November 25, 1986 Dr. A. Bournia Project Manager U.S. Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, MD 20014
Subject:
LaSalle County Station Units 1 and 2 SOR Differential Switch Calibration Data through Nov. 24, 1986 NRC Docket Nos. 50-373 a_nd 50-374
Dear Dr. Bournia:
Attached are the data sheets for the safety related static "O"
ring differential pressure switches installed in LaSalle Units 1 and 2.
This data is provided to you per your request to assist in preparing a Safety Evaluation Report for LaSalle Unit 1 interim operations.
Please direct any questions you may have regarding this matter to this office.
l ry trul
- ours, J
M. Allen i
Nuclear Licensing Administrator bc Attachments cc:
Resident Inspector - LSCS 2435K
\\
8612O20266 861125 g.I PDR ADOCK 05000373 j
P PDR
.n Paga 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-N024A APPLICATION:
LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPOINT:
58.90" WC CALIBRATION TOLERANCE:
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC REJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - - - = - - - - - -
_ _ = _
=-.
07/30/86 58.90 53.60 C8/18/86 58.30 52.40 59.10 54.40 C9/01/86 59.30 54.00 58.80 53.60 9/3D/86 59.03 53.60 58.90 54.10 11/21/86 61.4 53.0 58.9 52.9
Page 1
-UNIT-2-CALIBRATION DATA
=======================-
' EQUIPMENT PIECE NUMBER:
2B21-N024B APPLICATION:-
LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPDINT:
58.90" WC CALIBRATION' TOLERANCE:-
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC REJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip.
Reset 07/30/86 58.90 54.00 08/18/86-59.15 54.05 59.00 54.40 C9/01/86 58.90 53.80-58.90 54.10 9/30/86 59.05 54.30 59.05.
54.60 11/2*/86-60.4 52.5 58.6 52.2
!=
l 5
i f
1 I
i 0
0 i
Page 1
UNIT 2' CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-N024C APPLICATION:
LEVEL 3 SCRAM AND ISOLATION NOMINAL'SETPOINT:
58.90" WC CALIBRATION TOLERANCE:
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC REJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC lCalibration Date-
"As Found" As Found" "As Left" "As Left" Trip Reset Trip.
Reset
--- = _ _ _ _
07/30/86 58.90 53.30
~ 08/18/86 58.85 52.70 58.80 53.10 C9/01/86 58.50 52.60 58.50 52.70
'9/30/86 58.75 53.10 58.70 53.20 11/21/86 60.4 52.2 58.6 50.5 i
h i
4 i
a 4
~
-m'
,, ~,
,c
.. ~..,,,+_ e
,r.,_
y.,m.,,,
r,.._.m,,
,,...y._
____r_.
Pagm 1
UNIT 2 CALIBRATION DATA
===========
. EQUIPMENT PIECE NUMBER:
2B21-N024D APPLICATION:
LEVEL 3 SCRAM AND ISOLATION NOMINAL SETPOINT:
58.90" WC CALIBRATION TOLERANCE:
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC HEJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_ _ - - = _
_ _ - - - - - - = = _
07/30/86 59.00 53.80 08/18/86 58.90 54.00 59.00 54.00 C9/01/86 58.75 53.50 58.70 53.70 9/30/86 59.00 54.10 59.00 54.30 11/21/86 59.7 52.0 58.9 52.4 i
l
. _ _ - -.=_
Page.
1 i
- ' UNIT.R CALIBRATION DATA
>=======================
I. EQUIPMENT' PIECE NUMBER:
2B21-NO38A APPLICATION:
LEVEL 3 LOW WATER LEVEL ADS CONFIRMED
' NOMINAL SETPOINT:
58.90" WC
~
- CALIBRATION. TOLERANCE
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC REJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC
)CalibrationDate "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset i
=________________
' 07/33/86 58.90 53.70 08/19/86 59.55 54.10 58.80 53.65 7 09/02/86' 59.05 54.00 59.00 54.15
-9/30/86 61.30 54.50 58.70 52.80 i
4 t
4 i
1
{
i i
s
Pags 1
_'l ONIT/2' CALIBRATION DATA
===========
tEGUIPMENT PIECE NUMBER:
. APPLICATION:
LEVEL 3 LOW WATER LEVEL ADS CONFIRMED NOMINAL SETPOINT:
58.90"'WC CALIBRATION. TOLERANCE:
- 58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC 4
REJECTION LIMITS:
56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC
- l. Calibration Date "As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset j
==--
- --==-
m.
!07/30/86_
58.90 53.50 08/19/86 59.20 53.35 59.15 54.10 09/02/86 59.40 54.05 58.80 53.-70 i
9/30/86 59.20 53.00 59.00 53.60 i
i i
I t
i h;
t w
yw
^r-w y,
-^cem,
-,==~-,?
-,---,g-mm. - - - e,, es. w w w y e -v
-em.,-.--,
w-- *
--e,-
..we a
w
,----+
4
-+- - - -
-ee m -,
e Pcg2 1
UNIT C CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-N101B APPLICATION:
REACTOR HIGH LEVEL RCIC TURBINE TRIP NOMINAL SETPOINT:
38.7" WC CALIBRATION TOLERANCE:
38.2-39.2" WC ACTION LIMITS:
N/A REJECTION LIMITS:
36.5-40.9" WC TECH SPEC ALLOWABLE:
32.8" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C8/02/86 38.5 45.1 10/23/86 38.6 46.9 38.4 46.3
Paga 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-N026AB APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As'Left" Trip Reset Trip Reset 08/02/86 133.5 121.7 09/24/86 133.8 123.25 134.5 124.4 I
Pcgn i
R
, UNIT 2 CALIBRATION DATA
====================-
EQUIPMENT PIECE NUMBER:
2B21-N026BB APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TCLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date-
"As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_=-----------==-
- - = = = - - -
C8/02/86 133.8 122.5 C9/24/86 138.25 128.0 133.75 124.3
Page 1
UNIT 2 CALIBRATION DATA
.umnuua===========
-EQUIPMENT PIECE NUMBER:
2B21-N026CB APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION
' NOMINAL SETPOINT:
134.0" WC CALIERATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
= _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - _ -
C8/02/86 133.9 121.0 C9/24/86 134.7 122.5 134.6 122.7
a Page 1
-UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-N026DB APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
.=--
=
---=_
C8/02/86 134.5 119.8 09/24/86 136.7 122.2 133.75 120.25
C -
Pege 1
UNIT 2 CALIBRATION DATA
'=======================
EQUIPMENT PIECE NUMBER:
2B21-NO31A APPLICATION:
REACTOR LEVEL 2 HPCS INITIATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.6" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset-
- = = - - - - - - - -
- _ - =.
