the sleeve because a severed tube is quite rare.
As previously discussed in section 3.1, t
Thus, it would be a relatively rare occurrence j
for a sleeve in a low-yield peripheral tube to be subjected to the full max-imum operating loads.
However, when this happens, the rolled joint is cap-able of carrying the load without failure.
3-7 Babcock & Wilcox l
a McDermott company L
Although no acceptance criteria were established for the ultimate failure of a rolled joint, most of the test specimens were pulled to failure.
These failures included failed specimens had a mean failure load maximum load that a joint could experience under accident conditions.
3.3.
Light Expansion Tests The tightness of a rolled joint depends upon the amount of roller expan-sfon.
In the qualification tests, all sleeves which were rolled at the tubesheet end had a regardless of tube dimensions and strength.
The free-span expansions were Figure 3-10A plots test data which confirm The amount of the freespan diameter increase depends on 9g 1
In the event that r
the rolled joint may have less strength and leak more.
I l
assess the effect of light expansion.
Figures 3-11 and 3-12 show the scatter diagrams of the light expansion mean measured leakage and joint strength and the regression lines for both light and normal expansion.
Tables 3-10 and 3-11 tabulate specific values from these curves, and the determine the leakage and strength of service-condi tioned lightly expanded joints at various axial loads.
4 The effect of the amount of roller expansion on the quality of the joint is also shown in Figures 3-13 and 3-14, 4
- Again, 3-8 Babcock & Wilcou a McDermott company L
they show that they clearly indicate that the effect of light expansions on both leakage and displacement is The sensitivity of the joint to light expansions is l
The roller expansion tool However, these dimensio1s vary as I
illustrated by the sample distributions of Figure 3-15.
The normal expan-sion that has been qualified 8
r
(
T 3-9 Babcock &Wilcox a McDermott company L..
r The effect of light expansions on an OTSG can be estimated by applying fac-tors to the expected portion of light expansions.
Figure 3-16 indicates Figure 3-17, which is a modified version of Figure 3-10, shows within the strength acceptance limits.
If the expected leakage curves of Figure 3-4 are as shown in Figure 3-18.
As described in section 3.1, these the predicted leakage for the total plant would be of the usual plant Technical Specification limit.
Under the worst normal operation loads, the expected mean leakage 3.4.1.
Corrosion Tests Accelerated stress corrosion cracking tests were performed on sleeved tube mockup specimens to determine whether residual stresses from the sleeving process are sufficient to cause stress corrosion cracking of the sleeve or the OTSG tube.
The mockups were rolled at the tube-sheet joint, In the free span expansion, the tube and sleeve walls were respectively, which is greater than expected in a normal expansion.
In the tubesheet expan-sion, the tube was in the initial roll and the sleeve was by the sleeve rolling, which is the normally expected Babcock &Wilcom 3-10 a ucoermou company 1
amount at Specimens were removed from the tubesheet sleeve joints, free-span sleeve joints, and bent and straightened sleeve samples and mounted in autoclaves along with control specimens from both U-bend and virgin sleeves and tubes.
In the autoclaves, they were exposed to a 10% sodium hydroxide solution at 550F with a +190 mV applied potential The results of the corrosive tests are listed in Table 3-12.
All U-bend con-trol specimens cracked which demonstrates that the test was rigid enough to produce severe cracking in highly strained specimens.
Qd Use of the accelerated caustic corrosion " test results to predict failure in service with all-volatile-treated (AVT) water is based In autoclave tests, the time to crack initia-tion was measured at various strains for specimens subjected to 650F AVT water and 550F 10% caustic solution with an applied electric po tential.
a linear curve was fit to define the relationship between failure times Although the data are limited, this correlation indicates that a i
These correlations are for well controlled AVT water and may not apply to other water treatments or water with impurities which may be present in steam generator opera-tions.
3-11 Babcock &Wilcox a McDermott company
I I
Actual steam generator water chemistries and loading conditions may reduce this predic-tion s
3.4.2.
Flow-Induced Vibration Analysis The effect which a sleeve has on the vibration characteristics of a tube is
]
not obvious because the sleeve stiffens the tube and tends to increase the syste.1 damping.
However, the additional mass tends to reduce the natural freque ncy.
The characteristics of the sleeved tube depend upon n
4 These averaged curves are plotted in Figure 3-20.
)
3-12 Babcock &WIIcox J McDermott Comparty L.
Finite element models were set up with different assumed rotational spring constants at the lower face of the tubesheet in order to match the computed and the observed frequency in the mockup.
