Forwards Data Sheets for safety-related Static O-Ring Differential Pressure Switches Installed at Plant,Per Request to Assist in Preparing SER for Unit 1 Interim Operations
ML20214K325
Person / Time
Site: LaSalle  
Issue date: 11/25/1986
From: Allen C
COMMONWEALTH EDISON CO.
To: Bournia A
NRC
References
2435K, NUDOCS 8612020266
Download: ML20214K325 (119)


Text

~

. ],

.s

, [

} Commonwealth Edison i

r One First Nabonal Plaza. Chca0o. lilinois 4

\\

,7 Address Reply to: Post Omco Box 767

_y V/ Chcago, Illinois 60600 0767 J

November 25, 1986 Dr. A. Bournia Project Manager U.S. Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, MD 20014

Subject:

LaSalle County Station Units 1 and 2 SOR Differential Switch Calibration Data through Nov. 24, 1986 NRC Docket Nos. 50-373 a_nd 50-374

Dear Dr. Bournia:

Attached are the data sheets for the safety related static "O"

ring differential pressure switches installed in LaSalle Units 1 and 2.

This data is provided to you per your request to assist in preparing a Safety Evaluation Report for LaSalle Unit 1 interim operations.

Please direct any questions you may have regarding this matter to this office.

l ry trul

ours, J

M. Allen i

Nuclear Licensing Administrator bc Attachments cc:

Resident Inspector - LSCS 2435K

\\

8612O20266 861125 g.I PDR ADOCK 05000373 j

P PDR

.n Paga 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-N024A APPLICATION:

LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPOINT:

58.90" WC CALIBRATION TOLERANCE:

58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC REJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - - - = - - - - - -

_ _ = _

=-.

07/30/86 58.90 53.60 C8/18/86 58.30 52.40 59.10 54.40 C9/01/86 59.30 54.00 58.80 53.60 9/3D/86 59.03 53.60 58.90 54.10 11/21/86 61.4 53.0 58.9 52.9

Page 1

-UNIT-2-CALIBRATION DATA

=======================-

' EQUIPMENT PIECE NUMBER:

2B21-N024B APPLICATION:-

LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPDINT:

58.90" WC CALIBRATION' TOLERANCE:-

58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC REJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip.

Reset 07/30/86 58.90 54.00 08/18/86-59.15 54.05 59.00 54.40 C9/01/86 58.90 53.80-58.90 54.10 9/30/86 59.05 54.30 59.05.

54.60 11/2*/86-60.4 52.5 58.6 52.2

!=

l 5

i f

1 I

i 0

0 i

Page 1

UNIT 2' CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-N024C APPLICATION:

LEVEL 3 SCRAM AND ISOLATION NOMINAL'SETPOINT:

58.90" WC CALIBRATION TOLERANCE:

58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC REJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC lCalibration Date-

"As Found" As Found" "As Left" "As Left" Trip Reset Trip.

Reset

--- = _ _ _ _

07/30/86 58.90 53.30

~ 08/18/86 58.85 52.70 58.80 53.10 C9/01/86 58.50 52.60 58.50 52.70

'9/30/86 58.75 53.10 58.70 53.20 11/21/86 60.4 52.2 58.6 50.5 i

h i

4 i

a 4

~

-m'

,, ~,

,c

.. ~..,,,+_ e

,r.,_

y.,m.,,,

r,.._.m,,

,,...y._

____r_.

Pagm 1

UNIT 2 CALIBRATION DATA

===========

. EQUIPMENT PIECE NUMBER:

2B21-N024D APPLICATION:

LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPOINT:

58.90" WC CALIBRATION TOLERANCE:

58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC HEJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_ _ - - = _

_ _ - - - - - - = = _

07/30/86 59.00 53.80 08/18/86 58.90 54.00 59.00 54.00 C9/01/86 58.75 53.50 58.70 53.70 9/30/86 59.00 54.10 59.00 54.30 11/21/86 59.7 52.0 58.9 52.4 i

l

. _ _ - -.=_

Page.

1 i

' UNIT.R CALIBRATION DATA

>=======================

I. EQUIPMENT' PIECE NUMBER:

2B21-NO38A APPLICATION:

LEVEL 3 LOW WATER LEVEL ADS CONFIRMED

' NOMINAL SETPOINT:

58.90" WC

~

CALIBRATION. TOLERANCE

58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC REJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC

)CalibrationDate "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset i

=________________

' 07/33/86 58.90 53.70 08/19/86 59.55 54.10 58.80 53.65 7 09/02/86' 59.05 54.00 59.00 54.15

-9/30/86 61.30 54.50 58.70 52.80 i

4 t

4 i

1

{

i i

s

Pags 1

_'l ONIT/2' CALIBRATION DATA

===========

tEGUIPMENT PIECE NUMBER:

2B21-NO38B

. APPLICATION:

LEVEL 3 LOW WATER LEVEL ADS CONFIRMED NOMINAL SETPOINT:

58.90"'WC CALIBRATION. TOLERANCE:

- 58.40-59.40" WC ACTION LIMITS:

56.10-61.70" WC 4

REJECTION LIMITS:

56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC

l. Calibration Date "As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset j

==--

- --==-

m.

!07/30/86_

58.90 53.50 08/19/86 59.20 53.35 59.15 54.10 09/02/86 59.40 54.05 58.80 53.-70 i

9/30/86 59.20 53.00 59.00 53.60 i

i i

I t

i h;

t w

yw

^r-w y,

-^cem,

-,==~-,?

-,---,g-mm. - - - e,, es. w w w y e -v

-em.,-.--,


w-- *

--e,-

..we a

w

,----+

4

-+- - - -

-ee m -,

e Pcg2 1

UNIT C CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-N101B APPLICATION:

REACTOR HIGH LEVEL RCIC TURBINE TRIP NOMINAL SETPOINT:

38.7" WC CALIBRATION TOLERANCE:

38.2-39.2" WC ACTION LIMITS:

N/A REJECTION LIMITS:

36.5-40.9" WC TECH SPEC ALLOWABLE:

32.8" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C8/02/86 38.5 45.1 10/23/86 38.6 46.9 38.4 46.3

Paga 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-N026AB APPLICATION:

REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As'Left" Trip Reset Trip Reset 08/02/86 133.5 121.7 09/24/86 133.8 123.25 134.5 124.4 I

Pcgn i

R

, UNIT 2 CALIBRATION DATA

====================-

EQUIPMENT PIECE NUMBER:

2B21-N026BB APPLICATION:

REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TCLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date-

"As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_=-----------==-

- - = = = - - -

C8/02/86 133.8 122.5 C9/24/86 138.25 128.0 133.75 124.3

Page 1

UNIT 2 CALIBRATION DATA

.umnuua===========

-EQUIPMENT PIECE NUMBER:

2B21-N026CB APPLICATION:

REACTOR LOW LOW LEVEL MSIV ISOLATION

' NOMINAL SETPOINT:

134.0" WC CALIERATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

= _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - _ -

C8/02/86 133.9 121.0 C9/24/86 134.7 122.5 134.6 122.7

a Page 1

-UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-N026DB APPLICATION:

REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

.=--

=

---=_

C8/02/86 134.5 119.8 09/24/86 136.7 122.2 133.75 120.25

C -

Pege 1

UNIT 2 CALIBRATION DATA

'=======================

EQUIPMENT PIECE NUMBER:

2B21-NO31A APPLICATION:

REACTOR LEVEL 2 HPCS INITIATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.6" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset-

- = = - - - - - - - -

- _ - =.