_=-------------
C8/01/86 134.25 127.75 08/27/86 137.80 130.80 134.20 127.30
Paga 1
UNIT.2 CALIBRATION DATA
mu===mu==unumu=
EQUIPMENT PIECE NUMBER:
2B21-NO31B APPLICATION:
REACTOR LEVEL 2 HPCS INITIATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
120.6-139.4" WC 125.4-142.6" WC REJECTION LIMITS:
TECH SPEC ALLOWABLE:
150.6" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=-
=
G8/02/86 134.00 125.50 08/27/86 134.50 128.00 134.50 128.00
Pagn
'l
~
UNIT 2' CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
- APPLICATION:.
REACTOR LEVEL 2 HPCS INITIATION' NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC
- ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.6" WC T
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - =. -
)
i i:C8/02/86 134.00 125.50 08/27/86 135.50 126.50 134.30 126.00 1
i I
4 f
I t
a i
(
l l
I.
I l
s
d
.s Page 1
= UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
'2B21-NO31D APPLICATION:
REACTOR LEVEL 2 HPCS INITIATION s
- NOMINAL ~SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC
-TECH SPEC ALLOWABLE:
150.6" WC 3
- Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_ _ _ _ _ _ _ = - -.
_= _ _ _ _ _ _ _ _ _ _-
08/02/86 134.20 127.00 LO8/27/86' 134.60 127.20-134.70 127.50 1
A 5
'l b
I
Page 1
' UNIT.2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-NO37AA APPLICATION:
REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
= = _
_ _ _ _ _ = - - _ _ _ _
C8/02/86 189.20 179.50 08/13/86 189.75 179.75 189.75 179.75 11/12/86 189.8 179.2 189.6 180.4 l
l
~__
. ~
Paga 1
UNIT'a CALIBRATION DATA
===========
-EQUIPMENT. PIECE NUMBER:
{ -. APPLICATION:
REACTOR LEVEL 1 ECCS INITIATION I
NOMINAL ~SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0 "WC ACTION-LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17 "WC Calibration Date.
"As Found" "As Found" "As Left" "As Left" Trip-Reset Trip-Reset C8/03/86 189.90 169.60
- C8/13/86 190.00 170.40 190.00 170.40-11/12/86 189.0 169.0.
189.0 171.0 l
T t
r i
i
[.
I.
i '., - _.. _..., _., _.,.. _. - _
Pego 1-ON'IT 2' CALIBRATION DATA
===========
EQUIPMENT. PIECE' NUMBER:
2B21-NO37CA APPLICATION:
REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:-
187.0-191.0" WC
~ ACTION LIMITS:
181.2-196.8"-WC REJECTION LIMITS:
178.8-199.2" WC
. TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - = - -
C8/02/86 188.50 176.00-08/13/86 189.50 177.50 189.50 177.50 11/12/86 190.0 178.2 189.9 178.2 h'
i n
+.
.., -. - ~,. -.. _ - - -,
-.m_
e Pega 1
UNIT 2-CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-NO37DA APPLICA, TION:
REACTOR LEVEL 1 ECCS INITIATION NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - =. - -
C8/03/86 188.40 175.80 08/13/86 189.60 177.00 189.60 177.00 11/12/86 189.0 175.0 189.0 177.0 t
Pagn 1
l ONITL2 CALIBRATION DATA
===========
~ EQUIPMENT PIECE NUMBER:
2B21-NO37AB APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION
- NOMINAL SETPOINT:
134.0" WC
- CALIBRATION TOLERANCE:-
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC
' TECH SPEC ALLOWABLE:
150.64" WC
- Calibration'Date "As Found" As Found" As Left" "As Left" Trip Reset Trip
. Reset 08/02/86 134.20 126.80 8/13/86 134.75 127.5 133.75 126.50 11/12/86 133.3 126.6 133.4 126.3-l
[
i l
t
}
i i
i t
1 em -
-stv---
t-y
,y.-.. -,.,
y
,_,.....-.-__y..,_,_._.,..,_,y,,,
m,
Pago 1
UNIT 2 CALIERATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-NO37BB APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
= - - - - - - - - - - - - - - - - - - - - - - - - - -
=-----------------------------
,'C8/03/86 134.10 128.30 08/13/86 135.50 129.50 134.50 128.60 11/12/86 135.5 128.0 133.8 127.0 i
6 Page 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT-PIECE NUMBER:
APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION NOMINAL'SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC
~
128.6-139.4" WC ACTION LIMITS:
,' REJECTION LIMITS:
125.4-142.6" WC
TECH SPEC ALLOWABLE:
150.64" WC
- Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_=____
08/02/86 133.80 128.70 08/13/86 135.00 131.00 134.50 129.75 3 11/12/86 134.1 128.7 134.1 128.8
+
1 i
4 1
f i
I 4
4 4
i t
i l
[
l l
l I
I
Page 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2B21-NG37DB APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C8/03/86 133.90 126.80 08/13/86 135.75 129.00 134.00 127.75 11/12/86 134.3 127.0 134.3 127.0
-, - - ~.
p,
Page 1
s UNIT 2 CALIBRATION DATA
.n===========
EQUIPMENT PIECE NUMBER:
2E31-N008A APPLICATION:
MSL HI FLOW ISOLATION NOMINAL SETPOINT:
85.0 PSID CALIBRATION TOLERANCE:
84.0-86.0 PSID ACTION LIMITS:
69.50-100.50 PSID REJECTION L IMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
111.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
.-------------------------------------------==
_=--
C8/02/86 85.50 62.50 08/29/86 85.70 61.80 85.30 61.80 11/20/86 86.0 59.0 85.5 60.0 r
i I
1 l
I i
Pagn 1
f UNIT 2 CALIBRATION DATA
- -:=======================
r EQUIPMENT PIECE NUMBER:
2E31-N008B APPLICATION:
-MSL HI FLOW' ISOLATION NOMINAL SETPOINT:
85.0 PSID I CALIBRATION TOLERANCE:
84.0-86.0 PSID ACTION LIMITS:
69.50-100.50 DSID
' REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
111.0 PSID I'Ca'11bration Date "As Found"-
"As Found" "As Left" "As Left" t
Trip Reset Trip.