The modal frequencies compare as follows:
Computed Hz Mock-up Hz Unsleeved tube Sleeved tube Sleeved tube severed at tubesheet The response plots from the in-air tests (Figure 3-20) were used to deter-mine approximate critical damping ratios These values were rounded off to conservative test damping values, and then more conservative operational damping values for the analysis were obtained '
D p'
These damping values are as follows:
r-Hal f-power Test Assumed for method (rounded) analysis Unsleeved tube Sleeved tube Sleeved tube severed at TS Sleeved tube severed at TSP A NASTRAN finite element model was used for the analysis wi th a at the tubesheet face and damping as listed above.
Secondary side crossflow velocities of OTSGs with both internal and external auxiliary feedwater headers were evaluated.
The resul ting worst-case generic fluid-elastic stabili ty margins and randon vibration and vortex shedding responses are as follows:17 3-13 Babcock &Wilcox a McDermott company
Sleeved tube Sleeved tube Unsleeved Sleeved severed severed tube tube at TS at TSP Minimum fluid-elastic stability margin Random vibration response max. displacement ms, in.
max. stress ms, psi 4
Vortex shedding response max. displacement, in.
max. stress, psi Therefore, it is concluded that flow-induced vibration will not be detrimental in any OTSG tube sleeved in the upper span, even if if
'l the tube is completely severed aniwhere between the upper tubesheet and the number 15 tube support plate.
g 3.4.3.
Strain Tests Specimens were processed to evaluate the sleeve and tube elongation due to sleeve rolling.
During the tubesheet roll, the sleeve is 1
1 g
i 9
i I
3-14 Babcock &WIIcox a McDermott company
3.4.4.
Adjacent Tube Tests There was some concern that rolling a sleeve in a tube adjacent to a tube which previously had been sleeved may loosen the first expansion, causing increased leakage.
it is conservative when applied to rolled sleeves in the OTSG tubesheet.
~
3.5.
Analysis
- t
~
g 3.5.1.
Performance The installation of a significant number of sleeves in the OTSG could re-duce the OTSG's thermal performance due to the insulating effect of the sleeve (especially the annulus between sleeve and tube) and the change in primary flow distribution caused by higher flow resistance.
The net result of these effects The analysis of thennal and hydraulic effects assumed that 5000 80-inch long sleeves were installed in the peripheral tubes of each OTSG.
These worst-case assumptions reduce primary flow by The effect of this reduction in superheat temperature on plant opera-tion is considered to be minimal.
The first OTSG put into operation was warranted to produce a minimum of 35F superheat steam at full power, The new oper-ating point for the OTSGs, turbines, and feedwater control system would be 3-15 Babcock &Wilcox a McDermott company
i 1
l 3.5.2.
Structural The minimum acceptable wall thickness for degraded sleeves was detennined in accordance with the allowable stress and pressure limits of ASME Section III and NRC draft Regulatory Guide 1.121.
Primary membrane stress, burst pressure, and fatigue analysis were considered for normal operation, and primary membrane stress, burst pressure, collapse pressure, and primary mem-brane plus bending stresses were considered for postulated accident condi-tions.
In addi tion, primary plus thermal stresses were evaluated.
The l
minimum sleeve wall thickness was calculated for these eight different ac-I ceptance criteria.
For the expected type of defects, the greatest required
]
minimum wall was found to be j
a 70% through-wall defect would require that a sleeve be removed from service.
This compared to a 69% defect limit for the OTSG tubes.
The sleeve must be bent and straightened for installation in the outennost OTSG tubes.
This results in a slightly elliptical cross section, which was evaluated for buckling pressure.
The maximum expected ovality (i.e., dif-ference in extreme ODs at any one cross section) was found to be inch based on sample dimensions.2 The critical external pressure depends on the material yield strength.
..z Under the maximum secondary pressure of 1050 psi with no primary pressure, neitner tube nor sleeve would collapse.
In the Obrigheim steam generator, tube blisters were found inside the tube-
]
sheet between tubesheet rolls.
This plastic deformation of the tube was at-tributed to water that had leaked through roll transition cracks and became trapped in the annulus betwaen the tube OD and the hole ID by corrosion products.
Upon heatup, the water expanded more rapidly than it could leak out, causing the tube deformation.
Should water be trapped in a similar 3-16 Babcock &WIIcom a McDermott company
manner between the OTSG sleeve OD and tube ID, the annular pressure increase is more likely to blow out the corro-sion products which plugged the leak than to collapse the sleeve.
- Thus, the likelihood of sleeve collapse is very small.