_=-------------

C8/01/86 134.25 127.75 08/27/86 137.80 130.80 134.20 127.30

Paga 1

UNIT.2 CALIBRATION DATA

mu===mu==unumu=

EQUIPMENT PIECE NUMBER:

2B21-NO31B APPLICATION:

REACTOR LEVEL 2 HPCS INITIATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

120.6-139.4" WC 125.4-142.6" WC REJECTION LIMITS:

TECH SPEC ALLOWABLE:

150.6" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=-

=

G8/02/86 134.00 125.50 08/27/86 134.50 128.00 134.50 128.00

Pagn

'l

~

UNIT 2' CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-NO31C

- APPLICATION:.

REACTOR LEVEL 2 HPCS INITIATION' NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC

ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.6" WC T

Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - =. -

)

i i:C8/02/86 134.00 125.50 08/27/86 135.50 126.50 134.30 126.00 1

i I

4 f

I t

a i

(

l l

I.

I l

s

d

.s Page 1

= UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

'2B21-NO31D APPLICATION:

REACTOR LEVEL 2 HPCS INITIATION s

- NOMINAL ~SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC

-TECH SPEC ALLOWABLE:

150.6" WC 3

- Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_ _ _ _ _ _ _ = - -.


_= _ _ _ _ _ _ _ _ _ _-

08/02/86 134.20 127.00 LO8/27/86' 134.60 127.20-134.70 127.50 1

A 5

'l b

I

Page 1

' UNIT.2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-NO37AA APPLICATION:

REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

= = _

_ _ _ _ _ = - - _ _ _ _

C8/02/86 189.20 179.50 08/13/86 189.75 179.75 189.75 179.75 11/12/86 189.8 179.2 189.6 180.4 l

l

~__

. ~

Paga 1

UNIT'a CALIBRATION DATA

===========

-EQUIPMENT. PIECE NUMBER:

2B21-NO37BA

{ -. APPLICATION:

REACTOR LEVEL 1 ECCS INITIATION I

NOMINAL ~SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0 "WC ACTION-LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17 "WC Calibration Date.

"As Found" "As Found" "As Left" "As Left" Trip-Reset Trip-Reset C8/03/86 189.90 169.60

C8/13/86 190.00 170.40 190.00 170.40-11/12/86 189.0 169.0.

189.0 171.0 l

T t

r i

i

[.

I.

i '., - _.. _..., _., _.,.. _. - _

Pego 1-ON'IT 2' CALIBRATION DATA

===========

EQUIPMENT. PIECE' NUMBER:

2B21-NO37CA APPLICATION:

REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:-

187.0-191.0" WC

~ ACTION LIMITS:

181.2-196.8"-WC REJECTION LIMITS:

178.8-199.2" WC

. TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - = - -

C8/02/86 188.50 176.00-08/13/86 189.50 177.50 189.50 177.50 11/12/86 190.0 178.2 189.9 178.2 h'

i n

+.

.., -. - ~,. -.. _ - - -,

-.m_

e Pega 1

UNIT 2-CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-NO37DA APPLICA, TION:

REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - =. - -

C8/03/86 188.40 175.80 08/13/86 189.60 177.00 189.60 177.00 11/12/86 189.0 175.0 189.0 177.0 t

Pagn 1

l ONITL2 CALIBRATION DATA

===========

~ EQUIPMENT PIECE NUMBER:

2B21-NO37AB APPLICATION:

REACTOR LEVEL 2 RCIC INITIATION

- NOMINAL SETPOINT:

134.0" WC

CALIBRATION TOLERANCE:-

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC

' TECH SPEC ALLOWABLE:

150.64" WC

- Calibration'Date "As Found" As Found" As Left" "As Left" Trip Reset Trip

. Reset 08/02/86 134.20 126.80 8/13/86 134.75 127.5 133.75 126.50 11/12/86 133.3 126.6 133.4 126.3-l

[

i l

t

}

i i

i t

1 em -

-stv---

t-y

,y.-.. -,.,

y

,_,.....-.-__y..,_,_._.,..,_,y,,,

m,

Pago 1

UNIT 2 CALIERATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-NO37BB APPLICATION:

REACTOR LEVEL 2 RCIC INITIATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

= - - - - - - - - - - - - - - - - - - - - - - - - - -

=-----------------------------

,'C8/03/86 134.10 128.30 08/13/86 135.50 129.50 134.50 128.60 11/12/86 135.5 128.0 133.8 127.0 i

6 Page 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT-PIECE NUMBER:

2B21-NO37CB.

APPLICATION:

REACTOR LEVEL 2 RCIC INITIATION NOMINAL'SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC

~

128.6-139.4" WC ACTION LIMITS:

,' REJECTION LIMITS:

125.4-142.6" WC

TECH SPEC ALLOWABLE:

150.64" WC

Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_=____

08/02/86 133.80 128.70 08/13/86 135.00 131.00 134.50 129.75 3 11/12/86 134.1 128.7 134.1 128.8

+

1 i

4 1

f i

I 4

4 4

i t

i l

[

l l

l I

I

Page 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2B21-NG37DB APPLICATION:

REACTOR LEVEL 2 RCIC INITIATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C8/03/86 133.90 126.80 08/13/86 135.75 129.00 134.00 127.75 11/12/86 134.3 127.0 134.3 127.0

-, - - ~.

p,

Page 1

s UNIT 2 CALIBRATION DATA

.n===========

EQUIPMENT PIECE NUMBER:

2E31-N008A APPLICATION:

MSL HI FLOW ISOLATION NOMINAL SETPOINT:

85.0 PSID CALIBRATION TOLERANCE:

84.0-86.0 PSID ACTION LIMITS:

69.50-100.50 PSID REJECTION L IMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

111.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

.-------------------------------------------==

_=--

C8/02/86 85.50 62.50 08/29/86 85.70 61.80 85.30 61.80 11/20/86 86.0 59.0 85.5 60.0 r

i I

1 l

I i

Pagn 1

f UNIT 2 CALIBRATION DATA

- -:=======================

r EQUIPMENT PIECE NUMBER:

2E31-N008B APPLICATION:

-MSL HI FLOW' ISOLATION NOMINAL SETPOINT:

85.0 PSID I CALIBRATION TOLERANCE:

84.0-86.0 PSID ACTION LIMITS:

69.50-100.50 DSID

' REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

111.0 PSID I'Ca'11bration Date "As Found"-

"As Found" "As Left" "As Left" t

Trip Reset Trip.