Reset
+
- - - - - - - - = = - - - -
, 08/02/86 85.20 65.40 08/29/86 87.~00 65.50 85.00 65.40
- 11/20/86 90.0 62.0 85.0 58.0 4
P
't i
s i
1 I
t
l Pagn 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N008C APPLICATION:
MSL HI FLOW ISOLATION NOMItJAL SETPOINT:
85.0 PSID CALIBRATION TOLERANCE:
84.0-86.0 PSID 4
ACTION LIMITS:
69.50-100.50 PSID REJECTION LIMITS:
69.50-100.50 PSID
' TECH SPEC ALLOWABLE:
111.0 PSID Calibration Date "As Found" As Found" As Left" As Left"
' Trip Reset Trip Reset 1
C8/02/86 85.00 65.60
'C8/29/86 86.00 64.00 85.50 64.00 i
11/20/86 87.0
- 62.0 85.0 63.0 1
I i
4 i
a i
i
, ~.
,,,m-.
.m.
-._m,,_---...
,=%-. -.,... _ - -. -, - -
.c 1.1Y
- l
6
, ;).
pags 1
c.i n
~. UNIT-2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
. APPLICATION:
MSL HI FLOW ISOLATION
-NOMINAL SETPOINT:
85.0 PSID-84.0-86.0 PSID CALIBRATION TOLERANCE:
c 69.50-100.50 PSID
. ACTION LIMITS:
REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:.
111.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" c
Trip Reset Trip Reset
,. = _
=_
- ------------=-
+
1C8/03/86 84.40 67.00
. 08/29/86 84.20 68.00 85.30 69.50
-11/20/86-87.0 67.0 85.0 67.0 t
't 4
3 i
\\
r t
i e
I i
ff,.
p,g, i
f
' UNIT;2 CALIBRATION DATA
===========
-EGOIPMENT PIECE NUMBER:~
'2E31-N009A APPLICATION -
. NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID
- 7. ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID
' TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/'2/86 85.40 67.00
!9/26/86-88.00 61.00 85.50 62.00 4
4 L
f t
r--
,4-t-+,*
~
v,-
-ew r
v vi
+rrv omv -
e-*--
1 r, w -v - ~, -
-vv-'=-
-w--~ &-+ - - - - * - = - - ' - - ' - - - -
[
Pag 2 1
, UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N009B APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID
-ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=--
8/ 2/86 85.20 67.00 9/26/86 88.00 62.00 84.80 62.00
E' l
Paga 1
ONITf2' CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
-APPLICATION:
. NOMINAL'SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID STECH SPEC ALLOWABLE:
116.00 PSID
' Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- ___=
8/ 2/86 85.20 60.70-9/26/86 88.50 58.00 85.00 56.50 1
1 I
l f
4
.I
'i
[~e:
Paga 1
^
l UNIT 2 CALIBRATION DATA
===========
' EQUIPMENT. PIECE NUMBER:
2E31-N009D APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID
' CALIBRATION TOLERANCE:
84.00-86.00 PSID
.A'CTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID
~
-TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date-As Found" As Found" As Left" As'Left" Trip Reset Trip Reset
_= - --
8/ 2/86 84.50 59.40
-9/26/86 88.00~
56.00 85.00 57.00 9/27/86 85.50 56.50 85.50 56.50 1
t e
d f
.er ay yy-3
-,wc
-rtv,,
r, r r
-3 y
w-r,--yir yv w-
-*-w,.m
--y-twrr
=,
.w r-e-
e:
- Pagn 1
' UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
' APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID:
, CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" As Found" As Left" As Left" Trip Reset Trip Reset 8/ 2/86 85.00 61.20 10/14/86 85.5 59.5 85.0 59.0 l
i i
-"*+$
- s9
+
r we9 y-mr 9
4WNu-w--
cw
---y-
---pi-1-e--wy-w-
- 9%syyw,eg--
+
g--wera e
e
+r i+t--*~me-v+-
+wey e--
Pago 1
k.;;.
" UNIT 2 CALIBRATION DATA
===========
- EQUIPMENT PIECE NUMBER:
' - APPL'ICATION:
MSL HIGH FLOW MSIV ISOLATION 4
NOMINAL SETPOINT:
85.00 PSID CALIBRATION. TOLERANCE:
.84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID' i TECH SPEC ALLOWABLE:
116.00 PSID
' Calibration Date As Found" "As Found" As Left" "As Left" Trip Reset Trip-Reset
- - - _ __ _ _ _ = = - --
_=-
8/ 2/86 84.50 65.50 10/14/86 86.0 63.0 85.5 60.5 ir i
+
k s
i
+7 g---,y..
....-c-
,,-%m, _, _y my,
,w-.
3
,%.%,m,,m,,,e..,
.my_,,____,w-,m mm m,y,,
m,
a Pags 1
t-UNIT.2 CALIBRATION DATA
.=======================
EQUIPMENT PIECE NUMBER:
2E31-N010C APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=-
- - - - = = =
8/ 2/86 84.60 61.60 10/14/86 89.0 58.0 85.0 58.0 t
f
Pega 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N010D APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
-69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left"c Trip Reset Trip Reset 8/ 2/86 85.10 62.10 10/14/86 88.0 58.0 85.0 57.0
r--s
.Pago 1
- UNIT 2-CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
, APPLICATION:
' ' NOMINAL' SETPOINT:
'85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID 3,
t-~ ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID
-TECH SPEC ALLOWABLE:
116.00 PSID Calibration-Date "As Found"=
"As Found" "As Left" "As Left"
. Trip Reset.