3.5.3.
Process Control The parameters of the free-span expansion were evaluated to assure that the amount of expansion can be controlled within a qualified range.
A general equation was developed to define the relationships among tube, sleeve, and expansion tool parameters before and af ter expansion.13 This equation is:
I
(
U a
3 This process was qualified for a range
)
i 3-17 Babcock &Wilcox a MCDermott Comparty i
Most of the qualification samples were rolled to represent the nonnal range of expansion.
to evaluate the effect of light expan-sion on leakage and strength, and another set was rolled at an average to evaluate the effect of cold working on corrosion resistance.
The range of nonnal expansion is while the range of assure that any tube diameter will be
'l I
expanded within the qualified range.
1 1
d,
- -}
A I
4 4
4 3-18 Babcock &WIIcox a McDermott company l
4.
SLEEVE INSTALLATION The installation of a sleeve in an in-situ steam generator is accomplished by special tooling heads mounted on B&W's Remotely Operated Generator Examination and Repair (ROGER) System.
The installed sleeves are examined to verify proper expansions.
A final eddy current baseline defect examination of the sleeved tube provides a basis for comparison to any indications found in subsequent in-service inspection outages.
These installation and inspection methods minimize the personnel radiation exposures x
in accordance with ALARA principles.
4.1 Remote Tooling The ROGER system consists of a mast providing vertical motion with a single rotating arm and wrist for lateral motion which can deliver and operate a tool head over any selected tube.
ROGER can be installed in the primary head of an OTSG without personnel entry - a no-jump installation.
Each tool head is mounted on ROGER by reaching into the manway from an external staging area.
The tool head can be moved to a particular tube location through manual controls monitored by television cameras or by entering the desired tube location in the computer console for automatic indexing.
The tooling heads required for OTSG sleeve installation are:
tube end flaring tool sleeve insertion tool tubesheet expansion tool freespan expansion tool The flaring tool head is used to prepare the end of a tube to receive a sleeve.
This tube end preparation is t 4-1
tool is positioned by R0GER and
, operated to l
in the projecting tube end.
The depth The sleeve insertion tool delivers a sleeve to a tube and feeds it into the tube as it is inserted.
Straight sleeves are
~
to any tube location regardless of the space limitations of the primary head.
sleeve is installed on the tool by a man at the manway staging area and the j
ROGER manipulator moves the sleeve to the pre-selected tube.
Video monitoring ensures proper alignment before proceeding with the insertion.
The operator receives feedback throughout the process via digital displays on the control panel, and has manual override capability for all operations.
The tubesheet expansion tool positions a roller expander inside the upper end of the sleeve and expands the sleeve against the tube and the bore of t5e tubesheet hole.
The expansion tool is positioned in a sleeve by ROGER, and powered by a reversible air motor.
The amount of expansion All operations are controlled from a remote control center under computer sequencing with video monitoring to i
assure proper positioning and operation of the tools.
The freespan expansion tool positions near the bottom of the sleeve bore and performs of the sleeve against the tube.
As this area of the tube is not backed by a tubesheet, both sleeve and tube are expanded together is positioned in the sleeve by and powered by computer controlled with feedback to assure the desired expansion 4
automatically.
4-2
4.2 Verification of Free-Span Expansion Proper installation of a sleeve in the free-span is confirmed by a measured increase in the tube diameter.
In a generator, the tube 0.D. is inaccessible and the tube 10 becomes the interface between tube and sleeve.
~
The relationship 3
among these variables is:
i 6
y i.
6 0
g O
i I
4-3 1
4.3 Examination for Defects The sleeved tube is examined after installation to provide a baseline examination for comparison to future eddy current results after time in service.
The examination consists of
- 8 e 4
_t W
s 4-4
L
^
?,
4.4 Radiological Safety The development of a mechanical sleeve proc'ess for repair of defective OTSG tubes relies upon use of remote installation equipment.
This results in field I
implementation methods which achieve ALARA exposure goals, i
This sleeving process was tested during a proving run conducted in a full-scale OTSG mockup using actual sleeving equipment.
The proving run was intended to evaluate the performance of the tooling and to assess personnel exposure for the process.
Two batches each were installed in the OTSG mockup during the proving run.
Expected site working conditions were duplicated, incuding use of protective clothing and respirators.
Exposures were assigned based on time i
4-5 L
spent in the tent area, time in front of the OTSG manway, and time reaching into the OTSG head.