Reset

+

- - - - - - - - = = - - - -

, 08/02/86 85.20 65.40 08/29/86 87.~00 65.50 85.00 65.40

11/20/86 90.0 62.0 85.0 58.0 4

P

't i

s i

1 I

t

l Pagn 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N008C APPLICATION:

MSL HI FLOW ISOLATION NOMItJAL SETPOINT:

85.0 PSID CALIBRATION TOLERANCE:

84.0-86.0 PSID 4

ACTION LIMITS:

69.50-100.50 PSID REJECTION LIMITS:

69.50-100.50 PSID

' TECH SPEC ALLOWABLE:

111.0 PSID Calibration Date "As Found" As Found" As Left" As Left"

' Trip Reset Trip Reset 1

C8/02/86 85.00 65.60

'C8/29/86 86.00 64.00 85.50 64.00 i

11/20/86 87.0

- 62.0 85.0 63.0 1

I i

4 i

a i

i

, ~.

,,,m-.

.m.

-._m,,_---...

,=%-. -.,... _ - -. -, - -

.c 1.1Y

  • l

6

, ;).

pags 1

c.i n

~. UNIT-2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N008D

. APPLICATION:

MSL HI FLOW ISOLATION

-NOMINAL SETPOINT:

85.0 PSID-84.0-86.0 PSID CALIBRATION TOLERANCE:

c 69.50-100.50 PSID

. ACTION LIMITS:

REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:.

111.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" c

Trip Reset Trip Reset

,. = _


=_

- ------------=-

+

1C8/03/86 84.40 67.00

. 08/29/86 84.20 68.00 85.30 69.50

-11/20/86-87.0 67.0 85.0 67.0 t

't 4

3 i

\\

r t

i e

I i

ff,.

p,g, i

f

' UNIT;2 CALIBRATION DATA

===========

-EGOIPMENT PIECE NUMBER:~

'2E31-N009A APPLICATION -

MSL HIGH FLOW MSIV ISOLATION

. NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID

7. ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID

' TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/'2/86 85.40 67.00

!9/26/86-88.00 61.00 85.50 62.00 4

4 L

f t

r--

,4-t-+,*

~

v,-

-ew r

v vi

+rrv omv -

e-*--

1 r, w -v - ~, -

-vv-'=-

-w--~ &-+ - - - - * - = - - ' - - ' - - - -

[

Pag 2 1

, UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N009B APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID

-ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=--

8/ 2/86 85.20 67.00 9/26/86 88.00 62.00 84.80 62.00

E' l

Paga 1

ONITf2' CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N009C

-APPLICATION:

MSL HIGH FLOW MSIV ISOLATION

. NOMINAL'SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID STECH SPEC ALLOWABLE:

116.00 PSID

' Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- ___=

8/ 2/86 85.20 60.70-9/26/86 88.50 58.00 85.00 56.50 1

1 I

l f

4

.I

'i

[~e:

Paga 1

^

l UNIT 2 CALIBRATION DATA

===========

' EQUIPMENT. PIECE NUMBER:

2E31-N009D APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID

' CALIBRATION TOLERANCE:

84.00-86.00 PSID

.A'CTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID

~

-TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date-As Found" As Found" As Left" As'Left" Trip Reset Trip Reset

_= - --

8/ 2/86 84.50 59.40

-9/26/86 88.00~

56.00 85.00 57.00 9/27/86 85.50 56.50 85.50 56.50 1

t e

d f

.er ay yy-3

-,wc

-rtv,,

r, r r

-3 y


w-r,--yir yv w-

-*-w,.m

--y-twrr

=,

.w r-e-

e:

- Pagn 1

' UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N0109

' APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID:

, CALIBRATION TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" As Found" As Left" As Left" Trip Reset Trip Reset 8/ 2/86 85.00 61.20 10/14/86 85.5 59.5 85.0 59.0 l

i i

-"*+$

- s9

+

r we9 y-mr 9

4WNu-w--

cw

---y-

---pi-1-e--wy-w-

  • 9%syyw,eg--

+

g--wera e

e

+r i+t--*~me-v+-

+wey e--

Pago 1

k.;;.

" UNIT 2 CALIBRATION DATA

===========

- EQUIPMENT PIECE NUMBER:

2E31-N010B

' - APPL'ICATION:

MSL HIGH FLOW MSIV ISOLATION 4

NOMINAL SETPOINT:

85.00 PSID CALIBRATION. TOLERANCE:

.84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID' i TECH SPEC ALLOWABLE:

116.00 PSID

' Calibration Date As Found" "As Found" As Left" "As Left" Trip Reset Trip-Reset

- - - _ __ _ _ _ = = - --

_=-

8/ 2/86 84.50 65.50 10/14/86 86.0 63.0 85.5 60.5 ir i

+

k s

i

+7 g---,y..

....-c-

,,-%m, _, _y my,

,w-.

3

,%.%,m,,m,,,e..,

.my_,,____,w-,m mm m,y,,

m,

a Pags 1

t-UNIT.2 CALIBRATION DATA

.=======================

EQUIPMENT PIECE NUMBER:

2E31-N010C APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=-

- - - - = = =

8/ 2/86 84.60 61.60 10/14/86 89.0 58.0 85.0 58.0 t

f

Pega 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N010D APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

-69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left"c Trip Reset Trip Reset 8/ 2/86 85.10 62.10 10/14/86 88.0 58.0 85.0 57.0

r--s

.Pago 1

- UNIT 2-CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N011A

, APPLICATION:

MSL HIGH FLOW MSIV ISOLATION

' ' NOMINAL' SETPOINT:

'85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID 3,

t-~ ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID

-TECH SPEC ALLOWABLE:

116.00 PSID Calibration-Date "As Found"=

"As Found" "As Left" "As Left"

. Trip Reset.

Trip' Reset

=----------- _-

8/ 2/86 85.00 58.80

.' 10/14/86 86.0 57.5

'85.0 56.O i

I i

1 J

ll.