Trip' Reset
=----------- _-
8/ 2/86 85.00 58.80
.' 10/14/86 86.0 57.5
'85.0 56.O i
I i
1 J
ll.
4
+
d 4
7
Paga 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
. APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_==----- ___
8/ 2/86 85.40 69.70 10/14/86 85.5 60.0 85.5 68.0 i
l l
i l
i l
t I
l l
l l
l t
Pags 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
. APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION. TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 2/06 84.71 64.50 10/14/86 87.75 60.0 85.5 61.0
1 1
Pcgn 1
UNIT 2 CALIBRATION DATA
=======.,===
EQUIPMENT PIECE NUMBER:
2E31-N011D APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:.
84.00-86.00 PSID ACTION LIM 7.TS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left' "As Left" Trip Reset Trip Reset 8/ 1/86 REVISED SETPOINT 85.00 61.50 8/ 2/86 84.70 60.30 84.60 60.40 1C/14/86 90.0 59.0 85.0 58.0 i
Pcgm 1
UNIT 2 CALIBRATION DATA
=:===r.:======
EQUIPMENT PIECE NUMBER:
2E31-N012AA APPLICATION:
RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:
168.4" WC
~
CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - - - - - - - - - - - = - - - - - - - - - - -
08/03/86 168.0 157.0 C9/16/86 164.0 154.0 168.5 160.0 i
.. ~..
Paga 1
).
UNIT E~ CALIBRATION DATA
===========
4 4-EQUIPMENT PIECE NUMBER:
' APPLICATION:
.t NOMINAL SETPOINT:
168.4" WC
{CALIBRATIONTOLERANCE:
167.4-169.4" WC
-ACTION LIMITS:
-163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC i TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" i
. Trip Reset Trip Reset C8/03/06 168.0
'160.0
' 09/16/86 166.0-157.0 168.0 159.9 s
4
'l i
i l
i l
{
{
l^
i l,
,.. _ - -,....,,,. _ _,,,.,,, - -,, _ _,, _. ~ _, -.. - - -,. -,. - -., _... _ _..., - - -., - -
Pegn 1-UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
-APPLICATION:
RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:
168.4" WC
-CALIBRATION TOLERANCE:
'167.4-169.4" WC
. ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC-
. TECH SPEC ALLOWABLE:
186.0" WC
-Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - = _ -= _ _ = _ - - - -
-==
-08/03/86 168.0 155.0
'09/16/86 165.0 152.0 168.5 155.0 4
I r-i s
i i
i i
F
Paga 1
UNIT'2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N012BB APPLICATION:
RHR SDC HIGH SUCTION FLOW NOMINAL SETPOINT:
168.4" WC CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
-=__________:-
- _ _ _ _ _ _ _ _ = -
=
=---______________=-
C8/03/86 168.5 157.0 09/16/86 168.0 157.0 168.0 157.0 t
Paga i
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N007AA APPLICATION:
STEAM LINE HIGH FLLOW RCIC ISOLATION NOMINAL SETPOINT:
111.4" WC CALIBRATION TOLERANCE:
110.4-112.4" WC ACTION LIMITS:
106.0-116.8" WC REJECTION LIMITS:
102.8-120.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
= - - - - - - - - - - -
=-----
08/04/86 111.5 106.0 10/ 9/86 112.0 107.5 112.0 107.5
Pagn 1
. UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N007AB APPLICATION:
STEAM LINE HIGH FLLOW RCIC ISOLATION NOMINAL SETPOINT:
111.4" WC CALIBRATION TOLERANCE:
110.4-112.4" WC ACTION LIMITS:
106.0-116.8" WC REJECTION LIMITS:
102.8-120.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 111.5 105.5-10/ 9/86 111.5 105.0 111.5 105.0
Pagu 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N007BA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
75.4" WC CALIBRATION TOLERANCE:
74.4-76.4" WC ACTION LIMITS:
70.0-80.8" WC REJECTION LIMITS:
66.8-84.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 75.7 71.0 10/ 9/86 75.5 71.5 75.5 71.5 s
Pagn 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N007BB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
75.4" WC CALIBRATION TOLERANCE:
74.4-76.4" WC ACTION LIMITS:
70.0-80.8" WC REJECTION LIMITS:
66.8-84.0" WC TECH SPEC ALLOWABLE:
128.0" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
-___________----______----------___=_
8/ 4/86 75.7 69.5 10/ 9/86 80.0 69.0 75.5 67.0
Paga 1
1
' UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N013AA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0" WC TECH SPEC ALLOWABLE:
185.0" WC Calioration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 166.7 159.5 10/ 9/86 168.0 163.0 166.0 161.0 4
4
Paga 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N013AB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0" WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 166.8 158.5 10/ 9/06 168.0 161.0 166.5 160.0 6
4
1 Pag 9 1
O UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E31-N013BA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIDRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.0" WC REJECTION LIMITS:
155.8-177.0" WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset 8/ 4/86 166.0 157.5 10/ 9/86 166.0 153.0 166.0 153.0
U e
Page 1
UNIT 2 CALIBRATION DATA
===u=======
EQUIPMENT PIECE NUMBER:
2E31-N013BB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC-CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC
. REJECTION LIMITS:
155.8-177.0" WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 4/86 165.6 152.5 10/ 9/86 171.5 159.5 167.0 157.0 i,
5 l
. _ _ _.. _ = _. _. _ _ _ _
Pzg2 1
1 UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E21-N004 APPLICATION:
LOW PRESS CORE SPRAY MIN FLOW BYPASS NOMINAL SETPOINT:
23.0.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
20.6-25.4" WC TECH SPEC ALLOWABLE:
2.187" WC Colibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=
07/30/86 22.9 29.4 10/20/86 23.0 34.6 23.2 34.6
o Page 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E22-N006 APPLICATION:
HPCS MINIMUM FLOW NOMINAL SETPOINT:
23.00" WC CALIBRATION TOLERANCE:
22.40-23.60" WC ACTION LIMITS:
21.30-24.70" WC REJECTION LIMITS:
20.00-26.00" WC TECH SPEC ALLOWABLE:
9.70" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/30/86 23.20 32.40 08/15/86 23.60 32.40 23.60 31.60 11/15/86 23.4 34.0 23.4 34.0
--G.
f Pagn.