The following typical dose rates for areas around the OTSG head were used:
i 1" from tubesheet 18" from tubesheet centerline of manway 3 ft. outside manway low backround area outside staging area The remote manipulator had already been installed at the start of the proving run, and that exposure is not reflected in the proving run results.
- However, actual site data indicates that installation and removal results in an average The data from the preving run indicates that the major sleeving activities would result in the following projected exposures:
[
.w 4-6
These results provide good estimates for evaluating the radiological advantage of the sleeving process, as well as providing exposure goals for tooling and procedural improvements as actual field experience is gained.
The proving run provides a sound basis for the conclusion that remote mechanical sleeving of OTSG tubes using ROGER will result in lower overall i
personnel exposures than if the process were performed by manual means, Comparison of this data with data from similar OTSG repairs by manual means indicate that exposure reductions by a factor of three or more are achievable.
For larger numbers of sleeves the savings are greater.
Figure 4-3 illustrates the typical projected per-tube exposure results.
Based on these results and radiological evaluation of the process, the process i
was found to result in less cumulative exposure than other tube repair methods and is not expected to result in significant increased radiological risk to plant personnel.
??
n 9
9 4-7
J Figure 4-3.
Typical Expected Personnel Exposures
~
-f REMOTE SLEEVING MANUAL PLUGGING (2 Plugs) s I
i f
i R
R R R 0 t
i a
a a
1 e a &
A I
I 4
I 100 500 Quantity of Tubes I
4-10
i o
O 5.
SUMMARY
AND RECOMMENDATIONS Mechanical tube sleeves have been qualified for use in degraded OTSG tubes by a series of tests and analyses.
The design is strong enough and suf-ficiently leak-free to be used as a permanent remedy to keep degraded tubes in service.
The criteria for this qualification have been summarized in Table 5-1 along with the results, which show that all the criteria are sat-isfied.
It is recommended that up to 10,000 of these mechanical sleeves be in-stalled in the OTSGs of any plant as needed to correct or prevent tube degradation which would otherwise require that the tube be removed from ser-4..
vice.
if w
ES$>COCis & Micom 5-1
Table 5-1.
OTSG Sleeve Qualification Criteria Reference Sleeving criterion Justification Results section Installation Capable of installation in any tube in Degradation has been found in tubes Tooling designed to permit the installa-2.1 an OTSG at depths up to 80 in, below across the face of the OTSG, concen-tion of an 80-in. sleeve in any t4e in the top of the teesheet.
trated at elevations in or near the upper an OTSG.
tsesheet and at the 15th t@e support plate.
Leakage Average leakage of no more than 10,000 sleeves wf th this average leak
'The average leakage for a sleeved tde 3.1 per sleeve under normal operating con-rate could be installed in a plant, and undar nazimum operating loads was found to di tions.
the overall steam generator primary to be under maximum secondary leakage would be only one-tenth loads.
of the leakage which requires plant shet-down.
ui Strength b
Pullout strength of at least Accident conditions could load a s1'eeve llo joints failed at loads below the tube 3.2 up to the yleid limit of the tse in yleid strength, dich it is installed Process Control The sleeve installation process must be The Ilmits of the amount of expanston light eApanslons are eRpected, 3.3 controllable so that predictable joint must be estabitshed in order to adequate-and these would have adequate strength quality is maintained.
Iy control the expansion process.
9{
J Corrosion The corrosion resistance of the installed The tube / sleeve assembly is required to Accele~ rated corrosion tests representing 3.4.1 sleeve is to be at least as good as that remain functional in the OTSG.
primary and secondary coolant indt-cated 2 $8 of the original OTSG t@es when sejected sleeved tees will not cract 8 ej to conditions expected in the OTSG.
ih 2-a8 M
t
- Iy;y r.
- c. m r
i.
Table 5 -1.
(Cont' d)
Reference Sleeving criterion Justification Resul ts section Vibration A sleeved tube, either severed or un-Tube / sleeve integrity is required under The sleeved tube, whether severed or not, 3.4.2 severed, is to be adequate for the 40-normal operating conditions.
has a smaller maximum displacement and a year design 11fe as confirmed by an, greater fluid-elastic stability margin ALME 111 fatigue analysts.
than the unsleeved tube, and the maximum stresses are well below allowable.
2 Tube Strain Sleeving installation should not leue Dif ferential expansion in postulated ac-Sleeving will increase the tension in a 3.4.3 a tube in compression or pemit tse to cident conditions must not permit adja-tube. Maximum slippage tube contact.
cent tubes to contact each other.
would not bow the tube in neatup enough to contact an adjacent tube.