4

+

d 4

7

Paga 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N011B

. APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_==----- ___

8/ 2/86 85.40 69.70 10/14/86 85.5 60.0 85.5 68.0 i

l l

i l

i l

t I

l l

l l

l t

Pags 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N011C

. APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION. TOLERANCE:

84.00-86.00 PSID ACTION LIMITS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 2/06 84.71 64.50 10/14/86 87.75 60.0 85.5 61.0

1 1

Pcgn 1

UNIT 2 CALIBRATION DATA

=======.,===

EQUIPMENT PIECE NUMBER:

2E31-N011D APPLICATION:

MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

85.00 PSID CALIBRATION TOLERANCE:.

84.00-86.00 PSID ACTION LIM 7.TS:

N/A REJECTION LIMITS:

69.50-100.50 PSID TECH SPEC ALLOWABLE:

116.00 PSID Calibration Date "As Found" "As Found" "As Left' "As Left" Trip Reset Trip Reset 8/ 1/86 REVISED SETPOINT 85.00 61.50 8/ 2/86 84.70 60.30 84.60 60.40 1C/14/86 90.0 59.0 85.0 58.0 i

Pcgm 1

UNIT 2 CALIBRATION DATA

=:===r.:======

EQUIPMENT PIECE NUMBER:

2E31-N012AA APPLICATION:

RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:

168.4" WC

~

CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - - - - - - - - - - - = - - - - - - - - - - -

08/03/86 168.0 157.0 C9/16/86 164.0 154.0 168.5 160.0 i

.. ~..

Paga 1

).

UNIT E~ CALIBRATION DATA

===========

4 4-EQUIPMENT PIECE NUMBER:

2E31-N012AB

' APPLICATION:

RHR SDC HIGH SUCTION FLOW

.t NOMINAL SETPOINT:

168.4" WC

{CALIBRATIONTOLERANCE:

167.4-169.4" WC

-ACTION LIMITS:

-163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC i TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" i

. Trip Reset Trip Reset C8/03/06 168.0

'160.0

' 09/16/86 166.0-157.0 168.0 159.9 s

4

'l i

i l

i l

{

{

l^

i l,

,.. _ - -,....,,,. _ _,,,.,,, - -,, _ _,, _. ~ _, -.. - - -,. -,. - -., _... _ _..., - - -., - -

Pegn 1-UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N012BA

-APPLICATION:

RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:

168.4" WC

-CALIBRATION TOLERANCE:

'167.4-169.4" WC

. ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC-

. TECH SPEC ALLOWABLE:

186.0" WC

-Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - = _ -= _ _ = _ - - - -

-==

-08/03/86 168.0 155.0

'09/16/86 165.0 152.0 168.5 155.0 4

I r-i s

i i

i i

F

Paga 1

UNIT'2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N012BB APPLICATION:

RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:

168.4" WC CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

-=__________:-

- _ _ _ _ _ _ _ _ = -

=

=---______________=-

C8/03/86 168.5 157.0 09/16/86 168.0 157.0 168.0 157.0 t

Paga i

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N007AA APPLICATION:

STEAM LINE HIGH FLLOW RCIC ISOLATION NOMINAL SETPOINT:

111.4" WC CALIBRATION TOLERANCE:

110.4-112.4" WC ACTION LIMITS:

106.0-116.8" WC REJECTION LIMITS:

102.8-120.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

= - - - - - - - - - - -

=-----

08/04/86 111.5 106.0 10/ 9/86 112.0 107.5 112.0 107.5

Pagn 1

. UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N007AB APPLICATION:

STEAM LINE HIGH FLLOW RCIC ISOLATION NOMINAL SETPOINT:

111.4" WC CALIBRATION TOLERANCE:

110.4-112.4" WC ACTION LIMITS:

106.0-116.8" WC REJECTION LIMITS:

102.8-120.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 111.5 105.5-10/ 9/86 111.5 105.0 111.5 105.0

Pagu 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N007BA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

75.4" WC CALIBRATION TOLERANCE:

74.4-76.4" WC ACTION LIMITS:

70.0-80.8" WC REJECTION LIMITS:

66.8-84.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 75.7 71.0 10/ 9/86 75.5 71.5 75.5 71.5 s

Pagn 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N007BB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

75.4" WC CALIBRATION TOLERANCE:

74.4-76.4" WC ACTION LIMITS:

70.0-80.8" WC REJECTION LIMITS:

66.8-84.0" WC TECH SPEC ALLOWABLE:

128.0" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

-___________----______----------___=_

8/ 4/86 75.7 69.5 10/ 9/86 80.0 69.0 75.5 67.0

Paga 1

1

' UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N013AA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC REJECTION LIMITS:

155.8-177.0" WC TECH SPEC ALLOWABLE:

185.0" WC Calioration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 166.7 159.5 10/ 9/86 168.0 163.0 166.0 161.0 4

4

Paga 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N013AB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC REJECTION LIMITS:

155.8-177.0" WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 166.8 158.5 10/ 9/06 168.0 161.0 166.5 160.0 6

4

1 Pag 9 1

O UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E31-N013BA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIDRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.0" WC REJECTION LIMITS:

155.8-177.0" WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset 8/ 4/86 166.0 157.5 10/ 9/86 166.0 153.0 166.0 153.0

U e

Page 1

UNIT 2 CALIBRATION DATA

===u=======

EQUIPMENT PIECE NUMBER:

2E31-N013BB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC-CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC

. REJECTION LIMITS:

155.8-177.0" WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 165.6 152.5 10/ 9/86 171.5 159.5 167.0 157.0 i,

5 l

. _ _ _.. _ = _. _. _ _ _ _

Pzg2 1

1 UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E21-N004 APPLICATION:

LOW PRESS CORE SPRAY MIN FLOW BYPASS NOMINAL SETPOINT:

23.0.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

20.6-25.4" WC TECH SPEC ALLOWABLE:

2.187" WC Colibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=

07/30/86 22.9 29.4 10/20/86 23.0 34.6 23.2 34.6

o Page 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E22-N006 APPLICATION:

HPCS MINIMUM FLOW NOMINAL SETPOINT:

23.00" WC CALIBRATION TOLERANCE:

22.40-23.60" WC ACTION LIMITS:

21.30-24.70" WC REJECTION LIMITS:

20.00-26.00" WC TECH SPEC ALLOWABLE:

9.70" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/30/86 23.20 32.40 08/15/86 23.60 32.40 23.60 31.60 11/15/86 23.4 34.0 23.4 34.0

--G.

f Pagn.