'1
. UNIT'2 CALIBRATION DATA
===========
EQUIPMENT PIECE' NUMBER:
'? APPLICATION:
RHR A MINIMUM FLOW
- NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
- 21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC
' TECH SPEC ALLOWABLE:
1.78" WC Calibration Date As Found" As Found" As Left" "As Left"
- Trip Reset Trip Reset
------=-
=
07/31/86 23.0 29.2 09/10/86-21.6 28.4 22.9 29.2 4
5' i
l
?
I i
l v
r'-
w
-w s-w,e-e se-~=w
, n,w
,v
,-e-
-arr-ws s w,-
-v m m -
g~-+,-w-w~,meewsn,es,---s
-y:m-ar,
-n-wn n-w-- w ~ w~-
me q~
~
ge~mmm w,-wm~e-~~w--w m
6 Page 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMErlT PIECE NUMBER:
2E12-N010BA APPLICATION:
RHR B MININUM FLOW NOMINAL SETPOINT:
23.0" WC CALIBRATION TULERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/31/86 23.0 29.2 C9/10/86 24.4 29.4 23.1 28.2
m 1
Pegs 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E12-N010CA APPLICATION:
RHR C MINIMUM FLOW NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
===----------------
07/31/86 23.0 28.6 09/10/86 22.8 28.8 23.4 30.0
~;
Paga 1
6 UNIT.2 CALIBRATION DATA
===========
EQUIPMENT: PIECE NUMBER -
2E12-N010AB APPLICATION:
RHR A MINIMUM FLOW ALARM NOMINAL SETPOINT:
25.0" WC
' CALIBRATION TOLERANCE:
24.0-26.0" WC ACTION LIMITS:
NA REJECTION ~ LIMITS:
NA TECH SPEC ALLOWABLE:
NA Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 07/31/86 24.4-19.8 09/10/86 22.6 16.0 24.8 18.6 o
i 1.
f I
I 1
L
O e
Pag 9 1
o UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
2E12-N010BB APPLICATION:
RHR B MINIMUM FLOW ALARM NOMINAL SETPOINT:
25.0" WC CALIBRATION TOLERANCE:
24.0-26.0" WC ACTION LIMITS:
NA REJECTION LIMITS:
NA TECH SPEC ALLOWABLE:
NA Calibration Date "As Found" "As Found" "As Left" As Left" Trip Reset Trip Reset
_ =-- __------------=
_== _ ;-=-------=_ -
07/31/86 25.2 20.9 09/10/86 26.2 21.4 25.6 21.4 1
,__m._
4 Paga 1
e UNIT 2 CALIBRATION DATA
=======================-
EQUIPMENT PIECE NUMBER:
2E12-N010CD APPLICATION:
RHR C MINIMUM FLOW ALARM NOMINAL SETPOINT:
25.0" WC CALIBRATION TOLERANCE:
24.0-26.0" WC ACTION LIMITS:
NA REJECTION LIMITS:
NA TECH SPEC ALLOWABLE:
NA
-Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
______________--------__-____-=.
--- =-
G7/31/86 25.4 17.6 09/10/86 25.4 17.1 25.2 17.4
(
l
n-P;ga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-N024A APPLICATION:
REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:
63.15" WC
/ 58.90" WC CALIBRATION TOLERANCE:
63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:
/ 56.10-61.70" WC REJECTION LIMITS:
/ 56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" 1
Trip Reset Trip Reset
/
9/ 9/86 58.70 53.60 9/24/86 58.50 52.80 58.70 53.60 10/ 6/86 59.20 53.40 59.10 53.40 10/20/86 60.00 54.10 58.90 53.60 11/17/86 59.05 53.25 58.4 53.4 I
]
Pcgm 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1821-N024B APPLICATION:
REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:
63.15" WC
/ 58.90" WC CALIBRATION TOLERANCE:
63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:
/ 56.10-61.70" WC REJECTION LIMITS:
/ 56,00-61.80" WC
-TECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/ 9/86 59.00 54.30 9/24/86 59.00 53.70 59.00 54.80 10/ 6/86 60.30 55.20 59.10 54.40 10/20/86 59.40 55.00 58.90 54.40 11/17/86 58.9 54.6 58.75 54.6 l
I i
1 l
l l
?
I l
=p.Y
Pegn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1821-N024C APPLICATION:
REACTOR VESSEL LOW LEVEL SCRAM
? NOMINAL SETPOINT:
63.15" WC
/ 58.90" WC CALIBRATION TOLERANCE:
63.78-62.51" WC / 59.40-58.40" WC
' ACTION LIMITS:
/ 56.10-61.70" WC REJECTION LIMITS:
/ 56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_-------------------------------===-.
- = - - :=---------
9/ 9/86 58.80 52.00 9/24/86 58.70 52.20 58.65 52.60 10/ 6/86 59.70 52.30 59.20 52.00 10/20/86 60.20 52.80 58.80 51.00 11/17/86 58.7 50.4 58.5 51.4
Pcgm 1
' UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
IB21-N024D APPLICATION:
REACTOR VESSEL LOW LEVEL SCRAM NOMINAL SETPOINT:
63.15" WC'
/ 58.90" WC CALIBRATION TOLERANCE:
63.78-62.51" WC / 59.40-58.40" WC ACTION LIMITS:
/ 56.10-61.70" WC REJECTION LIMITS:
/ 56.00-61.80" WC TECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - - - - = -
9/ 9/86 58.80 52.80 9/24/86 58.65 53.50 58.90 54.30 10/ 6/86 61.00 55.00 59.20 53.40 10/20/86 58.90 53.30 58.90 53.60 11/17/86 58.95 52.8 59.0 53.4
Paga 1
UNIT"1 CALIBRATION DATA-
-~
===========
- EQUIPMENT PIECE NUMBER:-
- 1B21-NO38A APPLICATION:
REACTOR LOW LEVEL CONFIRMED ADS PERMISSIVE NOMINAL SETPOINT:
58.9" WC' CALIBRATION TOLERANCE:
58.4-59.4" WC-ACTION LIMITS:
56.1-61.7" WC
- REJECTION LIMITS:
56.0-61.8" WC TECH SPEC ALLOWABLE:
64.84" WC
- Calibration Date As Found" As Found" "As Left" As Left" Trip Reset-Trip Reset 9/ 9/86 58.85 52.4 9/24/86-58.1 52.1 58.9 53.2
.10/ 9/86 59.45 53.4 58.75 52.9.