Adjacent Sleeves Sleeve installations must not damage a Quantity sleeve installations must not be Adjacent sleeve installations are unaf-3.4.4 O
p.-lor sleeve installation in an adjacent restrained by sequence or location lin-fected by a new sleeve installation.
tube.
i ta tions.
4 Performance 4
l The ef fect of sleeving up to 10,000 The thennel/ hydraulic effects of sleeving 10,000 sleeved tubes would reduce primary 3.5.1 j
tubes must have a tolerable effect up-must be acceptable, flow and reduce full power steam s.merneat The effect of on plant performance.
this would have a minimal effect on plant operation.
Code 1
The minimum required sleeve wall for nor-3.5.2 i
Tube / sleeve funtional integrity must be Tube / sleeve integrity is required under m
maintained under stress and pressure postulated accident conditions.
mal and accident conditions e, E limits of AS4E Section III and NRC permits sleeve defects less g
than tus through-wall.
Q Collapse 9
1 f; Nm A sleeve must not collapse under exter-Sleeve collapse in a leaking tube would The sleeve is about as strong as 3.5.2 i
g nal pressure.
create a primary to secondary leak path. -the tube under external pressure, and gf collapse is unlikely, j
g i
8 M
O 6.
REFERENCES 1.
177-FA OTSG Tube Sleeve Desic i Criteria, B&W Document No. 51-1146626, Babcock & Wilcox, Lynchburg, Virginia, February 1984.
2.
177 OTSG Tube / Sleeve Loads, B&W Document No. 32-1147602, Babcock &
Wilcox, Lynchburg, Virginia, May 1984.
3.
Qualification Specification for OTSG Mechanical Sleeves, B&W Document No. 11-1147592, Babcock & Wilcox, Lynchburg, Virginia, November 1983.
4.
Test Plan for OTSG Mechanical Sleeve Qualification, B&W Document No.
51-1148156, Babcock & Wilcox, Lynchburg, Virginia, October 1983.
L
~
51-1148145-01, 5.
Sleeve Installation Rolling Procedure, B&W Document No.
Babcock & Wilcox, Lynchburg, Virginia, February 1,1984.
6.
Initial Leak Test Procedure, B&W Document No. 51-1148146-01, Babcock &
Wilcox, Lynchburg, Virginia, February 1,1984.
7.
Themal Cycling Conditioning Procedure, B&W Document 51-1148147-01, Babcock & Wilcox, Lynchburg, Virginia, February 1,1984.
8.
Axial Load Conditioning of Sleeved
- Mockups, B&W Document No.
54-1023433-02, B&W R&D Division Technical Procedure ARC-TP-611, Rev.
2_, Babcock & Wilcox, Lynchburg, Virginia, November 15, 1983.
9.
Vib ration Condi tioning of Sleeved
- Mockups, B&W Document No.
54-1023434-02 and B&W R&D Division Technical Procedure ARC-TP-612, i
Rev. 2, Babcock & Wilcox, Lynchburg, Virginia, November 10, 1983.
10.
Cyclic Pressure Conditioning Procedure, B&W Document No.
51-1147649-00, Babcock & Wil cox, Lynchburg, Virginia, October 19, 1983.
11.
L.eak and Load Pressure Testing Procedure, B&W Document No.
51-1147650-01, Babcock & Wil cox, Lynchburg, Virginia, February 1,
1984.
6-1 Babcock &Wilcor a McDermott company
)
PROPRIETARY
- 12. Detemination of tiinimum Requi red Tube Wall Thickness for 177-FA OTSGs, BAW-10146, Babcock & Wilcox, Lynchburg, Virginia, October 1980.
- 13. Mechanical Sleeve Free Span Expansion
- Study, B&W Document No.
32-1148881, Babcock & Wilcox, Lynchburg, Virginia, February 1984.
14.
G.
V.
Theus, Stress Corrosion Cracking Tests of Alloy 600, EPRI WS-80-136, Electric Power Research Institute Proceedings, Palo Alto, California, June 1981.
80"
- 15. Thermal / Hydraulic Performance 32-1149041, Babcock & Wilcox, Lynchburg, Virginia, January 1984.
- 16. Flow-Induced Vibration Analysis of Three Mile Island Unit 2
Once-Through Steam Generator Tubes, EPRI NP-1876, Electric Power Re-search Institute, Palo Alto, California, June 1981.
- 17. Flow-Induced Vibration Analysis of Sleeved Tubes in the 177 OTSG, B&W Document 32-1151170, Babcock & Wilcox, Lynchburg, Virginia, June 1984.