'1

. UNIT'2 CALIBRATION DATA

===========

EQUIPMENT PIECE' NUMBER:

2E12-N010AA

'? APPLICATION:

RHR A MINIMUM FLOW

NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

- 21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC

' TECH SPEC ALLOWABLE:

1.78" WC Calibration Date As Found" As Found" As Left" "As Left"

- Trip Reset Trip Reset


------=-


=

07/31/86 23.0 29.2 09/10/86-21.6 28.4 22.9 29.2 4

5' i

l

?

I i

l v

r'-

w

-w s-w,e-e se-~=w

, n,w

,v

,-e-

-arr-ws s w,-

-v m m -

g~-+,-w-w~,meewsn,es,---s

-y:m-ar,

-n-wn n-w-- w ~ w~-

me q~

~

ge~mmm w,-wm~e-~~w--w m

6 Page 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMErlT PIECE NUMBER:

2E12-N010BA APPLICATION:

RHR B MININUM FLOW NOMINAL SETPOINT:

23.0" WC CALIBRATION TULERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC TECH SPEC ALLOWABLE:

1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/31/86 23.0 29.2 C9/10/86 24.4 29.4 23.1 28.2

m 1

Pegs 1

UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E12-N010CA APPLICATION:

RHR C MINIMUM FLOW NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC TECH SPEC ALLOWABLE:

1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

===----------------

07/31/86 23.0 28.6 09/10/86 22.8 28.8 23.4 30.0

~;

Paga 1

6 UNIT.2 CALIBRATION DATA

===========

EQUIPMENT: PIECE NUMBER -

2E12-N010AB APPLICATION:

RHR A MINIMUM FLOW ALARM NOMINAL SETPOINT:

25.0" WC

' CALIBRATION TOLERANCE:

24.0-26.0" WC ACTION LIMITS:

NA REJECTION ~ LIMITS:

NA TECH SPEC ALLOWABLE:

NA Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/31/86 24.4-19.8 09/10/86 22.6 16.0 24.8 18.6 o

i 1.

f I

I 1

L

O e

Pag 9 1

o UNIT 2 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

2E12-N010BB APPLICATION:

RHR B MINIMUM FLOW ALARM NOMINAL SETPOINT:

25.0" WC CALIBRATION TOLERANCE:

24.0-26.0" WC ACTION LIMITS:

NA REJECTION LIMITS:

NA TECH SPEC ALLOWABLE:

NA Calibration Date "As Found" "As Found" "As Left" As Left" Trip Reset Trip Reset

_ =-- __------------=

_== _ ;-=-------=_ -

07/31/86 25.2 20.9 09/10/86 26.2 21.4 25.6 21.4 1

,__m._

4 Paga 1

e UNIT 2 CALIBRATION DATA

=======================-

EQUIPMENT PIECE NUMBER:

2E12-N010CD APPLICATION:

RHR C MINIMUM FLOW ALARM NOMINAL SETPOINT:

25.0" WC CALIBRATION TOLERANCE:

24.0-26.0" WC ACTION LIMITS:

NA REJECTION LIMITS:

NA TECH SPEC ALLOWABLE:

NA

-Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

______________--------__-____-=.

--- =-

G7/31/86 25.4 17.6 09/10/86 25.4 17.1 25.2 17.4

(

l

n-P;ga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-N024A APPLICATION:

REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:

63.15" WC

/ 58.90" WC CALIBRATION TOLERANCE:

63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:

/ 56.10-61.70" WC REJECTION LIMITS:

/ 56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC

/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" 1

Trip Reset Trip Reset

/

9/ 9/86 58.70 53.60 9/24/86 58.50 52.80 58.70 53.60 10/ 6/86 59.20 53.40 59.10 53.40 10/20/86 60.00 54.10 58.90 53.60 11/17/86 59.05 53.25 58.4 53.4 I

]

Pcgm 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1821-N024B APPLICATION:

REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:

63.15" WC

/ 58.90" WC CALIBRATION TOLERANCE:

63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:

/ 56.10-61.70" WC REJECTION LIMITS:

/ 56,00-61.80" WC

-TECH SPEC ALLOWABLE:

64.84" WC

/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/ 9/86 59.00 54.30 9/24/86 59.00 53.70 59.00 54.80 10/ 6/86 60.30 55.20 59.10 54.40 10/20/86 59.40 55.00 58.90 54.40 11/17/86 58.9 54.6 58.75 54.6 l

I i

1 l

l l

?

I l

=p.Y

Pegn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1821-N024C APPLICATION:

REACTOR VESSEL LOW LEVEL SCRAM

? NOMINAL SETPOINT:

63.15" WC

/ 58.90" WC CALIBRATION TOLERANCE:

63.78-62.51" WC / 59.40-58.40" WC

' ACTION LIMITS:

/ 56.10-61.70" WC REJECTION LIMITS:

/ 56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC

/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_-------------------------------===-.

- = - - :=---------

9/ 9/86 58.80 52.00 9/24/86 58.70 52.20 58.65 52.60 10/ 6/86 59.70 52.30 59.20 52.00 10/20/86 60.20 52.80 58.80 51.00 11/17/86 58.7 50.4 58.5 51.4

Pcgm 1

' UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

IB21-N024D APPLICATION:

REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:

63.15" WC'

/ 58.90" WC CALIBRATION TOLERANCE:

63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:

/ 56.10-61.70" WC REJECTION LIMITS:

/ 56.00-61.80" WC TECH SPEC ALLOWABLE:

64.84" WC

/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - - - - = -

9/ 9/86 58.80 52.80 9/24/86 58.65 53.50 58.90 54.30 10/ 6/86 61.00 55.00 59.20 53.40 10/20/86 58.90 53.30 58.90 53.60 11/17/86 58.95 52.8 59.0 53.4

Paga 1

UNIT"1 CALIBRATION DATA-

-~

===========
EQUIPMENT PIECE NUMBER:-

- 1B21-NO38A APPLICATION:

REACTOR LOW LEVEL CONFIRMED ADS PERMISSIVE NOMINAL SETPOINT:

58.9" WC' CALIBRATION TOLERANCE:

58.4-59.4" WC-ACTION LIMITS:

56.1-61.7" WC

REJECTION LIMITS:

56.0-61.8" WC TECH SPEC ALLOWABLE:

64.84" WC

- Calibration Date As Found" As Found" "As Left" As Left" Trip Reset-Trip Reset 9/ 9/86 58.85 52.4 9/24/86-58.1 52.1 58.9 53.2

.10/ 9/86 59.45 53.4 58.75 52.9.

, 11/06/86 59.2 53.1 59.2 53.2 4

i i

A 4

e e-

+

.y.rwew-r,--r3-we e

.c---e-e-

--r.c3-,-w w-4-

se

.-,,n-

.w

-,,. - - + - -3.-,.