, 11/06/86 59.2 53.1 59.2 53.2 4
i i
A 4
e e-
+
.y.rwew-r,--r3-we e
.c---e-e-
--r.c3-,-w w-4-
se
.-,,n-
.w
-,,. - - + - -3.-,.
,ww-
.-,. =,
Paga 1
UNIT'1' CALIBRATION DATA
.=======================
EQUI'PMENT PIECE NUMBER:
1B21-NO38B APPLICATION:
REACTOR LOW LEVEL CONFIRMED-ADS PERMISSIVE NOMINAL SETPOINT:
58.9" WC CALIBRATION TOLERANCE:
58.4-59.4" WC ACTION LIMITS:
56.1-61.7" WC REJECTION LIMITS:
56.0-61.8" WC
~ TECH SPEC ALLOWABLE:
64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=_--- ----
-9/ 9/86 59.1 53.0 9/25/86 58.7 52.8 58.7 52.9 10/ 9/86 58.8 52.8 58.8 53.0 l
11/06/86' 59.4 52.6 59.3 52.8 l
--m.
Paga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-N026AB APPLICATION:
REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 09/12/86 134.1 123.0 10/29/86 135.0 122.5 134.8 122.5 4
m
. page 1
' UNIT-1 CALIBRATION DATA
=======================-
i EQUIPMENT PIECE. NUMBER:
1B21-N026BB APPLICATION:
REACTOR' LOW / LOW LEVEL-MSIV ISOLATION f
- NOMINAL SETPOINT:
134.0" WC
- CALIBRATION TOLERANCE:
133.0-135.0" WC
- ACTION. LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC
- TECH SPEC ALLOWABLE:
150.64" WC Calibration Date-As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset
_ - - =..
09/12/86' 134.0 123.5 10/30/86 137.5 123.5 134.0 115.0 f
i f
a y
-,,m.,r.-ry.-#.,_,,_-.-__mm_,-
7-~.--.. m..-
,.n,-,
_--e
,m.,2 e
.,r-,, -,
4
--..,..,,.-o,_.__
Page 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1921-N026CB APPLICATION:
REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION. LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/12/86 133.75 123.0 10/30/86 134.2 123.0 134.2 123.0
Pagn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-N026DB APPLICATION:
REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" UC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=___
= = = - - - -. - - - - - - - - -
09/12/86 134.5 123.5 10/30/86 135.2 123.5 134.4 122.5
Pagn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-NO31A APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE-NOMINAL SETPOINT:
134.00" WC
' CALIBRATION TOLERANCE:
133.00-135.00" WC ACTION LIMITS:
128.60-139.40" WC REJECTION LIMITS:
125.40-142.60" WC TECH SPEC ALLOWABLE:
150.64" WC (-57.0" ACT. RX. LEVEL)
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
==--
9/11/86 134.0 126.25 9/30/86 134.0 126.5 134.0 126.5
pags-1.
y '. UNIT 1 CALIBRATION DATA
============_
EQUIPMENT PIECE NUMBER:
1B21-NO31B APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE t
l NOMINAL SETPOINT:
134.00" WC 4 CALIBRATION-TOLERANCE:
133.00-135.'00" WC-i ACTION LIMITS:
128.60-139.40" WC REJECTION: LIMITS:
125.40-142.60" WC i TECH SPEC ALLOWABLE:
150.64" WC (-57.0" ACT. RX. LEVEL) 1 Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset-Trip Reset
_ = _ _ _
L
.9/11/86 134.0 125.0 4
9/30/86 134.0 126.0 134.0 126.0 4
i i
i k
i 1
J 9
i
Paga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
IB21-NO31C APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE NOMINAL SETPOINT:
134.00" WC CALIBRATION TOLERANCE:
133.00-135.00" WC ACTION LIMITS:
128.60-139.40" WC REJECTION LIMITS:
125.40-142.60" WC TECH SPEC ALLOWABLE:
150.64" WC (-57.0" ACT. RX. LEVEL)
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=______________
9/11/86 134.0 126.25 9/30/86 134.2 126.5 134.2 126.5 L
Pcgs 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1821-NO31D APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE NOMINAL.SETPOINT:
134.00" WC CALIBRATION TOLERANCE:
133.00-135.00" WC ACTION LIMITS:
128.60-139.40" WC REJECTION LIMITS:
125.40-142.60" WC TECH SPEC ALLOWABLE:
150.64" WC (-57.0" ACT. RX. LEVEL)
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/11/86 134.0 127.0 9/30/86 134.0 127.0 134.0 127.0 l
l
Pegu 1
~
UNIT 1. CALIBRATION DATA
==========
z EOUIPMENT PIECE NUMBER:
1B21-NO37AA APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset 9/14/86 189.5 175.6 10/14/86 190.3 175.2 189.9 176.0 I
a
-._-p c-r
Pega 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-NO37BA APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" "As Found"
" As Le f t "
"As Left" Trip Reset Trip Reset
= -----------
9/15/86 189.2 179.6 10/14/86 189.8 179.5 189.7 180.0 6
Page 1
UNIT 1 CALIBRATION DATA
.=======================
EGUIPMENT PIECE NUMBER:
1B21-NO37CA APPLICATION:
RX'LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Cx11bration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
__=----_---__--___---__---
9/14/86 187.9 169.1 10/14/86 189.3 169.5 189.0 170.1 i
Pegn 1
~'
UNIT 1 CALIDRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-NO37DA APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
= - - - - - -
9/15/86 188.6 178.5 10/14/86 189.1 178.5 189.3 178.8
Pcgn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-NO37AB APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=-
9/14/86 134.2 126.9 10/14/86 134.4 127.4 134.6 127.6
Page 1
UNIT-1 CALIBRATION DATA
===========
. EQUIPMENT PIECE NUMBER:
1B21-NO378B APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" IWC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=-----------------------------=___ _ _ _
9/15/86 133.9 125.7 10/14/86
' 135.0 125.8 134.3 125.7 4
y
e Paga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1B21-NO37CB APPLICATION:
'_O LPCS/RHR; ADS PERM NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/15/86 133.5 126.7 10/14/86 134.1 126.8 133.9 126.9
,r
Pcg2 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1921-NO37DB APPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=.
9/15/86 134.0 126.3 10/14/86 134.7 126.2 134.5 126.4 l
z
a Page 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N008A APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - - - - - - =. = _ _
9/12/86 97.4 73.9 10/15/86 98.4 73.2 98.3 75.7 l
l l
1
r Pcga 1
UNIT 1. CALIBRATION DATA
===========
EOUIPMENT PIECE NUMBER:
1E31-N008B APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID
-ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID
-TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset.
Trip Reset
=-
. = _ _ -
9/14/86 97.2 69.7 10/15/86 97.9 70.2 97.1 69.3
r::
~*.
Pag 2 1
UNIT-1 CALIBRATION DATA'
===========
' EQUIPMENT PIECE' NUMBER:
1E31-N008C APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6~PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left'
-Trip Reset Trip
. Reset
- - - - - - - - - - - - - -=
9/13/86 97.6' 72.7
.10/15/86 98.6 74.9 97.85 74.1
J' Paga-1-
-UNIT 1 CALIBRATION DATA
===========
. EQUIPMENT PIECE NUMBER:
1E31-N008D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID
. ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC' ALLOWABLE:
116.0 PSID Cclibration Date
~"As Found" "As Found" "As Left" "As Left" Trip Reset-Trip Reset ~
9/14/86' 97.1 71.0 10/15/86 101.3 69.0 97.35 72.3 i
t 1
4 I.
I
{
l f.
I m
Psgm 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N008D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - = -
.-----------------==_
9/14/86 97.1 71.0 10/15/86 101.3 69.0 97.35 72.3
Pcga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N009A APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=
=-- ----------------
==___---------------
9/13/86 97.5 72.5 11/07/86 98.9 68.0 97.8 71.2
Psga 1
'a UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N009B APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-100.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID CeJibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=.
9/14/86 97.4 74.9 11/07/86 99.0 72.0 97.6 73.0
r-Paga 1
~
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N009C APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
__=
-=
===---------
9/13/86 97.9 75.1 11/07/86 100.5 71.5 97.5 72.0 i
~. _ _ _..
e-Psgn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N009D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- _ = _
9/14/86 97.9 74.6 11/08/86 102.0 72.0 97.7 69.0
J*
rpagn l '-
UNIT.1 CALIBRATION DATA ~-
===========
' EGUIPMENT PIECE NUMBER:
- APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL ~SETPOINT::
97.6 PSID' CALIBRATION TOLERANCE:
-96.6-98.6 PSID
- ACTION LIMITS
89.5-105.7 PSID
' REJECTION LIMITS:
87.2-108.0 PSID
' -TECH SPEC ALLOWABLE:
116.0 PSID-
~
-. Calibration Date "As Found" As Found"-
"As Left" "As Left" Trip Reset Teip Reset
. = _ - -
-9/13/86 97.4' 75.7 i
1
+
r 5
i.
1 Y
l a
1
.nv
--,_,,_-..,n-,_.,_-__,.,.--,,-,,,n..,,
... + -.,,,, - -,. -,, -, _,, -. -., - -., -,, -, - -, -...
I Pags 1
~ - -
UNIT 1-CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N010B APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID
-CALIBRATION TOLERANCE:
96.6-98.6 PSID
' ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date As Found" "As Found" "As Left" As Left" Trip Reset Trip Raset 9/14/86 97.2 70.5 y.-
y-
-s-_,
,+
s Pagn 1-UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N010C APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION
-NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
==
=_-
9/13/86 97.9 71.3 t
T' Pags 1
UNIT I. CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N010D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID
~ REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
_=-
_ = - -
=____________________
.9/14/86 97.6 74.0 4
Pegs 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N011A APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION t>0MINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=
9/13/86 97.5 71.6
7.
Pcgn 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N011B APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=_
9/14/86 97.3 70.6 i
r
Pcg2 1
' UNIT 1 CALIBRATION DATA
..======================
EQUIPMENT PIECE NUMBER:
1E31-N011C APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/13/86 97.9 74.5 f
i L
r-Pag 9 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N011D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=-----
9/14/86 97.6 76.8
Peg 9 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N012AA APPLICATION:
RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:
168.4" WC CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=--------------------------
C9/11/86 168.0 155.0 11/05/86 167.5 153.0 167.5 153.0
r__
Pega 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N012AB APPLICATION:
RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:
168.4" WC CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset
- - - = = = = = - - - - - - - - - -
_==--------
C9/11/86 168.0 158.0 11/05/86 170.0 150.0 169.0 152.0 l
Pega 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N012BA APPLICATION:
RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:
168.4" WC CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - = - - = _ - - -
C9/11/86 168.2 157.5 11/05/86 169.0 150.0 168.0 150.5
Paga 1
e UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N012BB APPLICATION:
RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO NOMINAL SETPOINT:
168.4" WC CALIBRATION TOLERANCE:
167.4-169.4" WC ACTION LIMITS:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/11/86 169.2 153.5 11/05/86 170.5 149.0 169.0 152.0
Pega 1
UNIT 1 CALIBRATION DATA
===========
' EQUIPMENT PIECE NUMBER:
1E31-N007AA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
111.4" WC CALIBRATION TOLERANCE:
110.4-112.4" WC ACTION LIMITS:
106.0-116.8" WC REJECTION LIMITS:
102.8-120.0" WC TECH SPEC ALLOWABLE:
128.0" WC Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 86-6-2517 1
09/09/86 REVISED SETPOINT 111.0 104.3 C9/13/86 114.0 102.0 111.0 105.0 11/19/86 113.5 106.0 111.2 105.2 i
(
I l
i
I 1
1 Pega 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N007AB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
111.4" WC CALIBRATION TOLERANCE:
110.4-112.4" WC ACTION LIMITS:
106.0-116.8" WC REJECTION LIMITS:
102.8-120.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER I
85-4-261 09/10/86 REVISED SETPOINT 111.1 105.0 C9/13/86 112.0 106.0 111.5 106.0 11/19/86 111.8 105.6 111.6 106.0
Pcg2 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N007BA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
75.4" WC CALIBRATION TOLERANCE:
74.4-76.4" WC ACTION LIMITS:
70.0-80.8" WC REJECTION LIMITS:
66.8-84.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-262 09/10/86 REVISED SETPOINT 75.7 69.5 C9/13/86 76.0 69.0 76.0 69.0 11/19/86 77.2 71.0 75.0 68.5 r
i l
I
=
Pag 2 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N0078B APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
75.4" WC CALIBRATION TOLERANCE:
74.4-76.4" WC ACTION LIMITS:
70.0-80.8" WC REJECTION LIMITS:
66.8-84.0" WC TECH SPEC ALLOWABLE:
128.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-263 09/10/86 REVISED SETPOINT 75.0 67.5 C9/13/86 76.5 68.0 76.0 69.0 11/19/86 76.0 68.5 75.4 69.5
Pagm 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N013AA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0"WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-4-264 09/10/86 REVISED SETPOINT 166.6 158.5 C9/13/86 167.0 158.0 167.0 159.0 11/19/86 168.6 160.9 165.7 158.0
Paga 1
+
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N013AB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
155.4-167.4" WC ACTION LIMITS:
161.0-171.0" WC REJECTION LIMITS:
155.8-177.0"WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
===---------------------
SERIAL NUMBER 85-5-265 09/10/86 REVISED SETPOINT 166.1 156.5 C9/13/86 167.5 157.0 166.0 157.0 11/19/86 167.0 158.8 166.7 159.0 t
Paga 1
. UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N013BA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0"WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "An Left" "As Left" Trip Reset Trip Reset SERIAL NUMBER 85-1-2425 09/10/86 REVISED SETPOINT 166.5 158.2 C9/13/86 166.5 161.0 166.5 161.0 11/19/86 168.5 161.5 165.5 157.5
Pagm 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E31-N013BB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0"WC TECH SPEC ALLOWABLE:
185.0" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - =.
_ - - = = - _ -
SERIAL NUMBER 86-6-2515 09/10/86 REVISED SETPOINT 166.0 157.5 C9/13/86 166.5 159.0 166.5 159.0 11/19/86 167.4 157.0 166.2 157.0 l
Paga 1
UNIT 1 CALIBRATION DATA
c====================
EQUIPMENT PIECE NUMBER:
1E21-N004 APPLICATION:
LPCS MIN FLOW BYPASS NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCES 23.6-22.4" WC ACTION LIMITS:
24.7-21.3" WC REJECTION LIMITS:
25.4-20.6" WC TECH SPEC ALLOWABLE:
3.187" WC Calibration Date "As Found" "As Found" "As Left" As Left" Trip Reset Trip Reset
=
09/07/8G 22.8 29.E 4
f f
c,
o 4
"E Page 1
? UNIT'1 CALIBRATION DATA'
.=======================-
EQUIPMENT PIECE NUMBER:-
1E22-N006 APPLICATION:
HPCS MIN FLOW BYPASS NOMINAL SETPOINT:
23.00 "WC CALIBRATION TOLERANCE:
22.40-23.60 "WC ACTION LIMITS:
21.30-24.70 "WC
-REJECTION LIMITS:
20.00-26.00 "WC TECH ~ SPEC ALLOWABLE:
7.85 "WC Calibration ~Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Roset
.9/15/86 23.10 31.10
,10/10/86 23.30 31.00 23.20 31.00
7 Pcgo 1
UNIT 1 CALIBRATION DATA
===========
' EQUIPMENT PIECE NUMBER:
1E12-N010AA APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
- - - - - - - - - - - = = _ _ _ _ _ _ _
=.
09/10/86 23.0 27.2 10/22/86 22.8 29.6 23.0 27.8 I
Pzga 1
UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E12-N010BA APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset C9/10/86 22.8 28.4 10/22/86 22.4 29.2 22.8 28.2
r-
]
Page 1
?
-UNIT-1' CALIBRATION DATA
,-======================
EQUIPMENT PIECE NUMBER:
1E12-N010AB APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
-.' NOMINAL. SETPOINT:
25.0" WC CALIBRATION TOLERANCE:
24.0-26.0" WC
-ACTION' LIMITS:
.N/A REJECTION LIMITS:
N/A TECH SPEC ALLOWABLE:
N/A Calibration Date "As Found" "As Found"
'= As Lef t "
"As Left" Trip Reset Trip Reset
= - - _ _ _ = - - - - - -
=
09/10/86 24.4 17.0 10/22/86 24.2 18.0 24.8 20.4 i
t i
i s
I
o Pags i
e UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBEP:
1E12-N010BB APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
NOMINAL SETPOINT:
- 25. 0" WC -
CALIBRATION TOLERANCE:
24.0-26.0" WC ACTION LIMITS:
N/A REJECTION LIMITS:
N/A TECH SPEC ALLOWABLE:
N/A Celibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
. - _ = _ _ _ _ _.
C9/10/86 25.8 20.4 10/22/86 25.6 20.6 25.4 20.8
r-Pags 1
0 UNIT 1 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
1E12-N010CA APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC ACTION LIMITS:
21.3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
=
=----------------------=.
==-
C9/1'1/86 23.4 29.2 10/22/86 23.8 29.6 23.2 28.4
y-e-
pega 1
a UNIT 1 CALIBRATION DATA
.-======================
-EQUIPMENT PIECE NUMBER:
(
APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI MODE)
NOMINAL SETPOINT:
25.2" WC' CALIBRATION TOLERANCE:
- 24. 0--26. 0" WC ACTION' LIMITS:
N/A
' REJECTION LIMITS:
N/A
. TECH. SPEC ALLOWABLE:
N/A Cclibrati'on Date "As.Found" "As Found" "As Left" "As Left"'
Trip Reset Trip Reset
=------------------------------ -
- - - - - - _ - =
69/10/86' 24.6 19.4 10/22/86.
24.8 19.4 24.6 19.6 4
k.
N-..
,...,,,.