,ww-

.-,. =,

Paga 1

UNIT'1' CALIBRATION DATA

.=======================

EQUI'PMENT PIECE NUMBER:

1B21-NO38B APPLICATION:

REACTOR LOW LEVEL CONFIRMED-ADS PERMISSIVE NOMINAL SETPOINT:

58.9" WC CALIBRATION TOLERANCE:

58.4-59.4" WC ACTION LIMITS:

56.1-61.7" WC REJECTION LIMITS:

56.0-61.8" WC

~ TECH SPEC ALLOWABLE:

64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=_--- ----

-9/ 9/86 59.1 53.0 9/25/86 58.7 52.8 58.7 52.9 10/ 9/86 58.8 52.8 58.8 53.0 l

11/06/86' 59.4 52.6 59.3 52.8 l

--m.

Paga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-N026AB APPLICATION:

REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 09/12/86 134.1 123.0 10/29/86 135.0 122.5 134.8 122.5 4

m

. page 1

' UNIT-1 CALIBRATION DATA

=======================-

i EQUIPMENT PIECE. NUMBER:

1B21-N026BB APPLICATION:

REACTOR' LOW / LOW LEVEL-MSIV ISOLATION f

- NOMINAL SETPOINT:

134.0" WC

- CALIBRATION TOLERANCE:

133.0-135.0" WC

- ACTION. LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC

TECH SPEC ALLOWABLE:

150.64" WC Calibration Date-As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset

_ - - =..

09/12/86' 134.0 123.5 10/30/86 137.5 123.5 134.0 115.0 f

i f

a y

-,,m.,r.-ry.-#.,_,,_-.-__mm_,-

7-~.--.. m..-

,.n,-,

_--e

,m.,2 e

.,r-,, -,

4

--..,..,,.-o,_.__

Page 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1921-N026CB APPLICATION:

REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION. LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/12/86 133.75 123.0 10/30/86 134.2 123.0 134.2 123.0

Pagn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-N026DB APPLICATION:

REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" UC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=___

= = = - - - -. - - - - - - - - -

09/12/86 134.5 123.5 10/30/86 135.2 123.5 134.4 122.5

Pagn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-NO31A APPLICATION:

REACTOR LOW LOW LEVEL HPCS INITIATE-NOMINAL SETPOINT:

134.00" WC

' CALIBRATION TOLERANCE:

133.00-135.00" WC ACTION LIMITS:

128.60-139.40" WC REJECTION LIMITS:

125.40-142.60" WC TECH SPEC ALLOWABLE:

150.64" WC (-57.0" ACT. RX. LEVEL)

Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

==--

9/11/86 134.0 126.25 9/30/86 134.0 126.5 134.0 126.5

pags-1.

y '. UNIT 1 CALIBRATION DATA

============_

EQUIPMENT PIECE NUMBER:

1B21-NO31B APPLICATION:

REACTOR LOW LOW LEVEL HPCS INITIATE t

l NOMINAL SETPOINT:

134.00" WC 4 CALIBRATION-TOLERANCE:

133.00-135.'00" WC-i ACTION LIMITS:

128.60-139.40" WC REJECTION: LIMITS:

125.40-142.60" WC i TECH SPEC ALLOWABLE:

150.64" WC (-57.0" ACT. RX. LEVEL) 1 Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset-Trip Reset

_ = _ _ _

L

.9/11/86 134.0 125.0 4

9/30/86 134.0 126.0 134.0 126.0 4

i i

i k

i 1

J 9

i

Paga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

IB21-NO31C APPLICATION:

REACTOR LOW LOW LEVEL HPCS INITIATE NOMINAL SETPOINT:

134.00" WC CALIBRATION TOLERANCE:

133.00-135.00" WC ACTION LIMITS:

128.60-139.40" WC REJECTION LIMITS:

125.40-142.60" WC TECH SPEC ALLOWABLE:

150.64" WC (-57.0" ACT. RX. LEVEL)

Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=______________

9/11/86 134.0 126.25 9/30/86 134.2 126.5 134.2 126.5 L

Pcgs 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1821-NO31D APPLICATION:

REACTOR LOW LOW LEVEL HPCS INITIATE NOMINAL.SETPOINT:

134.00" WC CALIBRATION TOLERANCE:

133.00-135.00" WC ACTION LIMITS:

128.60-139.40" WC REJECTION LIMITS:

125.40-142.60" WC TECH SPEC ALLOWABLE:

150.64" WC (-57.0" ACT. RX. LEVEL)

Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/11/86 134.0 127.0 9/30/86 134.0 127.0 134.0 127.0 l

l

Pegu 1

~

UNIT 1. CALIBRATION DATA

==========

z EOUIPMENT PIECE NUMBER:

1B21-NO37AA APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset 9/14/86 189.5 175.6 10/14/86 190.3 175.2 189.9 176.0 I

a

-._-p c-r

Pega 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-NO37BA APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" "As Found"

" As Le f t "

"As Left" Trip Reset Trip Reset

= -----------

9/15/86 189.2 179.6 10/14/86 189.8 179.5 189.7 180.0 6

Page 1

UNIT 1 CALIBRATION DATA

.=======================

EGUIPMENT PIECE NUMBER:

1B21-NO37CA APPLICATION:

RX'LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Cx11bration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

__=----_---__--___---__---

9/14/86 187.9 169.1 10/14/86 189.3 169.5 189.0 170.1 i

Pegn 1

~'

UNIT 1 CALIDRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-NO37DA APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

189.0" WC CALIBRATION TOLERANCE:

187.0-191.0" WC ACTION LIMITS:

181.2-196.8" WC REJECTION LIMITS:

178.8-199.2" WC TECH SPEC ALLOWABLE:

207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

= - - - - - -

9/15/86 188.6 178.5 10/14/86 189.1 178.5 189.3 178.8

Pcgn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-NO37AB APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=-

9/14/86 134.2 126.9 10/14/86 134.4 127.4 134.6 127.6

Page 1

UNIT-1 CALIBRATION DATA

===========

. EQUIPMENT PIECE NUMBER:

1B21-NO378B APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" IWC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=-----------------------------=___ _ _ _

9/15/86 133.9 125.7 10/14/86

' 135.0 125.8 134.3 125.7 4

y

e Paga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1B21-NO37CB APPLICATION:

RX LO LO RCIC; LO LO

'_O LPCS/RHR; ADS PERM NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/15/86 133.5 126.7 10/14/86 134.1 126.8 133.9 126.9

,r

Pcg2 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1921-NO37DB APPLICATION:

RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:

134.0" WC CALIBRATION TOLERANCE:

133.0-135.0" WC ACTION LIMITS:

128.6-139.4" WC REJECTION LIMITS:

125.4-142.6" WC TECH SPEC ALLOWABLE:

150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=.

9/15/86 134.0 126.3 10/14/86 134.7 126.2 134.5 126.4 l

z

a Page 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N008A APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - - - - - - =. = _ _

9/12/86 97.4 73.9 10/15/86 98.4 73.2 98.3 75.7 l

l l

1

r Pcga 1

UNIT 1. CALIBRATION DATA

===========

EOUIPMENT PIECE NUMBER:

1E31-N008B APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID

-ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID

-TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset.

Trip Reset


=-

. = _ _ -

9/14/86 97.2 69.7 10/15/86 97.9 70.2 97.1 69.3

r::

~*.

Pag 2 1

UNIT-1 CALIBRATION DATA'

===========

' EQUIPMENT PIECE' NUMBER:

1E31-N008C APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6~PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left'

-Trip Reset Trip

. Reset

- - - - - - - - - - - - - -=

9/13/86 97.6' 72.7

.10/15/86 98.6 74.9 97.85 74.1

J' Paga-1-

-UNIT 1 CALIBRATION DATA

===========

. EQUIPMENT PIECE NUMBER:

1E31-N008D APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID

. ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC' ALLOWABLE:

116.0 PSID Cclibration Date

~"As Found" "As Found" "As Left" "As Left" Trip Reset-Trip Reset ~

9/14/86' 97.1 71.0 10/15/86 101.3 69.0 97.35 72.3 i

t 1

4 I.

I

{

l f.

I m

Psgm 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N008D APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - = -

.-----------------==_

9/14/86 97.1 71.0 10/15/86 101.3 69.0 97.35 72.3

Pcga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N009A APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=

=-- ----------------

==___---------------

9/13/86 97.5 72.5 11/07/86 98.9 68.0 97.8 71.2

Psga 1

'a UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N009B APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-100.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID CeJibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=.

9/14/86 97.4 74.9 11/07/86 99.0 72.0 97.6 73.0

r-Paga 1

~

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N009C APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


__=

-=

===---------

9/13/86 97.9 75.1 11/07/86 100.5 71.5 97.5 72.0 i

~. _ _ _..

e-Psgn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N009D APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- _ = _

9/14/86 97.9 74.6 11/08/86 102.0 72.0 97.7 69.0

J*

rpagn l '-

UNIT.1 CALIBRATION DATA ~-

===========

' EGUIPMENT PIECE NUMBER:

- 1E31-N010A

- APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL ~SETPOINT::

97.6 PSID' CALIBRATION TOLERANCE:

-96.6-98.6 PSID

ACTION LIMITS

89.5-105.7 PSID

' REJECTION LIMITS:

87.2-108.0 PSID

' -TECH SPEC ALLOWABLE:

116.0 PSID-

~

-. Calibration Date "As Found" As Found"-

"As Left" "As Left" Trip Reset Teip Reset

. = _ - -

-9/13/86 97.4' 75.7 i

1

+

r 5

i.

1 Y

l a

1

.nv

--,_,,_-..,n-,_.,_-__,.,.--,,-,,,n..,,

... + -.,,,, - -,. -,, -, _,, -. -., - -., -,, -, - -, -...

I Pags 1

~ - -

UNIT 1-CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N010B APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID

-CALIBRATION TOLERANCE:

96.6-98.6 PSID

' ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date As Found" "As Found" "As Left" As Left" Trip Reset Trip Raset 9/14/86 97.2 70.5 y.-

y-

-s-_,

,+

s Pagn 1-UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N010C APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION

-NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


==


=_-

9/13/86 97.9 71.3 t

T' Pags 1

UNIT I. CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N010D APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID

~ REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

_=-

_ = - -

=____________________

.9/14/86 97.6 74.0 4

Pegs 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N011A APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION t>0MINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=

9/13/86 97.5 71.6

7.

Pcgn 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N011B APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=_

9/14/86 97.3 70.6 i

r

Pcg2 1

' UNIT 1 CALIBRATION DATA

..======================

EQUIPMENT PIECE NUMBER:

1E31-N011C APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/13/86 97.9 74.5 f

i L

r-Pag 9 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N011D APPLICATION:

MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:

97.6 PSID CALIBRATION TOLERANCE:

96.6-98.6 PSID ACTION LIMITS:

89.5-105.7 PSID REJECTION LIMITS:

87.2-108.0 PSID TECH SPEC ALLOWABLE:

116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=-----

9/14/86 97.6 76.8

Peg 9 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N012AA APPLICATION:

RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:

168.4" WC CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

=--------------------------

C9/11/86 168.0 155.0 11/05/86 167.5 153.0 167.5 153.0

r__

Pega 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N012AB APPLICATION:

RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:

168.4" WC CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset

- - - = = = = = - - - - - - - - - -

_==--------

C9/11/86 168.0 158.0 11/05/86 170.0 150.0 169.0 152.0 l

Pega 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N012BA APPLICATION:

RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:

168.4" WC CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - = - - = _ - - -

C9/11/86 168.2 157.5 11/05/86 169.0 150.0 168.0 150.5

Paga 1

e UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N012BB APPLICATION:

RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:

168.4" WC CALIBRATION TOLERANCE:

167.4-169.4" WC ACTION LIMITS:

163.0-173.8" WC REJECTION LIMITS:

158.8-178.0" WC TECH SPEC ALLOWABLE:

186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/11/86 169.2 153.5 11/05/86 170.5 149.0 169.0 152.0

Pega 1

UNIT 1 CALIBRATION DATA

===========

' EQUIPMENT PIECE NUMBER:

1E31-N007AA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

111.4" WC CALIBRATION TOLERANCE:

110.4-112.4" WC ACTION LIMITS:

106.0-116.8" WC REJECTION LIMITS:

102.8-120.0" WC TECH SPEC ALLOWABLE:

128.0" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 86-6-2517 1

09/09/86 REVISED SETPOINT 111.0 104.3 C9/13/86 114.0 102.0 111.0 105.0 11/19/86 113.5 106.0 111.2 105.2 i

(

I l

i

I 1

1 Pega 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N007AB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

111.4" WC CALIBRATION TOLERANCE:

110.4-112.4" WC ACTION LIMITS:

106.0-116.8" WC REJECTION LIMITS:

102.8-120.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER I

85-4-261 09/10/86 REVISED SETPOINT 111.1 105.0 C9/13/86 112.0 106.0 111.5 106.0 11/19/86 111.8 105.6 111.6 106.0

Pcg2 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N007BA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

75.4" WC CALIBRATION TOLERANCE:

74.4-76.4" WC ACTION LIMITS:

70.0-80.8" WC REJECTION LIMITS:

66.8-84.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-262 09/10/86 REVISED SETPOINT 75.7 69.5 C9/13/86 76.0 69.0 76.0 69.0 11/19/86 77.2 71.0 75.0 68.5 r

i l

I

=

Pag 2 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N0078B APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

75.4" WC CALIBRATION TOLERANCE:

74.4-76.4" WC ACTION LIMITS:

70.0-80.8" WC REJECTION LIMITS:

66.8-84.0" WC TECH SPEC ALLOWABLE:

128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-263 09/10/86 REVISED SETPOINT 75.0 67.5 C9/13/86 76.5 68.0 76.0 69.0 11/19/86 76.0 68.5 75.4 69.5

Pagm 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N013AA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC REJECTION LIMITS:

155.8-177.0"WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-264 09/10/86 REVISED SETPOINT 166.6 158.5 C9/13/86 167.0 158.0 167.0 159.0 11/19/86 168.6 160.9 165.7 158.0

Paga 1

+

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N013AB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

155.4-167.4" WC ACTION LIMITS:

161.0-171.0" WC REJECTION LIMITS:

155.8-177.0"WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

===---------------------

SERIAL NUMBER 85-5-265 09/10/86 REVISED SETPOINT 166.1 156.5 C9/13/86 167.5 157.0 166.0 157.0 11/19/86 167.0 158.8 166.7 159.0 t

Paga 1

. UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N013BA APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC REJECTION LIMITS:

155.8-177.0"WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "An Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-1-2425 09/10/86 REVISED SETPOINT 166.5 158.2 C9/13/86 166.5 161.0 166.5 161.0 11/19/86 168.5 161.5 165.5 157.5

Pagm 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E31-N013BB APPLICATION:

STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:

166.4" WC CALIBRATION TOLERANCE:

165.4-167.4" WC ACTION LIMITS:

161.0-171.8" WC REJECTION LIMITS:

155.8-177.0"WC TECH SPEC ALLOWABLE:

185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - =.

_ - - = = - _ -

SERIAL NUMBER 86-6-2515 09/10/86 REVISED SETPOINT 166.0 157.5 C9/13/86 166.5 159.0 166.5 159.0 11/19/86 167.4 157.0 166.2 157.0 l

Paga 1

UNIT 1 CALIBRATION DATA

c====================

EQUIPMENT PIECE NUMBER:

1E21-N004 APPLICATION:

LPCS MIN FLOW BYPASS NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCES 23.6-22.4" WC ACTION LIMITS:

24.7-21.3" WC REJECTION LIMITS:

25.4-20.6" WC TECH SPEC ALLOWABLE:

3.187" WC Calibration Date "As Found" "As Found" "As Left" As Left" Trip Reset Trip Reset

=

09/07/8G 22.8 29.E 4

f f

c,

o 4

"E Page 1

? UNIT'1 CALIBRATION DATA'

.=======================-

EQUIPMENT PIECE NUMBER:-

1E22-N006 APPLICATION:

HPCS MIN FLOW BYPASS NOMINAL SETPOINT:

23.00 "WC CALIBRATION TOLERANCE:

22.40-23.60 "WC ACTION LIMITS:

21.30-24.70 "WC

-REJECTION LIMITS:

20.00-26.00 "WC TECH ~ SPEC ALLOWABLE:

7.85 "WC Calibration ~Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset

.9/15/86 23.10 31.10

,10/10/86 23.30 31.00 23.20 31.00

7 Pcgo 1

UNIT 1 CALIBRATION DATA

===========

' EQUIPMENT PIECE NUMBER:

1E12-N010AA APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC TECH SPEC ALLOWABLE:

1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

- - - - - - - - - - - = = _ _ _ _ _ _ _


=.

09/10/86 23.0 27.2 10/22/86 22.8 29.6 23.0 27.8 I

Pzga 1

UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E12-N010BA APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC TECH SPEC ALLOWABLE:

1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/10/86 22.8 28.4 10/22/86 22.4 29.2 22.8 28.2

r-

]

Page 1

?

-UNIT-1' CALIBRATION DATA

,-======================

EQUIPMENT PIECE NUMBER:

1E12-N010AB APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

-.' NOMINAL. SETPOINT:

25.0" WC CALIBRATION TOLERANCE:

24.0-26.0" WC

-ACTION' LIMITS:

.N/A REJECTION LIMITS:

N/A TECH SPEC ALLOWABLE:

N/A Calibration Date "As Found" "As Found"

'= As Lef t "

"As Left" Trip Reset Trip Reset

= - - _ _ _ = - - - - - -

=

09/10/86 24.4 17.0 10/22/86 24.2 18.0 24.8 20.4 i

t i

i s

I

o Pags i

e UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBEP:

1E12-N010BB APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

NOMINAL SETPOINT:

25. 0" WC -

CALIBRATION TOLERANCE:

24.0-26.0" WC ACTION LIMITS:

N/A REJECTION LIMITS:

N/A TECH SPEC ALLOWABLE:

N/A Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset

. - _ = _ _ _ _ _.

C9/10/86 25.8 20.4 10/22/86 25.6 20.6 25.4 20.8

r-Pags 1

0 UNIT 1 CALIBRATION DATA

===========

EQUIPMENT PIECE NUMBER:

1E12-N010CA APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

NOMINAL SETPOINT:

23.0" WC CALIBRATION TOLERANCE:

22.4-23.6" WC ACTION LIMITS:

21.3-24.7" WC REJECTION LIMITS:

17.7-28.3" WC TECH SPEC ALLOWABLE:

1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset


=

=----------------------=.

==-

C9/1'1/86 23.4 29.2 10/22/86 23.8 29.6 23.2 28.4

y-e-

pega 1

a UNIT 1 CALIBRATION DATA

.-======================

-EQUIPMENT PIECE NUMBER:

1E12-N010CB

(

APPLICATION:

RHR PUMP MIN FLOW BYPASS (LPCI MODE)

NOMINAL SETPOINT:

25.2" WC' CALIBRATION TOLERANCE:

24. 0--26. 0" WC ACTION' LIMITS:

N/A

' REJECTION LIMITS:

N/A

. TECH. SPEC ALLOWABLE:

N/A Cclibrati'on Date "As.Found" "As Found" "As Left" "As Left"'

Trip Reset Trip Reset

=------------------------------ -

- - - - - - _ - =

69/10/86' 24.6 19.4 10/22/86.

24.8 19.4 24.6 19.6 4

k.

N-..

,...,,,.